CHILLED BEAMS IN HEATING: DESIGN CRITERIA AND CASE STUDY. Halton Oy, Haltonintie 1-3, Kausala, Finland
|
|
- Sheryl Pope
- 7 years ago
- Views:
Transcription
1 CHILLED BEAMS IN HEATING: DESIGN CRITERIA AND CASE STUDY Maija Virta 1 and Risto Kosonen 1 Halton Oy, Haltonintie 1-3, Kausala, Finland maija.irta@halton.com Keywords: chilled beams, entilation, heating, thermal comfort ABSTRACT The chilled beam system is suitable for spaces with a high cooling requirement, low humidity load and relatiely small entilation requirement. Although the chilled beam system is quite popular and well known, there is still limited experience in using actie chilled beams for primary heating. The main objectie of this paper is to gie design criteria for actie chilled beam system and present results of a case study, where actie chilled beams were used for heating. The study is carried out in laboratory conditions. The results show that the occupied zone conditions are good and the temperature gradient is low. BACKGROUND The design of the heating system begins by defining the required heating capacity. In traditional heating systems the design is often based on high safety margins when heat losses are calculated. When a chilled beam system is used for heating, proper system operation cannot be achieed by oersizing the heating system. In a new office building W/m 2,floor of heating capacity is typically enough. The required heating capacity is strongly dependent on the thermal properties of the building and the outdoor climate conditions. Figure 1 shows the required heating capacity as a function of the aerage thermal conductance and the outdoor temperature. In this case, the room dimensions are 2.8 m (room width), 4.5 m (room length) and 3.0 m (room height), giing a the floor area of 12.6 m2 and a total external wall area of 8.4 m2. In this case, the glazing ratio of the total outdoor wall area is fixed to 50. In the European case, there is a double-glazed window (U-alue 3 W/m 2 K) and the U-alue of the wall is 0.45 W/m 2 K. In the Scandinaian case, there is a triple-glazed window (U-alue 2 W/m 2 K) and the U- alue of the wall is 0.28 W/m 2 K. Figure 1 also shows an example, which incurs high heat losses: this case is like a European one, except for haing a single-glazed window.
2 In addition, a case representing low heating demand is shown. Here, the heat losses are simply fixed 50 lower than the Scandinaian case. Based on this calculation, the required heating capacity of 500 W per room-module is enough for the normal case in arious European climate and design conditions. Heating demand (W) High losses G=27.1 W/m2K European G=14.5 W/m2K Scandinaia G=9.6 W/m2K Low energy G=4.8 W/m2K Outdoor temperature oc Figure 1. The required heating capacity as a function of thermal conductance and external temperature for a case room-module (room area 12.6 m 2 and external wall area 8.4 m 2 ). The basic guideline for thermal comfort is laid down in the ISO 7730 Standard (1990). The major part of this report concerns thermal comfort in terms of the temperature gradient in the room space and the room air elocities. ISO 7330 recommends the following: Air elocity (to aoid draughts): < 0.15 m/s (winter) < 0.25 m/s (summer) Vertical air temperature difference: < 3 C from foot to head when sitting, 0.1 m to 1.1 m, or standing, 0.1 m to 1.7 m. With the traditional heating system, the maximum gradient is typically 3 5 C. Of course, the existing conditions considerably affects a lot for the gradient, e.g. heat losses, positioning of the heating deice, surface temperatures, and the design temperature leels of system. All in all, the installation has a consequential effect on the gradient: it is more difficult to keep the gradient low when the installation height of the heat emitter is high. HEATING DESIGN CRITERIA WITH ACTIVE CHILLED BEAMS The actie chilled beam is one of the most popular air-conditioning systems in Europe. With chilled beams, it is possible to create high-quality indoor climate conditions, including thermal comfort and a low noise leel within reasonable life-cycle costs. Chilled beam systems are dedicated outdoor air systems to be applied primarily in spaces where internal humidity loads are moderate. They can also be used for heating. Actie chilled beams are connected to both the entilation supply air ductwork, and the chilled water system. When desired, hot water can be used in this system for heating. The main air-handling unit supplies primary air into the arious rooms through the chilled beam. Primary air supply induces room air to be recirculated through the heat exchanger of the chilled beam. In order to cool or heat the room either cold (14-18 C) or warm (30-45 C) water is cycled through the heat exchanger. Recirculated room air and the primary air are mixed prior to diffusion in the space. Room temperature is controlled by the water flow rate through the heat exchanger.
3 Figure 2. Typical exposed installation of actie chilled beams in office enironment. If the heating inlet water temperature of a chilled beam is higher than 45 C (linear output of an actie beam is higher than a. 150 W/m) in a typical installation, secondary air is often too warm to mix properly with the room air. The relatiely low temperature gradient in the space raises the air temperature near the floor thus maintaining comfortable thermal conditions, as well as ensuring the energy efficiency of the system (by decreasing the short circuit and thus the exhaust air temperature). Figure 3. Typical example of an actie chilled beam system operation principle in heating mode. This has been confirmed in preious papers based on laboratory measurements, where both the heating capacity and the temperature gradient of the room were analyzed. The studied inlet water temperature leels were 40 C, 60 C and 70 C.
4 3 Room heigh 2,5 2 1, deg.c 60 deg.c 74 deg.c 0, Temperature difference dt (C) Figure 4. Temperature gradient in the space with different inlet water temperatures. The data in Fig. 4 shows the effect of the inlet water temperature leel on the temperature gradient. With relatiely high temperatures, the gradient in the room rises: the temperature leel of 74 C leads to far too high gradient 8 10 C in the room. 40 C inlet water temperature gies much lower gradient in the room of under 3 C. Increasing the supply airflow rate decreases the temperature gradient but in this measured case, using 22 l/s instead of 13 l/s reduced the gradient only about 1 C. Therefore, the key factor is to control the inlet water temperature at a reasonably low leel. With the temperature leel of 40 C, it is possible to reach 500 W, which is in most cases enough. The mixing is also dependent on the window size and surface temperature. The higher and colder the window, the colder the air falling down to the floor, and the temperature gradient between secondary air and room air becomes higher. For this reason using beams for heating is recommended when the heat transmission of the windows is moderate (e.g. surface temperature is higher than 14 C and height is not more than 1.5 m). The heating capacity of actie beams is dependent on the primary airflow rate. This is why entilation must be operating when heating is required. When an office room is occupied the internal heat sources normally reduce the required heating output and the temperature gradient stays at an acceptable leel. The control principle in heating case is ery important. It can be on-off, time proportional on-off or modulating. The selection of the control system is dependent on the system design. In most cases all the aboe mentioned control principles proide reliable operation of the system. In cases where the difference between the design and normal operating conditions is large (e.g. the design is based on a much higher heating capacity leel than the real leel), time proportional on off or modulating controls are recommended. Otherwise the mixed air temperature of chilled beam becomes too quickly too warm, and there is no sufficient mixing in the space and therefore the occupied zone becomes too cold. In some cases the operation of heating system can be improed by installing the room air temperature measurement at higher leel in the space. In that case the heating mode is controlled based on higher room air temperature in heating mode and in cooling mode with fully mixed situation, the positioning of temperature sensor is irreleant.
5 CASE STUDY OF EXPOSED CHILLED BEAMS IN HEATING The main idea of the conducted case study measurement was to study a chilled beam system in heating mode with correctly calculated heat losses (35 W/m 2 ) without oerdesign and relatiely low inlet water temperature (35 O C). The office room is also relatiely high (3.6m) and chilled beams are installed at 800 mm under the soffit. This measurement was so-called early morning case without any internal loads. The measurements were carried out in a laboratory measurement room with room length of 6.5 m, width of 4.4 m and height of 3.6 m. There was cold window (surface temperature of 15 O C and height 2m) in the room. This project was designed at London weather conditions with double-glazed window. Two open types of chilled beams with actie length of 4.6 m and width of 0.3 m were installed exposed at height of 2.8 m. The beam installation can be seen in Fig. 5. Figure 5. The measurement room sizes, measurement grid and chilled beam location during the measurement.
6 The comfort conditions were measured in 25 different points throughout the space at 6 different heights (0.1m, 0.2m, 0.6m, 1.1m, 1.5m and 1.8m). The air elocity, air temperature and turbulence intensity was measured in each measurement point and from these results the draught rate was calculated using following formula: 0,62 = (34 Ta )( 0,05) (0,37* * Turb + 3,14) (1) Where: = draught rate = air temperature ( O C) = air elocity Turb = turbulence intensity Table 1. gies all the input data alues. The design inlet water temperature was 35 O C and with 0.04 kg/s water flow rate, the chilled beam heating output was 1425 W. The primary air was slightly colder than room air in order to generate free cooling in the space when all internal heat loads are effectie and therefore cooling is needed instead of heating. At room air temperature of 21.3 O C the 18 O C primary air has a cooling effect of 487 W. Therefore the net heating capacity to compensate heat loads was 937 W, corresponding heating capacity per floor area of 33 W/m 2. Table 1. Input alues of a chilled beam case study. T R Room Temperature 21,3 q S air Supply Air Flow Rate 116,0 l/s q S air/m Supply Air Flow Rate /m 25,8 l/s/m q E air Exhaust Air Flow Rate 116,0 l/s T S Supply Air Temperature 17,8 T E Exhaust Air Temperature 21,7 Window Surface Temperature 14,6 T W T W1 T W2 Inlet Water Temperature Outlet Water Temperature 35,0 26,5 q mw Total water Flow Rate 0,040 kg/s P W Total capacity of water 1425 W P A Capacity of air -487 W P T Total Capacity 937 W dt T R -aerage (T W1 andt W2 ) -9,45 The chilled beam heating operates fine also in this kind of installation. The achieed temperature gradient is low enough and elocities are ery low. Results of comfort measurement are shown in Table 2. In all measured points the air elocity is under 0.18 m/s and majority of them is under 0.15 m/s. Calculated draught rates in all points are under 15 (except 3 points at 1.8m height). Temperature gradient in the occupied zone is less than 2 O C and is below the comfort criteria of ISO 7730 Standard (<3 O C between 0.1m and 1.7m). This means that the airflow from chilled beam is well mixed with room air in the whole occupied zone and therefore the entilation efficiency is good. In addition it also shows relatiely good energy efficiency of system with exhaust air temperature of 21.7 O C een the space was 800 mm higher than the installation height of chilled beams. With internal loads (lights, persons and computers all together 55 W/m 2 ), the room air temperature increases a. 2 O C if water flow rate is not reduced. This means that een the maximum heating output is defined with room air temperature of 21 O C, in practice the personal control of +2 O C can be achieed.
7 Table 2. Comfort measurement results and calculated draught rates in arious measurement points ,80 0,05 21,4 55-0,05 21,4 51-0,03 21,6 56-0,04 21,6 45-0,03 21,6 42-1,50 0,07 21, ,05 21,3 47-0,04 21,4 47-0,04 21,4 35-0,03 21,4 44-1,10 0,06 21, ,04 21,1 39-0,04 21,1 38-0,03 21,1 39-0,02 21,2 38-0,60 0,03 20,6 42-0,03 20,6 37-0,03 20,6 31-0,04 20,6 48-0,03 20,7 35-0,20 0,02 20,3 35-0,02 20,4 40-0,03 20,5 34-0,03 20,4 53-0,02 20,5 44-0,10 0,02 20,1 25-0,03 20,3 27-0,05 20,3 36-0,04 20,3 36-0,03 20, ,80 0,09 21, ,13 21, ,18 22, ,09 21, ,07 21, ,50 0,10 21, ,09 21, ,14 21, ,10 21, ,04 21,6 47-1,10 0,10 21, ,06 21, ,06 21, ,06 21, ,02 21,2 40-0,60 0,06 20, ,04 20,4 35-0,04 20,5 36-0,03 20,5 34-0,05 20,6 34-0,20 0,03 20,4 59-0,02 20,3 44-0,02 20,4 32-0,02 20,4 43-0,03 20,4 33-0,10 0,03 20,2 36-0,02 20,2 27-0,03 20,3 34-0,03 20,3 32-0,03 20, ,80 0,07 21, ,12 21, ,15 22, ,10 21, ,05 21,8 51-1,50 0,07 21, ,08 21, ,11 21, ,07 21, ,05 21,6 40-1,10 0,08 21, ,05 21,3 54-0,06 21, ,03 21,1 38-0,03 21,3 54-0,60 0,04 20,7 57-0,03 20,6 42-0,03 20,5 34-0,03 20,5 36-0,04 20,6 50-0,20 0,02 20,4 47-0,02 20,5 41-0,02 20,4 34-0,02 20,4 31-0,03 20,4 52-0,10 0,03 20,2 34-0,03 20,3 28-0,02 20,3 24-0,02 20,3 23-0,03 20, ,80 0,09 21, ,10 21, ,13 22, ,08 21, ,05 21,6 35-1,50 0,10 21, ,08 21, ,08 21, ,04 21,3 54-0,05 21,4 36-1,10 0,10 21, ,04 21,1 46-0,04 21,1 47-0,03 20,9 30-0,05 21,0 22-0,60 0,04 20,6 56-0,02 20,5 41-0,03 20,4 40-0,03 20,3 41-0,04 20,3 37-0,20 0,02 20,3 34-0,02 20,3 28-0,03 20,3 36-0,03 20,3 48-0,06 20, ,10 0,02 20,1 24-0,03 20,2 29-0,03 20,1 30-0,03 20,2 44-0,05 20,2 44-1,80 0,06 21, ,06 21, ,05 21,3 46-0,03 21,4 42-0,04 21,4 52-1,50 0,08 21, ,06 21, ,04 21,1 43-0,04 21,2 38-0,04 21,1 47-1,10 0,08 21, ,05 20,9 66-0,04 20,8 41-0,04 20,8 40-0,04 20,9 34-0,60 0,04 20,5 53-0,03 20,5 42-0,03 20,5 49-0,03 20,4 46-0,03 20,5 40-0,20 0,04 20,4 41-0,05 20,5 45-0,06 20, ,08 20, ,08 20, ,10 0,04 20,2 52-0,10 20, ,11 20, ,10 20, ,12 20, Temperature gradients with and without internal loads with max heating capacity 2,00 1,50 1,00 0, with internal loads 8 with internal loads 13 with internal loads 18 with internal loads 23 with internal loads 0,00 20,0 21,0 22,0 23,0 24,0 25,0 Temperature Figure 6. Temperature gradients are lower than 2 O C throughout the whole floor area. Measurement point 3 is nearest from the window and 23 is close to the door. All the points are in the middle of the room halfway between the chilled beams. With internal loads the room air temperature is a. 2 O C warmer, if water flow rate is not reduced.
8 CONCLUSIONS Integration of the heating mode in the actie chilled beam system is a challenging task. The main problem has been to control the temperature gradient in the space and to creating thermal comfort conditions in an energy-efficient way. On the other hand, meeting the heating capacity requirement with chilled beam is not a problem in most cases. The key factor is the temperature leel of the inlet water. Lower the inlet water temperature is, lower is also the temperature gradient in the space. Based on the measurements, a temperature leel of 40 C or below, gies a reasonable gradient for the room space. For design practice, this also means the possibility to use low temperature leel heating sources. During working hours, there is normally enough or een too much of a heat loads to keep indoor temperature within acceptable comfort leels. This means that this worst case exists in the beginning of the working day when the external temperature is also near design conditions. In the case study of exposed chilled beams in heating mode, the right design alues (inlet water temperature of 35 O C) with relatiely low heating output (33 W/m 2,floor) demonstrated excellent thermal comfort and good energy efficiency. It was also showing, that earlier gien design guidelines are a good basis for design of actie chilled beams in heating. LITERATURE Kosonen, R., Horttanainen, P, Dunlop, G. Integration of heating mode into entilated cooled beam. Proceedings of Rooment Virta, M., Butler, D., Gräslund, J., Hogeling, J., Kristiansen, E. Reinikainen, M., Sensson, G. Chilled Beam Application Guidebook, Reha Guidebook n:o 5. International Standard ISO 7730, Moderate thermal enironments- Determination of the PMV and PPD indices and specification of the conditions for thermal comfort, 1990.
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International
More informationFederation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
More informationEnergy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: maija.virta@halton.com SUMMARY This paper
More informationCAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
More informationDevelopment of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: panu.mustakallio@halton.com
More informationThis article appeared in a journal published by Elsevier. The attached copy is furnished to the author for internal non-commercial research and
This article appeared in a journal published by Elsevier. The attached copy is furnished to the author for internal non-commercial research and education use, including for instruction at the authors institution
More informationEco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015
EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW
More informationSBi 2013:14. Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings
SBi 2013:14 Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Rouzbeh Norouzi,
More informationMistrale. Fusion Terminal
Mistrale Fusion Terminal PUBLICATION NATURAL VENT. 1 SEPT 2015 Features - Slimline energy efficient ventilation solution - Standard and high capacity terminals provide 128 or 256 L/s capacity - Compliant
More informationEFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
More informationAir Conditioning in Green Office Buildings?
Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation
More informationUnder sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
More informationAdaptive strategies for office spaces in the UK climate
International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate
More informationSELECTIVE GLAZING FOR SUN CONTROL
SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level
More informationPerformance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation
Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation M. Kubota, K. Sagara, T. Yamanaka, H. Kotani Division of Global Architecture, Graduate School of Engineering,
More informationENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.
1 ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS. - EXPERIENCE FROM A PLANT RECONSTRUCTION BASED ON A NEW SUPPLY AIR TERMINAL
More informationResearcH JournaL 2009 / VOL 01.01. www.perkinswill.com
ResearcH JournaL 2009 / VOL 01.01 www.perkinswill.com PERKINS+WILL RESEARCH JOURNAL / VOL 01.01 05. CONTEXT BASED DESIGN OF DOUBLE SKIN FACADES Climatic Considerations During the Design Process Ajla Aksamija,
More informationMethods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
More informationDESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple
CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the
More informationResidential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
More informationThermal environments. www.swema.com swema@swema.com Tel. +46 8 94 00 90
ISO 7730 Moderate Thermal Environments Thermal environments Swema equipment for the measurement of Moderate Thermal Environments is designed to comply with the standards: ISO7726 - Thermal environments
More informationWALLS Three common wall types are described below, with their insulation solutions.
APPENDIX 5: Building Envelope Insulation is vitally important for temperature controlled buildings. If fuel (and therefore money) is being used to heat a building, less fuel (and money) will be used if
More informationNEW CEILING MODULE DS-W1 WAVE : SUBSTANTIALLY HIGHER CAPACITY AND ENERGY EFFICIENCY
NEW CEILING MODULE DS-W1 WAVE : SUBSTANTIALLY HIGHER CAPACITY AND ENERGY EFFICIENCY With the groundbreaking new heating and cooling module DS-W1 Wave, compared to conventional radiant solutions, the heating
More informationHow To Make A Building Energy Efficient
An Introduction to Chilled Beams and Ceilings July 2012 Version 1 DISCLAIMER All rights reserved. Apart from any fair dealing for the purposes of private study or research allowed under applicable copyright
More informationCFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER
International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)
More informationUDSA - UDSBD unit heater
APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the
More informationAir-water systems for efficient air conditioning
Air-water systems for efficient air conditioning The art of handling air System overview Passive cooling systems Induction units Façade ventilation units Page 4 Page 6 Page 10 Passive Chilled ceiling Undersill
More informationKan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13
Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13 1 Kan behovsstyrt ventilasjon erstatte lokal varme? Principles Challenges VABAT Project 2 Principles Increased envelope
More informationEnergy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat
Energy Saving Tips Nowadays when Energy costs are skyrocketing and the awareness to environmental issues is increasing, we all want to reduce energy consumption and have a greener lifestyle. Heating &
More informationFläkt Woods Building Future
Energy, Expertise and Environment with Fläkt Woods Fläkt Woods Building Future Saving energy in building ventilation You must save 20% on energy before 2020. Following the Kyoto protocol the European Union
More informationInstructions for designing heating systems.
Instructions for designing heating systems. In order to obtain the required effect, a lower consumption, a smaller quantity of impurities and improved comfort, heat and domestic hot water installations
More informationTHERMAL LOSSES Thermal Losses Calculations
Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak
More informationyour comfort. our world. User Guide Altherma HT For your new Daikin Altherma high temperature heat pump
your comfort. our world. User Guide Altherma HT For your new Daikin Altherma high temperature heat pump Your new Daikin Altherma heat pump In this manual you will find information and guidelines that
More informationSchool Performance Specifications. SPACES Engineering Technical Meeting 22 September 2015
School Performance Specifications SPACES Engineering Technical Meeting 22 September 2015 EFA Facilities Output Specification: Introduced in 2013 to promote: well-integrated and simple buildings that benefit
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationProblem Statement In order to satisfy production and storage requirements, small and medium-scale industrial
Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.
More informationResearch Project F 2071. W. Richter. Manual of thermal comfort of Summer cooling mode
Research Project F 2071 W. Richter Manual of thermal comfort of Summer cooling mode Dortmund/Berlin/Dresden 2007 This publication is a summary of the final report of a project Development of a manual on
More informationOpening the Bonnet. Prof Darren Woolf WYSINWYG 1
Opening the Bonnet Prof Darren Woolf WYSINWYG 1 WYSINWYG What You See Is NOT What You Get: Looking inside the Pandora s Box Prof Darren Woolf WYSINWYG 2 WYSIWYG implies a user interface that allows the
More informationDisplacement ventilation
General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air
More informationAIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
More informationRadiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE
TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically
More informationUsing Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers
Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data
More informationDataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
More informationNew Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
More informationStudies energy efficiency of the renewable sources use considering climate in Latvia
Available online at www.sciencedirect.com ScienceDirect Energy Procedia (25) www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 25 Studies energy efficiency of the renewable
More informationPriority School Building Programme
UPDATE Includes June 2013 changes to FOS Priority School Building Programme Making sense of the new Priority School Output Specification from the Education Funding Agency. How is the output specification
More informationLesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More informationGuidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
More informationHorizontal ventilation units
THE ART OF AIR INNOVATION SINCE 1983 FOR HOMES AND BUSINESSES Horizontal ventilation units Healthy indoor air increases your well-being Today people spend much of their life indoors. It is therefore important
More informationHDA -----------------------------------------------------------
----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS
More informationHow To Design A Room Air Conditioning System
Comparison of HVAC Technology in Buildings Conventional HVAC Technology Bauer Optimising Technology The Differences Room environment (Occupant Comfort) Energy Consumption Architecture Air flows in a room
More informationAIR CONDITIONERS ROOF TOP & UNDERBUNK INSPIRED BY COMFORT NEW RELEASE DOMETIC FRESHJET
AIR CONDITIONERS ROOF TOP & UNDERBUNK INSPIRED BY COMFORT NEW RELEASE DOMETIC FRESHJET 2 HOW AIR CONDITIONING WORKS Air s work on basically the same principle as the cooling units of kitchen refrigerators.
More informationEnergy efficient home design
Energy efficient home design GUIDELINES How an energy efficient home can help you live in comfort and save money An energy efficient home is designed to provide shade and allow cooling breezes to enter
More informationSoftware Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
More informationLife cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE
Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE 3 213 2 2 UPONOR LIFE CYCLE COST COMPARISON OF TAB VS. OTHER HVAC Contents Introduction... 4 Base building... 5 System and tested
More informationTechnical Support Bulletin Nr. 20 Special AC Functions
Technical Support Bulletin Nr. 20 Special AC Functions Summary! Introduction! Hot Start Control! Adaptive Control! Defrost Start Temperature Compensation Control! Anti-Sticking Control! Water Free Cooling
More informationChilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
More informationVENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING
VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEFINITION OF VENTILATIVE COOLING VENTILATIVE COOLING IS APPLICATION (DISTRIBUTION IN TIME AND SPACE) OF VENTILATION AIR FLOW TO REDUCE COOLING LOADS IN
More informationDaikin Altherma Hybrid Heat Pump
your comfort. our world. Daikin Altherma Hybrid Heat Pump Smart heating technology for the best of both worlds Heating Integrated Solutions Ventilation Air Conditioning Refrigeration Forward thinking About
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationDaikin Altherma Hybrid Heat Pump
Daikin Altherma Hybrid Heat Pump Smart technology for the best of both worlds NATIONAL HEAT PUMP 19 JUNE 2014 ICC BIRMINGHAM WINNER Forward thinking Now is the time to rethink the way we heat our homes
More informationManaging Heat Stress in Poultry
Managing Heat Stress in Poultry Amy E. Halls, Monogastric Nutritionist Shur-Gain, Nutreco Canada Inc. Heat stress has several serious and economical effects on poultry. In broilers and turkeys, it can
More informationSolar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
More informationCHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
More informationCHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
More informationWhite paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004
White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004 Contents : 1. Introduction 2. Fundamentals of heating 3. Temperature distribution
More informationASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationSIMULATION - ASSISTED AUDIT OF AN AIR CONDITIONED OFFICE BUILDING
SIMULATION - ASSISTED AUDIT OF AN AIR CONDITIONED OFFICE BUILDING Stephane Bertagnolio Research Assistant Jean Lebrun Professor Jules Hannay Research Engineer Cleide Aparecida Silva Research Engineer Thermodynamics
More informationDaikin Altherma Hybrid Heat Pump
your comfort. our world. Daikin Altherma Hybrid Heat Pump The natural combination Heating Integrated Solutions Ventilation Air Conditioning Refrigeration About Daikin Forward thinking... Daikin has a worldwide
More informationContents. Part 1 General Information... 1. Part 2 Outdoor Units... 9. Part 3 Installation... 50. Part 4 Troubleshooting 73
MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF Contents Part 1 General Information... 1 Part 2 Outdoor Units... 9 Part 3 Installation... 50 Part 4 Troubleshooting 73 Part 5 Control System... 100 Manufacture
More informationPERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING LI CHUNYING DOCTOR OF PHILOSOPHY CITY UNIVERSITY OF HONG KONG FEBRUARY 2012 CITY UNIVERSITY OF HONG KONG 香 港 城 市 大 學 Performance Evaluation of Water-flow
More informationIntegrated Solar Radiant Systems
Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant
More informationClimate control of a bulk storage room for foodstuffs
Climate control of a bulk storage room for foodstuffs S. an Mourik, H. Zwart, Twente Uniersity, K.J. Keesman*, Wageningen Uniersity, The Netherlands Corresponding author: S. an Mourik Department of Applied
More informationAir distribution effectiveness with stratified air distribution systems
Lee, K.S., Jiang, Z., and Chen, Q. 2009 Air distribution effectiveness with stratified air distribution systems, ASHRAE Transactions, 115(2). Air distribution effectiveness with stratified air distribution
More informationGreen Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
More informationPurpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside.
Lab Exercise: Dew Point and Relative Humidity Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside. Relative humidity is a measure
More informationComparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures
Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: kai.siren@tkk.fi
More information3-2. Using the air conditioning system and defogger Automatic air conditioning system
Automatic air conditioning system Airflow and outlets are automatically adjusted according to the temperature setting. Press to display the air conditioning operation screen. Air conditioning operation
More informationEVERYDAY ENGINEERING EXAMPLES FOR SIMPLE CONCEPTS
EVERYDAY ENGINEERING EXAMPLES FOR SIMPLE CONCEPTS Thermal Properties ENGR 3350 - Materials Science Dr. Nedim Vardar Copyright 2015 Thermal Properties of Materials Engage: MSEIP Engineering Everyday Engineering
More informationPool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
More informationHeat Pumps for Swimming Pools
Page 1 of 5 Heat Pumps for Swimming Pools This factsheet provides members with invaluable information about heat pumps and their use for heating swimming pool water. There is a consumer factsheet already
More informationThe Warm Edge for insulating glass
The Warm Edge for insulating glass 1. 3. SGGSWISSPACER 2. 4. The best product on the market by quite an edge Energy saving Lower heating costs through better insulation: the thermally improved spacer SGG
More informationHEATING OF DOMESTIC OUTDOOR SWIMMING POOLS
HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS INTRODUCTION 1. There are no general EU regulations and standards for outdoor swimming pool heating. Local regulations in the member countries are covering most
More informationRPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationOutline. Thermal storage for low carbon buildings. Effect of global warming on design summer year. Environment impacts of buildings
http://www.brighton.ac.uk/csbe Thermal storage for low carbon buildings Kenneth Ip Centre for Sustainability of the Built Environment Outline Background Basic principles of thermal storage in buildings
More informationEffect of Rack Server Population on Temperatures in Data Centers
Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,
More informationSubtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
More informationIntroducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational
More informationInformation paper 20. Prepared by: David Clark. book:
Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information
More informationAll Electrical School
All Electrical School with GS in Quebec Preliminary Results Vasile MINEA Workshop on Canadian Heat Pumps & Refrigeration Activities Montreal, May 10, 2004 Hydro-Quebec Contribution Sector: Commercial,
More informationPerformance of low pressure mechanical ventilation concept with diffuse ceiling inlet for renovation of school classrooms
Downloaded from orbit.dtu.dk on: Jun 22, 2016 Performance of low pressure mechanical ventilation concept with diffuse ceiling inlet for renovation of school classrooms Terkildsen, Søren; Svendsen, Svend
More informationData Centers. Comparing Data Center & Computer Thermal Design
Data Centers Comparing Data Center & Computer Thermal Design By Michael K. Patterson, Ph.D., P.E., Member ASHRAE; Robin Steinbrecher; and Steve Montgomery, Ph.D. The design of cooling systems and thermal
More informationDual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
More informationCOOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -
pcoolingandheating COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - Bjarne W. Olesen, Ph.D. D. F. Liedelt "Velta" Summary Due to intensive use of
More informationCoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
More informationHeat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools
Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL
More informationAir Conditioning, Comfort and Energy in India s Commercial Building Sector
Air Conditioning, Comfort and Energy in India s Commercial Building Sector THINK.CHANGE.DO Leena Thomas Richard dedear Rajan Rawal Ashok Lall PC Thomas University of Technology, Sydney Sydney University
More information