RGA-4001 Single Zone Gas Leak Detector

Size: px
Start display at page:

Download "RGA-4001 Single Zone Gas Leak Detector"

Transcription

1 Product sheet GS7.61 Gas Detector Type Single Zone Gas Leak Detector are panel/wall mounted gas leak detectors for single zone. The RGA control unit has been designed and built according to European regulations to flexibly detect the presence of toxic and/or explosive gas, through the connection of a remote gas leak sensors (Natural Gas, LPG Gas or O). A microprocessor is used to create a complete monitoring and control system with maximum flexibility. Thanks to this and its other features is suitable for commercial applications, industrial use and for underground car parks. The is configured through bit switches for:- Enable/disable gas leak sensor Type of gas detected (explosive or toxic) Intrinsically safe option (on or off) Main alarm relay operation (latching or auto-reset) The has three different alarm levels:- First level alarm 8% L.E.L. or 120ppm Second level alarm 13% L.E.L or 200ppm Main Alarm Level set to 20% L.E.L or 300ppm Model Type Model Description Gas Leak Detector, Single Zone Technical Data Power Supply 230Vac 50Hz +/-10% Back-Up Battery 12Vdc +/-10%, Max 2.2Ah (Option) Power onsumption 230V., Main Alarm Relay 10A 250VA Resistive SPDT; Alarm Limit 20% L.E.L or 300ppm O Pre-Alarm 1 Relay 10A 250VA Resistive SPST; Alarm Limit 8% L.E.L or 120ppm O Pre-Alarm 2 Relay 10A 250VA Resistive SPST; Alarm Limit 13% L.E.L or 200ppm O Fault Relay 10A 250VA Resistive SPST Sensor Fault Short ircuit, Interruption, Sensor Deterioration No of Remote Sensors 1 - Natural Gas, LPG Gas or O Input Signal 4..20mA Device Precision 1% FS Reaction Time < 10 Seconds Start-Up 120 Seconds Self-Diagnostics Delay Sensor Types RGA-4100MET/GPL, RGA-4200MET/GPL, RGA-4400O Manual Test Built-In Max. Sensor Distance 100m able Size 1 mm2 Ambient Temp IP Rating IP44 Mounting Wall Mounting or Panel Door Mounting Dimensions W144 x H144 x D110mm PS GS7.61-1/6

2 SyxthSense Ltd Operation When the remote sensor detects the presence of the target gas a 4-20mA signal is sent to the detector, proportional to the level of gas. The then operates a pre-alarm relay -used for remote sirens or visua lindicators. If the level of gas continues to rise then the second pre-alarm is actuated. In the case of explosive gases, when the level of gas reaches 20%LEL, the main alarm relay is activated to break the electrical supply to the gas safety shut-off valve. The also has a separate volt-free sensor fault relay that actuates if the correct return signal is not sensed by the detector. The can be configured to detect explosive or toxic gases. The front panel has also two overload lights which indicate when a short circuit or an overload has occurred on the sensor wiring. Font Fascia Layout (1) (5) Pre-Alarm 1 The diagram illustrates the front fascia operation. Please refer to below legend to individual items. Battery (2) (6) Pre-Alarm 2 Battery Overload Sensor Overl oad (3) (4) (7) Test (14) Main Alarm (8) (10) Alarm Fault (9) (11) (12) LIE ppm Reset (13) 1) LED. It blinks for about 1 minute (warm up time) when the mains power is supplied. When ready, the LED stays on without blinking. During the initialisation the detector cannot detect the gas. 2).BATTERY LED. It lights up (permanently) when no mains power is present and the control unit is supplied by a 12Vdc battery. It blinks when the battery is flat. 3) BATTERY OVERLOAD LED. If this LED turns on, it means the battery is not connected properly,or it has an anomalous voltage absorption. 4) SENSOR OVERLOAD LED. If this LED turns on, it means there is a short circuit or high current absorption in the sensor, indicating either fault with wiring or with the sensor. 5) PRE- 1 LED. This LED will light up when the gas concentration level has reached 8% of LEL, or 120ppm (ref. O), and the Pre-Alarm 1 relay contact is closed. The relay disenergizes when the 13% of LEL, or 200ppm O, threshold is exceeded. 6) PRE- 2 LED. This LED will light up when the gas concentration level has reached 13% of LEL,or 200ppm (ref. O), and the Pre-Alarm 2 Relay is closed. The buzzer will issue a low frequency sound. The relay disenergizes when dropping below the 13% of LEL, or 200ppm O, threshold. 7) MAIN LED. This LED will light up when the gas concentration level has reached 20% of LEL, or 300ppm (ref. O), and the MAIN relay contact is closed. 8) LED. Indicates an alarm status i.e. explosive or toxic gas has been detected. 9) EXPLOSIVE GAS LED. If this LED is turned on, the sensor is set to detect explosive gases (Methane, LPG, etc.). 10) FAULT LED. This LED blinks when the connected sensors is faulty, if there is an interruption in the cable connection, or if an error was made during the wiring. 12) TOXI GAS LED. If this LED is turned on, the probe is set to detect toxic gas (arbon Monoxide). 12) PRE LEDs. These LEDs light up in sequence according to the environment gas concentration level increase. When the first LED turns on, the gas concentration level has reached8% of LEL and the 1st THRESHOLD relay contact is closed. When the second LED turns on, the gasconcentration level has reached 13% of LEL and the 2nd THRESHOLD relay contact is closed. Whenthe third LED turns on, the gas concentration level has reached 20% of LEL and the MAIN relaycontact is closed. opyright 2012 SyxthSense Ltd. All rights reserved - 05/2012 PS GS7.61-2/6

3 nsi SI I OFF O GAS SyxthSense Ltd 13) RESET BUTT. This button is pressed to clear all memories, or to restore the control unit after a failure. 14) TEST BUTT. Pressing down the TEST button, you can obtain a gas leakage simulation.this way, all pre-alarm LEDs until the final alarm LED will light up in sequence, switching the correspondent relays. onfiguration of Gas Detector (Bit Switches) The has two bit switches on the PB. The left switch is used to control the sensor connected to the system (if the sensor is activated and type of the sensor). The right switch is used to configure the controller itself. S1 OFF OFF sensor activation gas type selection Switch 1 Intrinsic safety selection Switch 2 Main alarm relay functioning mode Power and Relay Terminal Block Sensor Terminal Block SENSOR FIGURATI SWITH 1: SENSOR ENABLE/DISABLE SWITH 2: O SENSOR / GAS (NATURAL GAS/LPG) SENSOR DETETOR FIGURATI SWITH 1: INTRINSI SAFETY ENABLE SWITH 2: RELAY MODE onfiguring the Sensor Bit Switch 1: In position the sensor is activated. If in OFF position the detector does not monitor (it is not necessary to remove the wires). Bit Switch 2: Selects the type of gas monitored. These are labelled as GAS or O. For Natural Gas, LPG Gas and Hydrogen move the bit switch to GAS position. For arbon Monoxide move the bit switch to O position. The front fascia of the detector refers to EN standard symbols for toxic (e.g. arbon Monoxide - O) or explosive gases (e.g. Natural Gas or LPG gas) and illuminates the appropriate LED. onfiguring Detector Mode Bit Switch 1: In position the intrinsic safety mode is activated that this determines the main alarm relay (i.e. gas valve) operation. When intrinsic mode is "" the relay is in a normally open state. When intrinsic mode is in "OFF" position the relay is in a normally closed state. opyright 2012 SyxthSense Ltd. All rights reserved - 05/2012 PS GS7.61-3/6

4 nsi nm M SI I nsi nm M SI I SyxthSense Ltd Bit Switch 2: The second bit switch determines the main alarm relay actuation method. This can be configured to provide either latching or a temporay alarm condition. In "" position the main alarm remains activated even after the concentration of gas has reduced below the alarm threshold. This should be normally selected for auto-reset gas valves. The alarm is reset by pressing "RESET2 button. If the switch is in the "I" position the main alarm relay will actuate for 60 seconds and then if the level of gas has dropped below the alarm threshold, the alarm relay returns to the normal operating state. The indication on the panel fascia and the audible alarm will still indicate main alarm. This mode of operation is used with manual reset gas valves and battery systems to extend the standby battery life. Mainalarmswitch in 'I' position 3 Gas Sensed MainAlarm relay Reset Pressed 60 Seconds Mainalarmswitch in '' position 3 Gas Sensed MainAlarm relay Reset Pressed Time Wiring Diagram and Electrical Installation FAULT RELAY PRE-. 1 PRE-. 2 MAIN RELAY N N N N Ph N /5A Power Supply 230V A N Alarm Note: onnections when Intrinsic Safety is off. Gas Valve (IF STANDBY BATTERY REQUIRED) 12 V BATTERY SENSOR 3 RGA-4100MET/GPL RGA-4200MET/GPL RGA-4400O Main Alarm Relay onnections when Intrinsic Safety is. MAIN RELAY N Gas Valve Installation and Positioning of the Sensor The most essential factor for the proper functioning of the is its correct installation.by following the instructions in this paragraph high accuracy can be obtained, together with the absence of false alarms.the is designed so that it can be mounted externally or built into electrical panels.during installation the normal precautions required for electronic devices should be maintained. Install the device away from sources of heat. Prevent liquids from coming into contact with the ; the external structure has an IP44 grade of protection. opyright 2012 SyxthSense Ltd. All rights reserved - 05/2012 PS GS7.61-4/6

5 SyxthSense Ltd You can connect various types of remote sensors (Natural Gas, LPG Gas, O) to this unit. Therefore, they should be positionedat different heights depending on the type of gas to be detected. Installation heights are: 30 cm from the lowest point of the floor in order to detect heavy gases (L.P.G. etc.) 30 cm from the highest point of the ceiling in order to detect light gases (Methane etc.) 160 cm from the lowest point of the floor in order to detect volatile gases (O, etc.) MOUNTING LEVELS OF GAS DETETORS Light gases (e.g. Natural Gas) Max 30 cm from ceiling Volatile gases (e.g. O) 160 cm from floor It is important to note that the remote sensors should be installed according to the following restrictions: Heavy gases (e.g. LPG) Max. 30 cm from floor 1) The sensors should not be placed near the appliances to be controlled (boilers, burners, industrial kitchens, etc.) but on the opposite side. 2) The sensors should not be affected by smoke, vapour, etc. as they could distort their measurement. 3) The sensors should not be placed near sources of heat, ventilators or fans.it should be noted that the internal sensors of the probe are perishable components with avariable average life span from 5 to 10 years (you can request the relative table). Therefore, after this period of time has elapsed it is advisable to check the fault LEDs regularly. Should these LEDs light up, a specialised technician must replace the sensor. 4) The sensors must be installed in correct way upwards, the sintered head pointing downwards. Switching Power to RGA-4004 Troubleshooting Before turning on the, check the connections have been made as illustrated in the diagrams shown on the relevant pages, and read the warnings carefully. 1) Apply power using the proper switch. This switch should be fitted with protection fuses. 2) You will notice that some LEDs will light up in turn for about 20 seconds to test the LEDs. 3) The LED will continue blinking for about 2 minutes and then remain. Now the is ready for detection. 4) By pushing and maintaining pressure on the MANUAL TEST button a function test can be performed for all pre-alarm relays and main alarm relay, together with LEDs. First the 8% LEL LED, together with the relay, that will switch to its 1st threshold position (terminals 6 and 7 will close). The buzzer will issue a low frequency sound. Then the 13% LEL LED, together with the relay, that will switch to its 2nd threshold position (terminals 8 an 9 will close). The will issue a high frequency sound. Finally the 20% LEL LED, together with the relay, that will switch to its Main Alarm and Zone Memory position. The buzzer will issue a very high frequency sound. When releasing the MANUAL TEST button, you will see the opposite: Only the Main Alarm and the zone alarm LEDs will remain. 5) The main alarm will continue until the RESET button is pressed, clearing the alarm from all the memories. 6) To complete the general test, use SyxthSense approved or equivalent test gas from a pre-calibrated aerosol within 20% of L.E.L. WARNING: Do not use anything other that recommended test gas e.g. use a cigarette lighter, as this can damage the sensors. The maximum concentrations are: 40% L.E.L for methane, 350pp, for carbon monoxide, 0.85% (MOL) for propane. 7) If you want to simulate a zone fault, you only need to disconnect the return cable of the sensor. When the fault LED turns on a continuous sound will warn you of the failure. At the same time,the relevant relay will switch to its position. The Problem No lights are displayed on the fascia of the detector The Solution heck the electrical supply and that the plug-in terminal is correctly installed. opyright 2012 SyxthSense Ltd. All rights reserved - 05/2012 PS GS7.61-5/6

6 SyxthSense Ltd The Problem If the fault LED lights up. If the Sensor Overload LED lights up. If the Over Load Battery LED lights up. If the ontrol Unit is repeatedly issuing analarm If the ontrol Unit is issuing an alarm anddoes not shut off the devices connected to it. If a 12Vdc solenoid valve, which does notwork well, is connected to the. The Solution heck that the wiring plug is inserted correctly. heck that the connecting cables from the to the sensors are intact, and that the sensors are properly powered,and that the signal cable is correctly connected. heck that the power polarity has not been inverted, that no short-circuit is present,that the probes were not damaged during installation, and that no excessive current absorption is present. heck that the connection cables are not short-circuited, that the polarity has not been inverted, orthat the battery is not damaged heck that there are no gas leaks.if the alarm signal and the FAULT indicator light turn on together, check the sensor. heck that the wiring is correct and that the jumper that carries power to the relay has been set properly. All relays must be free from electrical power. heck the drawing of the connections. Direct connection of 12Vdc solenoid valves orsirens to the is not permitted.an external power unit must always be used.the gives a max current of 100mA. Dimensions and Mounting Bracket for Panel TEST RESET 140 Screw Max 5mm 140 Bracket opyright 2012 SyxthSense Ltd. All rights reserved - 05/2012 PS GS7.61-6/6

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P

SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P 2 Alarm Levels Bargraph + LED Indication of Gas Concentration Visual and Audible Signalization of Activated Alarm Levels 2 SPDT 5A/250V Output Relays Shock-Proof

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

WD-AMX Water Detection Controllers

WD-AMX Water Detection Controllers Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation

More information

600-GD & 600-GDL 600 SERIES GAS DETECTOR

600-GD & 600-GDL 600 SERIES GAS DETECTOR 600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING

More information

DUCT SMOKE DETECTOR D4120

DUCT SMOKE DETECTOR D4120 Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity

More information

CO2 Alarm. Operation. Application

CO2 Alarm. Operation. Application CO Alarm 100-77V AC Supply Voltage Two pre-configured alarm and control thresholds Thresholds factory set to customer requirements on dispersive infrared sensing technology Optional internal audible alarm

More information

Fire Standards & Regulations Are you confused?

Fire Standards & Regulations Are you confused? Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Fire & Security DETECTORS

Fire & Security DETECTORS Fire & Security DETECTORS Smoke Sensitivity 0.98 ~.0%/ft Obscuration Ceiling Spacing 50 foot rating for heat sensor Temperature Range 10ºC to 50ºC Humidity 0 to 95% RH, no condensation or icing Dimensions

More information

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.: Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

PUSH BUTTON START INSTALLATION MANUAL

PUSH BUTTON START INSTALLATION MANUAL PUSH BUTTON START INSTALLATION MANUAL ALTHOUGH THIS PRODUCT HAS BEEN THOROUGHLY TESTED KPIERSON TECHNOLOGIES ASSUMES NO RESPONSIBILITY FOR ANY DAMAGE THAT MAY RESULT BY THE INSTALLATION OF THIS PRODUCT.

More information

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 DESCRIPTION CO transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

BEP FD-2 CONTOUR MATRIX FUME DETECTOR

BEP FD-2 CONTOUR MATRIX FUME DETECTOR BEP FD-2 CONTOUR MATRIX FUME DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING GAS SENSORS...3 4 FEATURES...4 5 SPECIFICATION...4 6

More information

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

DKG 972 Gas Burner Safety Control

DKG 972 Gas Burner Safety Control A Honeywell Company Gas Burner Safety Control For 2-stage atmospheric gas burners Flame detection: - Ionisation probe - Infrared-flicker detector IRD 1020.1 - UV flame sensor UVD 971 EN1C-0127SZ20 R0305

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer) Operating Manual for the Electronic Built-in Interval Timer Micro II (Countdown Timer) Note: This document has been designed for our OEM customers. They can use it as supporting material when creating

More information

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual QUALITY STEAM SPECIALTIES SINCE ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual Section: C500 Bulletin: C500.40 Date: 06-26-01 Supersedes: New PRODUCT DESCRIPTION: The Clark-Reliance

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY RV Products Division SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY Airxcel, Inc. RV Products Division P.O. Box 4020 Wichita, KS 67204 1976A376 (1-11) TABLE OF CONTENTS

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Heating Controller. Building Technologies HVAC Products

Heating Controller. Building Technologies HVAC Products 2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

www.ringautomotive.co.uk Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

www.ringautomotive.co.uk Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A SmartChargePro7 RSCPR7-12v, 7A SmartChargePro10 RSCPR10-12v, 10A SmartChargePro15 RSCPR15-12v, 15A SmartChargePro25 RSCPR25-12v, 2 / 6 / 12 / 25A SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A SmartChargePro50

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

SMART SENSOR COLLECTION

SMART SENSOR COLLECTION TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp. EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy. Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module 1. General Description 1 2. General Warnings 1 3. Interface 2 4. Temp Alarms Setting 3 5. Programming 3 6. Light Management 4 7. Installation and

More information

LUCCI AIRFUSION QUEST II CEILING FAN

LUCCI AIRFUSION QUEST II CEILING FAN LUCCI AIRFUSION QUEST II CEILING FAN WITH IR REMOTE INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0 QUEST II IR

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184 EN KNX TH65-AP Thermo-Hygrometer Technical specifications and installation instructions Item number 70184 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe - Infrared flicker detector 1020 - UV flame sensor UVD 971

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

Fire Alarm Control Panel. Family. Operating Manual

Fire Alarm Control Panel. Family. Operating Manual Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

Residential & Commercial Alarm Systems by Gross Security, LLC

Residential & Commercial Alarm Systems by Gross Security, LLC 151 Main Street, Suite, 1, Get these great features with a landline or cellular alarm system from Gross Security, LLC Alarm system prices include installation Base system includes one hour of training

More information

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS WG2 Dimensions: LxHXW: 26 x 14.5 x 29.5 cm INTERNAL Alarm Terminals EXTERNAL Alarm Terminals WG2 Control Unit WaterGuard

More information

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting Overview & Identification The is designed to sense the presence of water and alert a central monitoring system of the potentially destructive situation. Upon water detection, an alarm relay changes state,

More information

MAKING MODERN LIVING POSSIBLE. living connect. Installation and User Guide. Danfoss Heating Solutions

MAKING MODERN LIVING POSSIBLE. living connect. Installation and User Guide. Danfoss Heating Solutions MAKING MODERN LIVING POSSIBLE living connect Installation and User Guide Danfoss Heating Solutions 2 living connect Thank you for buying a Danfoss product Danfoss Heating Solutions 3 Contents 1. System

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

EzFlex Combustible Gas Leak Detector Model EZ40

EzFlex Combustible Gas Leak Detector Model EZ40 User's Guide EzFlex Combustible Gas Leak Detector Model EZ40 Introduction Congratulations on your purchase of the Extech EZ40 Combustible Gas Leak Detector. The EZ40 detects the presence of combustible

More information

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification 1.0 This specification details the attributes and operating characteristics of the MSA Ultima X Series sensors/transmitters.

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases

More information

TYXIA. *2702178_Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF 642-1 channel

TYXIA. *2702178_Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF 642-1 channel Installation and User Guide TYXIA Wireless receiver TYXIA RF 642-1 channel DELTA DORE Bonnemain - 35270 COMBOURG - France E-mail : deltadore@deltadore.com Unit compliant with the requirements of directives:

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

SET1E. Installation & User Instructions. Electronic timeswitch for heating & hot water. Certification Mark

SET1E. Installation & User Instructions. Electronic timeswitch for heating & hot water. Certification Mark SET1E Electronic timeswitch for heating & hot water Installation & User Instructions Certification Mark Index INDEX Installation Product specification 3 Installation 4-5 Wiring 5-10 Replacement 11-13 User

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

PD 100A. Printing data system

PD 100A. Printing data system PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep

More information

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12 Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of

More information

Wireless Alarm System

Wireless Alarm System Wireless Alarm System BLY1 Barcode 5397007039283 BLY1 Wireless Alarm System - Version: 01 Wireless Alarm System.indd 1 01/06/2012 10:57 Getting started... Let s get started... These instructions are for

More information

Operating instructions IV / 2007

Operating instructions IV / 2007 General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation

More information

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit

More information

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

User Manual 1K/2K/3K Online UPS

User Manual 1K/2K/3K Online UPS User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...

More information

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations 12S, 14S, 15S Series Time Delay Relays and Sequencers Time Delay Relays and Sequencers The Therm-O-Disc type 12S, 14S and 15S series time delay relays and sequencers are field-proven devices for controlling

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

TIG INVERTER INSTRUCTION MANUAL

TIG INVERTER INSTRUCTION MANUAL TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop

More information

Manual. Solar Fountain Mobile Phone Charger

Manual. Solar Fountain Mobile Phone Charger EN Manual Solar Fountain Mobile Phone Charger Copyrights 2008 Victron Energy B.V. All Rights Reserved This publication or parts thereof may not be reproduced in any form, by any method, for any purpose.

More information

T5000 T000 LCD Digital Fan Coil Thermostat

T5000 T000 LCD Digital Fan Coil Thermostat T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,

More information

Install Guide 3M-50. Caution. Caution

Install Guide 3M-50. Caution. Caution PG 1 Install Guide 3M-50 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the HVA system before installing or servicing thermostat or any part of the system.

More information

AlarmSense 2-wire detection and alarm system. Product Guide

AlarmSense 2-wire detection and alarm system. Product Guide AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Product Manual ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Intelligent Installation Systems Contents Page 1 Introduction.......................................

More information

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS.  Construction Automotive Industry DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.

More information

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control

More information

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type

More information

Manual Ranging MultiMeter

Manual Ranging MultiMeter Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

COMBUSTIBLE GAS AND HC REFRIGERANT LEAK DETECTOR OPERATING INSTRUCTIONS DETECTS ALL HYDROCARBON & OTHER COMBUSTIBLE GASES JB INDUSTRIES

COMBUSTIBLE GAS AND HC REFRIGERANT LEAK DETECTOR OPERATING INSTRUCTIONS DETECTS ALL HYDROCARBON & OTHER COMBUSTIBLE GASES JB INDUSTRIES LDC-4000 COMBUSTIBLE GAS AND HC REFRIGERANT LEAK DETECTOR OPERATING INSTRUCTIONS DETECTS ALL HYDROCARBON & OTHER COMBUSTIBLE GASES WWW.JBIND.COM 800.323.0811 SALES@JBIND.COM TABLE OF CONTENTS LDC-4000

More information

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/ CW-5000/ 5200 Contents Cautions ---------------------------------------------------------------- 3 Parts introduction --------------------------------------------------- 4 Installation ------------------------------------------------------------

More information

3000W Power Inverter

3000W Power Inverter 3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE

More information

Square D Clipsal C-Bus Network Analyzer

Square D Clipsal C-Bus Network Analyzer Square D Clipsal C-Bus Network Analyzer for Use with C-Bus Wired Networks Instruction Bulletin Retain for future use. Square D Clipsal C-Bus Network Analyzer 63249-420-234A1 Instruction Bulletin 12/2006

More information

TS93 EMR T/PT/TDE. Surface applied door closer

TS93 EMR T/PT/TDE. Surface applied door closer TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double

More information

How To Use A Power Supply On A Powerline 2.2 (Ai)

How To Use A Power Supply On A Powerline 2.2 (Ai) KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang

More information

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw rather than providing multiple choices. The sensor modules used may only be suitable for use with the matching controller so it is wise to read the specifications to make sure the unit suits your application.

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

Series B14 Monitor System

Series B14 Monitor System Series B14 Monitor System Home Office European Office Analytical Technology, Inc. ATI (UK) Limited 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park Collegeville, PA 19426 Delph New Road, Delph Saddleworth

More information

GST301. (Single Protection Zone) Operation Manual

GST301. (Single Protection Zone) Operation Manual GST301 Gas Extinguishing Control Panel (Single Protection Zone) Operation Manual 2 of 19 CONTENTS 1 OVERVIEW... 4 2 TECHNICAL DATA... 4 3 STRUCTURES... 5 3.1 FRONT SURFACE DESCRIPTION... 5 3.1.1 Indicators...

More information