Product Catalog. Packaged Rooftop Air Conditioners Precedent Cooling, Gas/Electric, Heat Pump 5 to 10 Tons 50 Hz RT-PRC039C-EN.

Size: px
Start display at page:

Download "Product Catalog. Packaged Rooftop Air Conditioners Precedent Cooling, Gas/Electric, Heat Pump 5 to 10 Tons 50 Hz RT-PRC039C-EN."

Transcription

1 Product Catalog Packaged Rooftop Air Conditioners Precedent Cooling, Gas/Electric, Heat Pump 5 to 10 Tons 50 Hz March 2015 RT-PRC039C-EN

2 Introduction Packaged Rooftop Air Conditioners Copyright Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Precedent. Precedent features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer-aided run testing and Integrated Comfort Systems. So, whether you re the contractor, the engineer, or the owner, you can be certain Precedent products are built to meet your needs. Through the years, Trane has designed and developed the most complete line of packaged rooftop products available in the market today. Trane was the first to introduce the micro microelectronic unit controls and has continued to improve and revolutionize this design concept. Electromechanical controls are available for simpler applications, and for the more sophisticated, ReliaTel microprocessor controls. The ReliaTel control platform offers the same great features and functionality as the original micro, with additional benefits for greater application flexibility. With its sleek, compact cabinet, Precedent continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products. This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content with obligation to notify any person of such revision or change. Trademarks Revision History All trademarks referenced in this document are the trademarks of their respective owners. RT-PRC039C-EN (15 March 2015) General data 6 to 10 ton updates 2 RT-PRC039C-EN

3 Table of Contents Table of Contents Features and Benefits Standard Features Options Other Benefits Standard Features Variety of Options Other Benefits Application Considerations Selection Procedure Cooling, Gas/Electric Units Cooling Capacity Heating Capacity Air Delivery Selection Selection Procedure Heat Pump Units Cooling Capacity Heating Capacity Air Delivery Selection Model Number Descriptions 5 to 10 Tons General Data Performance Data Evaporator Fan Performance Fan Performance Heating Performance Data Controls ReliaTel Controlled Units Electrical Data Jobsite Connections Dimensional Data Weights Mechanical Specifications RT-PRC039C-EN 3

4 Features and Benefits Standard Features 5-year limited compressor warranty 5-year limited heat exchanger warranty 1-year limited parts warranty Anti-short cycle timer Colored and numbered wiring Convertible airflow Crankcase heaters Discharge line temperature switch for compressor protection Easy access low voltage terminal board (LTB) Filters are standard on all units Foil-faced and edge captured insulation High pressure control IAQ dual sloped and removable non-corrosive drain pans Liquid line refrigerant drier Low ambient cooling to 0 F Low pressure control Operating charge of R-410A Patent-pending hybrid condenser coil for easy cleaning Phase monitor Progressive tubular aluminized steel heat exchanger Provisions for through-the-base condensate drain connections Quick access panels Quick adjust fan motor mounting plate ReliaTel microprocessor controls Reversing valve for cooling and heating mode (available only on heat pump models) Single point power Single side service Standardized components Thermal expansion valve Trane built scroll compressors 4 RT-PRC039C-EN

5 Features and Benefits Options Note: Refer to model number description for option availability. Factory-Installed Options. Black epoxy pre-coated coils CompleteCoat condenser coil Condensate overflow switch Frostat Hinged access doors Stainless steel drain pan Factory-Installed or Field-Installed Options 2" MERV 8 filters or 2" MERV 13 filters with filter removal tool Barometric relief Clogged filter/fan failure switch Discharge air sensing kit Economizer LonTalk communications interface (LCI) Oversized motors (optional on T/Y/W090E and T/Y102E) Reference or comparative enthalpy Tool-less hail guards Trane communications interface (TCI) Field-Installed Options CO2 sensor Dual thermistor remote zone sensor Electric heaters High static drive LP conversion kit Manual outside air damper Motorized outside air dampers Quick adapt curbs Quick start kit Remote potentiometer Roof curb Thermostat Ventilation override accessory Wireless zone sensor Zone sensor RT-PRC039C-EN 5

6 Features and Benefits Other Benefits Standard Features Cabinet design ensures water integrity Ease of service, installation and maintenance Mixed model build enables fastest in the industry ship cycle times Outstanding airflow distribution ReliaTel controls Unmatched product support is one of our finest assets. Trane sales representatives are a support group that can assist you with: Product Application Service Training Special applications Specifications Computer programs and much more Anti-Short Cycle Timer Provides a 3-minute minimum ON time and 3-minute OFF time for compressors to enhance compressor reliability by assuring proper oil return. Belt Drive Motors (Three-phase) For additional static requirements, Precedent three-phase belt drive motors offer capability for a wide range of airflow needs. Colored and Numbered Wiring Save time and money tracing wires and diagnosing the unit. Compressors Precedent contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions, and system back-up applications. Dual compressors are available on 8½ to 10 ton models. Condenser Coil Precedent boasts a patent-pending condenser coil, permanently gapped for easy cleaning. 6 RT-PRC039C-EN

7 Features and Benefits Controls ReliaTel ReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel also provides outputs for building automation systems and expanded diagnostics. For a complete list of ReliaTel offerings, refer to the Other Benefits section within the Features and Benefits section of this catalog. Convertible Units The units ship in a downflow configuration. They can be easily converted to horizontal by simply moving two panels. Units come complete with horizontal duct flanges, so the contractor doesn t have to field fabricate them. These duct flanges are a time and cost saver. Crankcase Heaters These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. Discharge Line Temperature Switch This feature is standard on all units. Dual Sloped Drain Pans Every Precedent unit has a non-corrosive, removable, double-sloped drain pan that is easy to clean and reversible to allow installation of drain trap on either side of the unit. Easy Access Low Voltage Terminal Board Precedent s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature. Foil Faced Insulation All panels in the evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream. Heat Exchanger The compact cabinet features a progressive tubular heat exchanger in low, medium and high heat capacities. The heat exchanger is fabricated using stainless steel burners and corrosion-resistant, aluminized steel tubes as standard on all models. It has an induced draft blower to pull the gas mixture through the burner tubes. The heater has a direct spark ignition system which doubles as a safety device to prove the flame. RT-PRC039C-EN 7

8 Features and Benefits High Pressure Control All units include high pressure control as standard. Low Ambient Cooling All Precedent microprocessor units have cooling capabilities down to 0 F as standard. Low Voltage Connections The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire. Phase Monitoring Protection Precedent units with 3-phase power are equipped with phase monitoring protection as standard. These devices protect motors and compressors against problems caused by phase loss, phase imbalance and phase reversal indication. Quick-Access Panels Remove two screws for access to the standardized internal components and wiring. Single Point Power A single electrical connection powers the unit. Single Side Service Single side service is standard on all units. Standardized Components Components are placed in the same location on all Precedent units. Due to standardized components throughout the Precedent line, contractors/owners can stock fewer parts. Thermal Expansion Valve This feature is standard on all units. Through-the-Base Condensate Every unit includes provisions for through-the-base condensate drain connections. This allows the drain to be connected through the roof curb instead of a roof penetration. 8 RT-PRC039C-EN

9 Features and Benefits Variety of Options Factory-Installed Options Note: Refer to model number description for option availability. Black Epoxy Pre-Coated Coils (not available on microchannel condenser coils) The pre-coated coils are an economical option for protection in mildly corrosive environments. CompleteCoat Condenser Coil These coils provide excellent corrosion resistance as well as uniformity of coverage and coating thickness. This option is available for both fin-tube and microchannel condenser coils. Condensate Overflow Switch A condensate overflow switch is available to shut the unit down in the event that the condensate drain line becomes clogged. This option protects the unit from water overflowing from the drain pan and entering the base of the unit. Frostat This capillary bulb embedded in the face of the evaporator coil monitors coil temperature to prevent evaporator icing and protect the compressor. Recommended for applications with low leaving air temperatures, low airflow, and or high latent load applications. Hinged Access Doors These doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners. Stainless Steel Drain Pan For excellent corrosion and oxidation resistance, the optional stainless steel drain pan provides a cleanable surface that compliment other IAQ solutions such high efficiency filtration (MERV 8 or 13) and demand control ventilation (CO2). Factory-Installed or Field-Installed Options Note: Refer to model number description for option availability. Barometric Relief Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess building pressure. Clogged Filter/Fan Failure Switch A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These sensors allow a zone sensor service light or integrated comfort system to indicate a dirty filter or a fan that s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment. RT-PRC039C-EN 9

10 Features and Benefits Discharge Air Sensing Kit Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel options module. Fresh Air Options Dampers and Economizer 0 to 25% manual or 0 to 50% motorized outside air hoods are available. Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure proper installation. The economizers come with three control options dry bulb is standard; enthalpy and differential enthalpy are optional. High Efficiency Filtration Precedent units offer a variety of high efficiency filtration option. MERV 8 and MERV 13 filters provide additional filtration beyond the capabilities of typical 2" throwaway filters. When MERV 8 or MERV 13 filters are ordered, units come with a filter removal tool. LonTalk Communications Interface The LonTalk communications interface allows the unit to communicate as a Tracer LCI-V device or directly with the generic LonTalk network building automation system controls. Oversized Motors Factory-installed or field-installed oversized motors available for high static applications. Reference or Comparative Enthalpy Measures and communicates humidity while maximizing comfort control. Trane Communication Interface (TCI) Available factory installed or field installed. This module, when applied with the ReliaTel, easily interfaces with Trane s Integrated Comfort System. Tool-less Hail Guards Tool-less, hail protection quality coil guards shall be either factory installed or field installed for condenser coil protection. This option protects the condenser coil from vandalism and/or hail damage. 10 RT-PRC039C-EN

11 Features and Benefits Field-Installed Options Note: Refer to model number description for option availability. CO2 Sensor Demand Control Ventilation (DCV) Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand (need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO2 sensor measures the concentration (parts per million, ppm) of CO2 (carbon dioxide) in the air. As the CO2 concentration changes, the outside air damper modulates to meet the current ventilation needs of the zone. The CO2 sensor kit is available as a field installed accessory. Dual Thermistor Remote Zone Sensor This sensor will reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls. Electric Heaters Electric heat modules are available within the basic unit. High Static Drive Available on many models, this high static drive accessory extends the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory. LP Conversion Kit Provided for field conversion of gas/electric units from natural gas to propane. Quick Adapt Curbs Enables easy conversion of existing Voyager 3 to 10 ton units to Precedent units on replacement jobs. Roof Curbs Available for downflow units. Only three roof curbs for the entire line simplifies curb selection. Remote Potentiometer When properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position. Ventilation Override Accessory With the ventilation override accessory installed, the unit can be set to transition to up to three different pre-programmed sequences for smoke purge, pressurization, and exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This typically would be a hard-wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field-installed accessory. Zone Sensors/Thermostats Available in programmable, automatic and manual styles. RT-PRC039C-EN 11

12 Features and Benefits Other Benefits Easy to Install, Service, and Maintain Because today s owners are very cost conscious when it comes to service and maintenance, the Precedent was designed with direct input from service contractors. This valuable information helped to design a product that would get the service person off the job quicker and save the owner money. Precedent offers outstanding standard features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support. Airflow Distribution Airflow is outstanding. Precedent can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution. Cabinet Integrity For added water integrity, Precedent has a raised 1 1/8" lip around the supply and return of the downflow units to prevent water from blowing into the ductwork. Flexibility Precedent offers ultimate flexibility. Units are built to order in our standard shortest in the industry ship cycle time. ReliaTel Controls ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature. ReliaTel control logic enhances quality and reliability: Prevents the unit from short cycling, considerably improving compressor life. Ensures that the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor. Precedent units with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure. ReliaTel Makes Installing and Servicing Easy ReliaTel eliminates the need for field installed anti-short cycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them. The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer. ReliaTel Makes Testing Easy ReliaTel requires no special tools to run the Precedent unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the low voltage terminal board and the unit will walk through its operational steps automatically. 12 RT-PRC039C-EN

13 Features and Benefits The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit. As long as the unit has power and the system on LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly. ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort Systems. Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example). Other ReliaTel Benefits The ReliaTel built-in anti-short cycle timer, time delay relay and minimum on time control functions are factory tested to assure proper operation. ReliaTel softens electrical spikes by staging on fans, compressors and heaters. Intelligent fallback is a benefit to the building occupant. If a component fails, the unit will continue to operate at predetermined temperature setpoint. Intelligent anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats. The same ReliaTel board fits all packaged gas/electric and cooling with electric heat models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel. Unit Cabinet The compact cabinet with rounded corners takes up less room. The beveled and ribbed top aesthetically pleasing and designed to prevent water from pooling. VariTrac Building Automation System When Trane s changeover VAV system for Roof Top Unit light commercial applications is coupled with Precedent, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac. Rigorous Testing All of Precedent s designs were rigorously rain tested at the factory to ensure water integrity. Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging design. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested to 3206 kpa (465 psig). The assembled unit is leak tested to 4137 kpa (600 psig). All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it meets rigorous Trane requirements. RT-PRC039C-EN 13

14 Application Considerations Application of this product should be within the cataloged airflow and cooling considerations. Barometric Relief This product line offers an optional barometric relief damper for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space. Note: The effectiveness of barometric relief damper during economizing operation is system related. Pressure drop of the return air system should be considered to control building pressurization. Black Epoxy Coil The coils are manufactured with a thermoset vinyl coating that is bonded to the aluminum fin stock prior to the fin stamping process. These coils are an economical option for protection in mildly corrosive environments. Note: Not to be used where seacoast applications exist. Clearance Requirements The recommended clearances identified with unit dimensions should be maintained to assure adequate service maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel. CompleteCoat Condenser Coil The coils provide protection from corrosive environments and are ideal for seacoast applications. Condensate Trap The evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the cooling cycle. Heating Operation (Gas/Electric Models Only) The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50% outside air or a minimum mixed air temperature of 40 F. Low Ambient Cooling The Precedent line features, with ReliaTel microprocessor controls, low ambient cooling down to 0 F. The following features or options need to be included/considered when low ambient applications are required: continuous fan operation, crankcase heaters, thermal expansion valves, frostat. Contact a local Trane representative for more assistance with low ambient cooling applications. Unit Pitch These units have reversible sloped condensate drain pans. Units must be installed level. Any unit slope must be toward the side of unit where condensate drain is connected. 14 RT-PRC039C-EN

15 Selection Procedure Cooling, Gas/Electric Units Cooling Capacity Note: Cooling capacity procedure is the same for electric heat (T*C) and gas heat (Y*C). Step 1 Calculate the building s total and sensible cooling loads at design conditions. Use the Trane calculation methods or any other standard accepted method. Factors used in unit selection: Packaged cooling with optional electric heat Total cooling load: 17.3 kw/59 MBh Sensible cooling load: 11.7 kw/40 MBh Airflow: 3400 m 3 h/2000 cfm Electrical characteristics: /50/3 Summer design conditions: entering evaporator coil: 27 C/80 F DB/19 C/60 F WB Outdoor ambient: 35 C/95 F External static pressure: 90 Pa/0.36 in. wg Downflow configuration EER: 10.4 COP: 3.1 Economizer Step 2 As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal kw per ton (3.517 kw per ton) or Btuh per ton (12 MBh per ton); then round up to the nearest unit size kw/3.517 = approx. 5 tons 59 MBh/12 MBh = approx. 5 tons Step 3 Table 3, p. 23 (Table 4, p. 24) shows that a TSC060ED has a gross cooling capacity of kw/62 MBh and13.4 kw/45.72 MBh sensible capacity at 3400 m 3 h /2000 cfm and 35 C/95 F DB outdoor ambient with 27 C/80ºF DB, 19 C/60 F WB air entering the evaporator. To find capacity at intermediate conditions not in the table: When the design conditions are between two numbers in the capacity table, use interpolation to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended. Step 4 To select the correct unit that meets the building s requirements, deduct the fan motor heat from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor cfm and static pressure. To determine the total unit static pressure: External static duct system 90 Pa/0.36 wg Standard filter 2 inches from Table 107, p. 119 (Table 108, p. 119) 15 Pa/0.06 wg Economizer (100% outside air) (worst case) 45 Pa/0.18 wg Electric heater size 6 kw (see Heating Capacity section to determine heater size) 20 Pa/0.08 wg Total static pressure 170 Pa/0.68 wg RT-PRC039C-EN 15

16 Selection Procedure Cooling, Gas/Electric Units Heating Capacity Air Delivery Selection Note: The evaporator fan performance, Table 21, p. 41 (Table 22, p. 42) has deducted the pressure drop for a filter already in the unit. Therefore, the actual total static pressure is: = 155 Pa = 0.62 wg. With 3400 m 3 h and 155 Pa/2000 cfm and 0.62 wg. Table 21, p. 41 (Table 22, p. 42) shows 0.51 kw/0.69 bhp for this unit. Note: Following the table is the formula to calculate Fan Motor Heat 1.07 x fan kw = kw/2.72 x bhp = MBh 1.07 x = 0.80 kw/2.72 x = 2.73 MBh Now subtract the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity: kw = kw/62 MBh = MBh Net Sensible Cooling Capacity: 13.4 kw = 12.6 kw/45.72 MBh = MBh Subtracting sensible from total capacity to find latent capacity: Net Latent Capacity: = 4.77 kw/ = MBh Step 5 Compare resulting capacities to the building load. If the performance will not meet the required load of the building s total or sensible cooling load, try a selection at the next higher size unit. Note: Heating capacity procedure DIFFERS for electric heat (T*C) and gas heat (Y*C) units Step 1 Calculate the building heating load using the Trane calculation form or other standard accepted method. Step 2 Size the system heating capacity to match the calculated building heating load. The following are building heating requirements: Total heating load of 14.4 kw/50 MBh 3400 m 3 h/2000 cfm TSC060EDR units with optional electric heat: 380V/3 phase power supply The electric heat accessory capacities are listed in Table 129, p From the table, there are 3 heating capacities available for the TSC060ED, 7.5 kw/26 MBh, 10.9 kw/38 MBh, and 14.4 kw/50 MBh at 380 V. Referring to Table 129, p. 136, the electric heater selection that will supply 14.4 kw/ 50 MBh of heat is BAYHTRR423B. YSC060EDR units with gas heat: Fuel natural gas For the YSC060ED, two heating capacities available are available: 19.6 kw/67 MBh and 29.3 kw/100 MBh input models shown in Table 111, p The output capacities of these furnaces are 15.7 kw/ 54 MBh and 23.4 kw/80 MBh, respectively. The low heat model with 15.7 kw/54 MBh output best matches the building requirements, indicating a YSC060EDRL should be selected. Note: Air Delivery procedure is the same for electric heat and gas heat units. External static pressure drop through the air distribution system has been calculated to be 155 Pa. Use Table 21, p. 41 for a TSC060ED at 3400 m3/h and 155 Pa. The belt drive motor will give the desired airflow at a rated kw of 0.51 and 965 rpm. 16 RT-PRC039C-EN

17 Selection Procedure Heat Pump Units External static pressure drop through the air distribution system has been calculated to be 0.62 inches of water. Use Table 22, p. 42 for a TSC060ED at 2000 cfm and 0.62 static pressure. The belt drive motor will give the desired airflow at a rated bhp of 0.69 and 965 rpm. Selection Procedure Heat Pump Units Cooling Capacity Step 1 Calculate the building s total and sensible cooling loads at design conditions. Use the Trane calculation methods or any other standard accepted method. Factors used in unit selection: Total cooling load: 20.8 kw/71 MBh Sensible cooling load: 13.2 kw/45 MBh Airflow: 4080 m 3 h/2400 cfm Electrical characteristics: /50/3 Summer design conditions: entering evaporator coil: 27C DB, 19C WB (80F DB, 67F WB) Outdoor ambient: 35C DB (95F DB) External static pressure: Pa (0.46 in.wg) Downflow configuration Economizer Step 2 As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size. 71 MBh / 12 MBh = approx. 6 tons Step 3 Table 15, p. 35 (Table 16, p. 36) shows that a WSC072ED has a gross cooling capacity of kw (80.00 MBh) and kw (57.81 MBh) sensible capacity at 4080m 3 /h (2400 cfm) and 35C DB (95F DB) outdoor ambient with 27C DB, 19C WB (80F DB, 67F WB) air entering the evaporator. To find capacity at intermediate conditions not in the table: When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity. Note: Extrapolation outside of the table conditions is not recommended. Step 4 To select the correct unit that meets the building s requirements, deduct the fan motor heat from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor cfm and static pressure. To determine the total unit static pressure: External static duct system Economizer from Table 109, p. 120 (Table 110, p. 120) (100% outside air) Electric heater size 11.3 kw from Table 113, p. 121 (see Heating Capacity section to determine heater size) Total static pressure External static duct system Pa (0.46 wg) 27.4 Pa (0.11 wg) 7.5 Pa (0.03 wg) Pa (0.60 wg) Pa (0.46 wg) RT-PRC039C-EN 17

18 Selection Procedure Heat Pump Units Heating Capacity Air Delivery Selection With 4080m 3 /h (2400 cfm) and Pa (0.60 wg). Table 49, p. 69 (Table 50, p. 70) shows.52 kw (.70 bhp) for this unit. Note: Following the table is a formula to calculate Fan Motor Heat x Fan kw = kw (2.720 x Fan bhp = MBh) x 0.52 kw = 0.81 kw (2.720 x 0.70 bhp = 2.75 MBh) Now subtract the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity: kw = kw/80.0 MBh = MBh Net Sensible Cooling Capacity: kw = kw/57.81 MBh = MBh Step 5 Compare results to original load requirements. If the performance will not meet the required total or sensible cooling load, try a selection at the next higher size unit. Step 1 Calculate the building heating load using the Trane calculation form or other standard accepted method. Step 2 Size the equipment using Table 121, p. 126 (Table 122, p. 127) to match the heating loads at design conditions. Total heating load of 19.0 kw/65 MBh Outdoor Ambient (Winter): -8C DB/17F DB Indoor Return Temperature: 21C DB/70F DB Airflow: 3400 m 3 /h/2000 cfm Use the integrated portion of Table 121, p. 126 (Table 122, p. 127) for the WSC072E to determine capacity at winter design conditions. The mechanical heating portion of the heat pump will provide 12.0 kw/41.15 MBh. Step 3 Because 12.0 kw/41.15 kw is less than the building s required heating capacity at winter design conditions, a supplementary heater must be selected kw kw = 7.0 kw/65 MBh MBh = MBh From Table 130, p. 137, the BAYHTRS418B heater will deliver 11.3 kw (39 MBh) at 380 volts which will be adequate to do deliver the necessary heat. External static pressure drop through the air distribution system has been calculated to be Pa/0.60 inches of water. Use Table 49, p. 69 (Table 50, p. 70) for a WSC072ED at 4080m3/h (2400 cfm) and Pa (0.60 wg) static pressure. The belt drive motor will give the desired airflow at a rated kw of 0.52 (0.70 bhp) and 826 rpm. 18 RT-PRC039C-EN

19 Model Number Description 5 to 10 Tons Y S C E 3 R L A * * Digit 1 Unit Type T DX cooling Y DX cooling, gas heat W Packaged heat pump Digit 2 Efficiency S Standard Efficiency Digit 3 Airflow C Convertible Digit 4,5,6 Nominal Gross Cooling Capacity (MBh) ton (17.6 kw) ton (21.1 kw) 090 7½ ton (26.4 kw) 102 8½ ton (29.9 kw) ton (35.1 kw) Digit 7 Major Design Sequence E R-410A refrigerant Digit 8 Voltage Selection D /50/3 Digit 9 Unit Controls R ReliaTel microprocessor K European Digit 10 Heating Capacity 0 No electric heat 7 L Low heat 8 H High heat 8 Digit 11 Minor Design Sequence A First sequence Digit 12,13 Service Sequence ** Factory assigned Digit 14 Fresh Air Selection 0 No Fresh air A Manual outside air damper 0 50% 1 B Motorized Outside air damper 0 50% C Economizer, dry bulb 0 100% without barometric relief 4 D Economizer, dry bulb 0 100% with barometric relief 4 E Economizer, reference enthalpy 0-100% without barometric relief 3,4 F Economizer, reference enthalpy 0-100% with barometric relief 3,4 G Economizer, comparative enthalpy 0 100% without barometric relief 3,4 H Economizer, comparative enthalpy 0 100% with barometric relief 3,4 Digit 15 Supply Fan/Drive Type/ Motor 0 Standard drive 3 1 Oversized motor Digit 16 Hinged Service Access/ Filters 0 Standard panels/standard filters A Hinged access panels/standard filters B Standard panels/2" MERV 8 filters C Hinged access panels/2" MERV 8 filters D Standard panels/2" MERV 13 filters E Hinged access panels/2" MERV 13 filters Digit 17 Condenser Coil Protection 0 Standard coil 1 Standard coil with hail guard 2 Black epoxy pre-coated condenser coil 3 Black epoxy pre-coated Condenser coil with hail guard 4 CompleteCoat condenser coil 9 5 CompleteCoat condenser coil with hail guard 9 Digit 18 Through the Base Provisions 0 No through-the-base provisions Digit 19 Disconnect/Circuit Breaker (three-phase only) 0 No disconnect/no circuit breaker Digit 20 Convenience Outlet 0 No convenience outlet Digit 21 Communications Options 0 No communications interface 1 Trane communications interface 2 LonTalk communications interface Digit 22 Refrigeration System Option 0 Standard refrigeration system 5 Digit 23 Refrigeration Controls Note: Applicable to digit 7 = E 0 No refrigeration control 2 1 Frostat 6 Digit 24 Smoke Detector 0 No smoke detector Digit 25 System Monitoring Controls 0 No monitoring control 1 Clogged filter switch 2 Fan failure switch 3 Discharge air sensing tube 4 Clogged filter switch and fan failure switch 5 Clogged filter switch and discharge air sensing tube 6 Fan failure switch and discharge air sensing tube 7 Clogged filter switch, fan failure switch and discharge air sensing tube A Condensate drain pan overflow switch B Clogged filter switch and condensate drain pan overflow switch C Fan failure switch and condensate drain pan overflow switch D Discharge air sensing and condensate drain pan overflow switch E Clogged filter switch, fan failure switch and condensate drain pan overflow switch F Clogged filter switch, discharge air sensing tube and condensate drain pan overflow switch G Fan failure switch, discharge air sensing tube and condensate drain pan overflow switch H Clogged filter switch, fan failure switch, discharge air sensing and condensate drain pan overflow switch Digit 26 System Monitoring Controls 0 No monitoring controls A Demand control ventilation (CO 2) 10 Digit 27 Unit Hardware Enhancements 0 No enhancements 1 Stainless steel drain pan Model Number Notes 1. Manual outside air damper will ship factory supplied within the unit, but must be field installed. 2. High pressure control crankcase heaters are standard on all units. 3. Belt drive is standard on all units. 4. Economizer with barometric relief is for downflow configured units only. Order economizer without barometric relief for horizontal configuration. Barometric relief for horizontal configured units must be ordered as field-installed accessory. 5. Standard metering devices are TXVs. 6. Frostat is available as factory-installed option only. 7. Electric heaters are available only for field-installed options. 8. Available only for gas heat models. 9. Not available on heat pumps. 10. Demand control ventilation option includes wiring only. The C0 2 sensor is a field-installed only option. RT-PRC039C-EN 19

20 General Data Table 1. General data 5 to 10 tons cooling and gas/electric, standard efficiency Cooling Performance (a) Gross Cooling - kw (MBh) COP (EER) (b) Nominal Airflow - m 3 /h (cfm) ARI Rated Airflow - m 3 /h (cfm) Net Capacity - kw (MBh) IEER System Power (kw) Compressor 5 Tons 6 Tons 7½ Tons 8 Tons 10 Tons T/YSC060ED T/YSC072ED T/YSC090ED T/YSC102ED T/YSC120ED 18.2 (62.0) 3.05 (10.4) 3400 (2000) 3400 (2000) 17.6 (60.0) (79.0) 3.08 (10.5) 4080 (2400) 3570 (2100) 22.0 (75.0) (92.0) 2.96 (10.1) 5100 (3000) 4460 (2625) 25.2 (86.0) (105.0) 2.96 (10.1) 5780 (3400) 5050 (2975) 29.3 (100.0) (119.0) 2.78 (9.5) 6800 (4000) 5950 (3500) 32.5 (111.0) Number/Type 1/Scroll 1/Scroll 1/Scroll 2/Scroll 2/Scroll Sound Outdoor Sound Rating (db) (c) Outdoor Coil - Type Lanced Lanced Lanced Lanced Lanced Configuration Tube Size OD mm (in) Face Area m 2 (sq ft) Rows/FPI Full Face 7.94 (0.3125) 1.02 (10.96) 3/16 Full Face 7.94 (0.3125) 1.58 (17.00) 3/16 Full Face 7.94 (0.3125) 1.58 (17.00) 3/16 Intertwined 7.94 (0.3125) 1.84 (19.83) 3/16 Intertwined 7.94 (0.3125) 1.84 (19.83) 3/16 Indoor Coil - Type Lanced Lanced Lanced Lanced Lanced Configuration Tube Size OD mm (in) Face Area m 2 (sq ft) Rows/FPI Refrigerant Control Drain Connection Number/Size (in) Full Face 7.94 (0.3125) 0.72 (7.71) 3/16 Expansion Valve 1/0.75 NPT Full Face 7.94 (0.313) 0.92 (9.89) 3/16 Expansion Valve 1/0.75 NPT Full Face 7.94 (0.313) 0.92 (9.89) 3/16 Expansion Valve 1/0.75 NPT Face Split 7.94 (0.3125) 1.15 (12.36) 3/16 Expansion Valve 1/0.75 NPT Face Split 7.94 (0.3125) 1.15 (12.36) 4/16 Expansion Valve 1/0.75 NPT Outdoor Fan - Type Propeller Propeller Propeller Propeller Propeller Number Used/Diameter (in.) Drive Type/No. Speeds Air Flow - m 3 /h (ft 3 /min.) No. Motor kw (HP) Motor rpm 1/560 (22) Direct/ (2900) 1/0.3 (0.40) 950 1/660 (26) Direct/ (5100) 1/0.56 (0.75) 950 1/660 (26) Direct/ (5200) 1/0.56 (0.75) 950 1/660 (26) Direct/ (5500) 1/0.56 (0.75) 950 1/660 (26) Direct/ (5800) 1/0.56 (0.75) 950 Belt Drive Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal Number Used/Diameter (in)/width (in) Drive Type/Number Speeds Number Motors Standard Motor Power - kw (HP) Oversized Motor Power - kw (HP) Motor RPM - Standard/Oversized Motor Frame Size Filters (d) Type Furnished (No.) Size Recommended - mm (No.) Size Recommended - in Refrigerant Charge (e) 1 280x280 (11x11) Belt/Variable Speed (1.5) 1450/ 56 Throwaway (2) 508x762x50 (2) 20x30x x305 (12x12) Belt/Variable Speed (1.5) 1450/ 56 Throwaway (4) 406x635x50 (4) 16x25x x305 (12x12) Belt/Variable Speed (2.0) 2.2 (3.0) 1450/ Throwaway (4) 406x635x50 (4) 16x25x2 kg (lbs.) of R-410A 3.49 (7.7) 5.35 (11.8) 5.44 (12.0) continued on next page 1 381x381 (12x12) Belt/Variable Speed (2.0) 2.2 (3.0) 1450/ Throwaway (4) 508x635x50 (4) 20x25x x381 (15x15) Belt/Variable Speed (3.0) 2850/ 56 Throwaway (4) 508x635x50 (4) 20x25x2 Circuit (7.7) Circuit (8.0) Circuit (5.8) Circuit (6.3) 20 RT-PRC039C-EN

21 General Data Table 1. General data 5 to 10 tons cooling and gas/electric, standard efficiency (continued) Heating Performance (f) (Gas/Electric Only) Heating Models Low High Heating Input - kw (MBh) Low High Heating Ouput - kw (MBh) Low High Steady State Efficiency% Low High No. Burners Low High No. Stages Low High Gas Supply Line Pressure G20 (minimum/maximum) (MB) G25 (minimum/maximum) (MB) G31 (minimum/maximum) (MB) Gas Connection Pipe Size (in) Low High 5 Tons 6 Tons 7½ Tons 8 Tons 10 Tons T/YSC060ED T/YSC072ED T/YSC090ED T/YSC102ED T/YSC120ED G80 G (67) 29.3 (100) 15.7 (54) 23.4 (80) /25 20/30 25/45 1/2 NPT 1/2 NPT G120 G (100) 48.9 (167) 23.4 (80) 39.1 (134) /25 20/30 25/45 1/2 NPT 3/4 NPT G120 G (100) 48.9 (167) 23.4 (80) 39.1 (134) /25 20/30 25/45 1/2 NPT 3/4 NPT G150 G (125) 60.9 (208) 29.3 (100) 48.7 (166) /25 20/30 25/45 3/4 NPT 3/4 NPT G150 G (125) 60.9 (208) 29.3 (100) 48.7 (166) /25 20/30 25/45 3/4 NPT 3/4 NPT (a) Cooling performance is rated at 35 C (95 F) ambient, 27 C (80 F) entering dry bulb, 19 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 340/360, depending below or above 19,000 W (65,000 Btu/h). (b) EER is rated at ARI conditions. (c) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table Sound Power Level. (d) Optional 2" MERV 8 and MERV 13 filters also available. (e) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. (f) Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/Electric units only. RT-PRC039C-EN 21

22 General Data Table 2. General data 5 to 10 tons heat pumps, standard efficiency Cooling Performance (a) Gross Cooling - kw (MBh) COP (EER) (b) Nominal Airflow - m 3 /h (cfm) ARI Rated Airflow - m 3 /h (cfm) Net Capacity - kw (MBh) IEER System Power (kw) Heating Performance (a) High Temperature Capacity - kw (MBh) COP System Power - kw Compressor 5 Tons 6 Tons 7½ Tons 10 Tons WSC060ED WSC072ED WSC090ED WSC120ED 17.6 (60.0) 3.05 (10.4) 3400 (2000) 3400 (2000) 17.0 (58.0) (54.0) (80.0) 3.37 (11.5) 4080 (2400) 3570 (2100) 22.3 (76.0) (72.0) (96.0) 3.11 (10.6) 5100 (3000) 4460 (2625) 26.7 (91.0) (90.0) (122.0) 2.93 (10.0) 6800 (4000) 5950 (3500) 33.7 (115.0) (115.0) Number/Type 1/Scroll 1/Scroll 1/Scroll 2/Scroll Sound Outdoor Sound Rating (db) (c) Outdoor Coil - Type Lanced Lanced Lanced Lanced Configuration Tube Size OD mm (in) Face Area m 2 (sq ft) Rows/FPI Refrigerant Control Full Face 7.94 (0.3125) 1.02 (10.96) 3/16 Expansion Valve Full Face 7.94 (0.3125) 1.58 (17.00) 3/16 Expansion Valve Full Face 7.94 (0.3125) 1.58 (17.00) 3/16 Expansion Valve Intertwined 7.94 (0.3125) 1.84 (19.83) 3/16 Expansion Valve Indoor Coil - Type Lanced Lanced Lanced Lanced Configuration Tube Size OD mm (in) Face Area m 2 (sq ft) Rows/FPI Refrigerant Control Drain Connection Number/Size (in) Full Face 7.94 (0.3125) 0.72 (7.71) 3/16 Short Orifice 1/0.75 NPT Full Face 7.94 (0.3125) 0.92 (9.89) 3/16 Short Orifice 1/0.75 NPT Full Face 7.94 (0.3125) 0.92 (9.89) 4/16 Short Orifice 1/0.75 NPT Face Split 7.94 (0.3125) 1.15 (12.36) 4/16 Short Orifice 1/0.75 NPT Outdoor Fan - Type Propeller Propeller Propeller Propeller Number Used/Diameter (inches) Drive Type/No. Speeds Face Area m 3 /h (ft 3 /min) No. Motor/kW (HP) Motor rpm 1/560 (22) Direct/ (2900) 1/0.3 (0.40) 950 1/660 (26) Direct/ (5100) 1/0.56 (0.75) 950 1/660 (26) Direct/ (5200) 1/0.56 (0.75) 950 1/660 (26) Direct/ (5800) 1/0.56 (0.75) 950 Belt Drive Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal Number Used/Diameter (in)/width (in) Drive Type/Number Speeds Number Motors Standard Motor Power - kw (HP) Oversized Motor Power - kw (HP) Motor RPM - Standard/Oversized Motor Frame Size Filters (d) Type Furnished (No.) Size Recommended - mm (No.) Size Recommended - in 1 280x280 (11x11) Belt/Variable Speed (1.5) 1450/ 56 Throwaway (2) 508x762x50 (2) 20x30x x305 (12x12) Belt/Variable Speed (1.5) 1450/ 56 Throwaway (4) 406x635x50 (4) 16x25x x305 (12x12) Belt/Variable Speed (2.0) 2.2 (3.0) 1450/ Throwaway (4) 406x635x50 (4) 16x25x2 Refrigerant Charge (e) - kg (lbs) of R-410A 3.86 (8.5) 5.53 (12.2) 6.17 (13.6) 1 381x381 (15x15) Belt/Variable Speed (3.0) 2850/ 56 Throwaway (4) 508x635x50 (4) 20x25x2 Circuit (7.3) Circuit (6.6) (a) Cooling performance is rated at 35 C (95 F) ambient, 27 C (80 F) entering dry bulb, 19 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 340/360, depending below or above 19,000 W (65,000 Btu/h). (b) EER is rated at ARI conditions. (c) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table Sound Power Level. (d) Optional 2" MERV 8 and MERV 13 filters also available. (e) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 22 RT-PRC039C-EN

23 Performance Data Table 1. Gross cooling capacities kw 5 tons standard efficiency T/YSC060ED (SI) Ambient Temperature m 3 /h Ent Entering Wet Bulb Entering Wet Bulb Entering Wet Bulb Airflow DB (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC Ambient Temperature m 3 /h Ent Entering Wet Bulb Entering Wet Bulb Airflow DB (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. TGC = Total Gross Capacity 3. SHC = Sensible Heat Capacity RT-PRC039C-EN 23

Packaged Cooling with Electric Heat Rooftop Units

Packaged Cooling with Electric Heat Rooftop Units Packaged Cooling with Electric Heat Rooftop Units Voyager 12½ - 25 Tons - 60 Hz December 2003 RT-PRC002-EN Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager

More information

Packaged Gas/Electric Rooftop Units

Packaged Gas/Electric Rooftop Units Packaged Gas/Electric Rooftop Units Precedent 3-10 Tons 60 Hz October 2004 Introduction Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged

More information

Packaged Gas/Electric Rooftop Units

Packaged Gas/Electric Rooftop Units Packaged Gas/Electric Rooftop Units Voyager 12½ 25 Tons 60 Hz December 2003 Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager continues to provide the highest

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT 48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED

More information

TWE+TTA TWE+TWA 6.25-20 T.R.

TWE+TTA TWE+TWA 6.25-20 T.R. TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.

More information

27 1 /2 to 50 Ton - 60 Hz Voyager Commercial

27 1 /2 to 50 Ton - 60 Hz Voyager Commercial RT-DS-9 May 1998 First Printing July 1998 Packaged Rooftop Air Conditioners RT-DS-9 27 1 /2 to 50 Ton - 60 Hz Voyager Commercial Features and Benefits SM Over the years the Voyager product line has developed

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined

More information

Cooling/Heat Pump Convertible Air Handlers

Cooling/Heat Pump Convertible Air Handlers Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water 2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

FTQ. Daikin Inverter Ducted Heat Pump

FTQ. Daikin Inverter Ducted Heat Pump FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative

More information

GCS16 GCS20 WARNING CAUTION

GCS16 GCS20 WARNING CAUTION Service Literature Corp. 0110 L6 Revised 12 2004 GCS16/GCS20 SERIES UNITS GCS16 GCS20 2 to 5 Ton GCS16/20 series units in the 2 to 5 ton (7.0 to 17.0 kw) cooling size are packaged combination gas heat

More information

Cased/Uncased Coils For Gas And Oil Furnaces

Cased/Uncased Coils For Gas And Oil Furnaces Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Rheem Indoor Coils are designed for use

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess

More information

INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-211 REV. 7 Supersedes Form No. C11-211 Rev. 6 INDOOR COILS RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-211 REV. 3 Supersedes Form No. C11-211 Rev. 2 INDOOR COILS RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS

More information

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE UPF/HORIZONTAL 2-, VARIABLE SPEED GAS-FIRED FURNACE XV80 MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VB TUD2B00A9V3VB, TUD2C00A9V5VB TUD2C00B9V5VB, TUD2DA9V5VB TUD2DB9V5VB, TUD2DA9V5VB

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]

More information

50LC Ultra High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3 to 5 Nominal Tons Product Data

50LC Ultra High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3 to 5 Nominal Tons Product Data Ultra High Efficiency Cooling Only/Electric Heat Packaged Rooftop 3to5NominalTons Product Data C11536 Carrier s Most Efficient Commercial Rooftop Ever! TABLE OF CONTENTS PAGE UNIT FEATURES... 4 MODEL NUMBER

More information

INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-212 REV. 1 Supersedes Form No. C11-212 INDOOR COILS RCFM- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES

More information

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

How To Buy A Lennox Power System

How To Buy A Lennox Power System HVAC for Schools A Comprehensive Look at Products for a Clean, Comfortable Learning Environment Why Schools Choose Lennox Even as resources for schools continue to be constrained, education leaders and

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Single Package Vertical Air Conditioners. Vert-I-Pak

Single Package Vertical Air Conditioners. Vert-I-Pak Single Package Vertical Air Conditioners Vert-I-Pak Installs easily in a closet for quiet operation and provides a more homelike appearance for your guests. THE EXPERTS IN ROOM AIR CONDITIONING A Better

More information

GCS16-024-030-036-048-060

GCS16-024-030-036-048-060 Packaged Unit & Gas Heat 2-5 Ton Capacity 50,000-120,000 Btuh Input Heating Capacity GCS16-024-030-036-048-060 FEATURES Designed for outdoor rooftop or ground level installations Down-flow or horizontal

More information

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment 5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary

More information

Product Data. Split System Cooling 22-1904-1F-EN. March 2015

Product Data. Split System Cooling 22-1904-1F-EN. March 2015 Product Data Split System Cooling 4TTR4018L1000A 4TTR4024L1000A 4TTR4025L1000A 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000A Note:

More information

K-Series Rooftop Units 60 HZ ASHRAE 90.1 COMPLIANT

K-Series Rooftop Units 60 HZ ASHRAE 90.1 COMPLIANT PRODUCT SPECIFICATIONS PACKAGED GAS ELECTRIC KG K-Series Rooftop Units 60 HZ Bulletin No. KGA-092-50 (3/206) ASHRAE 90. COMPLIANT 7.5 to 2.5 Tons Net Cooling Capacity 86,000 to 38,000 Btuh Gas Input Heat

More information

SINGLE PACKAGE VERTICAL AIR CONDITIONERS

SINGLE PACKAGE VERTICAL AIR CONDITIONERS SINGLE PACKAGE VERTICAL AIR CONDITIONERS AIR CONDITIONERS l HEAT PUMPS l ELECTRIC HEAT QUIETER BY DESIGN SIMPLE TO INSTALL CONCEALED INSTALLATION www.friedrich.com VERT-I-PAK ideal for extended stay properties,

More information

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MC, PC, FC, HD, UC 600-2000 CFM 1.5-5 TON COILS UPFLOW/DOWNFLOW FULL CASED FC UPFLOW PARTIAL CASED PC UPFLOW UNCASED

More information

RNDC. Houston, TX. HVAC O&M Manuals. September 10, 2014. Paulson-Cheek Mechanical, Inc. 6145 Northbelt Parkway Suite F Norcross, GA 30071

RNDC. Houston, TX. HVAC O&M Manuals. September 10, 2014. Paulson-Cheek Mechanical, Inc. 6145 Northbelt Parkway Suite F Norcross, GA 30071 Paulson-Cheek Mechanical 6145 Northbelt Parkway Suite F Norcross, GA 30071 770. 729. 0076 770. 729. 1076 Fax RNDC Houston, TX HVAC O&M Manuals September 10, 2014 General Contractor: Mechanical Engineer:

More information

INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES

INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES FORM NO. C11-213 REV. 4 Supersedes Form No. C11-213 Rev. 3 INDOOR COILS RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM

More information

catalog Single Package Vertical Air Conditioners and Heat Pumps

catalog Single Package Vertical Air Conditioners and Heat Pumps catalog Single Package Vertical Air Conditioners and Heat Pumps Catalog: SK145.00-EG1 (1008) TABLE OF CONTENTS Single Package Vertical Units Introduction...............................................................................

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

Lower Energy Costs with Rooftop Air-Conditioning Package Units

Lower Energy Costs with Rooftop Air-Conditioning Package Units Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency

More information

AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency

AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2 AIR HANDLERS AIR HANDLERS RHLA- Efficiency featuring R-22 Refrigerant RHLL- Efficiency featuring Earth-Friendly R-10A Refrigerant earth friendly refrigerant

More information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

Operation and Installation Manual. Max Series

Operation and Installation Manual. Max Series Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance Installation, Operation, and Maintenance Packaged Rooftop Air Conditioners Precedent Gas/Electric 5 to 10 Tons 50 Hz SAFETY Only qualified personnel should install and service the equipment. The installation,

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF

More information

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems 1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system

More information

Energy Efficiency. Energy Efficient Home Cooling:

Energy Efficiency. Energy Efficient Home Cooling: Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models. Up to 17.0 SEER, Up to 12.8 EER

Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models. Up to 17.0 SEER, Up to 12.8 EER Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models Up to 17.0 SEER, Up to 12.8 EER SAVING ENERGY WITH INTELLIGENCE Designed to intelligently achieve the lowest total cost of ownership Energence

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Installation Instructions

Installation Instructions 05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:

More information

Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011

Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011 Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws

More information

180, 210, AND 240 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LGA PACKAGED COOLING & GAS HEAT LHA PACKAGED HEAT PUMP

180, 210, AND 240 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LGA PACKAGED COOLING & GAS HEAT LHA PACKAGED HEAT PUMP ENGINEERING DATA 180, 210, AND 240 MODELS LCA PACKAGED COOLING & ELECTRIC HEAT LGA PACKAGED COOLING & GAS HEAT LHA PACKAGED HEAT PUMP PACKAGED L SERIES 50hz 15, 17.5 & 20 Ton (52.8, 61.5 & 70.3 ) *Net

More information

LSA LSE, LSR & LST LPA LPE, LPG & LPH LAA LAE, LAG & LAH COMMERCIAL WALK-IN COOLERS AND FREEZERS

LSA LSE, LSR & LST LPA LPE, LPG & LPH LAA LAE, LAG & LAH COMMERCIAL WALK-IN COOLERS AND FREEZERS FOR COOLERS ABOVE +34ºF Low silhouette, draw through, high velocity units Capacity from 4,500 to 39,000 BTU/HR./10ºF TD LSA LSE, LSR & LST FOR COOLERS AND FREEZERS FROM -20ºF TO +34ºF Low silhouette, draw

More information

F9MXE. Product Specifications

F9MXE. Product Specifications 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports

More information

DESIGN STANDARDS SECTION 23 60 00

DESIGN STANDARDS SECTION 23 60 00 PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.

More information

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy

More information

Explosion-Proof Electric Unit Heaters

Explosion-Proof Electric Unit Heaters Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,

More information

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Data XL20i 4TWZ0024, 036, 048 & 060 with ComfortLink II and Charge Assist 2, 3, 4 & 5 Tons PUB. NO. 22-1826-01 Features and Benefits Two Climatuff compressors Efficiency

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW - AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Product Data. FV4C Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL

Product Data. FV4C Performancet Series Fan Coil Sizes 002 Thru 006 PREMIUM ENVIRONMENTALLY SOUND FAN COIL Performancet Series Fan Coil Sizes 002 Thru 006 Product Data PREMIUM ENVIRONMENTALLY SOUND FAN COIL The is the premium air handler combining the proven technology of Carrier fan coils with environmentally

More information

T CLASS ROOFTOP UNITS 60 HZ Bulletin No. 210392 August 2007 Supersedes May 2007

T CLASS ROOFTOP UNITS 60 HZ Bulletin No. 210392 August 2007 Supersedes May 2007 E N G I N E E R I N G D A T A P A C K A G E D G A S / E L E C T R I C TG T CLASS ROOFTOP UNITS 60 HZ Bulletin No. 210392 August 2007 Supersedes May 2007 MODEL NUMBER IDENTIFICATION ASHRAE 90.1 COMPLIANT

More information

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08 Air Volume Requirement Air conditioning systems are engineered with a specific amount of indoor air passing across the surface of the evaporator coil. The amount of air is measured in cubic feet per minute.

More information

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs

More information

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO. Upflow/ Horizontal Left, Downflow/ Horizontal Right Speed Two Stage Condensing Gas-Fired Furnace XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB Direct Vent

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation

More information