Temperature Controller

Size: px
Start display at page:

Download "Temperature Controller"

Transcription

1 Your Lab Starts Here Temperature Controller Thermolyne LT2416DX1

2 2 Table of Contents: 2

3 3 Introduction The 16 segment, four programmable, furnace (Group D1) consists of a microprocess-based dual-mode PID (Proptional, Integral, Derivative) temperature controller with over-temperature protection and appropriate output switching devices to control the chamber temperature. The digital readout continuously displays the measured chamber temperature (upper display) and the setpoint chamber temperature (lower display) while in user run mode. The display reverts to showing the mnemonic (upper display) and cresponding set value parameter value (lower display) in the set up mode. These programmable controller modules can be utilized as either single setpoint controllers as a single program controllers defined by 16 segments of programming capability. A special feature, the call segment type, can be utilized to link segments from one program to another. This translates to a maximum of 1 program consisting of 64 segments. The controller discussed in this manual is used in a variety of Thermolyne furnace model types. Thermolyne has assigned a unique controller part number that cresponds with a specific Thermolyne furnace model. The control group of these furnace models described in sales literature is D1. A list of the Thermolyne replacement controller part numbers within group D1 are as follows: CN71X75 CN71X84 CN71X87 CN71X90 CN71X92 CN71X98 LT2416DX1 3

4 4 Understanding The Controller: Understanding The Controller: Controller Terminology Mnemonic - Mnemonic is a term used to reference what is shown in the upper display of the controller. Mnemonics will consist of numbers, such as the measured chamber temperature as well as letters, such as list headers. Whether the mnemonic is a group of letters numbers will depend upon what display you have navigated to. Mnemonics cannot be altered using the arrow keys. - is a term used to reference what is shown in the lower display of the controller. s will consist of numbers, such as deviation alarm setpoint as well as letters, such as the holdback function setting. Whether the parameter is a group of letters numbers will depend upon what display you have navigated to. Unlike mnemonics, parameters can be altered using the arrow keys. Value - Value is a term used to describe a parameter, particular a parameter that is associated with numbers. F example, the setpoint temperature, deviation alarm setting, segment number, ect. 4

5 5 Understanding The Controller: Levels of Operation The controller has four levels of operation. 1. Operat Level: Select mnemonics & cresponding parameters can be viewed and/ altered at the operation level. Controllers are facty installed in the furnace with the intent to be operated at this level. The operat level is also commonly referred to as the user run mode. 2. Full Level: All mnemonics & cresponding parameters can be viewed at the operat level, however only select parameters can be altered pending the edit level setting. The full level of operation is passwd protected. 3. Edit Level: Like the full level, the edit level is passwd protected. All mnemonics & cresponding parameters are defined in the edit level as either: - Alterable (ALtr) = Mnemonic & cresponding parameter can be viewed as well as altered at the operat full level. - Promoted (PrO) = Mnemonic & cresponding parameter are promoted to the HOME DISPLAY list & can be altered at the operat full level. - Read Only (read) = Mnemonic & cresponding parameter can be viewed at the operat full level, but cannot be altered. - Hidden (HidE) = Mnemonic & cresponding parameter cannot be viewed at the operat full level and cannot be altered. 4. Configuration Level: This special level is double passwd protected. The fundamental characteristics of the controller are set up at the configuration level. Extreme caution must be used if an operat enters the configuration level. The configuration level may also be referred to as the configuration mode of operation. F me infmation on how to access the various levels of operations see Access List Section. 5

6 6 16 Segment Programmable Models w/otp OP SP 2 REM AUTO RUN Button/Indicat Name Description 1. LED Output 1 Illuminates when controller energizes elements. 2. OP2 LED Output 2 Not activated f furnace operation. 3. SP2 LED Setpoint Not activated f furnace operation REM LED Remote Not activated f furnace operation. Setpoint 5. Upper Display Display Indicates measured chamber temperature mnemonic value (parameter). 6. Lower Display Display Indicates set point chamber temperature mnemonic. 7. Auto/Man Button Not activated f furnace operation. 8. Run/Hold Button once to initiate a program. twice to place a program in hold state. & hold button f 2 seconds to cancel a program in the run state. 9. Auto Mode LED Illuminates to indicate furnace is in operating in auto mode. 10. Manual Mode LED Not activated f furnace operation. 11. Run LED Illuminates to indicate controller is executing a program. 12. Hold LED Illuminates to indicate controller has paused program execution. 13. Page Button to select a new list header. 14. Scroll Button to view a mnemonic and parameter setting within a list header. 15. Down Button to decrease the value in the lower display. 16. Up Button to increase the value in the lower display. 6

7 7 HOME DISPLAY The controller is powered ON when the furnace is powered ON. The controller will perfm a sht power on self-test sequence and automatically revert to the home display of the operat level user run mode. The home display indicates the measured chamber temperature (also known as the process variable) in the upper display window and the chamber set point temperature in the lower display window. NOTE: This is what the home display appears like Measured Chamber Temp Set Point Temp AUTO RUN From the home display you can perfm one of five functions: 1. Adjust the chamber single set point temperature indicated in the lower display using the keys. (NOTE: Can not adjust single set point temperature if a program is being executed in a hold/pause state.) 2. Cycle through the mnemonic parameter/values promoted to the HOME LIST by using the key. 3. Cycle through the mnemonic list headers using the key. 4. Initiate a program by using the RUN button. 5. Place a program in pause mode canceling a program using the button. ( button once to pause a running program. & hold the button to cancel a program.) 7

8 8 HOME DISPLAY list of mnemonics and parameter settings: By pressing the key, the mnemonics promoted to the home display will appear in the upper lower display window. The cresponding mnemonic parameter/value will be displayed in the lower window. Some parameters/values can be altered using the keys when displayed and others cannot. The following pages include detailed controller drawings showing the various mnemonics of the home list C Chamber Measured Temperature Indicates all temperature values are expressed in degrees C. Cannot be altered in the HOME DISPLAY. OP Output Power Level Number is a % value of the output power being applied to the heating elements. Cannot be altered in the HOME DISPLAY. C.id Controller Identification Number This number may not be set to 75 on all control modules this manual is written f. The value has no impact on controller operation. Cannot be altered in the HOME DISPLAY. PrG Program Number to change 1-4 Number presents the program. (4 programs total) 8

9 9 AUTO IdHi 2416 RUN 50 High Deviation Alarm 50 to change The parameter number displayed represents the current alarm setpoint. NOTE: The deviation alarm is intended f load protection and should never be set lower than 10 degrees. Setting a lower deviation alarm may interfere with the PID control process. tune 2416 OFF Tune Feature OFF to change Status of tune feature/function is OFF. Can be altered from HOME DISPLAY to initiate a tune. NOTE: Tuning matches the characteristics of the controller to that of the process to eliminate temperature undershoot and/ overshoot of setpoint. Tuning should be initiated with the furnace at room temperature. F me infmation on this feature, please see the Tuning & PID Sections of this manual. 9

10 10 Mnemonic List Headers From the home display, the controller can also be cycled through the various mnemonic list headers by using the key. The various lists contain mnemonics and parameters set values that dictate how the controller operates Measured chamber temperature Set point temperature C AUT O RUN Measured chamber temperature Indicates all temperature values are expressed in degrees C. run 2416 LiSt Run List. The run list contains mnemonics that crespond to a program. You can start, end, place a program in check in the run list. You can also check the status of a running program. - What segment is currently being executed - How much program time has elapsed ProG 2416 LiSt Program List. The program list contains mnemonics that are used specifically to enter a program into the controller. 10

11 11 AL 2416 LiSt Alarm List. The alarm list contains mnemonics that define the alarm setting of the controller. Atun 2416 LiSt Auto Tune List. The auto tune list contains mnemonics that pertain to the tuning feature functions of a controller Pid 2416 LiSt Pid List. The Pid list contains mnemonics that define how well the controller responds to change in der to keep a stable chamber temperature. The proptional bands, integral, and derivative time bands as well as gain scheduling are listed in the Pid. cms 2416 LiSt Communication List (Comms). The communication list contains the address mnemonic that is utilized f RS232 communications. ACCS 2416 LiSt Access List. The Access list is used to enter the configuration mode as well as define mnemonic access levels. The Access list is passwd protected. 11

12 12 Run List Section The Run list contains mnemonics that detail a program. The run list is considered part of the set up mode of at the operat level. When a program is not being executed you can perfm two functions in the Run List. 1. Initiate a program (StAt = run) 2. Activate the display segment feature (SEG.d = YES) Deactivate the display segment feature (SEG.d = no) If you activate the display segment by altering SEG.d to YES, the lower home display will indicate which segment type is being executed in the lower home display window when the program is actually being executed. The segment type will cycle on and off with the temperature. When a program is being executed you can perfm three functions in the Run List. 1. Suspend Pause the program (StAt = hold) 2. Terminate and Reset the program (StAt = OFF) 3. Activate the display segment feature (SEG.d = YES) Deactivate the display segment feature (SEG.d = no) When a program is being executed (run) you can also check the following: 1. Programmer Set Point (PSP = Setpoint temperature of the active segment) 2. Cycles Remaining (CYC = Number of times the cycle has to repeat itself) 3. Segment (SEG = Active segment number of the program being executed) 4. Segment Type (StyP = Active segment type of the program being executed) 5. Segment Time (SEG.t = Amount of time [Expressed in min/hours/sec as defined by ramp and dwell units in the program list] remaining in the active segment in the program.) 6. Target Set Point (tgt = Setpoint temperature of the active segment) 7. Ramp Rate (rate = ramp rate of the active segment [only appears if the active segment type is defined as a ramp rate in the program list]) 8. Program Time (PrG.t = Amount of time [Expressed in hours] remaining in the active program. The following pages will step you through the various displays you will see in the run list. 12

13 13 Run List Mnemonics (run LiSt) (When a program is NOT being executed) run 2416 LiSt Run List Header PrG Program Number Paramete 1-4 Number presents the program. (4 programs total) StAt 2416 OFF Current Status of Program Program paused OFF Program reset & not being executed Program being executed (running) FASt 2416 no Fast Run through program (Facty preset to no) no This feature is not activated f furnace operation, all though the parameter can be changed when a program is not being executed. 13

14 14 SEG.d 2416 no AUTO RUN Active Segment Displayed (Facty preset to no) no Active segment is not flashed in the lower display during program execution. Active segment flashes in the lower display during program execution. Run List Mnemonics (run LiSt) (While a program is being executed) run 2416 LiSt Run List Header PrG Program Number 1-4 Program number currently being executed. cannot be adjusted. StAt 2416 run Status of program run Program being executed (running) Program paused Program reset & not being executed 14

15 15 PSP CYC SEG Programmer Set Point 235 This number will increase and decrease as a program is being executed. The oscillation is dictated by the program segment. Cannot be adjusted in this display. Cycles Remaining in the Program 0 The parameter number displayed represents the number of times the program will repeat itself. Cannot be adjusted in this display. Active Segment Number 1 This number represents what segment of the program is currently being executed.. Cannot be adjusted in this display. StyP 2416 rmp.r Active Segment Type rmp.r This parameter represents the segment type that is currently being executed by the controller. Cannot be adjusted in this display. SEG.t Segment Time Remaining 7.1 This number represents the amount of time remaining in the current segment of the program being executed. Defined in minutes, hours, seconds by the program setup. Cannot be adjusted on this display. 15

16 16 NOTE: Pending the segment type currently being executed will dictate what display(s) will appear next. tgt Target Set Point [this window appears only if the segment type is defined as a ramp rate ramp time] 500 This number represents the segment setpoint temperature currently being executed by the controller. Cannot be adjusted on this display. rate 2416 AUTO AUTO AUTO 1.0 RUN PrG.t RUN FASt 2416 no RUN Ramp Rate [this window appears only if the segment type is defined as a ramp rate ramp time] 1.0 This parameter represents the ramp rate of the segment that is currently being executed by the controller. Defined in degrees C per min/hour/sec in the program setup. Cannot be adjusted on this display. Program Time Remaining 0.1 This parameter number represents the amount of time remaining in the current program. Expressed in hours. Cannot be adjusted in this display. Fast Run Through Program (Facty preset to no) no This feature is not activated f furnace operation, all though parameter can be changed. 16

17 17 SEG.d 2416 AUTO no RUN Active Segment Displayed (Facty preset to no) no Active segment is not flashed in the lower display during program execution. Active segment flashes in the lower display during program execution. Program List Section The Program list contains mnemonics that are used to define a custom program. This section explains how to enter a custom program into the controller. A program can only consist of up to 16+ segments with the call feature. Each segment is defined as one of five types. 1. Ramp = Measured chamber temperature ramps linearly from it's current value at either a defined rate within a defined amount of time to a defined setpoint chamber temperature. Note: Measured chamber temperature can be ramped up (temperature increase) ramped down (temperature decrease). If a segment type is set as a ramp rate, mnemonics appear as follows: A) Ramp Rate (rmp.r) = Ramp rate B) Setpoint Temp (tgt) = Defined setpoint temperature. C) Rate of change (rate) = Defined rate of temperature increase decrease. Ramp units (rmp.u) define the time associated (hour, minutes, seconds) with rate of change. If a segment type is set as a ramp time, mnemonics appear as follows: A) Ramp Time (rmp.t) = Ramp time B) Setpoint Temp (tgt) = Defined setpoint temperature. C) Duration (dur) = Defined amount of time in which the measured chamber temp is allowed to reach the setpoint temp. 2. Dwell = A defined amount of time duration that is required to hold the chamber measured temperature constant. If a segment type is set as a dwell, mnemonics appear as follows: A) Dwell (dwell)= Dwell time 17

18 18 B) Duration (dur) = Amount of defined time in which the measured chamber temperature is to be controlled at the setpoint temperature f this segment only. Dwell units (dwl.u) define the time associated (hours, minutes, seconds) with the duration parameter. 3. Step = Step segment allows a new setpoint temperature to be defined. The control module will attempt to achieve the new setpoint temperature instantaneously with no ramping. If a segment type is set as a step, mnemonics appear as follows: A) Step (StEP) = Step Instantaneously. B) Setpoint (tgt) = Defined setpoint temperature 4. End = Defines signals the end of a program. If a segment type is set end, mnemonics appear as follows: A) End (End) = End program. B) End Type (End.t) = Defines what the controller is supposed to do now that the program is done running. There are three settings choices: 1. Dwell (dwell) = Controller holds the last programmed setpoint temp (tgt) of the program. 2. Reset (rset) = Controller resets and reverts to single setpoint operation/mode. 3. Segment Output Power (S OP) = Controller reverts from auto mode of operation to manual mode of operation and controls power to the heating element as expressed in a percentage of output power. WARNING: S OP end type should never be selected! Due to the configuration of the controller Thermolyne could not remove this option from the list of choices of the end type. Selecting S OP will result in uncontrollable chamber temperature and will shten element and thermocouple life span. NOTE: If you desire the chamber temperature to cool down to ambient temp (25C) at completion of the program, you will need to step the setpoint to 25 in the 2 nd to last segment of the program and select (dwell) as the end type OR you will need to reset the single setpoint temperature to 25C pri to initiating the program and select (rset) as the end type. 18

19 19 5. Call = The call segment links segment(s) from another program, as a subroutine, to the existing program. If a segment type is set call, mnemonics appear as follows: A) Program number (PrG.n) = Program number linking to. B) Cycle number (cyc.n) = How many times controller is to repeat the linked segment during program execution. The following pages of this section will step you through the various displays you will see in the program list. There is also an example program and spreadsheet you can use to help define your custom program. Program List Mnemonics (ProG LiSt) Programming the Controller The following section explains how to enter a program into the control module with use of an example program. Program protocol: (example) Our example program calls to heat from ambient to 500C at a rate of 10C per minute. Once the furnace reaches 500C, we need to hold the temperature at 500C f 2 hours. After two hours of holding at 500C, we need to increase the chamber temperature to 800C at a rate of 5C per minute. Once the furnace reaches 800C, we need to hold the temperature at 800C f 3 hours. After three hours, we need the chamber temperature to go back to ambient as quickly as possible. Segment 1 rmp.r Segment 2 dwell Segment 3 rmp.r Segment 4 dwell Segment 5 & 6 End Hr 2 Hr 3 Hr 4 Hr 5 Hr 6 Hr 7 Hr 8 Hr 9 Hr 10 Hr (60 Min) (120 Min)(180 Min) (240 Min)(300 Min) (360 Min) (420 Min) (480 Min) (540 Min) (600 Min) To help visualize our example program we chart the chamber temperature (temperature versus time) in a graph. 19

20 20 The Program List (ProG LiSt) contains the mnemonics that are used to define the program. The keystroke procedures required to enter a program, such as the example program are as follows: From the HOME DISPLAY, repeatedly to the Program List window. ProG 2416 LiSt Program List Header Hb 2416 Hi Holdback Disables holdback feature f all segments in a program Holds the program when the measured chamber temperature deviates below set point minus the hold back unit value. Hi Holds the program when the measured chamber temperature deviates above set point plus the hold back unit value. Holds the program when the measured chamber temperature deviates below above the setpoint by me than the holdback unit value. Hb U Hold Back Units 10 The parameter number represents the deviation tolerance from the setpoint temperature f the holdback feature. (value should never be adjusted below 10 f optimal furnace results) 20

21 21 rmp.u 2416 min Ramp Units min Ramp units defined in minutes. Ramp units defined in hours. Ramp units defined in seconds. dwl.u 2416 min Dwell Units min Dwell units defined in minutes. Dwell units defined in hours. Dwell units defined in seconds. CYC.n 2416 AUTO RUN 1 Cycles of Program 1 The parameter number displayed represents the number of time(s) the program will repeat itself. If set to "cont" the program will repeat itself continuously indefinitely NOTE: The previous mnemonics will need to be set f each and every program. They apply to the entire program. NOTE: The following mnemonics actually define the ramp and dwells of our program. 21

22 22 SEG.n Segment Number 1 This parameter number represents the 1 st segment of the program. type 2416 rmp.r Segment Type Ramp to a new setpoint within a defined amount of time rmp.r Ramp to setpoint at defined rate. Our program calls f a ramp rate of 10C per minute. Hold a desired setpoint temperature f a defined amount of time Steps temperature to a new setpoint as quickly as possible. Ends the program. Links segment(s) from one program as a subroutine to the existing program. [This feature allows f me than 16 segments of programmability.] tgt Target Temperature [this window appears only if the segment type is defined as a ramp rate] 500 Setpoint temperature. Our program calls f setpoint of 500C. 22

23 23 rate Rate of temperature change [this window appears only if the segment type is defined as a ramp rate] 10 number represents the rate of temperature change. Our program calls f a rate of 10C per minute. (We defined the time units in rmp.u) SEG.n Segment Number 2 This parameter number represents the 2nd segment of the program. type 2416 dwell Segment Type AUTO RUN Ramp to a new setpoint at defined rate of increase decrease Ramp to a new setpoint within a defined amount of time dwell Hold a desired setpoint temperature f a defined amount of time. Our program calls to hold the temperature at 500C f 2 hours. Steps temperature to a new setpoint as quickly as possible. Ends the program. Links segment(s) from one program as a subroutine to the existing program. [This feature allows f me than 16 segments of programmability.] 23

24 24 dur Duration [this window appears only if the segment type is defined dwell] 120 Represents the amount of time allowed f the temperature to hold at the 1 st setpoint of 500C (Remember: we set dwl.u to min, which means 2 hours = 120 minutes) SEG.n 2416 AUTO RUN 3 Segment Number 3 This parameter number represents the 3 rd segment of the program. type 2416 rmp.r Segment Type rmp.r Ramp to a new setpoint at defined rate of increase decrease Ramp to a new setpoint within a defined amount of time Hold a desired setpoint temperature f a defined amount of time Steps temperature to a new setpoint as quickly as possible. Ends the program. Links segment(s) from one program as a subroutine to the existing program. [This feature allows f me than 16 segments of programmability.] 24

25 25 tgt Target Temperature [this window appears only if the segment type is defined as a ramp rate] 800 number represents the target (set point) temperature of 800C. rate Rate of temperature change [this window appears only if the segment type is defined as a ramp rate] 5 number represents the rate of temperature change. Our program calls f a rate of 5C per minute. (We defined the time units in rmp.u) SEG.n Segment Number 4 This parameter number represents the 4 th segment of the program. 25

26 26 type 2416 dwell Segment Type Ramp to a new setpoint at defined rate of increase decrease Ramp to a new setpoint within a defined amount of time dwell Hold a desired setpoint temperature f a defined amount of time. Our program calls to hold the temperature at 500C f 2 hours. Steps temperature to a new setpoint as quickly as possible. Ends the program. Links segment(s) from one program as a subroutine to the existing program. [This feature allows f me than 16 segments of programmability.] dur Duration [this window appears only if the segment type is defined dwell] 180 Represents the amount of time allowed f the temperature to hold at the 2 nd setpoint of 800C (Remember: we set dwl.u to min, which means 3 hours = 180 minutes) SEG.n Segment Number 5 This parameter number represents the 5 th segment of the program.. 26

27 27 type 2416 StEP Segment Type Ramp to a new setpoint at defined rate of increase decrease Ramp to a new setpoint within a defined amount of time Hold a desired setpoint temperature f a defined amount of time StEP Steps temperature to a new setpoint as quickly as possible. Ends the program. Links segment(s) from one program as a subroutine to the existing program. [This feature allows f me than 16 segments of programmability.] tgt Target Temperature [this window only appears if the segment type is set to step] 25 Setpoint temperature. By "stepping" the setpoint from 800C to 25C in segment 5, the controller will attempt to achieve the new setpoint as quickly as possible as the program calls f. SEG.n Segment Number 6 This parameter number represents the 6 th segment of the program.. 27

28 28 type 2416 AUT O RUN End Segment Type Ramp to a new setpoint at defined rate of increase decrease Ramp to a new setpoint within a defined amount of time Hold a desired setpoint temperature f a defined amount of time Steps temperature to a new setpoint as quickly as possible. End Ends the program. Links segment(s) from one program as a subroutine to the existing program. [This feature allows f me than 16 segments of programmability.] End.t 2416 rset End Type Ends & resets the program. However, the controller will hold the chamber temperature at the last setpoint (target) of the program. rset Ends & resets the program. Controller will automatically revert to single setpoint operation. Ends & resets the program. However, chamber temperature is controlled by an output power percentage. WARNING: DO NOT SET THE END TYPE OF A PROGRAM TO THE "S OP" PARAMETER. THIS CHOICE COULD NOT BE ELIMINATED AT THE OPERATOR LEVEL HOWEVER. ELEMENT FAILURE IS LIKELY TO OCCUR. THERMOLYNE FURNACES ARE NOT DESIGNED TO OPERATE OFF A PERCENTAGE OF POWER. This completes entering the example program into the controller and hopefully gives you an ideal as to how the programmer list functions. 28

29 29 Call Segment type: Our example program did not execute a "call" segment. The call segment feature allows you to enter custom programs, which consist of me than 8 segments. The following displays are what you can expect to see when you "call" a segment from another program as a subroutine. type 2416 call Segment Type Ramp to a new setpoint at defined rate of increase decrease Ramp to a new setpoint within a defined amount of time Hold a desired setpoint temperature f a defined amount of time Steps temperature to a new setpoint as quickly as possible. Ends the program. call Links segment(s) from one program as a subroutine to the existing program. [This feature allows f me than 16 segments of programmability.] PrG.n 2416 AUT O RUN 2 Program Number cyc.n AUT O RUN 2 represents the program number the controller will call a segment from within. Number of Cycles f the Called Program 1 number represents the number of times the called subroutine segment will repeat itself 29

30 30 SEG.n AUT O RUN Segment Number 9 number represents the segment number of the called program that will be executed next in the program. (The segment number displayed will be in chronological der coinciding with the previous segments of the program.) This completes the list of windows you can expect to see if your custom program requires the call feature to be used as subroutine. 30

31 31 Alarm List Section Understanding Alarm Types: Process Alarms The control module has two process alarms: A process alarm warns there is a problem with the chamber temperature the controller is trying to control. 1. Deviation High Alarm (IdHi) = A deviation alarm can be reset by the operat. Facty preset to 50, means if the chamber measured temperature exceeds the set point temperature at any given time during furnace operation by me than 50 degrees, the controller will alarm. The alarm code will flash on the home display to alert operats and the controller will attempt to remove all power from the heating elements to stop the thermal runaway condition. The deviation alarm is intended f load protection and should never be set lower than 10 degrees. Setting a low deviation alarm (below 10 degrees) may interfere with the PID control process. 2. Full Scale High Alarm (2FSH) = The full scale high alarm is facty preset in the configuration mode and is not visible in the alarm list at the operat level. Unlike the deviation alarm, no attempts by operats to reset this alarm value should be made. This alarm is facty preset to a temperature value that exceeds the maximum recommended operating temperature of the unit. If a thermal runaway condition should occur this alarm protects the furnace from further damage by attempting to remove power from the elements. If the deviation alarm is set properly f the application, this alarm will never be activated in a thermal runaway condition as the deviation alarm will be tripped first. Understanding Process Alarms: What happens when an alarm condition occurs: Events that occur during a process alarm condition: - The home display will flash the alarm err mnemonic with the measured chamber temperature in the lower display to alert operats of the condition. - The controller will stop sending AC power to a mechanical relay contact. As a result the contact will open, effectively de-energizing the heating elements. - Both process alarms are non-latching, which means the controller will reset automatically when the measured chamber temperature is no longer over the defined alarm temperature value. Ultimately this means the controller will cycle power to the mechanical relay and re-energize the elements creating me heat. The controller essentially cycles power to the elements through the mechanical relay instead of the solid-state relay. Thus, the chamber temperature is controlled at the alarm temperature value. 31

32 32 Understanding Process Alarms: Troubleshooting In the event of a deviation high alarm (IdHi) condition, operats should first check the alarm value. In some situations, the alarm is merely set to low f the process of the PID control, taking into consideration program parameters and load type/mass. Resetting this alarm to a higher value often times crects the problem. If this alarm condition occurs after the alarm setting has been increased, please call Barnstead International technical suppt f additional troubleshooting procedures. Please obtain the model and serial number of your furnace pri to calling tech suppt. In the event of a full-scale high alarm (2FSH) condition, operats should power off the furnace immediately to avoid further damage and call Barnstead International technical suppt f troubleshooting procedures. Please obtain the model and serial number of your furnace pri to calling tech suppt. Understanding Alarm Types : Diagnostic Alarms The control module has ten diagnostic alarms. A diagnostic alarm warns there this a fault within the controller input module (thermocouple RTD). Please be aware combinations of alarm types can exist simultaneously. If such an occurrence should happen, alarm mnemonics will alter with each other on the display of the controller. The following diagnostic alarms are listed. 1. "S.br" (Sens Break Alarm): The home display will flash "S.br" indicating the thermocouple input is open. In this err state, the controller will not cycle power to the elements to generate any heat. Thermocouple replacement is usually required to resolve this alarm condition. 2. "EE.Er" (Electrically Erasable Memy Alarm): The home display will flash "EE.Er" indicating a mnemonic value in either the operat configuration mode has been crupted. In this err state, the controller will not cycle power to the elements to generate any heat. Controller replacement is usually required to resolve this alarm condition. 3. "TU.Er" (Tune Err Alarm): The home display will flash "TU.Er" indicating the tune procedure has failed. This err condition can only occur during a tune procedure. In this err state, the controller will stop submitting power to the heating element and chamber temperature will drop to ambient conditions. In most situations, the one-shot tune procedure was interrupted resulting in the err. Re-running the one-shot auto tune usually resolves the problem. However, thermocouple and/ controller replacement may be necessary to resolve this alarm condition. 4. "LLLL" (Out of Range Low Reading): The home display will flash "LLLL" indicating the input signal is out of range low. If the thermocouple was 32

33 33 recently replaced, it may not be connected properly connected in reverse polarity causing the err message. If you have verified the thermocouple is the connected properly, controller replacement may be necessary to resolve this alarm condition. 5. "HHHH" (Out of Range High Reading): The home display will flash "HHHH" indicating the input signal is out of range high If the thermocouple was recently replaced, it may not be connected properly connected in reverse polarity causing the err message. If you have verified the thermocouple is the connected properly, controller replacement may be necessary to resolve this alarm condition. 6. "Err1" (ROM Failure): The home display flashes "Err1". Controller replacement is usually required to resolve this alarm condition. 7. "Err2" (RAM Failure): The home display flashes "Err2". Controller replacement is usually required to resolve this alarm condition. 8. "Err3" (Watchdog Failure): The home display flashes "Err3". Controller replacement is usually required to resolve this alarm condition. 9. "Err4" (Keyboard Failure): The home display flashes "Err4". Controller replacement is usually required to resolve this alarm condition. 10. "Err5" (Internal Communication Failure): The home display flashes "Err5". Controller replacement is usually required to resolve this alarm condition. Understanding Diagnostic Alarms: What happens when an alarm condition occurs? When a diagnostic alarm is active, the controller will flash the alarm until the err condition has been crected. The controller will not attempt to cycle power to the heating elements, however the elements may generate heat if a double fault exists in the furnace. Obtain the model and serial number of the furnace and contact Barnstead International technical suppt if a diagnostic alarm condition should occur. 33

34 34 Alarm List Mnemonics (AL LiSt) AL 2416 LiSt Alarm List Header AUTO IdHi 2416 RUN 50 Deviation High Alarm 50 The parameter number displayed represents the current alarm setpoint. NOTE: The deviation alarm is intended f load protection and should never be set lower than 10 degrees. Setting a lower deviation alarm may interfere with the PID control process. 34

35 35 Auto Tune List Section The controller incpates a self-tuning feature, which determines the optimum control parameters (PID values) f best temperature accuracy with your load type. This feature should be used to eliminate temperature undershoot, over-shoot, oscillation conditions. There are two types of automatic tuning. 1. One Shot Auto Tune: The one-shot tuner functions by switching the heating elements on and off as a means to induce temperature oscillation. From the amplitude and period of the temperature fluctuation, the controller can calculate the optimal tuning parameters to help reduce totally eliminate such oscillation. The tuning parameters of the following mnemonics are automatically set f optimal operation as a result of a one shot tune: Mnemonic Meaning/Function Proptional Pb The bandwidth, in display units, over which the output Band power us proptioned between minimum & maximum. Integral ti Determines the time taken by the controller to remove Time steady-state err signals Derivative td Determines how strongly the controller will react to the Time rate of change of the measured chamber temperature. High Hcb The number of display units above set point at which Cutback the controller will cutback the output power, in der to prevent undershoot on cool down. Low Lcb The number of display units below set point at which Cutback the controller will cutback the output power, in der to Prevent overshoot on heat up. 2. Adaptive Tune: Adaptive tuning is a background algithm, which continuously monits the err from the setpoint and analyses the control respond during process disturbances. Adaptive tune is triggered whenever the err from setpoint exceeds a defined trigger level (dra). The tuning parameters changed as a result of an adaptive tune are the Proptional Band (Pb), Integral Time Band (ti), and Derivative Time Band (td) only. WARNING: While we may have not disabled the adaptive tune capability of the controller, it is strongly advised not to attempt this method of tuning, with a Thermolyne box furnace. There are very few applications with a labaty furnace that require this type of tuning. The process is too sensitive, usually causing me problems rather than crecting them. 35

36 36 Auto Tune List Mnemonics (Atun LiSt) AUTO Atun 2416 LiSt RUN Auto Tune List Header tune 2416 OFF Auto Tune (one shot) Auto tune on/initiated OFF Auto tune off/terminated NOTE: The following feature may not be present on all control types. As a result the following windows will not appear. dra 2416 AUT O RUN OFF Auto Tune (adaptive tune) OFF Auto tune off/terminated Auto tune on/initiated dra.t Adaptive Tune Trigger Level 20 Adaptive tune trigger level. Adaptive tune is triggered whenever the err from the setpoint exceeds this trigger level setting. (Only active if dra is set to on). 36

37 37 Suggested Tuning Procedure: 1. Load the furnace chamber with material that exhibits similar characteristics as your nmal loads you will be using the furnace to process. Please note: the material may not be of salvageable at completion of this process, however loading the furnace f the tune procedure will result in me accurate tune parameters given the characteristics of the load. 2. Power on the furnace. 3. Set the desired single set point temperature using the arrow keys. (If me than one known single set point temperature is going to be used over the course of time, average the set points together, and enter the average single set point into the controller.) 4. Page key to the atun list. 5. Scroll key to the one-shot tune mnemonic. 6. Use the arrow key to change the OFF to ON. 7. The furnace will heat from ambient to the set point temperature while tuning. The lower display will toggle the set point temperature with the wd "tune" to indicate the process is being executed. 8. When the furnace reaches the set point temp and the wd "tune" stops flashing in the lower display, the tune is complete and the tuner parameters have been automatically set f optimum results. NOTE: Initiating a one-shot tune while the chamber is at ambient usually results in obtaining the optimal PID values f the process, however with some applications, initiating a tune when the furnace actually reaches set point, may produce better results. NOTE: Programs cannot be tuned, only single set points. If you wish to set your PID tuning parameters f program operation, select the mean temperature of the program calculate the average temperature. Enter the mean the average as a single set point and initiate the one-shot auto tune with a mock load in the chamber. The PID tuning values the controller calculates at this value will wk best f the entire program. 37

38 38 PID List Section The PID list contains mnemonics that define the control module's ability to maintain set point with minimal deviation process err from set point. PID Control: What is PID Control? The control algithm is based on proptional gain, an integration action, and a derivative action. Gain, me commonly called, proptional band, simply amplifies the err between set point and measured chamber temperature to establish a power level. The term, proptional band, is one that expresses the gain of the controller as a percentage of the span of the instrument. It determines the magnitude of the response to an err. If the prop band is too small, meaning a high gain, the furnace temperature will oscillate through being over-responsive. If the prop band is too large, meaning low gain, the measured chamber temperature will oscillate due to the lack of response will be slow to react to disturbances. Having the proper gain alone will not allow f accurate control however. The integral action, expressed as the integral band, slowly shifts the output power level as a result of an err between set point and measured chamber temperature. If the measured chamber temperature is below set point the integral action will gradually increase the output power level in an attempt to increase the chamber temperature to meet the set point requirement. Likewise, if the measured chamber temperature is above the set point, the integral action will gradually decrease the output power level in an attempt to lower the chamber temperature to meet the set point requirement. The integral band is expressed as a time constant, meaning the longer the integral band (time constant) the me slowly the power level shift will occur. If set too large, the controller response time may be too slow and sluggish. If the integral band is set to smaller value, the controller essentially shifts the power level me quickly resulting in a faster response. However, if the power level is shifted too quickly it can cause unwanted temperature oscillation due to the load type. The last constant is referred to as the derivative band and like the integral band is expressed as a time constant. The derivative band provides a sudden shit in output power level as a result of a quick change in the measured chamber temperature (f example, opening the chamber do). It also aids the PI control process in dampening chamber temperature oscillation near set point. The derivative time band is typically set to a value equal to one sixth of the integral band. No matter how though discrete the explanation of PID control and the function of each of the three tuning parameters, it is a difficult concept to understand. When the PID tuning parameters are set to optimal values, the controller will heat to set point with minimal temperature overshoot undershoot. Unlike past control models, in which PI values needed to be 38

39 39 calculated long fm by end-users as well as manually entered into the controller, the new versions of PID controllers automatically calculate and set by the values into the controller as a result of a one-shot auto tune discussed in the previous section entitled Auto Tune List Section. Dual PID Control: What does this mean? The control module installed your labaty furnace has dual PID control capability. Due to the wide range of controllable temperatures, one set of PID values can be used f chamber set points below a defined level while a second set can be used f chamber set point above the defined level. The defined level is referred to as the gain set point (G.SP). Facty preset at 700C, means if the chamber set point temperature is below 700C, the controller will activate and use the 1 st set of PID values. If the chamber set point temperature is above 700C, the controller will automatically use the 2 nd set of PID values. The advantage of dual PID control lies in the fact controllers do not require re-tuning as often, saving you time. PID Control & Tuning: When should I tune re-tune my controller? Controllers should be re-tuned from ambient when one of the following events occur: - When the application changes. F example if a the furnace is being used to ash small samples of waste material one day and having a large piece of metal placed in the chamber to heat treat the following day. The mass of the load will exhibit characteristic differences as it absbs heat generated by the furnace. This can cause unwanted temperature over undershoot. - If chamber set point temperature is changed by a significant difference. F example, running at an average set point of 350C to running at an average set point of 900C. - If you are experiencing chamber measured temperature oscillation on the control display. The PID values may drift over time as a result of electrical interference and need to be reset. - If a thermocouple heating element is replaced in the furnace, the controller should be re-tuned. F instructions on how to properly initiate a tune please refer to the Tune List Section of this manual. 39

40 40 PID List Mnemonics (Pid LiSt) Pid 2416 LiSt PID List Header G.SP Gain Setpoint Pb 2416 ti Gain setpoint level. Level at which PID control switches from the 1 st set of PID values to the 2 nd set. Proptional Band Proptional Band 1 value. Facty preset to 9. Integral Time Band Integral time band 1 value. Facty preset to

41 41 td Pb ti td Derivative Time Band 1 Proptional Band Derivative time band 1 value. Facty preset to Proptional Band 2 value. Facty preset to 5. Integral Time Band Integral time band 2 value. Facty preset to 44. Derivative Time Band Derivative time band 2 value. Facty preset to 7. 41

42 42 Communication List Section The communication list contains only one mnemonic that defines the location of the controller when connected to a computer via RS232. cms 2416 LiSt Communication List Header Addr Address 1-99 number defines the address location of the controller. 42

43 43 Access List Section The access list is the gateway, so to speak of, to the configuration level as well as the Edit & FuLL modes of operation. Configuration Level: This special level is double passwd protected. The fundamental characteristics of the controller are set up in the configuration level. F this reason we have chosen not to supply the passwd necessary to enter the configuration level. If you feel you are required to enter the configuration level of your Thermolyne furnace controller, please obtain the model & serial number of your furnace & call our customer service technical suppt at f further assistance. Full & Edit Levels: The passwd required to enter the FuLL Edit level is the number {25}. FuLL Level: All mnemonics & cresponding parameters can be viewed at the operat level, however only select parameters can be altered pending the edit level setting. Access to the FuLL level of operation is required to change the calibration-offset value (if necessary). Edit Level: All mnemonics & cresponding parameters are defined in the Edit level as either: - Alterable (ALtr) = Mnemonic & cresponding parameter can be viewed as well as altered at the operat full level. - Promoted (PrO) = Mnemonic & cresponding parameter are promoted to the HOME DISPLAY list & can be altered at the operat full level. - Read Only (read) = Mnemonic & cresponding parameter can be viewed at the operat full level, but cannot be altered. - Hidden (HidE) = Mnemonic & cresponding parameter cannot be viewed at the operat full level and cannot be altered. Access to the Edit level of operation is required if you wish to lock out select mnemonics and cresponding parameter settings to prevent unwanted tampering. 43

44 44 Access List Mnemonics (ACCS LiSt) ACCS 2416 LiSt Access List Header code Code Number Passwd 44

45 Eurotherm: Offset Calibration NOTE: There are three imptant aspects you need to know when perfming this procedure: 1. If you do not press a key within a defined amount of time, the display will automatically revert back to the home display. 2. When you press the key, you must wait until the parameter in the lower display "blinks" befe pressing the next instructed key. The "blink" indicates the parameter change has been accepted by the controller. 3. If you press and hold the key, the parameter value in the lower display will toggle quicker ACCS 2416 LiSt code repeatedly to goto 2 to goto 3 repeatedly to goto code code 2416 PASS Goto 2416 FuLL 4 Automatic 5 to goto 6 repeatedly to goto ip 2416 LiSt OFS ** OFS to goto 8 to set offset 9 repeatedly to goto ACCS 2416 LiSt code 2416 PASS Goto 2416 FuLL 10 to goto 11 to goto 12 to goto Goto 2416 OPEr ACCS 2416 LiSt to goto 14 to goto 15 **Calibration offset value must be calculated. See following instructions on how to properly calculate this value. 45

46 46 Calculating a Temperature Offset Value Equipment Required F All Thermolyne Furnace Model Types: - N.I.S.T. traceable type K thermocouple with digital pyrometer. (Thermolyne Cat # AY589X1) Equipment Required F Select Thermolyne Model Types: - Tools necessary to remove the back cover of the furnace chamber (Screwdriver set) - Drill with 3/8" bit. 1. Route the N.I.S.T. traceable type K thermocouple probe into the geometric center of the chamber. a) Route the probe through a 3/8" diameter access pt located on the back wall of select Thermolyne furnace model types [select models must have the chamber back wall insulation drilled out through the access pt] See Pic A. b) Route the probe through a 1" diameter access/vent pt located on the roof of select Thermolyne furnace model types [select models must have the chamber roof insulation drilled out through the access pt] See Pic B. A) B) 2. Power on the furnace. 3. Set the desired single set point temperature. 4. Allow the furnace to heat to set point & stabilize. Stabilization allows the interi surfaces to reach thermal equilibrium resulting in a me accurate response. Pending Thermolyne furnace model type as well as the set point temperature, the time required f stabilization to occur will fluctuate. Please allow two additional hours f stabilization to occur once the set point temperature has been achieved. 5. Recd the measured chamber temperature from the display of the furnace controller. 6. Recd the measured chamber temperature from the digital pyrometer. 7. Subtract the displayed furnace controller temperature from the N.I.S.T. digital pyrometer temperature. The difference becomes the calibration offset value that is to be entered in step 11 of the procedure. EXAMPLE 1 (Negative offset value): 495ºC (N.I.S.T digital pyrometer reading) - 500ºC (Furnace controller measured chamber temp reading) - 5ºC (Calculated calibration offset value) EXAMPLE 2 (Positive offset value): 505ºC (N.I.S.T digital pyrometer reading) - 500ºC (Furnace controller measured chamber temp reading) 5ºC (Calculated calibration offset value) 46

Type 47900 & 48000 Furnaces

Type 47900 & 48000 Furnaces Type 47900 & 48000 Furnaces OPERATION MANUAL Series 1165, 1166 & 1205 Single Setpoint Models Single Setpoint Models with OTP F47910, F47910-26, F47910-33, F47914, F47915, F48010, F48010-26, F48010-33,

More information

MODEL 4400 TEMPERATURE CONTROL. 10100 Royalton Rd. Cleveland, OH 44133 (440) 237-3200 (440) 237-1744 http://iseinc.com

MODEL 4400 TEMPERATURE CONTROL. 10100 Royalton Rd. Cleveland, OH 44133 (440) 237-3200 (440) 237-1744 http://iseinc.com MODEL 4400 TEMPERATURE CONTROL 10100 Royalton Rd. Cleveland, OH 44133 (440) 237-3200 (440) 237-1744 http://iseinc.com Model 4400 Ramp Dwell Control Short Form Instructions This document is provided for

More information

Controller Automation, Model II+

Controller Automation, Model II+ Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control

More information

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 Display 1. Red measurement display (or the set point for CTD 43 by pressing, indicated by a flashing decimal point). 2. Green display of

More information

Type F6000 Furnace OPERATION MANUAL AND PARTS LIST. Series 1060

Type F6000 Furnace OPERATION MANUAL AND PARTS LIST. Series 1060 BARNSTEAD THERMOLYNE CORPORATION Type F6000 Furnace OPERATION MANUAL AND PARTS LIST Series 1060 MODEL NUMBER VOLTAGE CONTROL DISPLAY ( C& F) RS232 COMM. F6010 220-240 Basic Automatic X ( C only) F6010-33

More information

TC-9102 Series Surface Mount Temperature Controllers

TC-9102 Series Surface Mount Temperature Controllers TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may

More information

Process Control Primer

Process Control Primer Process Control Primer At the onset of the Industrial Revolution, processes were controlled manually. Men turned valves, pulled levers or changed switches based on the need to turn devices on or off. As

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

User Manual. Humidity-Temperature Chart Recorder. Model RH520

User Manual. Humidity-Temperature Chart Recorder. Model RH520 User Manual Humidity-Temperature Chart Recorder Model RH520 Introduction Congratulations on your purchase of the Extech RH520 Temperature + Humidity Chart Recorder. The RH520 measures and displays Temperature,

More information

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual Ⅰ. Warn Warning of connection Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual If the controller fails to operate or error occurs, the system will bring fault for it, please

More information

EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.

EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved. ENGLISH EATS6 EATS6N Installation and user manual Copyright 05 EATON All rights reserved. Service and suppt: Call your local service representative SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual

More information

Aurora UPC ZS Zone Sensors User Guide

Aurora UPC ZS Zone Sensors User Guide Aurora Universal Protocol Converter (UPC) ZS Zone Sensors User Guide Aurora UPC ZS Zone Sensors User Guide IG1581EW 04/14 Table of Contents Using ZS Sensors... 1 ZS Standard Sensor... 2 ZS Plus Sensor...

More information

*.ppt 11/2/2009 12:48 PM 1

*.ppt 11/2/2009 12:48 PM 1 Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers

More information

Programmer/Controller

Programmer/Controller Systems Plus START 7 8 9 envirotronics ALARM STOP 4 5 6 ALARM ACK Instrument Manual Systems Plus Programmer/Controller OFF HELP 1 2 0 3. ENTER ALARM RESET DEL Revision 6 9/12/97 Table of Contents 2 Menu

More information

HONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02

HONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02 HONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02 Before using this manual, please check to ensure the Model number, input type Range and output match your requirements.

More information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.

More information

EK908FHL - Thermostat for floor heating

EK908FHL - Thermostat for floor heating EK908FHL - Thermostat for floor heating EK908FHL is a programmable thermostat designed for floor warming application or helping to limit floor temperature. This thermostat can be used for hot water radiant

More information

Digital Radio/DAB+/FM RDS digital clock radio with dual alarm Operating instruction

Digital Radio/DAB+/FM RDS digital clock radio with dual alarm Operating instruction 381SE1D-A Digital Radio/DAB+/FM RDS digital clock radio with dual alarm Operating instruction GB Contents Controls... 2-3 Using the clock radio for the first time... 4 Operating your clock radio... 5 Selecting

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

CONTROL SETPOINT2408 PROGRAMMER ENG. Installation and operation handbook

CONTROL SETPOINT2408 PROGRAMMER ENG. Installation and operation handbook 2404 CONTROL SETPOINT2408 PROGRAMMER ENG Installation and operation handbook Contents MODELS 2408 and 2404 PID CONTROLLERS INSTALLATION AND OPERATION HANDBOOK Contents Page Chapter 1 INSTALLATION...1-1

More information

PUSH BUTTON START INSTALLATION MANUAL

PUSH BUTTON START INSTALLATION MANUAL PUSH BUTTON START INSTALLATION MANUAL ALTHOUGH THIS PRODUCT HAS BEEN THOROUGHLY TESTED KPIERSON TECHNOLOGIES ASSUMES NO RESPONSIBILITY FOR ANY DAMAGE THAT MAY RESULT BY THE INSTALLATION OF THIS PRODUCT.

More information

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety

More information

SMC 3000 Series Master Clock Programming Manual (V3) Table of Contents. Getting Started.. Page 2. Setting the Time of Day...

SMC 3000 Series Master Clock Programming Manual (V3) Table of Contents. Getting Started.. Page 2. Setting the Time of Day... User Password (default is 1111) GETTING STARTED Getting Started.. Page 2 SETTING THE TIME Setting the Time of Day... Page 3 SETTING THE DATE Setting the Date. Page 4 EVENTS Programming Events..... Pages

More information

GSM AD05 Slave GSM Auto Dialer- Instruction Manual

GSM AD05 Slave GSM Auto Dialer- Instruction Manual GSM AD05 Slave GSM Auto Dialer- Instruction Manual Please read these instructions before you start the installation Features LCD display Programmable 9 x 32 digit phone numbers for each trigger. 10 second

More information

Automated Inventory System

Automated Inventory System Automated Inventory System User Manual Developed by USDA Food and Nutrition Service June 2009 (Incomplete) Table of Contents Welcome Menu Client Services Report System Inventory System Operations Tailgate

More information

User s Information Guide R1A

User s Information Guide R1A HSC505-R Home Security Controller - User Manual Release R1a Pi HSC505 and Pi HSC505R Home Security Controller User s Information Guide R1A Page 1 QD Dynamics (Pty) Ltd reserves the right to make changes

More information

SYL-2372 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 2016)

SYL-2372 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 2016) AUBER INSTRUMENTS Instruction Manual SYL-7 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 16) Caution This controller is intended to control equipment under normal operating conditions.

More information

TECHNICAL. Add Peripherals without Changing Your Phone System C-1000A. Door Entry Controller

TECHNICAL. Add Peripherals without Changing Your Phone System C-1000A. Door Entry Controller TECHNICAL Practice TELECOM SOLUTIS FOR THE 21ST CENTURY C-1000A Do Entry Controller June 21, 2002 Features Allows two Viking doboxes paging amplifiers to share a single telephone line with a residential

More information

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1 Softstarters Type PSTX Fieldbus communication, Built-in Modbus RTU 1SFC132089M0201 April 2015 1SFC132089M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and status

More information

GAUGEMASTER PRODIGY EXPRESS

GAUGEMASTER PRODIGY EXPRESS GAUGEMASTER PRODIGY EXPRESS DCC01 USER MANUAL Version 1.1 2011 T A B L E O F C O N T E N T S 1 Getting Started Introduction Specifications and Features Quick Start Connecting to Your Layout Running a Loco

More information

PhoneWatch Smart Security System User Manual - Domonial

PhoneWatch Smart Security System User Manual - Domonial PW0002 10/13 Customer Support: 1850 753 753 PhoneWatch Ltd., Unit 3/4, Sandyford Park, Burton Hall Rd, Sandyford Industrial Estate, Dublin 18. Email: info@phonewatch.ie PhoneWatch Smart Security System

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

Dyeing Programmer DP - 01

Dyeing Programmer DP - 01 Dyeing Programmer DP - 01 Display and Controls. 1) Display: 16/2 alphanumeric display 2) Temperature range: 0 to 150 degree. 3) Resolution: 1 degree. 4) Accuracy: +/- 1 degree. 5) Temperature control setting:

More information

Owner s Manual. Model 8476 Thermostat with Event-Based Air Cleaning. Includes Operating Instructions and Warranty Information

Owner s Manual. Model 8476 Thermostat with Event-Based Air Cleaning. Includes Operating Instructions and Warranty Information Model 8476 Thermostat with Event-Based Air Cleaning Owner s Manual Includes Operating Instructions and Warranty Infmation READ AND SAVE THESE INSTRUCTIONS Table of contents About your new thermostat Thermostat

More information

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger

More information

Troubleshooting and Diagnostics

Troubleshooting and Diagnostics Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem

More information

LADDER LOGIC/ FLOWCHART PROGRAMMING DIFFERENCES AND EXAMPLES

LADDER LOGIC/ FLOWCHART PROGRAMMING DIFFERENCES AND EXAMPLES page 1/10 This document is designed as a quick-start primer to assist industrial automation programmers who are familiar with PLCs and Relay Ladder Logic programming to better understand the corresponding

More information

Drayton Digistat +2RF

Drayton Digistat +2RF Drayton Digistat +2RF T Programmable Room Thermostat Wireless 24 Hour Model: RF700/22090 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130

More information

HEAT PUMP PROGRAMMABLE THERMOSTAT

HEAT PUMP PROGRAMMABLE THERMOSTAT HEAT PUMP PROGRAMMABLE THERMOSTAT SA PM 3 COOL TEMP Form 44014-01 r010408 Model 43168 Owners Manual 1 Congratulations! Heat Pump Programmable Thermostat Model 43168 THERMOSTAT CONTROLS Switches & Buttons...15

More information

Matrix 424/832/832+ ICON & LCD User Manual. Software Version 5 RINS915-2. EN50131-1 Security Grade 2 Environmental Class 2

Matrix 424/832/832+ ICON & LCD User Manual. Software Version 5 RINS915-2. EN50131-1 Security Grade 2 Environmental Class 2 Matrix 424/832/832+ ICON & LCD User Manual Software Version 5 RINS915-2 EN50131-1 Security Grade 2 Environmental Class 2 CONTENTS CHAPTER 1: INTRODUCTION... 1 CHAPTER 2: REPLACING THE BATTERIES... 2 CHAPTER

More information

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March 2016 2016 Emerson Electric Co. All rights reserved.

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March 2016 2016 Emerson Electric Co. All rights reserved. Sensi TM Wi-Fi Programmable Thermostat MANUAL OPERATION Version: March 2016 2016 Emerson Electric Co. All rights reserved. Contents MANUAL OPERATION GUIDE Buttons and Icons 3 Basic Functionality 4 Manual

More information

SCORPION. micron security products

SCORPION. micron security products SCORPION 4120 6020 & 8020 USER INSTRUCTIONS Thank you for purchasing a Quality Micron Security Alarm Controller. Micron product is manufactured to exacting quality standards. We understand the importance

More information

ABB i-bus EIB Logic Module LM/S 1.1

ABB i-bus EIB Logic Module LM/S 1.1 Product Manual ABB i-bus EIB Logic Module LM/S 1.1 Intelligent Installation System Contents page 1 General... 3 1.1 About this manual... 3 1.2 Product and functional overview... 3 2 Device technology...

More information

CONTROLS KITS AND ACCESSORIES. 507240-01 12/2014 Supersedes10/2014

CONTROLS KITS AND ACCESSORIES. 507240-01 12/2014 Supersedes10/2014 2014 Lennox Industries Inc. Dallas, Texas, USA CONTROLS KITS AND ACCESSORIES 507240-01 12/2014 Supersedes10/2014 Litho U.S.A. Equipment Interface Module Installation Instructions for the Equipment Interface

More information

4-Channel Thermometer / Datalogger

4-Channel Thermometer / Datalogger USER GUIDE 4-Channel Thermometer / Datalogger RTD and Thermocouple Inputs Model SDL200 Introduction Congratulations on your purchase of the Extech SDL200 Thermometer, an SD Logger Series meter. This meter

More information

SMS GSM Alarm Messenger

SMS GSM Alarm Messenger SMS GSM Alarm Messenger Data Logging Alarm Input Relay Output Voice Temperature Humidity Analog Input Capture and Send Data via SMS Report triggered alarm via SMS Output triggered via SMS Auto pick up

More information

Programming Logic controllers

Programming Logic controllers Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,

More information

FAST METHODS FOR SLOW LOOPS: TUNE YOUR TEMPERATURE CONTROLS IN 15 MINUTES

FAST METHODS FOR SLOW LOOPS: TUNE YOUR TEMPERATURE CONTROLS IN 15 MINUTES FAST METHODS FOR SLOW LOOPS: TUNE YOUR TEMPERATURE CONTROLS IN 15 MINUTES Michel Ruel P.E. President, TOP Control Inc 4734 Sonseeahray Drive 49, Bel-Air St, #103 Hubertus, WI 53033 Levis Qc G6W 6K9 USA

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

SYMBOL MC9060 HAND HELD TERMINAL USER MANUAL

SYMBOL MC9060 HAND HELD TERMINAL USER MANUAL SYMBOL MC9060 HAND HELD TERMINAL USER MANUAL CORPORATE VERSION FEBRUARY 2007 TABLE OF CONTENTS Welcome... 3 Getting Started... 3 Equipment Setup... 3 Battery Installation... 4 About the Stylus... 5 Aligning

More information

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

HEAT HEAT COOL HEAT PUMP COOL

HEAT HEAT COOL HEAT PUMP COOL OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control

More information

TC 1818a. Operating Guide. Control Module SWM-015.5

TC 1818a. Operating Guide. Control Module SWM-015.5 TC 1818a Control Module Operating Guide SWM-015.5 This guide is intended solely for use by owners of Thermon HeatChek TM heat tracing control and monitoring units. This manual describes operation for TC

More information

APPLICATION NOTES. Bimetal Disc Thermostat. Operating Principle

APPLICATION NOTES. Bimetal Disc Thermostat. Operating Principle Bimetal Disc Thermostat APPLICATION NOTES Operating Principle Bimetal disc thermostats are thermally actuated switches. When the bimetal disc is exposed to its predetermined calibration temperature, it

More information

NOVA MULTI-MONITORING SOFTWARE. Instruction Manual

NOVA MULTI-MONITORING SOFTWARE. Instruction Manual NOVA MULTI-MONITORING SOFTWARE REMOTE OPERATION Precision Digital Corporation s Nova Multi-Monitoring software allows for the operation of common Nova control features remotely from a PC. Up to 30 Nova

More information

ITC-308 Plug and Play Temperature Controller

ITC-308 Plug and Play Temperature Controller ITC-308 Plug and Play Temperature Controller 1. Overview ITC-308 is an easy-to-use, safe and reliable dual relay output temperature controller. It can be used as Over-temperature protection and automatic

More information

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com Integrations LGAC-KNX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 ingeniumsl@ingeniumsl.com www.ingeniumsl.com

More information

Dr. Yeffry Handoko Putra, S.T., M.T

Dr. Yeffry Handoko Putra, S.T., M.T Tuning Methods of PID Controller Dr. Yeffry Handoko Putra, S.T., M.T yeffry@unikom.ac.id 1 Session Outlines & Objectives Outlines Tuning methods of PID controller: Ziegler-Nichols Open-loop Coon-Cohen

More information

My Weigh Ultraship Series User Manual

My Weigh Ultraship Series User Manual My Weigh Ultraship Series User Manual Low Batteries, bad battery connections & Faulty AC Adaptors are the #1 cause of Ultraship malfunction and inaccuracy! We test all of our scale returns from consumers.

More information

USER MANUAL EXTROLLER

USER MANUAL EXTROLLER COAIRE SCREW AIR COMPRESSORS USER MANUAL EXTROLLER SERIAL NO. : MODEL NO. : CAUTION For proper and safe use of the compressor, please follow all instructions and safety precautions as identified in this

More information

INSTALLATION OPERATING & MAINTENANCE MANUAL

INSTALLATION OPERATING & MAINTENANCE MANUAL INSTALLATION OPERATING & MAINTENANCE MANUAL Basic Climatic TM Controller Ecologic English November 2002 CONTENTS PAGE GENERAL DESCRIPTION 3 USER INTERFACE 4 The keypad incorporated on the unit 4 The keypad

More information

AMS ValveLink SNAP-ON Application

AMS ValveLink SNAP-ON Application AMS Suite: Intelligent Device Manager Product Data Sheet AMS ValveLink SNAP-ON Application Communicate with both HART and Foundation fieldbus FIELDVUE digital valve controllers in the same application.

More information

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE

More information

2014-02. Technical Service Bulletin

2014-02. Technical Service Bulletin Technical Service Bulletin 2014-02 Date: April 25, 2014 Title: Pinnacle Lite Version 14 (5.7 & 7.5 HMI Screens) Affected: 2010-2013 Pinnacle Lite 5.7 & 7.5 HMI Equipped Dryers Priority: Medium Overview

More information

ABB i-bus EIB Universal Interfaces US/U 4.2 US/U 2.2

ABB i-bus EIB Universal Interfaces US/U 4.2 US/U 2.2 Product Manual ABB i-bus EIB US/U 4.2 US/U 2.2 Intelligent Installation Systems Intelligent and limitless Contents Page 1 General............................................. 3 1.1 Product and functional

More information

Gastronorm Supra Cabinet & Counter

Gastronorm Supra Cabinet & Counter By Appointment to Gastronorm Supra Cabinet & Counter Her Majesty Queen Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator (UK) Ltd King s Lynn S e r v i c e M a n u a l Gastronorm Supra

More information

How To Set Up A Protocessor Protonode

How To Set Up A Protocessor Protonode Setup Manual BACnet Protocol Gateway for TempTrac and XR Water Heater Control When a BAS interface with TempTrac or the XR requires a protocol other than the standard Modbus RTU, PVI Industries offers

More information

B/S/H/ Error codes and service programmes PH

B/S/H/ Error codes and service programmes PH 1 ERROR CODES AND APPLIANCE MESSAGES... 3 1.1 Complete overview of all error codes (in order)... 3 Automatic switch-off... 3 Display is dark and any individual LEDs are lit... 3 E 005... 3 E 011... 3 E

More information

Dash 18X / Dash 18 Data Acquisition Recorder

Dash 18X / Dash 18 Data Acquisition Recorder 75 Dash 18X / Dash 18 Data Acquisition Recorder QUICK START GUIDE Supports Recorder System Software Version 3.1 1. INTRODUCTION 2. GETTING STARTED 3. HARDWARE OVERVIEW 4. MENUS & BUTTONS 5. USING THE DASH

More information

ADDING and/or DELETING PIN NUMBERS (Plus other simple programming commands) in My DK-16 or DK-26 DIGITAL KEYPAD

ADDING and/or DELETING PIN NUMBERS (Plus other simple programming commands) in My DK-16 or DK-26 DIGITAL KEYPAD ADDING and/or DELETING PIN NUMBERS (Plus other simple programming commands) in My DK-16 or DK-26 DIGITAL KEYPAD A recurring call that we get here at Securitron Technical Support is from end users of our

More information

STANDARD CLEANING AND CALIBRATION PROCEDURE FOR TGA-50(H) AND TGA-51(H)

STANDARD CLEANING AND CALIBRATION PROCEDURE FOR TGA-50(H) AND TGA-51(H) STANDARD CLEANING AND CALIBRATION PROCEDURE FOR TGA-50(H) AND TGA-51(H) by Joseph F. Greenbeck, Jr. And Courtney W. Taylor INTRODUCTION The following procedure is to be used for the maintenance and calibration

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy

More information

Delta Temperature Controller User Manual

Delta Temperature Controller User Manual Delta Temperature Controller User Manual Foreword The user manual details the process of using Delta DT series temperature controllers step by step for beginners to easily set up all kinds of parameters

More information

CA60 Plus Software Version 3.1 User Manual May 2000

CA60 Plus Software Version 3.1 User Manual May 2000 TeleT eletek ek CA60 Plus Software Version 3.1 User Manual May 2000 CONTENTS 1. CA60Plus Keypad... 3 1.1. LED display... 3 1.2. Keys... 4 1.3. Combinations of Keys... 4 1.4. Audible Indication... 4 2.

More information

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3

More information

MAGICAR M871A. Car alarm with two-way remote User s guide

MAGICAR M871A. Car alarm with two-way remote User s guide MAGICAR M871A Car alarm with two-way remote User s guide EN MAGICAR M871A Car alarm with two-way remote User s guide TABLE OF CONTENTS Table of contents...2 1. Important notice...4 2. Introduction...4

More information

BROOKFIELD MODEL VTE250 ELECTRIC VISCOSEL PROCESS VISCOMETER. Installation, Operation, and Maintenance Instructions. Manual No.

BROOKFIELD MODEL VTE250 ELECTRIC VISCOSEL PROCESS VISCOMETER. Installation, Operation, and Maintenance Instructions. Manual No. BROOKFIELD MODEL VTE250 ELECTRIC VISCOSEL PROCESS VISCOMETER Installation, Operation, and Maintenance Instructions Manual No. M06-512 SPECIALISTS IN THE MEASUREMENT AND CONTROL OF VISCOSITY BROOKFIELD

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

SINAMICS BOP-2. Basic Operator Panel 2. Operating Instructions March 2010 SINAMICS

SINAMICS BOP-2. Basic Operator Panel 2. Operating Instructions March 2010 SINAMICS SINAMICS BOP-2 Basic Operator Panel 2 Operating Instructions March 2010 SINAMICS Safety notes 1 Overview 2 SINAMICS SINAMICS Operating Instructions Installation 3 Monitoring 4 Control 5 Diagnostics 6

More information

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2

More information

VEHICLE SECURITY SYSTEM OPERATOR'S INSTRUCTIONS

VEHICLE SECURITY SYSTEM OPERATOR'S INSTRUCTIONS :). VEHICLE SECURITY SYSTEM OPERATOR'S INSTRUCTIONS (8 I NS070S Rev. A 12195 ThIs product is protected by U.S. patent number 5,049,867. @ Code Alarm, Inc. 1994 All rights reserved. Printed in the USA.

More information

AquaTrend Interface. Model 51200 AquaTrend Model 51350 AquaTrend/SOM Model51400 PortableAquaTrend. Instrument Manual. Catalog Number 51350-18

AquaTrend Interface. Model 51200 AquaTrend Model 51350 AquaTrend/SOM Model51400 PortableAquaTrend. Instrument Manual. Catalog Number 51350-18 Catalog Number 51350-18 AquaTrend Interface Model 51200 AquaTrend Model 51350 AquaTrend/SOM Model51400 PortableAquaTrend Instrument Manual Hach Company, 2001, 2002. All rights reserved. Printed in the

More information

IPB-IB ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESS CONTROL INDUSTRIAL STEAM BOILERS. BECK VIDEO Scan w/ Smartphone

IPB-IB ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESS CONTROL INDUSTRIAL STEAM BOILERS. BECK VIDEO Scan w/ Smartphone IPB-IB R ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESS CONTROL INDUSTRIAL STEAM BOILERS BECK VIDEO Scan w/ Smartphone 1 Increasing Business Pressures Necessitate Boiler Control Improvements Today s industrial

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

Garmin GNC 300XL Pilot s Quick Reference Guide ---------------------------------------------------------------

Garmin GNC 300XL Pilot s Quick Reference Guide --------------------------------------------------------------- Garmin GNC 300XL Pilot s Quick Reference Guide --------------------------------------------------------------- CURSOR/ DATA ENTRY Cursor control: The cursor key is used to activate the cursor in the comm

More information

KPN SMS mail. Send SMS as fast as e-mail!

KPN SMS mail. Send SMS as fast as e-mail! KPN SMS mail Send SMS as fast as e-mail! Quick start Start using KPN SMS mail in 5 steps If you want to install and use KPN SMS mail quickly, without reading the user guide, follow the next five steps.

More information

TP5000 Si Range Electronic 5/2 day programmable room thermostat Mains, Battery and RF versions Installation and User Instructions

TP5000 Si Range Electronic 5/2 day programmable room thermostat Mains, Battery and RF versions Installation and User Instructions TP5000 Si Range Electronic 5/2 day programmable room thermostat Mains, Battery and RF versions Certification Mark GB Installation and GB Index Index Installation Instructions 3-14 Product Specification

More information

DAB1001. Wireless Digital Radio Interface. Installation & User Guide

DAB1001. Wireless Digital Radio Interface. Installation & User Guide DAB1001 Wireless Digital Radio Interface Installation & User Guide Contents Contents... 2 Introduction... 3 Contents of Package... 4 Installation... 5 Product Overview... 5 Installation Procedure... 5

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

Using the STC-1000+ firmware

Using the STC-1000+ firmware Using the STC-1000+ firmware Project home at Github Features Both Fahrenheit and Celsius versions Up to 6 profiles with up to 10 setpoints. Each setpoint can be held for 1 999 hours (i.e. up to ~41 days).

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2]

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2] SMS Alarm Messenger SMSPro_Setup Revision 090210 [Version 2.2] ~ 1 ~ Contents 1. How to setup SMS Alarm Messenger?... 3 2. Install the SMSPro_Setup software... 5 3. Connection Type... 6 4. Connection Port

More information

Model 288B Charge Plate Graphing Software Operators Guide

Model 288B Charge Plate Graphing Software Operators Guide Monroe Electronics, Inc. Model 288B Charge Plate Graphing Software Operators Guide P/N 0340175 288BGraph (80207) Software V2.01 100 Housel Ave PO Box 535 Lyndonville NY 14098 1-800-821-6001 585-765-2254

More information

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire) FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control

More information

Thermistor Thermometer MODEL NO. 93210-00

Thermistor Thermometer MODEL NO. 93210-00 Thermistor Thermometer MODEL NO. 93210-00 Cole-Parmer Instrument Co. 625 East Bunker Court Vernon Hills, Illinois U.S.A. 60061-1844 (847) 549-7600 (847) 247-2929 (Fax) 800-323-4340 www.coleparmer.com e-mail:

More information

Security System. User Guide for the LED Command Center

Security System. User Guide for the LED Command Center Security System User Guide for the LED Command Center MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE

More information

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC HOJA TÉCNICA 1400H101 Edición 01 (02 de 08) www.ako.es GENERAL TECHNICAL SPECIFICATIONS Temperature range: -50ºC to +99ºC type: NTC Total accuracy ( + controller): ±1ºC lead extension with cable AKO-15586:

More information