Control of Underfloor Air-Distribution Systems

Size: px
Start display at page:

Download "Control of Underfloor Air-Distribution Systems"

Transcription

1 This article was published in ASHRAE Journal, May Copyright 2015 ASHRAE. Posted at This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit Control of Underfloor Air-Distribution Systems Daniel H. Nall BY DANIEL H. NALL, P.E., BEMP, HBDP, FAIA, FELLOW/LIFE MEMBER ASHRAE Underfloor air-distribution (UFAD) systems have been designed and built in the United States for more than 20 years with various degrees of success. The system remains controversial, with both advocates and detractors, but has experienced significant penetration in some markets. The most common complaint with these systems, however, is that spaces are chronically over-cooled. 1 Many critical factors have been identified for avoiding this pitfall, but the implementation of effective control strategies is arguably the most important step. Underfloor air-distribution system typically refers to an HVAC system that delivers conditioning air from an air-handling unit through an access floor plenum to multiple floor-located diffusers or terminals that modulate airflow to individual zones to maintain comfort. Underfloor air is not a universal solution for all office buildings. It is well-suited to open plan, single tenant or owner-occupied buildings. In those buildings, the overall cost of the system, including available economies in systems furniture and cable distribution and certain tax advantages, is competitive with conventional overhead air-distribution systems. For occupancies that require many closed rooms, however, or where construction costs are divided between landlord and tenant, UFAD may be less attractive. Selection of the system should follow a comprehensive review of the usage, goals and configuration of an occupancy and extensive discussion with the occupants and owner of the project. Differences between this system and a conventional single duct overhead delivery VAV system include: Air distribution is primarily through an open plenum under an access floor, rather than through closed ductwork above the ceiling. Air delivery from the floor-mounted diffusers is intended to be semi-displacement rather than full mixing and, therefore, the design supply air temperature to the space is much higher (~62 F vs. ~55 F [17 C vs. 13 C]) and diffuser face velocity is significantly lower than with overhead systems. Because floor registers are immediately accessible to occupants, manually adjustable diffusers are often used in interior workstations instead of thermostatically operated diffusers or terminals. Air temperature distribution in the space is usually markedly different with a UFAD system than with an overhead mixing system, showing significant stratification. Many of the parts of an UFAD system are conventional and familiar, although some require some special modifications for UFAD. Primary air-handling units are similar to those of overhead systems, although, in humid climates, air-handling units supplying directly to the plenum will require a coil bypass so that return air may be redirected around the cooling coil to raise the supply air temperature to the space while maintaining the required apparatus dew-point temperature. All humid outside ventilation air is directed across the coil to ensure that the supply airstream has an adequately low dew-point temperature to control space humidity. Many UFAD systems provide supply air for both interior and perimeter zones from the same source through the same supply plenum. Provision of a separate supply plenum or a separate, often hydronic, cooling source for perimeter zones usually is often ruled out because of operational or first cost considerations. Serving both the perimeter zones and interior zones from the same underfloor supply plenum requires a control sequence Daniel H. Nall, P.E., FAIA, is vice president at Syska Hennessy Group, New York. 46

2 Sprinkler Branch Line Ceiling Return Plenum Return Air Recessed Light Fixture Recessed Sprinkler Head Thermal Plume Warm Return Air Light Fixture Perimeter Heating/ Cooling Updraft Supply Multi-Slot Perimeter Floor Diffuser Stratification Boundary Level Variable Speed Fan with Hydronic Heating Coil High Performance Glass Façade Power Junction Box Run at Floor Slab Swirling Supply Air Floor Mounted Swirl Diffuser Supply Air Floor Plenum Flexible Conduit Whip Power Conduit Run at Floor Slab Multi-Service Floor Box with Power/Tele/Data Supply Cooling Air FIGURE 1 Configuration of the underfloor air-distribution system. that enables comfort control for both types of zones simultaneously. Supply air temperature degradation due to heat transfer across the access floor into the supply air and across the floor slab from the return air plenum below is a significant issue with UFAD systems. Many strategies have been developed to deal with this issue, but they are beyond the scope of this article. A well-designed underfloor plenum system using all of the known strategies to avoid thermal degradation should have a temperature rise across the plenum ranging from 2 F (1 C) to no more than 6 F (3.4 C). These strategies include location of supply air insertion points for the plenum to avoid lengthy or circuitous pathways to the most remote outlets and controlling insertion velocity to minimize the generation of large scale vortices under the floor. The fundamental hypothesis of UFAD systems is that loads in the open plan area served by the system will vary uniformly over time. Control schemes can be applied to the entire distribution system to handle the load variation that does occur in this space. Individual manual control can be applied to the floor diffusers to trim air delivery to individual workstations or to handle an extraordinary load event. Frequent manipulation of the floor diffusers is not considered to be a necessary component for maintaining comfort. A necessary corollary of this hypothesis is that comfort control for spaces not part of the general open plan can occur independently of the control stratagems imposed on the overall air-distribution system. These spaces might include closed offices, conference rooms and perimeter spaces. This corollary has significant implications for the design of the system to avoid conflict between comfort control in these separate spaces. Figure 1 shows typical UFAD system with both interior and perimeter zones served by the same floor supply plenum. System Control for Maximized Comfort Historically, UFAD systems have been designed and installed with various arrangements and control strategies with varying levels of success compared to conventional overhead systems. 2 Many times the project s physical form will guide the equipment locations and strategies, but in all cases, engineers should ensure that the systems are arranged to maximize occupant comfort and realize the other benefits possible with UFAD systems. Prior to committing to any control strategy, it is critical that the design team focus on creating system arrangements that minimize thermal decay and air leakage, promote air stratification and facilitate independent control of different space types served by the air-distribution system. Block loads in the interior zones of office spaces are not constant. Even in an open plan area with uniform work station MAY 2015 ashrae.org ASHRAE JOURNAL 47

3 density, the block load may demonstrate a variation across the day. Following a warm night or weekend, the cooling load will experience a peak during morning cool-down as the system overcomes high temperatures that result from the overnight deactivation of the HVAC system. In cooler weather, early morning cooling loads may be almost non-existent as the heat gain from lights, equipment and people must warm up the thermal mass of the space before the heat gain shows up as cooling load. A fundamental requirement for maintaining comfort is accommodation of these basic load profiles, while maintaining flexibility to meet loads in other spaces. Generally recognized schemes for tracking the block load profile of the open plan interior zone Maximum Design are to reset the positive pressure setpoint of the supply plenum with respect to the space and reset of the supply air temperature in the floor plenum. 3 Each of these alternatives has implications for comfort control in the non-open plan spaces. Reset of the plenum pressure setpoint requires that airflow to the zones that are not interior open-plan be independent of plenum pressure or that the air outlets in those spaces are sized for design airflow at a pressure lower than the maximum setpoint. Reset of supply air temperature implies that the air outlets be sized to meet design cooling loads with a higher supply air temperature than the minimum setpoint. Reset of supply air temperature also implies that the dew-point of the supply air is relatively independent of the supply air dry bulb temperature in order to maintain space humidity control in humid climates. Supply temperature downward reset should also be limited to a minimum of 60 F (15.6 C) to avoid thermal asymmetry discomfort (cold feet, warm head) for space occupants. Figure 2 is a control scheme that has been found successful for several different projects: Reset supply plenum static pressure setpoint based on interior space temperature. The logic resets the pressure setpoint to maximum design pressure (e.g., 0.1 in. w.g. [25 Pa]) when the interior spaces are warm down to 0.01 in. w.g. [2.5 Pa] when they are cold. Reset supply air temperature to satisfy the perimeter zone that requires the coldest air. The best reset strategy is trim and respond, which easily allows the user to ignore some non-critical zones from the logic. 4 The two strategies together can help prevent overcooling: as supply air temperature falls when perimeter zone 30% Design Lowest Possible (~15% Maximum ) 130 F Discharge Air Temperature Setpoint 60 F Heat Loop Output Deadband Cooling Loop Output FIGURE 2 Fan operation and airflow for perimeter fan terminals. 7 Airflow Design Airflow Airflow 30% Design Airflow Minimum Airflow (Due To Pressurized Plenum) cooling demand increases, the floor pressure falls to reduce airflow to interior spaces to reducing overcooling. These reset protocols require several temperature sensors mounted in the open office area. 3 The author s experience is that mounting these sensors approximately 6 ft (1.8 m) above the finished floor is an effective strategy. Several sensors, spaced around the open plan area, are used, and they can be averaged to determine whether or not reset is necessary. The setpoint temperature for these sensors, approximately at head height, should be a few degrees warmer than the ideal comfort temperature for seated chest height. These sensors should be identified on the documents as temperature sensors, as opposed to control thermostats, so as not to evoke Americans with Disabilities Act (ADA) requirements for location. Using differential pressure reset as a control stratagem is dependent upon two factors. The first of these is that the pressure sensors used have the sensitivity and accuracy to measure very low pressures. Inadequate sensors will not be able to deliver sufficiently fine control to modulate capacity in response to load variation. The sensor range should be as low as possible to capture the maximum design pressure. Sensors with accuracy as low as ±0.5% of full scale are readily available at reasonable cost. The second requirement is somewhat more subtle and it is that the pressure drop across the floor from the plenum to the space be sufficiently high to allow an adequate control range for re-setting the plenum pressure differential. Airflow through the floor from the plenum to the space is composed of both leakage through 48

4 Advertisement formerly in this space.

5 the floor and flow through the various diffusers and terminal units that control airflow to the space. Excessive leakage through the floor or deployment of too many floor diffusers can result in lower than anticipated pressure drop through the floor at design airflow. If design airflow is achieved at a much lower pressure differential across the floor than 0.05 in. w.g. (12.5 Pa), then the control range for floor pressure reset may be too small to achieve the required flow modulation to accommodate a varying load profile for the interior zones. In general, leakage from the supply plenum is classified as Type I, Leakage to Unoccupied Spaces (including outdoors, core and return air plenum), and Type II, Leakage to Occupied Spaces. While Type I leakage may represent energy waste, either fan energy for moving air directly from the supply plenum to the return plenum, or both fan and cooling energy by moving air out of the conditioned area, Type II leakage presents a more subtle controllability problem that may lead to overall occupant dissatisfaction with the building. Avoidance of this problem requires several different steps. The first is a robust performance specification for air leakage through the floor, accompanied by requirements for verification that the specified measures have been implemented. Recent testing data has indicated that leakage levels, at a pressure differential of 0.05 to 0.06 in. w.g., (12.5 Pa to 15 Pa) of less than 5% for Type I, and less than 7.5% for Type II, may be achieved. 5 Performance specification and testing requirements will enable the owner to require remediation should the floor system fail to comply. The second step is an accurate load calculation to determine the maximum amount of supply airflow that will be required to condition the area served by the underfloor plenum. The third step is to allocate the number of passive floor diffusers such that design flow will only be achieved when plenum pressure is at or above the target pressure differential. Sizing of air terminals and determination of the number and location of passive diffusers should recognize that Type II leakage will contribute a significant amount of uncontrolled conditioning air to the space. The author has often limited passive diffusers to workspace locations, completely eliminating them from transient areas such as passageways and congregation areas, in order to maintain an adequate pressure drop from the plenum to the space. If building commissioning reveals that airflow is achieved at a lower pressure differential than desired, then some of the floor diffusers may be closed off. Use of plenum pressure reset as a means of tracking the block load of the interior space means that other types of zones must be able to track their individual loads independently of plenum pressurization. For enclosed private offices or small conference rooms this may mean the use of thermostatically controlled floor diffusers that are sized to deliver design airflow at lower than design pressure. Thermostatic controls can restrict flow through the diffuser during periods of lower part loads in the space or of higher pressurization of the supply plenum. Areas with more intense cooling loads such as large interior conference rooms and perimeter zones require thermostatically controlled fan forced air supply to those zones. Variable speed fan terminals convey air from the plenum to the space independently of plenum pressurization, fully isolating perimeter zone temperature control from load tracking in the interior zone. Ideally, the heating mechanism for the perimeter zones is completely separated from the underfloor air system, for example, under-window convectors, but rarely is this solution architecturally acceptable. As a result, the fan terminals usually incorporate hydronic coils or electric resistance coils to provide heat to the perimeter zones. The fan terminal control scheme in Figure 2 recommended to be compliant with ASHRAE/IES Standard 90.1 restrictions on reheat of previously cooled air. 6 Large conference room variable speed fan terminals follow a similar control scheme except that the fan does not shut off in the deadband in order to fully comply with ASHRAE Standard CO 2 sensors can be used to dynamically reset the minimum airflow setpoint. Because CO 2 emission from occupants can cause CO 2 to rise faster than occupant heat gain causes space temperature to rise, reheat coils may be required to maintain the room within the required temperature range. If reduction of supply plenum differential pressure proves inadequate to avoid overcooling the interior zones of the space, the second stage of capacity control for the interior zones is raising the supply air temperature setpoint. Unfortunately, upward reset of supply air necessarily impacts system cooling capacity for the perimeter zones. This strategy should be avoided except during periods when perimeter or conference room loads are very unlikely to be at design levels, such as during nighttime partial occupancy. In most cases, occupied periods with the lowest internal zone cooling loads, possibly required supply air temperature reset, are the same periods that will likely have lower conference room and perimeter zone loads. 50

6 Advertisement formerly in this space.

7 Conclusion Many projects have demonstrated that UFAD systems are an appropriate and successful HVAC system selection for some office building applications. Successful design of UFAD systems requires reconciling passive comfort control in the interior open-plan zones with active comfort control in perimeter and enclosed zones. The most common comfort complaint in UFAD systems is overcooling in the open plan interior areas. Successful temperature control in these areas requires control schemes that allow the system to track interior zone load profiles without inordinately curtailing system capacity at the perimeter zones. Achievement of this goal can be accomplished through the following control measures: Use plenum pressure control as the primary means of tracking interior zone cooling loads. Use sensors that are sufficiently sensitive and accurate, precisely to control plenum pressurization. Ensure that supply air temperature reset does not compromise required cooling capacity at exterior zones, private offices or conference rooms. Use capacity modulation methods in perimeter and enclosed spaces that are relatively independent of supply plenum pressure. These goals can be achieved with either a common or a separate cooling source for perimeter and exterior zones. Success will be determined by rigorous recognition of how the control sequences interact to maintain comfort in both types of zones. References 1. Lee, E.S., et al A Post-Occupancy Monitored Evaluation of the Dimmable Lighting, Automated Shading, and Underfloor Air Distribution System in The New York Times Building. Lawrence Berkeley National Laboratory, pp Woods, J What real-world experience says about the UFAD alternative. ASHRAE Journal 46(2). 3. Megerson, J.E., et al UFAD Guide: Design, Construction and Operation of Underfloor Air Distribution Systems. Atlanta: ASHRAE. 4. Hydeman, M., et al Final Report: ASHRAE RP-1455 Advanced Control Sequences for HVAC Systems, Phase I. 5. Anticknap, S., M. Opalka Testing for leaks in underfloor plenums. ASHRAE Journal 53(12). 6. ASHRAE/IES Standard , Energy Standard for Buildings Except Low-Rise Residential Buildings, p Lee, K. H., et Lessons Learned In Modeling Underfloor Air Distribution Systems. Center for the Built Environment. Advertisement formerly in this space. 52

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

UNDERFLOOR AIR DISTRIBUTION

UNDERFLOOR AIR DISTRIBUTION FINAL REPORT NCEMBT-080801 UNDERFLOOR AIR DISTRIBUTION AN EXPERIMENTAL COMPARISON OF AIR DIFFUSION PERFORMANCE BETWEEN UNDERFLOOR AIR DISTRIBUTION AND CONVENTIONAL OVERHEAD AIR DISTRIBUTION SYSTEMS AUGUST

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering

Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Challenges and Failures in Green Building Design Using Under-Floor Air Distribution Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Agenda UFAD Overview Challenges / Failures Steps for a Successful

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

MULTIZONE APPLICATION OF SOLUTION UNITS

MULTIZONE APPLICATION OF SOLUTION UNITS MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Dual Maximum VAV Box Controls

Dual Maximum VAV Box Controls ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Integrated Solar Radiant Systems

Integrated Solar Radiant Systems Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design

J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal

More information

AIR DISTRIBUTION FOR COMFORT AND IAQ

AIR DISTRIBUTION FOR COMFORT AND IAQ AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant

More information

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Rev. No. 0 January 5, 2009

Rev. No. 0 January 5, 2009 ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic

More information

Key energy-efficient features of your new home

Key energy-efficient features of your new home Key energy-efficient features of your new home Your thermal envelope The thermal envelope, or shell, of your home (walls, roof and floor) is designed to keep you dry and comfortable. It protects you from

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE This article was published in ASHRAE Journal, September 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without

More information

Degrees of Freedom In HVAC Controls Design BY JOHN VARLEY, P.E., HBDP, MEMBER ASHRAE

Degrees of Freedom In HVAC Controls Design BY JOHN VARLEY, P.E., HBDP, MEMBER ASHRAE This article was published in ASHRAE Journal, June 05. Copyright 05 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work? engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony

More information

HVAC Characteristics. Test Space HVAC Characteristics

HVAC Characteristics. Test Space HVAC Characteristics HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

Principals of Condensing Boiler System Design

Principals of Condensing Boiler System Design Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-

More information

Center for the Built Environment UC Berkeley

Center for the Built Environment UC Berkeley Center for the Built Environment UC Berkeley Peer Reviewed Title: Analysis of a hybrid UFAD and radiant hydronic slab HVAC system Author: Raftery, Paul, National University of Ireland Galway Lee, Kwang

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS

UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS OVERHEAD SYSTEM UFAD SYSTEM ...... - A product of AirFixture USA I DON T CARE ZONE B R E A T H I N G Z O N E W E L L M I X E D CONSTANT VOLUME DIFFUSER WITH

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

HVAC Simplified Approach Option

HVAC Simplified Approach Option HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

Data Center Airflow Management Retrofit

Data Center Airflow Management Retrofit FEDERAL ENERGY MANAGEMENT PROGRAM Data Center Airflow Management Retrofit Technology Case Study Bulletin: September 2010 Figure 1 Figure 2 Figure 1: Data center CFD model of return airflow short circuit

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong

More information

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J. Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation

More information

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX Content Heating / Ventilation / Air Conditioning 3 The Right Room Climate 4 Optimised Energy Efficiency and well-being Room

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Energy Saving Fact Sheet Air Conditioning

Energy Saving Fact Sheet Air Conditioning Energy Saving Fact Sheet Air Conditioning Get your air conditioning into better shape Everyone wants air conditioning. But don t let your existing system, or one that you re considering installing, burn

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Dehumidification Design

Dehumidification Design Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental

More information

Central Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016

Central Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016 Central Plant Air Systems: Keeping the Heart and Click Lungs To Healthy Edit Master Title Style Better Buildings Summit May 2016 Introductions Michael Deru National Renewable Energy Laboratory New Resources

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Data Center Environments

Data Center Environments Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of

More information

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,

More information

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify

More information

Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland

Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC

More information

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2 providing insights for today s hvac system designer Engineers Newsletter volume 42 2 Understanding Single-Zone VAV Systems Single-zone variable-air-volume (VAV) is not a new concept, but due to new energy

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Active & Passive Beams

Active & Passive Beams Active & Passive Beams Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building and service the

More information

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

SIMULATION OF RADIANT COOLING PERFORMANCE WITH SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE

More information

Energy Efficient HVAC-system and Building Design

Energy Efficient HVAC-system and Building Design Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: maija.virta@halton.com SUMMARY This paper

More information

Energy Savings in High-Rise Buildings Using High-Reflective Coatings

Energy Savings in High-Rise Buildings Using High-Reflective Coatings Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

for Plans Examiners and Building Inspectors

for Plans Examiners and Building Inspectors Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History

Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems Ryan R. Hoger, LEED AP 708.670.6383 ryan.hoger@tecmungo.com History VAV systems came into favor for mid and large size

More information

The Data Center Dilemma - A Case Study

The Data Center Dilemma - A Case Study Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Acoustic Design Practices for Sustainable Buildings

Acoustic Design Practices for Sustainable Buildings Acoustics 2008 Geelong, Victoria, Australia 24 to 26 November 2008 Acoustics and Sustainability: How should acoustics adapt to meet future demands? Acoustic Design Practices for Sustainable Buildings Danny

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Energy Efficiency. Energy Efficient Home Cooling:

Energy Efficiency. Energy Efficient Home Cooling: Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Enclosed Football Stadium Design History and Lessons Learned

Enclosed Football Stadium Design History and Lessons Learned Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention

More information

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Thermal Mass Availability for Cooling Data Centers during Power Shutdown 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

Raised Floor Data Centers Prepared for the Future

Raised Floor Data Centers Prepared for the Future Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

Measure Server delta- T using AUDIT- BUDDY

Measure Server delta- T using AUDIT- BUDDY Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size

More information

The Benefits Really Add Up

The Benefits Really Add Up Unico, Inc. 7401 Alabama Ave. St. Louis, MO 63111 Unico, Inc. manufacturing plant and sub-assembly plant +1 800 527 0896 +1 314 481 9000 www.unicosystem.com Unico, Inc. is the leader in Small Duct High

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Protocol for the Certification of Energy Simulation Software: First edition, December 2009

Protocol for the Certification of Energy Simulation Software: First edition, December 2009 Copyright Agrément South Africa, December 2009 The master copy of this document appears on the website: http://www.agrement.co.za Protocol for the Certification of Energy Simulation Software: First edition,

More information

Heating and cooling. Insulation. Quick facts on insulation:

Heating and cooling. Insulation. Quick facts on insulation: Heating and cooling Heating and cooling your home can be one of the biggest users of energy. Efficency in this area can bring great savings. Heating and cooling depend on many contributing factors. The

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information