Service manual. ActivA
|
|
|
- Darrell Nathan Fields
- 10 years ago
- Views:
Transcription
1 Wall hung, fan flue, room sealed, high efficiency gas boiler Service manual ctiv Models: G.C. ppl. No. ctiv 25C ctiv 30C ctiv 35C ctiv 18S ctiv 25S ctiv 30S Leave this manual adjacent to the gas meter
2 Table of contents 1 Overall information Overall View Hydraulic diagram General access and emptying hydraulic circuits Nomenclature ody panels Control panel Main electronic p.c.b. box Emptying the primary circuit Emptying the d.h.w. circuit Diagrams Wiring diagram ctiv 25C ctiv 30C.ctiv 35C Wiring diagram ctiv 18S ctiv 25S ctiv 30S Circuit voltages Fault finding Display diagnostic Condensing heat exchanger Function Removal Cleaning D.h.w. heat exchanger Function Removal Pump Function Checks Removal pump Removal electrical capacitor Three way diverter valve Function Checks Removal of the electric actuator Removal of the tree way diverter valve Removal of the diverter group Main electronic control/ignition p.c.b Function Selection and adjustment devices Checking the temperature Setting the boiler control function modes Checks Removal of the electronic control p.c.b Thermal control in the mode Thermal control in the mode Control panel electronic p.c.b Function Info modality Function modes setting modality Removal of the control panel electr. p.c.b Gas valve Function Description of the parts djustment Checks Removal of the gas valve Primary circuit flow switch Function Checks Removal Expansion vessel and pressure gauge Function Checks Removal of the expansion vessel Removal of the pressure gauge D.h.w. flow switch, filter and flow limiter Function Description and location of parts Checks Removal of the sensor Removal of the flow switch group and d.h.w. circuit filter Flow limiter Temperature probe Function Checks Removal of the c.h.temperature probe Removal of the d.h.w.temperature probe y--pass valve Function Removal Fan and ir box Function Removal of the Fan and the ir box Ignition and detection electrodes and rner Function Removal of the Ignition and detection electrodes Removal of the rner Checks Safety thermostat Function Checks Removal Flue temperature probe NTC and Safety thermal fuse Function Removal Checks Condensate trap Function Check the cleanness of the trap Removal Short spare parts list... 44
3 1 Overall information 1.1 Overall View Flue temperature probe NTC Safety thermostat Condensing heat exchanger Detection electrode Expansion vessel C.h. temperature probe Ighition electrodes urner Pipe silencer D.h.w. flow switch Gas restrictor D.h.w. heat exchanger Main circuit pressure switch y --- pass valve Three way diverter valve Fan ir box (air/gas mixer) Electronic control box Condensate trap C.h. pressure relief valve utomatic air purger valve Pump Control panel Electric actuator diverter valve Pressure gauge D.h.w. temperature probe Gas valve 1.2 Hydraulic diagram Central heating (c.h.) operation Domestic hot water (d.h.w.) operation C.h. water return C.h. water flow D.h.w. inlet D.h.w. outlet 1
4 2 General access and emptying hydraulic circuits C 2.1 Nomenclature 1 C Fig Right side panel 2 Front panel 3 Control panel 4 Main electronic p.c.b. box 5 Left side panel 2.2 ody panels For the most part of the check and maintenance operations it is necessary to remove one or more panels of the case. Thesidepanelscanberemovedonlyaftertheremoval of the front panel. To remove the front panel loosen screws (Fig. 2.2). 3 Fig. 2.3 To remove the side panels loosen the screws (Fig. 2.2) and C (Fig. 2.3). Pullthesidepanelstowardstheoutside. 2.3 Control panel To gain access to the parts located inside the control panel proceed as follows: 1 Remove the front panel of the case. 2 To open the control panel by leverig with a screwdriver in as shown in Fig. 2.4 D Fig bottom view of the boiler Pull the lower part of the front panel and lift it upwards (Fig. 2.3). 2 Fig To access to the parts located inside the control panel to free the hook D (Fig. 2.4) and turn it as showninfig.2.5.
5 General access and emptying hydraulic circuits Fig Main electronic p.c.b. box Fig Remove the terminal block lid E (Fig. 2.6). 7 Free the hooks placed on the three sides indicated and rotate the lid towards left (Fig. 2.8). To gain access to the parts located into main electronic p.c.b. box proceed as follows: 1 Remove the front panel of the case. Terminal block lid removal 2 To remove the terminal block lid E (Fig. 2.6), free the front hooks. E Fig Emptying the primary circuit 1 Close the c.h. circuit flow and return cocks F. (Fig. 2.9). Fig Slightly rotate the lid as indicated by the curved arrow and free the rear hooks. 4 Remove the lid. Main electronic p.c.b. lid removal To get access to the main electronic p.c.b.: 5 Pull the box that contains the electronic p.c.b. and rotate it (Fig. 2.7). H Fig bottom view of the boiler 2 Remove the front and right panels of the boiler. 3 Open the drain tap G (Fig combi or Fig only c.h.) until the boiler is completely emptied. 4 Close drain tap once the emptying has been completed. F 3
6 General access and emptying hydraulic circuits CLOSED G OPEN Fig G Fig Emptying the d.h.w. circuit 5 Close the d.c.w. inlet cock H (Fig. 2.9). 6 Open one or more hot water taps until the boiler has been completely emptied. 4
7 3 Diagrams 3.1 Wiring diagram ctiv 25C ctiv 30C.ctiv 35C. Three way diverter valve 1 M ~ 3 bn bn bn 2 Pump gnye bn gnye Gas valve wh gnye bn gy Fan M ~ wh wh rd rd Ignition electrodes wh gy gy rd rd rd rd gy gy Condensate trap rd rd gy t t Flame detection electrode wh Flue temp. probe NTC D.h.w. temp. probe NTC D.h.w. flow switch COM og vt Fuse 2F 250VC 5x20 Primary circuit pressure switch bn gnye t C.h. temperature probe NTC bn Safety thermostat Remote External temp. probe terminal block rd rd rd Electric supply terminal block Room thermostat Frostat terminal block N L gnye bn ye wh vt og wh ye rd Time switch (option) bn = brown = blue = black wh = white rd = red gy = grey gn = green ye = yellow vt = violet og = orange gnye = green/yellow rdwh = red/white 5
8 Diagrams 3.2 Wiring diagram ctiv 18S ctiv 25S ctiv 30S Pump gnye Gas valve 1 3 bn gnye 4 gnye bn gy Fan M ~ wh wh rd rd Ignition electrodes wh gy gy gy gy Condensate trap gy t Flame detection electrode wh Flue temp. probe NTC bn bn wh rd rd COM og vt Fuse 2F 250VC 5x20 Primary circuit pressure switch gnye t C.h. temperature probe NTC bn Safety thermostat Remote External temp. probe terminal block rd rd rd Electric supply terminal block Room thermostat Frostat terminal block N L gnye bn ye wh vt og wh ye rd Time switch (option) bn = brown = blue = black wh = white rd = red gy = grey gn = green ye = yellow vt = violet og = orange gnye = green/yellow rdwh = red/white 6
9 Diagrams 3.3 Circuit voltages during c.h. or d.h.w. operation Electrical voltages with rner on only during c.h. operation only during d.h.w. operation Pump Gas valve 3way diverter valve D.h.w. Flow switch 230~ ~ 0 230~ 230~ 230~ 230~ 0 5= 0 Supply network Fan Main circuit pressure switch Safety thermostat 7
10 4 Fault finding Components to check Section of the manual! (note ref. in brackets) --- (1) --- (2) --- (3) (4) (7) Defect # ppliance lock---out (*) Power supply line Gas supply line Flue pipes Cond. drain pipe and trap C.h. circuit D.h.w. circuit Condensing heat exchanger D.h.w. heat exchanger Pump Diverter valve D.h.w. flow switch Fuses (Electronic p.c.b.) Main electronic p.c.b. oiler settings Control panel electr. p.c.b. Gas valve Main circuit pressure switch D.h.w. filter Main circuit temp. probe D.h.w. temp. probe y --- pass valve Fan / air restrictor Ignition electrode Detection electrode Safety thermostat Gas restrictor Flue temp. probe NTC Expansion vessel Safety valve Pressure gauge External temp. probe Er 01 J J J J Er 02 J J J Er 03 J Er 04 J J Er 05 J Er 06 J Er 07 J Er 08 J s Er r Er 09 J J Er 10 J J Er 11 J J J Er 14 J J J Li 01 J Display i indicates 8
11 Components to check Section of the manual! (note ref. in brackets) --- (1) --- (2) --- (3) (4) (7) ppliance lock---out (*) Cond. drain pipe and trap Condensing heat exchanger Control panel electr. p.c.b. Main circuit pressure switch Defect # Power supply line Gas supply line Flue pipes C.h. circuit D.h.w. circuit D.h.w. heat exchanger Pump Diverter valve D.h.w. flow switch Fuses (Electronic p.c.b.) Main electronic p.c.b. oiler settings Gas valve D.h.w. filter Main circuit temp. probe D.h.w. temp. probe y --- pass valve Fan / air restrictor Ignition electrode Detection electrode Safety thermostat Gas restrictor Flue temp. probe NTC Expansion vessel Safety valve Pressure gauge External temp. probe The boiler does not start either in c/h or d.h.w. mode. The control panel display OFF Fan still. J J J J The boiler does not supply d.h.w. (cold water from the tap). Regular operation in c/h mode even during a drawing off d.h.w. J J J On c/h mode the temperature of the main circuit reaches 90 C and the c/h system does not heat. The boiler operates correctly on d.h.w. mode. J J J Incorrect modulation J J J J Noisy bolier J J J J J J Poor c.h. / d.h.w. temperature (9) J J J J J Poor d.h.w. temperature. Regular operationinc/hmode. J J J (8) J No Er indication on display --- Low d.h.w. flow rate J J J Water leaks from the safety valve duringoperationonc/h J J J J J J --- Water leaks from the safety valve when the boiler is off. J J J * Lock out is indicated as Er on the display. Note Useful information can be obtained also from the optical indication given by the appliance display (see section 4.1). 1 Check for 230V~ between line (L) and neutral (N) Verify the integrity of supply cable, plug and external fuses. Check the polarity of line and neutral connection 2 Verify the soundness of the gas supply pipe, the position of stop valves. 3 Check for soundness and absence of obstructions. Verify that the flue terminal is correctly installed (see clearances) and ensure that exhaust gas is not sucked back by the boiler. 4 Check for soundness of the circuit and verify its correct filling (see also installation manual). 5 jammed by --- pass could cause the over --- heating of the main circuit and the intervention of the safety thermostat. 6 Using the flue analyzer, check the CO 2 value of the flue gases. This reading is a reference value for the gas valve setting. 7 Check the pressurization of the expansion vessel. Refer to the installation manual for proper values. 8 d.h.w. pressure too high or flow rate too high. If necessary insert a flow rate limiter (14.6). 9 The boiler doesn t reach the nominal heat input. 9
12 4.1 Display diagnostic n help for the fault finding may be given by the display indications. The display on the control panel gives many information. Only the indications useful for the fault finding are here described. The following table gives the relationship between the indications of error of the display and their meaning. Er 01 + RESET Er 02 + RESET Er 03 + RESET Er 04 + Er 05 + Er 06 + Er 07 + Er 08 + Er 09 + Er 10 + RESET Er 11 + RESET Er 14 + Er 14 + RESET Li 01 Lack of rner ignition Safety thermostat lockout Other faults Faulty primary circuit (no water or absence of flow) Faulty fan control system Faulty c.h. temperature probe NTC Faulty d.h.w. temperature probe NTC Faulty external temperature probe NTC (if fitted) Faulty flue temperature probe NTC Lockout --- flue temperature probe NTC (Flue temperature > 120 C) Parasite flame Faulty primary circuit (no water or absence of flow) (temperature increase > 2K/s) (the boiler can t restart for 10 minutes) Faulty pump (absence of water flow in the main circuit) or primary temperature above 105 C Primary circuit temperature limit during d.h.w. operation 10
13 5 Condensing heat exchanger O L 5.1 Function The Condensing heat exchanger in Fig. 5.1 has the function of transferring heat produced from comstion of the gas and from the flue exhausted gas to the water circulating in it. X Q T X J K I O S M D C W E F G H R Fig. 5.1 y reducing the comstion products temperature, the latent heat of the vapour is transferred to the water circuit, allowing an extra gain of useful heat. The condensed vapour is then drained through the condensate trap and the draining pipe C. 5.2 Removal 1 Turn off the gas supply. 2 Removeallthecasepanels(seesection2). 3 Disconnect the flue system from the boiler. 4 Disconnect the air manifold D (Fig. 5.2) by pulling it. 5 Disconnect the rubber pipe E. 6 Unscrew the gas connector F. 7 Remove the fixing fork G and remove the gas pipe H. 8 Unscrew the screws and remove the detection electrode connector I (Fig. 5.2) 9 Unscrew the screws and remove the ignition electrodes connector J. 10 Unscrew the screw and remove the overheat thermostat K. 11 Disconnect the connector L by pressing the plastic hook placed on the side of the connector. 12 Disconnect the connector M P Fig Disconnect the fan connector N by pressing the plastic hook placed on the side of the connector (Fig. 5.3). Fig Empty the primary circuit of the boiler. 15 Remove the expansion vessel following the instructions in section Remove the forks O (Fig. 5.2). 17 Loosen the connection P and remove the pipe Q from the Condensing heat exchanger. N 11
14 Condensing heat exchanger 18 Loosen the connection R and remove the pipe S from the Condensing heat exchanger. 19 Unscrew the screws T. 20 Remove the fan---rner group. Fig. 5.4 W U V 21 Using pliers, remove the spring U moving it downwards and disconnect the rubber pipe V (Fig. 5.4). 22 Loosen the screws W (Fig Fig. 5.2) 23 Unscrew the screws X (Fig. 5.2). 24 Remove the Condensing heat exchanger slightly move it upwards, turn it frontwards freeing it from the below screws W (Fig Fig. 5.2) and then extractitforwards. 25 Reassemble the Condensing heat exchanger carrying out the removal operations in reverse order. Ensure to tight the screws T --- Fig. 5.2 firmly 5.3 Cleaning If there are deposits of dirt between the fins of the Condensing heat exchanger, clean with a bristle paintbrush and remove the dust with a hoover. Warning: fter cleaning or replacement as detailed above, if it deemed necessary to undertake a comstion analysis, refer to the appropriate chapter Maintenance of the installation instructions manual. 12
15 6 D.h.w. heat exchanger 6.1 Function The d.h.w heat exchanger in Fig. 6.1 and Fig. 6.3 allows the instantaneous transfer of heat from the primary hydraulic circuit to the water destined for d.h.w use. 1 Remove the panels of the case. 2 Empty the primary circuit and the d.h.w circuit of the boiler. 3 Remove the control panel following the instructions from 3 in section Remove main electronic p.c.b. box following the instructions from 5 in section Remove the pump following the instructions in section Completely unscrew the llen key screws (Fig. 6.3) which hold the exchanger to the plastic groups. Fig. 6.1 The schematic structure is shown in Fig Fig Move the exchanger towards the rear of the boiler and extract it leftwards. Reassemble the d.h.w. heat exchanger carrying out the removal operations in the reverse order. Warning: to lubricate the O-- ring gaskets exclusively use a silicone base grease compatible to be in contact with foods and approved by the local water uthorities. ttention. When reassembling the exchanger be sure to put the off centre location/securing pin indicated in Fig. 6.4 towards the left side of the boiler. Fig. 6.2 Primary hydraulic circuit Domestic hot water circuit 6.2 Removal Fig
16 7 Pump 7.1 Function The pump in Fig. 7.1 and Fig. 7.3 has the function of making the water in the main circuit circulate through the main condensing heat exchanger and therefore through the c.h. system (during the c.h. function) or through the secondary heat exchanger (during the d.h.w. function). n Check that the impeller is integral with the rotor. With the boiler off remove the front and right hand side case panels, lower the control panel and empty the primary circuit. Remove the pump head by undoing the screws which hold it to the pump body and check that the impeller is firmly joined to the rotor. 480 Ω 213 Ω Coil 2 Coil 1 Fig Removal pump Fig Checks 14 n Check that the pump is not seized and that the movement of the rotor is not subject to mechanical impediments. With the boiler off, remove the front panel. Remove the air release plug of the pump and turn the rotor with a screwdriver. n Check the electrical continuity. With the boiler off, remove the front panel and disconnect the connector (Fig. 7.3). Measure the electrical resistance between the pump supply connections. Electrical resistance of the windings (at ambient temperature) must be about 213 Ω (coil 1) and 480 Ω (coil 2) (Fig. 7.2). n Check the absence of starting defects. With the boiler off remove the front case panel. Remove the air release plug from the pump. Start the boiler and with a screwdriver, turn the rotor in the direction of the arrow. If there is a defect in starting, the rotor will begin to turn normally only starting it manually. 1 Remove the front and right hand side case panels. 2 Empty the primary circuit of the boiler. 3 Disconnect the connector (Fig Fig. 7.4) following the indications given on the connector box. 4 Disconnect the earth connector C E D Fig Loosen the connection D,and pull up and turn to the left the pipe E. C K L
17 Pump G 3 Remove the connector M of the cover box by levering with a screwdriver in as shown in (Fig. 7.5) E D C I H J M F K L Fig C.H. only model remove the fork F, loosen the connection G and remove the pipe H (Fig. 7.4). 7 C.H. only model remove the fork I and remove the pressure gauge pipe J (Fig. 7.4). 8 Remove the locking plate K (Fig Fig. 7.4). 9 Unscrew the two screws L that hold the pump on theframeandremovethepump. Reassemble the pump carrying out the removal operations in the reverse order. When reassembling the pump, check the correct location of the O---ring gasket in the inlet port of the pump that seals the connection between the pump and the plastic group. Fig Remove the capacitor connection block N freeing it from the hook O and pulling it as indicated by the arrow (Fig. 7.6). N O 7.4 Removal electrical capacitor 1 Remove the front and right hand side case panels. 2 Disconnect the connector (Fig. 7.3) following the indications given on the connector box. Fig
18 8 Three way diverter valve 8.1 Function The diverter valve (Fig. 8.1) has the function of modifying the hydraulic circuit of the boiler by means of an electric command given by the electronic control p.c.b. in order to send the water that exits the primary heat exchanger towards the c.h. system or towards the d.h.w. heat exchanger Spindle visible 9,4 Kohm Open circuit bn 0V 230 V Fig D.h.w. mode = black = blue bn = brown Spindle not visible Open circuit 9,4 Kohm Fig Checks n Check the electrical continuity Fig. 8.2 indicates the relationship between the electric command coming from the electronic control p.c.b. and the position of the actuator (brass spindle) when the boiler operates in d.h.w. mode. Fig. 8.3 indicates the relationship between the electric command coming from the electronic control p.c.b. and the position of the actuator (brass spindle) when the boiler operates in c.h. mode. In both figures the relationship between the position of the actuator and the resistance of the motor windings (the motor must be disconnected from the wiring) is also given. bn Fig C.h. mode 230 V 0V = black = blue bn = brown 8.3 Removal of the electric actuator 1 Remove the front case panel. 2 Disconnect the connectors C (Fig. 8.4). 3 Remove the fixing spring D and remove the actuator. Reassemble the actuator carrying out the removal operations in the reverse order. When reassembling the actuator, refer to Fig. 8.2 or to the wiring diagram in section 8.2 for the correct wiring connection. 16
19 Three way diverter valve C 8.5 Removal of the diverter group 1 Remove the front and both side case panels. 2 Empty the primary circuit and the d.h.w circuit of the boiler. 3 Remove the electric actuator (see section 8.3). 4 Remove the fixing spring H (Fig. 8.6) and remove the primary circuit pressure switch I. I D H Fig. 8.4 M 8.4 Removal of the tree way diverter valve 1 Remove the front and both side case panels. 2 Empty the primary circuit and the d.h.w circuit of the boiler. 3 Remove the electric actuator (see section 8.3). 4 Remove the fixing spring E (Fig. 8.5) 5 Remove the tree way diverter valve F by levering with a screwdriver in as shown in Fig L Fig Disconnect d.h.w. temperature probe, respectively J (Fig. 8.7). N K F J G Fig. 8.5 Reassemble the tree way diverter valve carrying out the removal operations in the reverse order. Warning: to lubricate the O-- ring gaskets exclusively use a silicone base grease compatible to be in contact with foods and approved by the local water uthorities. ttention. When reassembling the tree way diverter valvebesurethatthetreewaydiverteriscorrectly oriented by matching the reference G with the notch of the water group Fig. 8.5 E Fig Unscrew the connector K (Fig. 8.6), the c.h. flow connector and the d.h.w. outlet connector. 7 Remove the d.h.w. heat exchanger (see section 6.2). 8 Remove the fork L and move away the pipe M (Fig. 8.6). 9 Unscrew the screws N and remove the diverter group (Fig. 8.6). 10 Reassemble the diverter group carrying out the removal operations in the reverse order. Warning: to lubricate the O-- ring gaskets exclusively use a silicone base grease compatible to be in contact with foods and approved by the local water uthorities. 17
20 9 Main electronic control/ignition p.c.b. 9.1 Function Fig Inlet Information On the Main electronic control/ignition p.c.b... Function control C.h. temperature adjustment D.h.w. temperature adjustment oiler reset tton (control panel electronic p.c.b.) From other boiler devices... C.h. temperature probe NTC D.h.w. temperature probe NTC D.h.w. flow switch Primary circuit pressure switch Flue temperature probe NTC Safety thermostat Flame detection electrode Room thermostat (if fitted) Time switch (if fitted) Outlet command Pump Three way diverter valve Gas valve Fan Ignition electrodes Display indicates Er * *control panel electronic p.c.b. The fundamental function of the Main electronic control/ignition p.c.b. is that of controlling the boiler in relation to the external needs (i.e. heating the dwelling or heating the water for d.h.w. use) and operating in order to keep the temperature of the hydraulic circuits constant. This is obviously possible within the useful power and maximum working temperature limits foreseen. Generally, the Main electronic control/ignition p.c.b. receives inlet information coming from the boiler (the sensors) or from the outside (control panel electronic p.c.b., room thermostat, etc.), processes it and consequently acts with outlet commands on other components of the boiler (Fig. 9.1). The Main electronic control/ignition p.c.b. is also a full sequence ignition device and does a sequence of operations (ignition cycle) which lead to the ignition of the gas at the rner It checks the presence of the flame during the entire period in which it is activated and supplies the fan regulating its speed. The Main electronic control/ignition p.c.b. has a safety function and any incorrect interventions or tampering can result in conditions of dangerous functioning of the boiler. The Main electronic control/ignition p.c.b. can lock the functioning of the boiler (lock state) and stop its functioning up to the resetting intervention. The lock---out is signalled on the display of the control panel electronic p.c.b. and can be reset only by using the boiler reset tton placed on the control panel electronic p.c.b. (see section 10.1). Some components which are connected to the device can activate the lock state. The causes of a lock state could be: f The intervention of the safety thermostat (overheat of the primary circuit). f f f f f f The intervention of the flue temperature probe (overheat of the comstion products). fault on gas supply. Faulty ignition (faulty ignition electrodes, their wiring or connection). Faulty flame detection (faulty detection electrode, its wiring or connection). Faulty condensate drainage. Faulty gas valve (faulty on---off operators or not electrically supplied). f Faulty Main electronic control/ignition p.c.b.. Other components like the primary circuit pressure switch can temporarily stop the ignition of the rner t allow its ignition when the cause of the intervention has stopped. Fig and Fig show the sequence of the operations that are carried out at the start of every ignition cycle and during normal functioning. 9.2 Selection and adjustment devices On the Main electronic control/ignition p.c.b. several selection, adjustment and protection devices are located. (Fig. 9.2).
21 Main electronic control/ignition p.c.b. Some of these devices are directly accessible by the user (function control, temperature adjustment etc.) others, like the fuses, are accessible by removing the main electronic p.c.b. lid The temperature of the water is converted into an electric signal by means of temperature probes. The user, setting the desired temperature with the control panel p.c.b. key or If the power requested is lower than 40% of the maximum power output then control is achieved by switching ON the rner at minimum power, then switching OFF (ON/OFF function). If the power requested is higher, then the rner is switched ON at maximum power and will control by modulating to 40% of the maximum power output. During the c.h. operation (Fig. 9.3), the signal coming from the c.h. temperature probe is compared to the signal given by the control panel p.c.b. through the adjustment made by the user (key ). The result of such a comparison operates the fan speed thus regulating the gas flow rate and consequently changing the useful output of the boiler Fig Connector --- ignition electrode. 2 Connector --- flame detection electrode. 3 Connector --- controler fan. 4 Connector --- flue temperature probe NTC. 5 Connector --- d.h.w. temperature probe NTC, d.h.w. flow switch and external temperature probe (optional). 6 Connector --- Primary circuit pressure switch. 7 Connector --- safety thermostat and c.h. temperature probe NTC. 8 Connector --- remote control (optional). 9 Connector --- display and function control / c.h. / d.h.w. temperature adjustment control panel p.c.b. 10 Fuse F1, F2 2 F 11 Connector --- electric supply Main electronic control/ignition p.c.b. 12 Connector --- 3way diverter valve. 13 Connector --- electric supply control panel p.c.b. 14 Connector --- gas valve, pump and fan. 9.3 Checking the temperature The Main electronic control/ignition p.c.b. makes it possible to separately adjust the c.h. water flow temperature and d.h.w. outlet temperature. Fig. 9.3 When the boiler functions in d.h.w. (Fig. 9.4), the signal coming from the d.h.w. temperature probe is compared with the signal given by the control panel through the adjustment made by the user (key ). 19
22 Main electronic control/ignition p.c.b. Fig To move trough the parameters press c.h. set keys ( or C Fig. 9.7) 90 C C Fig The display shows Fig. 9.8 Fig. 9.4 Normally, the result of the comparison between these two signals directly operates the fan speed adjusting the useful output generated in order to stabilize the temperature of the exiting water. If during the d.h.w. mode operation, the temperature of the primary circuit goes over 90 C, the useful output is automatically reduced so that the primary circuit cannot reach excessive temperatures. The control sequences in function and in function are illustrated in detail in sections 9.7 and Setting the boiler control function modes It is possible to select the various boiler control function modes hereafter named parameters by using the keys of the control panel p.c.b. Fig To modify the parameter press contemporary the keys ( --- Fig. 9.9) C Fig To enter in the parameters setting mode press contemporary the 3 keys ( C Fig. 9.5) for 10 second until the display shows Fig Fig To change the parameters press c.h. set keys ( or C Fig. 9.7) 6 To memorize the setting press the key ( Fig. 9.10)
23 Main electronic control/ignition p.c.b. Fig To exit for setting without modifing the set press the keys ( --- C Fig. 9.11) Fig To reset the boiler to the normal operation press contemporary the 3 keys ( C Fig. 9.5) for 10 second. The following table gives details of each parameter and thepossiblevaluethatcanbeset. Important: at the end of the setting operation it is important to fill/update the table in the installation manual see chapter COMMISSIONING section: Setting record. PRMETER DIGIT VLUES oiler type (to be updated with the com- Pr =NopowerEr99 01 = ctiv 25C plete range) 02 = ctiv 30C. 03 = ctiv 35C. 06 = ctiv 18S 08 = ctiv 25S 09 = ctiv 30S Not used Pr 02 Not used Pr 03 Not used Pr 04 Gas type Pr = G20Natural 05 =G31Propane Not used Pr 06 C.h. flow max temperature C Factory reset parameters Pr 07 Pr 08 C (factory set 85 C) 00 = No reset 04 = ll parameters return to factory set with the exclusion of Pr 01 and Pr = ll parameters return to factory set included Pr 01 and Pr 05 PRMETER DIGIT VLUES Chimney sweep Pr = No chimney function sweep fun (factory set) 01 = Low power sweep---test 04 = C.h. power sweep---test 07 = D.h.w. power sweep---test C.h. reignition frequency Pr (0 600 sec.) (factory set 30 = 3 minutes) C.h. pump post---circulation Max. useful output in c.h. mode C.h. pump working type Pr (0 600 sec.) (factory set 10 = 1 minute) Pr (0 100%) factory set: 74 = ctiv 25C 79 = ctiv 30C. 86 = ctiv 35C. 99 = ctiv 18S 99 = ctiv 25S 99 = ctiv 30S Pr = Depends on room thermostat (factory set) 04 = lways running Ignition power Pr (0 100%) factory set: Natural gas (G20) 20 = ctiv 25C 30 = ctiv 30C. 26 = ctiv 35C. 32 = ctiv 18S 38 = ctiv 25S 30 = ctiv 30S K value (external probe diagram) Not used Pr 16 D.h.w. rner turn off Pr 17 function NTC on the c.h. return Propane (G31) 31 = ctiv 25C 30 = ctiv 30C. 26 = ctiv 35C. 49 = ctiv 18S 37 = ctiv 25S 31 = ctiv 30S Pr (=0,1) 60 (=6,0) Kvalue factory set: 00 =Off Pr = urner off at fixed d.h.w. = 65 C (factory set) 01 = rurner off at set point +5 C 00 = Probe not present 01 = Probe present 21
24 Main electronic control/ignition p.c.b. PRMETER DIGIT VLUES Not used Pr 19 Not used Pr 20 Not used Pr 21 Not used Pr 22 Not used Pr 23 Not used Pr 24 Not used Pr 25 Not used Pr 26 C.h. minimum setpoint Pr (factory set 25 C) 4 Delicately flex the hooks D in the directions indicated (Fig. 9.12) in order to release the circuit from the box. 5 Remove the Main electronic control/ignition p.c.b.. Tab Checks n Check that the fuses are complete If the Main electronic control/ignition p.c.b. does not supply any device (pump, fan, etc.) check that the fuses 10 (Fig. 9.2) are complete. If a fuse has blown replace it with one that has the same characteristics after having identified the reason for failure. n Lock sequence Start the boiler until the rner is ignited. With the rner firing, interrupt the gas supply. The Main electronic control/ignition p.c.b. must carry out four complete ignition cycles and then, after about 4 minutes, goes to lock---out state. Switch off and on the electricity supply to the boiler, by means of the fused spur isolation switch, the device must not unlock and the rner must not turn on 9.6 Removal of the electronic control p.c.b When replacing the Main electronic control/ignition p.c.b. all parameters must be correctly checked / adjusted accordingly with the values noted in table in the installation manual see chapter COMMIS- SIONING section: Setting record (for information on parameters see also section 9.4). 1 Removeallthebodypanels(seesection2.2). 2 Gain access to the parts located inside the Main electronic p.c.b. box as explained in the section 2.4 of this manual. 3 Remove all the wiring connected to the Main electronic control/ignition p.c.b.. Fig D 6 Re --- assemble the Main electronic control/ignition p.c.b. following the removal procedures in the reverse order. Important When re --- assembling the Main electronic control/ignition p.c.b.: 7 It is not necessary to utilise static protections t it is advisable to ensure that the pcb is handled with care and held at the edges and with clean dry hands. ttention fter installing the Main electronic control/ignition p.c.b. properly set the parameters. Warning: fter cleaning or replacement as detailed above, if it deemed necessary to undertake a comstion analysis, refer to the appropriate chapter Maintenance of the installation instructions manual. D 22
25 Main electronic control/ignition p.c.b. 9.7 Thermal control in the mode Switch in the function mode circulator on Taking water from the domestic hot water circuit? circulator off fan still Is primary circuit temperature higher than that selected? Main circuit pressure switch consense? stop circulator (3min) lock memorised? cancels lock starts fan checks fan rpm Is fan rpm exact? Is flue temperature higher than 110 C? beginning of wait period flame presence? End of wait period? starts ignition discharges Opens gas valve beginning of ignition period flame presence? interrupts ignition discharges gas valve open fan runs End of ignition period? closes gas valve stops fan interrupts ignition discharges memorizes lock display show lock--- out Is fan rpm exact? reset key pressed? safety thermostat or flue temperature probe lock out? flame presence? Fig
26 Main electronic control/ignition p.c.b. 9.8 Thermal control in the mode Switch in the function mode See functioning with the function control in the mode (sec. 9.7) Taking water from the domestic hot water circuit? circulator on Request for heat from room thermostat? circulator off fan still Is primary circuit temperature higher than that selected? Main circuit pressure switch consense? stop circulator (3min) lock memorised? cancels lock starts fan checks fan rpm Is fan rpm exact? Is flue temperature higher than 110 C? beginning of wait period flame presence? End of wait period? starts ignition discharges Opens gas valve beginning of ignition period flame presence? interrupts ignition discharges gas valve open fan runs End of ignition period? closes gas valve stops fan interrupts ignition discharges memorizes lock display show lock--- out Is fan rpm exact? reset key pressed? safety thermostat or flue temperature probe lock out? flame presence? Fig
27 10 Control panel electronic p.c.b Function Fig F E D ) C.h. temperature increase key ) C.h. temperature reduce key C) Reset/Stand---by/Winter/Summer key D) D.h.w. temperature reduce key E) D.h.w. temperature increase key F) Display The Control panel electronic p.c.b. can give to the service 3 levels of informations: f Normally information (see the installation manual chapter PPLINCE DESCRIPTION section LCD general features. f Info modality f Function modes setting modality 10.2 Info modality TheINFOmodeallowsthedisplayofsomeinformation on the boiler functioning status. In case of malfunctioning of the boiler, it may be useful to communicate such information to the uthorised Service Centre Engineer so that the causes can be understood. In order to access the INFO mode, press keys and C (Fig.10.1)atthesametimeuntiltheletterdi appears on the display that alternates with a code (Fig. 10.2). C To scroll the values press (reduce) and (increase). keys (Fig. 10.1). In order to exit the INFO mode, hold keys and C (Fig. 10.1) pressed at the same time. The following table gives details of each parameter and thepossiblevaluethatcanbeshow. Description Parameter Value External temperature C d (if fitted) K value (external probe diagram) d2 12 (the value is x 10) Offset (Transaltion of K diagram d ±15 C) C.h. temperature C (calculated d4 66 by external sensor) C.h. flow temperature C d5 78 C.h. return temperature C (if d6 44 fitted) D.h.w. temperature C d7 40 Flue temperature C d8 67 Fan speedy (the value has to d9 44 be x 100 = 4400 rpm) SW version C (rner control) dc 01 SW version M (main board) dd 03 Tab Function modes setting modality It is possible to select the various boiler control function modes hereafter named parameters by using the keys of the control panel p.c.b. During the function modes setting, the boiler does not operate. To get in function modes setting modality see section Removal of the control panel electronic p.c.b Fig Removeallthebodypanels(seesection2.2). 2 Gain access to the parts located inside the Control panel electronic p.c.b. as explained in the section 2.3 of this manual. 3 Removeallthewiring connected to the Control panel electronic p.c.b. (Fig. 10.3). 25
28 Control panel electronic p.c.b. C C 4 Unscrew the screws 5 Delicately flex the hooks C in the directions indicated (Fig. 10.3) in order to release the circuit from the box. 6 Remove the Control panel electronic p.c.b.. 7 Reassemble the Control panel electronic p.c.b. carrying out the removal operations in the reverse order. C Fig
29 11 Gas valve 11.1 Function The Gas valve in Fig controls the gas inflow to the boiler rner. 5 Gas valve inlet pressure test point 11.3 djustment Check the supply pressure before making any adjustment to the gas valve. 1 Close the gas inlet valve. 2 Remove the front panel of the case and lower the control panel (see sections 2.2 and 2.3). 3 Loosen the internal screw on the Inlet Pressure Test Point 5 (Fig. 11.2) of the Gas valve and connect a pressure gauge using a suitable hose. 4 Open the gas inlet valve. 5 Turn on the electricity supply to the boiler, switching on the fused spur isolation switch. 6 Set the boiler in c.h. / d.h.w. function as illustrated in Fig C.h. / d.h.w. function Fig y means of an electric command given to the on---off operators the passage of the gas through the Gas valve can be opened or closed Description of the parts (Fig. 11.2) Fig Open at least one hot water tap fully. 8 Read the inlet pressure value and ensure that it is within the limits given in the table Gas supply pressures, of the user/installation manual If it does not comply with the required pressure check the gas supply line and governor for faults and/or correct adjustment. 9 Switch off the boiler close the gas inlet valve and close the water tap. 10 Disconnect the pressure gauge and close the Inlet Pressure Test Point 5 (Fig. 11.2). Gas valve adjustment 11 Fit the probe of the flue analyser in the flue exhaust sampling point located on the exhaust pipes of the boiler (Fig. 11.4). flue exhaust sampling point air intake sampling point 5 Fig Maximum gas pressure adjustment 2 Minimum gas pressure adjustment 3 On---off operators 4 On---off operators electric connector Fig Turn on the boiler, switching on the fused spur isolation switch. 13 Open the gas inlet valve. 27
30 Gas valve Fig To enter in the parameters setting mode press contemporary the 3 keys ( C Fig. 11.5) for 10 second until the display shows Fig C Model Type gas CO 2 % value (range) ctiv 25C Natural (G20) 8, ,2 ctiv 30C. ctiv 35C. ctiv 25S ctiv 30S Propane (G31) 9, ,1 ctiv 18S Natural (G20) 8, ,2 Propane (G31) 9, ,3 Tab To adjust the CO 2 % value remove the brass plug by unscrewing it and rotate the llen key screw ø 4 mm (2 --- Fig. 11.2) (by rotating it clockwise the CO 2 % increases). Checking the maximum gas valve setting 19 Press key to vary the output in chimney sweep mode: when the display shows the letters cp that alternate with the heating water temperature value (e.g.60), the chimney sweep function is at maximum output in heating mode (Fig. 11.8); Fig djusting minimum gas valve setting 15 Press keys and C (Fig. 11.5) at the same time until the display shows the letters LP that alternate with the heating water temperature value (e.g.45), indicating the activation of the chimney sweep function at minimum output (Fig. 11.7). Fig Press further key to vary again the output in chimney sweep mode: when the display shows the letters dp that alternate with the heating water temperature value (e.g.60), the chimney sweep function is at maximum output in domestic hot water mode (Fig. 11.9); Fig Open at least one hot water tap fully. 17 llow the analyser to give a stable reading. 18 Read the CO 2 %value. It should be between: 28 Fig llow the analyser to give a stable reading. 22 Read the CO 2 %value. It should be between:
31 Gas valve Model Type gas CO 2 % value (range) ctiv 25C Natural (G20) 9, ,9 ctiv 30C. ctiv 35C. Propane (G31) 10, ,9 ctiv 18S Natural (G20) 9,3--- 9,9 Propane (G31) 10, ,8 ctiv 25S Natural (G20) 9,2--- 9,8 ctiv 30S Propane (G31) 10, ,9 Tab To adjust the CO 2 % value rotate screw (1 --- Fig. 11.2) (by rotating it clockwise the CO 2 % decreases). 23 Press keys C (Fig. 11.5) at the same time again to exit the chimney sweep mode and return to the previously set boiler status (Fig ) C.h. / d.h.w. function 1 Remove the front panel of the case as explained in the section 2.3 of this manual. 2 Disconnect the connector D (Fig ). H F E D I G Fig Switch off the boiler and turn off the hot water tap(s). 25 Close the air---flue sampling points. 26 fter adjustment fit the protective brass plug (2, Fig. 11.2). Important: after the gas pressure checks and any adjustment operations, all of the test points must be sealed Checks n Check the on--- off operators coils 1 Remove the front panel of the case. 2 Disconnect the electrical connector 4 (Fig. 11.2). 3 Measure the electrical resistance between the connector pins of the on--- off operators as illustrated in Fig ON--- OFF Operator approx Ω* ON--- OFF Operator approx. 920 Ω* * at ambient temperature. Fig Removal of the gas valve Fig J 3 Turn off the gas supply and disconnect the gas isolation cock connector from the inlet port of the gas valve. 4 Using pliers, remove the spring E and the rubber pipe F (Fig ). 5 Unscrew the connector G (Fig ), remove the fixing fork H and remove the pipe I. 6 Unscrew the screws J and remove the valve (Fig ). 7 Reassemble the valve carrying out the removal operations in reverse order. Warning: e careful not to damage the OR gasket of the gas pipe when inserting the pipe in the air box (air/gas mixer). efore to fit a new valve it is advisable to pre--set it as follows. 8 Remove the brass plug and turn the plastic screw inside it fully clockwise until it stops. Do not overtight. 9 Turn it counter---clockwise 2 and 3/4 turns. 10 djustthegasvalveusingtheflueanalyserasdescribed in section fter any service operation on the components of the gas circuit check all the connections for gas leaks. Warning: fter cleaning or replacement as detailed above, it is deemed necessary to undertake a comstion analysis as detailed in chapter 11.3 section
32 12 Primary circuit flow switch 12.1 Function N.O. C The Primary circuit flow switch ( in Fig. 12.1) function is to check the presence of water in the primary hydraulic circuit and that the pressure is above the minimum. Fig Removal 1 Remove the front and right hand side panels of the case, turn off the flow and return isolation valves and empty the primary circuit. 2 Remove the fixing spring (Fig. 12.3) and remove the primary circuit pressure switch. 3 Disconnect the connectors C (Fig. 12.3). C D Fig This device is connected to the main electronic control p.c.b. and if, it does not activate the control board will indicate that a fault condition (see section 4.1 of this manual) has occurred Checks Fig Reassemble the primary circuit pressure switch in reverse order of removal. Warning: to lubricate the O-- ring gaskets exclusively use a silicone base grease compatible to be in contact with foods and approved by the local water uthorities. 13 Expansion vessel and pressure gauge n Electrical check 13.1 Function It is possible to verify the general operation of the switch by measuring the electric resistance between the contacts C. and N.O. of the switch. 1 Measure the electrical resistance between the tabs marked C. and N.O. (Fig. 12.2). The contact must close (resistance zero) with c.h. pressure of 0,35 bar or higher. 30 The Expansion vessel (D in Fig. 12.1) function is to allow for the volume expansion of the c.h. circuit water due to the temperature rise Checks 1 Turn off the flow and return isolation valves and empty the primary circuit of the boiler.
33 Primary circuit flow switch 2 Remove the protective cap E (Fig. 13.1) from the valve on the top of the expansion vessel and connect a suitable air pressure gauge. E 1 Remove the front and right hand side panels of the case, turn off the flow and return isolation valves and empty the primary circuit. 2 Completely unscrew the connection F, thelocknut G (Fig. 13.2). 3 Unscrew the screws H and remove the bracket I (Fig. 13.2). 4 Remove the expansion vessel from the front of the boiler. 5 Re---assemble the parts in reverse order of removal. Fig Check the pre---load pressure and refer to the section Expansion vessel in the User manual and installation instructions for the correct value Removal of the expansion vessel 13.4 Removal of the pressure gauge 1 Remove the front and side panels of the case, turn off the flow and return isolation valves and empty the primary circuit. 2 Remove the fork J (Fig. 13.3). H J I Fig Combi J G F Fig C.h. only Fig Squeeze the tabs K to release the pressure gauge L and remove it. 31
34 Primary circuit flow switch 4 Re---assemble the parts in reverse order of removal. L K Fig
35 14 D.h.w. flow switch, filter and flow limiter 14.1 Function The d.h.w. flow switch in Fig is a device that generates an electrical signal when hot water is drawn. 6 Filter 7 Sensorholderspring 8 Sensor Fig Whentheflowratethroughthed.h.w.circuitreaches about 2,5 litres/min, the float 5 (Fig. 14.3) is dragged upwards and the magnetic in it, getting closer to the sensor 8 closes the electric contact. Fig C 14.2 Description and location of parts (Fig. 14.3) 1 Flow switch plug 2 O --- ring 3 Flow limiter (ctiv 30C. ctiv 35C. optional accessory) 4 ody 5 Float D Fig Checks 6 n Sensor operation 1 Remove the front panel of the case. 2 Measure the electrical resistance at the leads of the sensor. Without water being drawn, the contact must be open. y opening a hot water tap the contact must be close (electrical resistance zero Ω) Removal of the sensor 1 Remove the front panel of the case. 2 Disconnect the connectors and remove the sensor holder spring C (Fig. 14.2). 3 Remove the sensor Removal of the flow switch group and d.h.w. circuit filter 1 Remove the front panel of the case and empty the d.h.w. circuit. 2 Remove the sensor (see section 14.4). 3 Remove the fork D and pull up the flow switch plug 1 with the help of a screwdriver. 4 To remove the filter from the flow switch group separate the filter 6 from the body 4 (Fig. 14.3) by levering it. 5 Reassemble the parts following the removing sequence in reverse order. 33
36 D.h.w. flow switch, filter and flow limiter 14.6 Flow limiter The ctiv 25C model is factory fitted with a 10 litres/ min. flow limiter. The ctiv 30C. model is factory fitted with a 12 litres/ min. flow limiter. The ctiv 35C. model is factory fitted with a 14 litres/ min. flow limiter. The following sizes are available: If the flow rate of the d.h.w. circuit is still too high, it is possible to limit it by replacing the flow limiter. The following sizes are available: Nominal flow rate (litres/min) Colour 10 lue 12 Red 14 Pink To install the flow limiter: 1 Remove the flow switch group as explained in the section Separate the flow switch plug 1 from the body 4 levering with a screwdriver one of the two hooks. Fig Insert the flow limiter 3 as shown in Fig Reassemble the group following the above sequence in reverse order
37 15 Temperature probe 15.1 Function The Temperature probe has the function of converting the temperature of the water in the hydraulic circuit where it is installed into an electrical signal (resistance). The relation between temperature and electrical resistance is stated in Fig Ω Fig On the boiler there are two Temperature probes. One on the output of the primary condensing heat exchanger (c.h. Temperature probe) in Fig and Fig. 15.3; one on the output of the d.h.w. heat exchanger (d.h.w. Temperature probe) in Fig and Fig C 15.2 Checks n Temperature---resistance relationship Disconnect the cable from the Temperature probe. Measure the temperature of the pipe C (only c.h. Temperature probe) where the Temperature probe is located and check the electrical resistance according to the graph in Fig Removal of the c.h.temperature probe 1 Removeallthecasepanels. 2 Empty the primary circuit of the boiler. 3 Remove the electric connector D and remove the c.h. Temperature probe --- Fig Reassemble the c.h.temperature probe carrying out the removal operations in reverse order. D C Fig Removal of the d.h.w.temperature probe 1 Remove the front panel of the case and lower the control panel. 2 Empty the d.h.w circuit of the boiler. 3 Remove the electric connector E 4 Remove the fork F and pull the d.h.w. Temperature probe --- Fig Reassemble the d.h.w. Temperature probe carrying out the removal operations in reverse order. Fig c.h. return c.h. flow d.h.w. inlet d.h.w. outlet Warning: to lubricate the O-- ring gaskets exclusively use a silicone base grease compatible to be in contact with foods and approved by the local water uthorities. 35
38 Temperature probe F E Fig
39 16 y --- pass valve 16.1 Function The y --- pass valve in Fig is located between the c.h. water flow and return and its function is that of guaranteeing a minimum flow across the primary heat exchanger if the circulation across the c.h. system is completely closed. They---passvalveisfittedontherearsideofthediverter group. Fig Reassemble the by--- pass valve as illustrated in Fig reversing the order of removal. Warning: to lubricate the O-- ring gaskets exclusively use a silicone base grease compatible to be in contact with foods and approved by the local water uthorities. ttention. When reassembling the y-- pass valve be sure that it is correctly oriented by matching the reference C with the notch D of the water group Fig D Fig C 16.2 Removal 1 Removeallthecasepanels. 2 Empty the primary circuit of the boiler. 3 Remove the locking plate andpulluptheby--- pass valve (Fig. 16.2). Fig
40 17 Fan and ir box 17.1 Function The function of the Fan (Fig. 17.1) is to force the mixture of air and gas into the rner. The function of the ir box is to mix the gas and the air in the right proportion. The flow rate of the air---gas mixture and consequently the input power of the boiler is proportional to the speed of the fan that is controlled by the electronic control p.c.b. 4 Disconnect the rubber pipe D. 5 Unscrew the gas connector E 6 Remove the fixing fork F and remove the gas pipe G. 7 Disconnect the connector H 8 Disconnect the fan connector I by pressing the plastic hook placed on the side of the connector. 9 Unscrew the screws J. 10 Remove the fan with the air box. 11 Remove the screws K and the air box (Fig. 17.3). K K K Fig Open the strip L by sliding the edges with the help of a screwdriver and remove the ir box Fig Fig Removal of the Fan and the ir box 1 Turn off the gas supply. 2 Removeallthecasepanels(seesection2). L H F D G E Fig Fan gasket 3 Disconnect the air manifold from pipe C by opening the strip (Fig. 17.2). I J C Fig ssemble the Fan and the ir box carrying out the removal operations in reverse sequence. efore reassembling ensure the fan gasket (Fig. 17.2) is correctly mounted. Warning: e careful not to damage the OR gasket of the gas pipe when inserting the pipe in the air box (air/gas mixer). fter any service operation on the components of the gas circuit check all the connections for gas leaks. Warning: fter cleaning or replacement as detailed above, if it deemed necessary to undertake a comstion analysis, refer to the appropriate chapter Maintenance of the installation instructions manual.
41 18 Ignition and detection electrodes and rner 18.1 Function Three electrodes are fitted on the fan---rner group. Two of them, fitted on the right side of the fan---rner group, are the ignition electrodes OntheleftsideisthedetectionelectrodeC and it detects the presence of the flame. H F H 2 Disconnect the ignition electrodes connector E and the earth wire F (Fig. 18.1) and disconnect the detection electrode connector G. 3 Unscrew the screws H and remove the ignition electrodes and the detection electrode C (Fig. 18.1). 4 ssemble the Ignition and detection electrodes carrying out the removal operation in reverse order Removal of the rner 1 Remove the air box and the fan (see section 17.2) 2 Unscrew the screws I (Fig ) and remove the fan---rner duct. 3 Remove the rner by sliding it forward. I locating tab H C G E Fig The rner D is fitted on the rear of the fan---rner group. Fig rner gasket 4 ssemble the rner carrying out the removal operation in reverse order. Ensure the rner is correctly located by lining up the locating tab (Fig. 18.3). efore reassembling ensure the rner gasket is correctly located. D Warning: fter cleaning or replacement as detailed above, if it deemed necessary to undertake a comstion analysis, refer to the appropriate chapter Maintenance of the installation instructions manual Checks Fig n Check the position of the electrode edges 18.2 Removal of the Ignition and detection electrodes 1 Removeallthecasepanels(seesection2). 1 Remove the ignition electrodes (see section 18.2) 2 Check for the correct distance between the metallic edges of the ignition electrode (see Fig. 18.4). 39
42 Ignition and detection electrodes earth electrode n Check the connection wires. 3,5 mm Ignition electrode Fig
43 19 Safety thermostat 19.1 Function The safety thermostat in Fig is a device that senses the temperature of the primary circuit water which flows in the outlet pipe of the condensing heat exchanger. If the temperature control system of the boiler fails and the temperature of the primary circuit reaches a dangerous temperature, the safety thermostat opens the electric circuit that supplies the on---off operators of the gas valve. Consequently, the full sequence ignition device attempts to light the rner and, at the end, locks the boiler and lights the lock---out signal lamp. n Electrical function 1 Removeallthecasepanelsandthelidofthe sealed chamber. 2 Disconnect the safety thermostat and check its electrical function. Normally (no intervention) the contact must be closed (electrical resistance zero Ω) Removal 1 Removeallthecasepanelsandthelidofthe sealed chamber. 2 Disconnect the wiring (detail in Fig. 19.2). 3 Unscrew the screws C and remove the overheat thermostat. C Fig Checks n Overheat temperature value 1 Set the temperature control knobs to their max. position and run the boiler in d.h.w. and c.h. 2 llow the boiler to reach its maximum operating temperature (monitor the temperature gauge on the instrument panel). The boiler should maintain a temperature below that of the safety thermostat and no overheat intervention should occur. Fig Reassemble the overheat thermostat carrying out the operations in reverse order. 5 pply an adequate quantity of heat conducting compound between the pipe and the thermostat. Warning: fter cleaning or replacement as detailed above, if it deemed necessary to undertake a comstion analysis, refer to the appropriate chapter Maintenance of the installation instructions manual. 41
44 20 Flue temperature probe NTC and Safety thermal fuse 20.1 Function The Flue temperature probe NTC in Fig and Fig senses the temperature of the comstion products that flow through the condensing heat exchanger Removal 1 Removeallthecasepanels. 2 Disconnect the connector from the Flue temperature probe NTC by pressing the plastic hook placed on the side of the connector. 3 Unscrew and remove the flue temperature probe (Fig. 20.2) from the condensing heat exchanger. 4 ssemble the Flue temperature probe NTC carrying out the removal operations in reverse sequence Checks Fig If the temperature of the comstion products circuit reaches the limit temperature, the Flue temperature probe NTC reduces the gas flow rate to the rner. The temperature of the comstion products should decrease to a safe value temperature. In the case that the temperature of the comstion products reaches a potentially dangerous value, it stops the boiler operation (lock--- out). This allows the use of plastic materials for the flue outlet pipes and bends. The use of kits different from the original isn t however allowed, since the flue pipes are integral parts of the boiler. n Overheat temperature value 1 Set the temperature control knobs to their max. position and run the boiler in d.h.w. and c.h. 2 llow the boiler to reach its maximum operating temperature (monitor the temperature gauge on the instrument panel). The boiler should maintain a temperature below that of the Flue temperature probe NTC and no overheat intervention should occur. n Temperature---resistance relationship 1 Remove the Flue temperature probe NTC (see section 20.2). 2 Measure the Flue temperature probe NTC electrical resistance at the ambient temperature and check it according to the graph in Fig Ω C Fig Fig. 20.3
45 21 Condensate trap 21.1 Function The condensate trap in Fig and Fig allows the discharge of the condensate via the condensate drain pipe avoiding in the mean time the escape of comstion products. plastic ball closes the trap outlet in case that the trap is empty Removal 1 Remove the front and right case panels. 2 Unscrew the threaded locking ring C and remove theflexiblepiped (Fig. 21.2). 3 Disconnect the electric connector E 4 Using pliers, remove the spring F moving it upwards. 5 Remove the trap from the pipe G. 6 Reassemble carrying out the removal operations in reverse order. G F Fig If the drain pipe is plugged or in any case in which the condensate isn t correctly evacuated, the condensate level in the trap rises till it reaches a screw that is in contact with the flame detection circuit thus causing the boiler lock --- out Check the cleanness of the trap Unscrew the plug on the bottom of the trap and remove dirt eventually deposit (Fig. 21.2). Fig D C E 43
46 22 Short spare parts list Key G.C. part no. Description Q.ty Manufacturer Manufacturer s reference part no. 1 urner (mod. ctiv 25C, ctiv 18S) 1 I urner (mod. ctiv 30C., ctiv 35C., 1 I ctiv 25S, ctiv 30S) 2 Expansion vessel 1 I Condensing heat exchanger (mod. ctiv 25C, 1 I ctiv 18S ) Condensing heat exchanger 1 I (mod. ctiv 30C., ctiv 35C., ctiv 25S, ctiv 30S) 4 Fan 1 I Gas valve 1 I SIT 848 Sigma H Safety valve 1 I Watts 7 Main Electronic control/ignition p.c.b. 1 I Control panel electronic p.c.b. 1 I H D.h.w. heat exchanger (ctiv 25C) 1 I E D.h.w. heat exchanger 1 I (mod. ctiv 30C., ctiv 35C.) 10 Pump (mod. ctiv 25C, ctiv 30C., 1 I ctiv 35C.) Pump (mod. ctiv 18S, ctiv 25S, 1 I ctiv 30S) 11 Temperature probe (main circuit) 1 I D.h.w. flow switch 1 KI Primary circuit pressure switch 1 I Three way diverter valve (electric actuator) 1 I E Overheat thermostat 1 I ELTH --- type H Flue temperature probe NTC 1 I E Fuse 2 F 250VC 5x20 2 I Temperature probe ( D.h.w. circuit) 2 KI Detection electrode 1 I Ignition electrode 1 I Pressure gauge 1 I Condensate trap 1 I
47 Short spare parts list
48 * * UK 16/ iasi UK Ltd Newman Park, Western Way Wednesry, WS10 7J Sales Tel No: Sales Fax No: Service Tel No: Service Fax No:
Spare Parts List Activ A 25C Activ A 30C Activ A 35C Activ A 18S Activ A 25S Activ A 30S
*1756202470* 17562.0247.0 REV3 06/09 2012 Spare Parts List Activ A 25C Activ A 30C Activ A 35C Activ A 18S Activ A 25S Activ A 30S Issue Table description Issue n. of pages Overall view 06/2009 1 C.h.
Spare Parts List M96A.24SM/B M96A.28SM/B
*16202390* 162.0239.0 REV5 14/04 2015 Spare Parts List M96A.24SM/B M96A.28SM/B Issue Table description Issue n. of pages Overall view 09/2008 1 C.h. return group and d.h.w. heat exchanger 09/2008 1 C.h.
SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009
Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model R8216470-01EN - Edition 01-26/10/2009 Boilers CUENOD Renewable 3121488 12 EAA1...... 3124527 25
For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
User's Instructions. Alpha HE CB25/33 and HE SY25
User's Instructions Alpha HE CB25/33 and HE SY25 Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Boiler Range For Technical help or for Service call... ALPHA HELPLINE Tel:
USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.
Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV. MULTIPOINT Please read and understand these instructions before starting work. Please leave this leaflet
LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
Spare Parts List Activ A 12OV Activ A 15OV Activ A 20OV Activ A 25OV
*175620240* 17562.024.0 REV1 01/06 2010 Spare Parts List Activ A 12OV Issue Table description Issue n. of pages Overall view 1 Main circuit assembly 1 Gas assembly 1 Valves and connection pipes 1 Control
ELECTRIC CENTRAL HEATING FLOW BOILER
ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment
SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model. CELTIC RSc b CUENOD. R8202395-02EN - Edition 02-21/04/2005
CUENOD Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model CELTIC RSc b R8202395-02EN - Edition 02-21/04/2005 Boilers Solar Panel 69214511 31 CELTIC
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4
PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: AW 120 / AW 122 / AW 125 AWD 120 / AWD 121 / AWD 129
PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: The information included in this Splendide Repair Manual may change without notice. Please see our web site www.splendide.com/service/docs.html for updates,
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book
USERS GUIDE LOGIC Heat 12, 15, 18, 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user
For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
SERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2
SERVICE COMPACT SERVICE 000 MANUAL Mod. 000 9X Mod. 000 9X Mod. 000 94X Part Forward This Service Handbook is intended to assist with servicing and fault-finding in Caravans and Motor Caravans equipped
TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table
New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
Luna 3 Comfort Troubleshooting Guide June 2008
Luna 3 Comfort Troubleshooting Guide June 2008 For Technical Assistance Call: (800)461-4657 WARNING! THIS DOCUMENT IS INTENDED ONLY AS AN EDUCATIONAL TOOL This Troubleshooting Guide, and the instructions
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html TECHNICAL SERVICE DEPARTMENT Removal, Cleaning, & Reinstallation of the Burner Assembly For models 74 & GT199 Required tools -
Response: The combi boiler. Response: The fit anywhere combi
Response: The combi boiler The Ideal Response is a wall mounted, fanned flue combination boiler which serves a home's central heating system and delivers hot water on demand. It has been designed to be
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
Cooling system components, removing and installing
Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,
Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS
Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar
Wall boiler spare parts
SAUNIER Disconnector see page.14 Wall boiler spare parts Saunier Duval/ Chaffoteaux/MTS/ ELM > CHAFFOTEAUX Printed Circuit see page.39 SD Substituted spare parts Saunier Duval Description New ref Old ref
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
SERVICE SERVICE MANUAL FOR ALDE ELECTRICAL HEATER
SERVIE SERVIE MNUL FOR LDE ELETRIL HETER 2737 2762 2763 ontents Page hap Title 3 1:0 Flow chart 4 2:0 bout the electrical heater 4 2:1 Technical data 4 3:0 General faultfinding 4 4:0 Faultfinding 4 4:1
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
Fossil fuel heating equipment
Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating
1 DESCRIPTION OF THE APPLIANCE
1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers
Cooling system components, removing and installing
Page 1 of 34 19-1 Cooling system components, removing and installing WARNING! The cooling system is pressurized when the engine is warm. When opening the expansion tank, wear gloves and other appropriate
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
Service Manual. Coffee maker Senseo Viva Café HD7825/30 10/05. Philips Consumer Lifestyle
Coffee maker Senseo Viva Café Philips Consumer Lifestyle Service Manual PRODUCT INFORMATION - This product meets the requirements regarding interference suppression on radio and TV. - After the product
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual
Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction
HeatSource HS1800 Heater
HeatSource HS1800 Heater Vehical Installation & Operating Instructions Propex Heatsource Ltd Unit 5, Second Avenue Buisness Park, Milbrook, Southampton, SO15 OLP Tel: 023 8052 8555 Fax: 023 8052 8800 Website:
POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT
POSEION 2-29, 2-25 & 2-22 POSEION 2-29, 2-25 & 2-22 XT Repair Manual Index A. Safety precautions 3 B. Technical data 4 C. Structure 5-6. Service / Repair 7-23 E. Tools 24 F. Function 25-26 G. Electric
Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions
Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy
Baxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler
User s Operating Instructions Baxi Combi 130 HE Gas Fired Wall Mounted Condensing Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount
G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
Powers Controls TH 192 HC Heating/Cooling Room Thermostat
Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional
Installation and maintenance instructions. Danfoss Vent
Installation and maintenance instructions Danfoss Vent 1 Unit design... 2 2 Project planning and installation instructions... 3 2.1 Ventilation...3 2.2 Piping installation....3 2.3 Condensation line...4
Installation and Servicing Instructions. Alpha 240/280. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers
Installation and Servicing Instructions Alpha 240/280 Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers For Technical help or for Service call... ALPHA HELPLINE Tel: 0870
Thermo Top - Troubleshooting Tree
Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may
OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)
OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12) Revision 1.0 Page 1 of 50 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE SOLE PROPERTY OF INTERNATIONAL THERMAL RESEARCH, LTD. ANY REPRODUCTION
Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)
17 Engine-Lubrication system (Page GR-17) Lubrication system components, removing and installing Oil pan, removing and installing Oil pressure and oil pressure switch, checking Dynamic oil pressure warning
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
SERVICE INSTRUCTIONS
SERVICE INSTRUCTIONS 18, 20,24, 26L Integrity Electronic Gas Continuous Flow Water Heater TM031 Reevvi issi ion:: B Publissheed:: Feebrruaarryy 0088 871018 871020 871024 871024-B 871024-C 871026 871026-B
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
Fleck 4650. Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET
Fleck 4650 Service Manual TABLE OF CONTENTS JOB SPECIFICATION SHEET...1 INSTALLATION AND START-UP PROCEDURE...1 CONTROL VALVE DRIVE ASSEMBLY...2 CONTROL DRIVE ASSEMBLY FOR CLOCK...3 BYPASS VALVE ASSEMBLY...4
RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions
RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create
TOBY DVR5 OIL CONTROL & SAFETY VALVE
TOBY DVR5 OIL CONTROL & SAFETY VALVE TECHNICAL HANDBOOK Principle of Operation The Toby DVR5 Oil Control Valve is a multi function unit for maintaining a constant oil level, regulating the oil flow and
TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Tankless Electric (RTE) Troubleshooting
Sequence of Operations 1 Power supply and field wiring block 2 Energy Cut Off (ECO) 3 Water flow plunger and cold inlet 4 Magnetic flow switch 5 Water temperature thermistor 6 Control panel and circuit
Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler
User s Operating Instructions Baxi Combi Instant 8e & 15e Gas Fired Wall Mounted Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.
SERVICE MANUAL REFRIGERATION
SERVICE MANUAL REFRIGERATION ELECTROLUX ZANUSSI S.p.A. Publication no. Spares Operations Italy 599 35 61-04 Corso Lino Zanussi, 30 021218 I - 33080 PORCIA / PN (ITALY) ITZ/SERVICE/AA Fax +39 0434 394096
Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)
17 Engine-Lubrication (Page GR-17) Lubrication system components, removing and installing Oil filter housing, disassembling and assembling Oil pan, removing and installing Oil pressure and oil pressure
Triac Printed Circuit Board Replacement
Technical Service Bulletin: Triac Printed Circuit Board Replacement TRONIC 5000C Pro Models: WH17, WH27, WH36 Introduction Fig. 1 ELECTRICITY IS EXTREMELY DANGEROUS. TAKE EXTRA PRECAUTIONS AND ENSURE ALL
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided)
ELECTRIC FUEL PUMPS P/N 12-801-1, 712-801-1, 12-802-1, 712-802-1, 12-815-1, & 712-815-1 FUEL PRESSURE REGULATORS P/N 12-803, 12-501, 12-804, 12-500, & 15812NOS Installation Instructions THESE INSTRUCTIONS
High Efficiency Boiler Range Technical Guide
High Efficiency Boiler Range Technical Guide Glow-worm Nottingham Road Belper Derbyshire DE56 1JT Head Office: 01773 824 639 Literature: 01773 596 105 After Sales Service: 01773 596 510 Technical Advice:
Rheem Spare Parts Manual. Commercial gas model A631265 Exterior 265L
Commercial gas model A631265 Exterior 265L Commercial gas model A631265 Exterior 265L Item Part No. Description 1 221735 Foam cover 2 221914 Anode x 3 (black) 1153mm 2 221924 Anode x 3 (blue) 1153mm 3
3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE
4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement
i ChatterBox! Motorcycle Security
i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before
Baxi Combi 80e & 105e
Baxi Combi 8e & 15e Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural
Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.
Model Number: Serial Number: Information Manual Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters. ATTENTION: IF YOU ARE NOT A LICENSED PLUMBER OR A LICENSED
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL
148 OLD CONCORD TURNPIKE, BARRINGTON NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:[email protected] www.seafrost.com ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL
AquaNova. Water heater. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER
AquaNova Water heater Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER Vokèra is a licensed member of the Benchmark scheme which aims to improve the standards of installation
User manual and Installation instructions
Wall hung, fanflue, roomsealed, high efficiency gas boiler User manual and Installation instructions Riva Plus HE Models G.C. Appl. No. M296.24SM/C 47-583-24 Combi boiler M296.28SM/C 47-583-25 Combi boiler
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for
Oil - kerosene burners
Installation, use and maintenance instructions Oil - kerosene burners One stage operation CODE MODEL TYPE 3747469 G0 474T5 90 (0) - 05/008 TECHNICAL FEATURES Thermal power output 95 3 kw 8 8 kg/h Fuel
Service Manual REU - 16 FUA - E. Infinity 16 i. Continuous Flow Water Heater. Important.
Service Manual REU - 16 FUA - E Infinity 16 i Continuous Flow Water Heater Important. Read these instructions carefully before attempting service of this appliance. All work must be carried out by competent
User Guide and Important Warranty Information. Heatmax Combi HE Range. Condensing Combination Boiler
You can rely on User Guide and Important Warranty Information Heatmax Combi HE Range Condensing Combination Boiler Please keep these instructions in a safe place. If you move house, please hand them over
Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
SF15K SF05KSS, SF10KSS
Product Instruction Manual Speedflow SF05K, SF10K & SF15K SF05KSS, SF10KSS & SF15KSS Undersink unvented water heater V15.6/6 Version 3.2 Jan 2015 Thank you for purchasing a Hyco Speedflow unvented water
Description of functions
Description of functions Laddomat 21 is designed to......allow the boiler to reach a high working temperature soon after firing....to preheat the cold tank water in the bottom of the boiler so that the
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
Mikrofill Ethos Condensing combination boiler
Mikrofill Ethos Condensing combination boiler Installation Instructions 24cc CE Mark No: 0201055 British Gas Service Listing G.C.No: 47-157-01 Mikrofill gas appliances comply with the requirements contained
Volvo Penta Quality Line Marine Water Heaters. Owners Manual
Volvo Penta Quality Line Marine Water Heaters Owners Manual Mounting Instructions Congratulations on your choice of a new QL Water Heater. A choice that will help you bring out the best in boating pleasure.
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
E-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating
Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW
Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...
E-gas Instant Gas Water Heaters
The Proven Preferred Choice! E-gas Instant Gas Water Heaters Training & Information Manual: There are important functional and operational differences between the conventional hot water geyser and the
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL
Laddomat 21-60 Charging unit
Laddomat 21-60 Charging unit User and installation instructions NOTE! Diagrams in this brochure only describe connection principles. Each installation must be measured and carried out according to the
Coolflo Safe Touch Shower Mixing Valve ST20015CP
Coolflo Safe Touch Shower Mixing Valve ST20015CP Installation and Maintenance Instructions In this procedure document we have endeavoured to make the information as accurate as possible. We cannot accept
This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink.
1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. The unit will start automatically. Please pay particular
Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
Elson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions
Part No. 130009 Iss. 12 August 2004 Elson www.elsonhotwater.co.uk Open Vented Thermal Store providing mains pressure hot water heated by electricity Installation, Servicing and User's Instructions Read
Turbocharger system components, servicing
21-1 Turbocharger system components, servicing Engine codes: AAZ, 1Z, AHU Observe rules of cleanliness Page 21-10 Turbocharger hoses and lines, connecting Page 21-11 WARNING! Do not re-use any fasteners
Munchkin Heat Exchanger Maintenance
Munchkin Heat Exchanger Maintenance By: Mike Granahan *Refer to the appropriate boiler manual for your specific model number. Adjustment procedures will vary. Boiler shown below is an HTP Munchkin 80M
