1 4 56 Electro-hydraulic actuators for valves with a 2 mm stroke SKD32.. SKD82.. SKD62.. SKD6 SKD32.. Operating voltage AC 23 V, 3-position control signal SKD82.. Operating voltage AC 24 V, 3-position control signal SKD6.. Operating voltage AC 24 V, control signal DC V, 4 2 ma or... Ω SKD6.. Choice of flow characteristic, position feedback, stroke calibration, LED status indication, override control SKD62UA with functions choice of direction of operation, stroke limit control, sequence control with adjustable start point and operating range, operation of frost protection monitors QAF2.. and QAF6.. Positioning force N Actuator versions with or without spring-return function For direct mounting on valves; no adjustments required Manual adjuster and position indicator Optional functions with auxiliary switches, potentiometer, stem heater and mechanical stroke inverter SKD..U are UL-approved Use For the operation of Siemens 2-port and 3-port valves, types VVF.., VVG.., VXF.. and VXG.. with a 2 mm stroke as control and safety shut-off valves in heating, ventilation and air conditioning systems. CMN456E Siemens Building Technologies HVAC Products
2 Types Type Standard electronics SKD32.5 SKD32.5 SKD32.2 SKD82.5 SKD82.5U * SKD82.5 SKD82.5U * SKD62 SKD62U * SKD6 Enhanced electronics SKD62UA * Operating voltage AC 23 V AC 24 V Positioning signal 3-position Spring-return Positioning time Function Time Opening Closing yes yes 8 s 8 s DC... V, ma, yes 5 s or... Ω yes 5 s 2 s 2 s 3 s s 2 s 2 s 3 s 5 s Enhanced functions yes ) ) Direction of operation, stroke limit control, sequence control, signal addition * UL-approved versions Accessories Ordering Delivery Spare parts Type Description For actuator Mounting location ASC.6 Auxiliary switch SKD6.. ASC9.3 Dual auxiliary switches ASZ7.3 Potentiometer Ω SKD32.. ASZ7.3 Potentiometer 35 Ω SKD82.. ASZ7.32 Potentiometer 2 Ω x ASC.6 or x ASC9.3 or x ASZ7.3 or x ASZ7.3 or x ASZ7.32 ASZ6.5 Stem heater AC 24 V x ASZ6.5 SKD.. ASK5 Mechanical stroke inverter x ASK5 When ordering please specify the quantity, product name and type code. Example: actuator, type SKD32.5 and potentiometer, 35 Ω, type ASZ7.3 The actuator, valve and accessories are supplied in separate packaging and not assembled prior to delivery. See overview, section «Replacement parts», page 5. Equipment combinations Valve type DN PN-class k vs [m 3 /h] data sheet Two-port valves VV... (control valves or safety shut-off valves)): VVF2.. Flange VVF3.. Flange VVF4.. Flange VVF4.. Flange VVG4.. Threaded VVF52.. Flange VVF6.. Flange Three-port valves VX... (control valves for «mixing» and«distribution»): VXF2.. Flange VXF3.. Flange VXF4.. Flange VXF4.. Flange VXG4.. Threaded VXF6.. Flange /6 For admissible differential pressures Δp max and closing pressures Δp s, refer to the relevant valve data sheets.
3 Note Third-party valves with strokes between 6 2 mm can be motorized, provided they are «closed with the de-energized» fail-safe mechanism and provided that the necessary mechanical coupling is available. The signal must be routed via an additional freely-adjustable end switch (ASC9.3) to limit the stroke. We recommend that you contact your local Siemens office for the necessary information. Technology Principle of electro-hydraulic actuators 4567Z 4567Z Manual adjuster 2 Pressure cylinder 3 Suction chamber 4 Return spring 5 Solenoid valve 6 Hydraulic pump 7 Piston 8 Pressure chamber 9 Position indicator ( to ) Coupling Valve stem 2 Plug Valve closed Valve open Opening the valve Closing the valve Manual operation mode Note: Controller in manual operation Automatic mode Minimal volumetric flow The hydraulic pump (6) forces oil from the suction chamber (3) to the pressure chamber (8) and thereby moving the pressure cylinder (2) downwards. The valve stem () retracts and the valve opens. Simultaneously the return spring (4) is compressed. Activating the solenoid valve (5) allows the oil in the pressure chamber to flow back into the suction chamber. The compressed return spring moves the pressure cylinder upwards. The valve stem extends and the valve closes Turning the manual adjuster () clockwise moves the pressure cylinder downwards and opens the valve. Simultaneously the return spring is compressed. In the manual operation mode the control signals and Z can further open the valve but cannot move to the «%» stroke position of the valve. To retain the manually set position, switch off the power supply or disconnect the control signals and Z. The red indicator marked «MAN» is visible. When setting the controller for a longer time period to manual operation, we recommend adjusting the actuator with the manual adjuster to the desired position. This guarantees that the actuator remains in this position for that time period. Attention: Do not forget to switch back to automatic operation after the controller is set back to automatic control. Turn the manual adjuster counterclockwise to the end stop. The pressure cylinder moves upward to the «%» stroke position of the valve. The red indicator marked «MAN» is no longer visible. The actuator can manually be adjusted to a stroke position > allowing its use in applications requiring constantly a minimal volumetric flow. 3/6
4 Spring-return facility SKD32../SKD position control signal The SKD32.5, SKD32.2, SKD82.5U.. and SKD62.. actuators, which feature a spring-return function, incorporate an additional solenoid valve which opens if the control signal or power fails. The return spring causes the actuator to move to the stroke position and closes the valve in accordance with the safety requirements set out in DIN The valve is controlled by a 3-position signal either via terminals or 2 and generates the desired stroke by means of above described principle of operation. Voltage on piston extends valve opens Voltage on 2 piston retracts valve closes No voltage on and 2 piston / valve stem remain in the respective position SKD62.., SKD6 control signal DC... V and/or DC ma, Ω Frost protection monitor Frost protection thermostat The valve is either controlled via terminal or override control Z. The positioning signal generates the desired stroke by means of above described principle of operation. Signal increasing: piston extends valve opens Signal decreasing: piston retracts valve closes Signal constant: piston / valve stem remain in the respective position Override control Z see description of override control input, page 7 A frost protection thermostat can be connected to the SKD6.. actuator. The added signals from the QAF2.. and QAF6.. require the use of SKD62UA actuators. Notes on special programming of the electronics are described under «Enhanced electronics» on page 5. «Connection diagrams» for operation with frost protection thermostat or frost protection monitor refer to page 3. Standard electronics SKD62.., SKD6 4567Z3 Calib. G G AC 24V 5/6Hz M U...V 4...2mA Z G G Ohm Calib. Status ON 2 Status green red ok calib. error valve jam Connection terminals 2 Mode DIL switches 3 LED status indication 4 Slot for calibration DIL switches SKD62.., SKD6 Positioning signal Position feedback U Flow characteristic ON ON Z5 DC 4 2 ma ON Z7 lin = linear OFF *) ON Z6 *) Factory setting: All switches OFF DC V ON Z8 Relationship between control signal and volumetric flow log = equal percentage V V V 4 lin log V 2 ma 4567Z4 4/6
5 Enhanced electronics SKD62UA 638 Calib. G G M U Z AC 24V G 5/6Hz...V G 4...2mA Ohm Calib. Status Status green red ok calib. error valve jam 2 Connection terminals 2 DIL switches 3 LED status indication 4 Stroke calibration 5 Rotary switch Up (factory setting ) 6 Rotary switch Lo DIL switches SKD62UA Direction of operation Sequence control or stroke limit control Control signal Position feedback U Flow characteristic ON reverseacting Sequence control Signal addition QAF2../QAF6.. DC ma lin = linear OFF * directacting Stroke limit control DC... V log = equal percentage * Factory settings: all switches OFF Relationship between control signal and volumetric flow V V V 4 lin log V 2 ma 4567Z4 Selection of direction of operation SKD62UA With normally-closed valves, «direct-acting» means that with a signal input of V, the valve closes (applies to all Siemens valves listed under «equipment combinations» on page 2) With normally-open valves, «direct-acting» means that with a signal input of V, the valve is open. Direct acting Reverse-acting Input DC... V DC ma... Ω ( V) Input ( V) DC... V DC ma... Ω Stroke Direct V 4 ma Ω Reverse-acting V 2 ma Ω Note The mechanical spring-return function is not affected by the direction of operation selected. 5/6
6 Stroke limit control and sequence control SKD62UA Setting the stroke limit control The rotary switches LO and UP can be used to apply an upper and lower limit to the stroke in increments of 3%, up to a maximum of 45% LO % Position of LO Lower stroke limit Position of UP % y UP Upper stroke limit Setting the sequence control The rotary switches LO and UP can be used to determine the starting point or the operating range of a sequence V UP Position of LO LO... 5 V Starting point for sequence control Position of UP y Operating range of sequence control V V 3 % 97 % V V * 2 6 % 2 94 % 2 2 V 2 V ** 3 9 % 3 9 % 3 3 V 3 3 V *** 4 2 % 4 88 % 4 4 V 4 4 V 5 5 % 5 85 % 5 5 V 5 5 V 6 8 % 6 82 % 6 6 V 6 6 V 7 2 % 7 79 % 7 7 V 7 7 V 8 24 % 8 76 % 8 8 V 8 8 V 9 27 % 9 73 % 9 9 V 9 9 V A 3 A 7 A V A V B 33 % B 67 % B V B V C 36 % C 64 % C 2 V C 2 V D 39 % D 6 % D 3 V D 3 V E 42 % E 58 % E 4 V E 4 V F 45 % F 55 % F 5 V F 5 V * Operating range of QAF2.. (see below) ** Operating range of QAF6.. (see below) *** The smallest adjustment is 3 V; control with 3 V is only possible via. Stroke control with QAF2.. / QAF6.. signal addition SKD62UA only Setting the signal addition The operating range of the frost protection monitor (QAF2.. or QAF6..) can be defined with rotary switches LO and UP. Position of LO Sequence control start point Position of UP QAF2.. / QAF6.. operating range QAF2.. 2 QAF6.. Calibration SKD62.., SKD6 In order to determine the stroke positions and in the valve, calibration is required on initial commissioning: Prerequisites Mechanical coupling of the actuator SKD6.. with a Siemens valve Actuator must be in «Automatic operation» enabling stroke calibration to capture the effective and values AC 24 V power supply Housing cover removed Calibration. Short-circuit contacts in calibration slot (e.g. with a screwdriver) 2. Actuator moves to stroke position () (valve closed) 3. Actuator moves to stroke position (2) (valve open) 4. Measured values are stored % Stroke 24 green LED flashes; position feedback U inactive Z9 Normal operation 5. Actuator moves to the position (3) as indicated by signals or Z % green LED is lit permanently; position feedback U active, the values correspond to the actual positions t A lit red LED indicates a calibration error. The calibration can be repeated any number of times. 6/6
7 Indication of operating state SKD62.., SKD6 The LED status indication indicates operational status with dual-colored LED and is visible with removed cover. LED Indication Function Remarks, troubleshooting Green Lit Normal operation Automatic operation; everything o.k. Red Flashing Calibration in progress Wait until calibration is finished (LED stops flashing, green or red LED will be lit) Lit Faulty stroke calibration Check mounting Restart stroke calibration (by short-circuiting calibration slot) Internal error Replace electronics Flashing Inner valve jammed Check valve Both Dark No power supply Electronics faulty Check mains network, check wiring Replace electronics As a general rule, the LED can assume only the states shown above (continuously red or green, flashing red or green, or off). Override control input Z SKD62.., SKD6 Override control input can be operated in following different modes of operation Z-mode no function fully open closed override with Ω Signal addition SKD62UA only Transfer Connections linear or equalpercentage linear or equalpercentage linear or equalpercentage Z-contact not connected Valve stroke follows -input Z-contact connected directly to G -input has no effect Z-contact connected directly to G -input has no effect Z-contact connected to M via resistor R Starting position at 5 Ω / end position at 9 Ω -input has no effect Z-contact is connected to R of the frost protection monitor QAF2.. or QAF6.. Valve stroke follows signals and R(Z) Note Shown operation modes are based on the factory setting «direct acting» -input has no effect in Z-mode. Accessories SKD.. ASZ6.5 stem heater 825 for media below C; mount between valve and actuator 7/6
8 SKD32.., SKD82.. ASC9.3 double auxiliary switch ASZ7.3.. potentiometer ASK5 stroke inverter 456Z Z adjustable switching points ASZ7.3: Ω ASZ7.3: 35 Ω ASZ7.32: 2 Ω actuator stroke corresponds to valve stroke; mount between valve and actuator SKD62.., SKD6 ASC.6 auxiliary switch Z8 switching point 5 % stroke See section «Technical data» on page for more information. Engineering notes Conduct the electrical connections in accordance with local regulations on electrical installations as well as the internal or connection diagrams. Caution Safety regulations and restrictions designed to ensure the safety of people and property must be observed at all times! Caution For media below C the ASZ6.5 stem heater is required to keep the valve from freezing. For safety reasons the stem heater is designed for an operating voltage of AC 24 V / 3 W. For this case, do not insulate the actuator bracket and the valve stem, as air circulation must be ensured. Do not touch the hot parts without prior protective measures to avoid burns. Non-observance of the above may result in accidents and fires! Recommendation: Above 4 C insulating the valves is strictly recommended. 4567Z Observe admissible temperatures, refer to «Use» on page and «Technical data» on page. If an auxiliary switch is required, its switching point should be indicated on the plant schematic. Every actuator must be driven by a dedicated controller (refer to «Connection diagrams», page 3). 8/6
9 Mounting instructions Mounting Instruction for fitting the actuator to the valve are by packed in the actuator packaging. The instructions for accessories are enclosed with the accessories themselves. Orientation Accessories Installation instructions Accessory Mounting instructions ASC.6 G ASZ6.5 M ASC9.3 G ASK5 M SKD ASZ SKD M Z Commissioning notes When commissioning the system, check the wiring and functions, and set any auxiliary switches and potentiometers as necessary, or check the existing settings. Coupling fully retracted stroke = % Coupling fully extended stroke = 456Z2 456Z3 The manual adjuster must be rotated counterclockwise to the end stop, i.e. until the red indicator marked «MAN» is no longer visible. This causes the Siemens valves, types VVF.., VVG.., VXF.. and VXG.. to close (stroke = %). Manual operation 33a Automatic operation 33b «MAN» «AUTO» Maintenance notes The SKD.. actuators are maintenance-free. When servicing the actuator: Switch off pump of the hydronic loop Interrupt the power supply to the actuator Close the main shutoff valves in the system Release pressure in the pipes and allow them to cool down completely If necessary, disconnect electrical connections from the terminals The actuator must be correctly fitted to the valve before recommissioning. Recommendation SKD6..: trigger stroke calibration. 9/6
10 Repair «Replacement parts», see page 5. Disposal The device contains electrical and electronic components and must not be disposed of together with domestic waste. This applies in particular to the PCB. Legislation may demand special handling of certain components, or it may be sensible from an ecological point of view. Current local legislation must be observed. Warranty The technical data relating to specific applications are valid only in conjunction with the valves listed in this Data Sheet under «Equipment combinations», page 2. The use of the actuators in conjunction with third-party valves invalidates all claims under Siemens Switzerland Ltd / HVAC Products warranty. Technical data Power supply /6 Operating voltage Voltage tolerance Frequency Max. Power consumption At 5 Hz SKD32.. SKD82.. SKD6.. AC 23 V AC 24 V AC 24 V ± 5 % ± 2 2 / +3 SELV / PELV 5 or 6 Hz SKD32.2: 2 VA / 3 W SKD32.5: 6 VA / W SKD32.5: 2 VA, 3 W SKD82.5,..5U 3 VA / 8 W SKD82.5,..5U 8 VA, W 7 VA / 2 W External supply cable fuse min..5 A, slow max..6 A, slow min. A, slow max. A, slow Signal inputs Control signal DC... V, 3-position DC ma or... Ω Terminal Voltage DC V Input impedance kω Current DC 4 2 ma Input impedance 24 Ω Signal resolution < % Hysteresis % Terminal Z Resistor Ω Override control Z not connected No function, priority terminal Z connected directly to G max. stroke Z connected directly to G min. stroke Z connected to M via... Ω stroke proportional to R Position Terminal U voltage DC...9,8 V ±2 % feedback load impedance > kω current DC 4...9,6 ma ±2 % load impedance < 5 Ω Operating data Positioning time at 5 Hz opening SKD s SKD s 3 s SKD s Closing SKD s SKD s 5 s SKD32.2 s Spring-return time (closing) SKD s SKD s SKD s SKD s SKD32.5 SKD82.5 SKD6
11 SKD32.. SKD82.. SKD6.. Positioning force N Nominal stroke 2 mm Max. permissible medium temperature C < C: requires stem heater ASZ6.5 Electrical Cable entry 4 x M2 ( 2.5 mm) connections..u With knockouts for standard ½" conduit connectors ( 2.5 mm) Norms and standards CE-conformity EMC-directive 24/8/EC Immunity EN Industrial Emission EN Residential Low voltage directive 26/95/EC Electrical safety EN 673- Product standards for EN automatic electric controls Protection standard I III EN 673 Housing protection standard Upright to horizontal IP54 to EN 6529 Conform with UL standards SKD82..U UL 873 SKD62U, SKD62UA UL873 C-tick N474 N474 Environmental compatibility ISO 4 (Environment) ISO 9 (Quality) SN 3635 (Environmentally compatible products) RL 22/95/EG (RoHS) Dimensions / Dimensions refer to «Dimensions», page 4 weight Weight SKD32.., SKD82.., SKD kg SKD82..U, SKD6..U, SKD6..UA 3.85 kg ASK5 stroke inverter. kg Materials Actuator housing, bracket Die-cast aluminum Housing box and manual adjuster Plastic Accessories SKD32.., SKD82.. SKD6.. ASC.6 Auxiliary switch Switching capacity AC 24 V, ma...4 A resistive, 2 A inductive ASC9.3 Switching capacity per AC 25 V, 6 A resistive, 2.5 A inductive double auxiliary auxiliary switch switch ASZ7.3 Potentiometer ASZ6.5 stem heater Change in overall resistance ASZ7.3 Ω of potentiometer at nominal ASZ Ω stroke ASZ Ω Operating voltage AC 24 V ± 2 Power consumption 3 VA /6
12 SKD62UA enhanced functions Direction of operation Direct-acting, reverse-acting DC... V / DC... V DC ma / DC ma... Ω /... Ω Stroke limit control Sequence control Signal addition Range of lower limit Range of upper limit Terminal Starting point of sequence Operating range of sequence Z connected to R of Frost protection monitor QAF2.. Frost protection monitor QAF % adjustable...55 % adjustable...5 V adjustable V adjustable... Ω, added to signal DC.6 V, added to signal General ambient conditions Operation EN Transport EN Storage EN Environmental conditions Class 3K5 Class 2K3 Class K3 Temperature C C C Humidity % rh < 95 % rh % rh Internal diagrams SKD32.5, SKD32.2 AC 23 V, 3-Position SKD32.5 AC 23 V, 3-Position 2 n a b c Cm c c2 N ASC a b c c c2 ASZ G2 4567G Cm end switch n solenoid valve for springreturn c, c2 ASC9.3 double auxiliary switch a, b, c ASZ7.. potentiometer Positioning signal «open» 2 Positioning signal «close» 2 spring-return function N neutral conductor Cm N SKD82.5 AC 24 V, 3-Position SKD82.5 AC 24 V, 3-Position 2 n ASC9.3 ASZ a b c Cm c c2 G ASC9.3 ASZ a b c c c2 4569G2 4569G Cm end switch n solenoid valve for springreturn c, c2 ASC9.3 double auxiliary switch a, b, c ASZ7.. potentiometer Positioning signal «open» 2 Positioning signal «close» 2 spring-return function G System potential Cm G ASC9.3 ASZ SKD6, SKD62 SKD62U, SKD62UA AC 24 V, DC V, 4 2 ma, Ω U Z M DC... V oder ma G G... Ω DC... V oder ma Hub voll offen ganz geschlossen Ausgang Eingang Zwangsteuerung (Signalpriorität) Eingang Valve Seat Detection Valve Jam Detection Pumpe Solenoid Hub Hub 76de U Z M position indication override control positioning signal measuring neutral G operating voltage AC 24 V: system neutral (SN) G operating voltage AC 24 V: system potential (SP) G G Speisung MMI Einstellungen und Anzeige Ventil 2/6
13 Connection terminals SKD6.. G G M U Z operating voltage AC 24 V: system neutral (SN) operating voltage AC 24 V: system potential (SP) Positioning signal DC... (3) V or DC ma Measuring neutral (= G) Position indication DC... V or DC ma Override control (functionality see page 7) Auxiliary switch ASC c 4 5 Connection diagrams SKD32.. AC 23 V 3-Position SKD32.2, SKD32.5 AC 23 V (L) L SKD G5 AC 23 V (L) L F () (2) (N) N () (2) (N) N G N N N 2 N F temperature limiter N, N2 controller, 2 actuators L N Phase neutral Positioning signal «open» 2 Positioning signal «close» 2 Spring-return function SKD82.. AC 24 V 3-Position SKD82.5, SKD82.5U AC 24 V 325G3 (G) G (SP) SKD82.5, SKD82.5U AC 24 V 325G2 (G) G (SP) F () (2) (G) N () (2) (G) N G G 2 F temperature limiter N, N2 controller, 2 actuators G (SN) SP Systempotential AC 24 V SN System neutral G (SN) Q, Q2 controller contacts Positioning signal «open» 2 Positioning signal «close» 2 Spring-return function 3/6
14 SKD6.. AC 24 V DC V, 4 2 ma, Ω Dimensions actuator N controller F temperature limiter F2 frost protection thermostat terminals: 3 frost hazard / sensor is interrupted (thermostat closes with frost) 2 normal operation F3 frost protection monitor QAF2.. or QAF6.. (for SKD62UA only) * G (SP) System potential AC 24 V G (SN) System neutral * Only with sequence control and the appropriate selector switch settings (see page 6) All dimensions in mm A 4 x M2 2.5 * * A * M * Height of actuator from valve plate without stroke inverter ASK5 = 3 mm Height of actuator from plate with stroke inverter ASK5 = 357 mm ** SKD..U with knockouts for standard ½" conduit connectors (Ø 2.5 mm) = > mm Minimum clearance from ceiling or wall for mounting, = > 2 mm connection, operation, maintenance etc. ASK5 stroke inverter 9, ,5 8 2* M2 8,5 8 * Maximum stroke = 2 mm 4/6
15 Replacement parts Order numbers for replacement parts Cover Hand control ) Control unit Actuator type SKD SKD SKD SKD SKD82.5U SKD SKD82.5U SKD SKD62U SKD SKD62UA ) hand control, blue with mechanical parts 5/6
16 6/ Siemens Building Technologies Ltd. Subject to alteration
2- and 3-port valves with flanged connections, PN 10
4 402 VVF32.. VXF32.. ACVATIX 2 and 3port valves with flanged connections, PN 10 From the largestroke valve line VVF32.. VXF32.. Performance valves for medium temperatures from 10 150 C Valve body of grey
More informationButterfly Valves PN 6/10/16 for flanged connection
4 136 ACVATIX Butterfly Valves PN 6/10/16 for flanged connection tight-closing VKF46.. VKF46..TS Grey cast iron housing EN-GJL-250 (to DN 300) nodular cast iron housing EN-GJS-400-15 (from DN 350) DN 40
More informationRRV934. Multi-controller. Synco living
s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard
More informationAir damper actuators
4 634 OpenAir TM Air damper actuators GDB...1 GLB...1 Rotary version, / AC 230 V Electronic motor driven actuators for three-position and modulating control Nominal torque 5 Nm (GDB), 10 Nm (GLB) Mechanically
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke
More informationDigital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationSKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function
SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function Document No. 155-751 SKP15U.. Description Only when assembled to Series VGU Gas valves SKP15 electro-hydraulic actuators combine with
More informationRDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationActuator for modulating control AME 435
Data sheet Actuator for modulating control AME 435 Description The actuator automatically adapts its stroke to the valve end positions which reduces commissioning time (self stroking). The advanced design
More informationCONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)
TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output
More informationSEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use
s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum
More informationFor UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.
s For UK only RX39.1 and the applications package SP-03 are sold in the United Kingdom only. 3 876 3876P01 RX Room controller Communicating controllers for fan-coil applications SP-03 RX39.1 The RX39.1
More informationVC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES PRODUCT DATA Design VC Series zone valves consist of: 2-way or 3-way valve housing available with various connection ends Spindle and cartridge
More informationRotary actuator for 2 and 3-way (control) ball valves Torque 5 Nm Nominal voltage AC 100... 240 V Control: Open/close or 3-point Auxiliary switch
echnical data sheet Rotary actuator LR-S Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage C... 4 V Control: Open/close or -point uxiliary switch echnical data Electrical data
More informationTX OPEN RS232/485 module
s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the
More informationTechnote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.
Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on
More informationAir damper actuators Rotary version, two-position control, with spring return, AC 24 V or AC 230 V
4 613 OpenAir TM Air damper actuators Rotary version, two-position control, with spring return, AC 24 V or AC 230 V GCA12...1 GCA32...1 Electromotive rotary actuators for two-position control, nominal
More informationQFP910. Water detector. Building Technologies. CE1N2732en. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More informationElectric Rotary Actuator - On/Off or programmable control actuator
Electric Rotary Actuator - On/Off or programmable control actuator Direct mounting on quarter-turn valves Manual override standard Corrosion resistant Adjustable limit switches Multi-voltage version Type
More informationThermostatic Actuators
2 111 EN 215-1 RTN51 with remote sensor RTN81 with remote adjuster Thermostatic Actuators for radiator valves VDN, VEN, VUN, VPD and VPE RTN51 RTN81 Self-acting, without auxiliary power High-quality fluid-filled
More informationDrayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
More informationHCR3.2/.. Chipcard reader HOTEL SOLUTION
s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages
More information225-230T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators
Actuators Technical data sheet 225-230T-05-S2 Rotary drive without spring return Description Actuator for adjusting air dampers of 90 angle of rotation to be used in HVAC installations. Torque Motor 5
More informationAdjustable room thermostat for heating only or cooling only systems
3 003 Room hermostat RAA30 Adjustable room thermostat for heating only or cooling only systems Room thermostat with manual O/OFF switch wo-position control witching voltage AC 24 250 V Use he RAA30 room
More informationProduct and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
More informationVP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control
VP, -way proportional pressure control valves > > Port size: G/... G/ > > All-digital control electronics > > Variable pressure control > > Optional actuation via fieldbus (separate datasheet on request)
More informationwith MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
More informationPositioner Versions. Remote feed-back. Local display, Electric / Hydraulic. Remote feed-back Electric / Hydraulic. Embedded Control Positioner
Quick Stepper 3G ECP Positioner Versions Mechanical feed-back Pneumatic Remote feed-back Local display, Pneumatic Remote feed-back Local display, Electric / Hydraulic Remote feed-back Electric / Hydraulic
More informationValve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)
Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv) Order code Series and function 1) Plug socket see page 5.042. MN-06-310-HN-442 Standard coil 1) 441 = 12 V DC, 4.2 W 442 = 24 V DC,
More informationXE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY
XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY PRODUCT SPECIFICATION SHEET switched off. This results in energy savings during mild weather. Normal control will resume when T3 fails to
More informationABB i-bus KNX Fan Coil Controller FC/S 1.1
Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation
More informationS03, S05 Series Low-Torque Spring- Return Direct-Coupled Actuators
S, S Series Low-Torque Spring- Return Direct-Coupled Actuators S, S, S, S, S, S INSTALLATION AND OPERATING INSTRUCTIONS S, S Series Low-Torque Spring-Return Direct-Coupled Actuators (DCA) are used for
More informationOPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
More informationM9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,
More informationSeries 71, 72, and 76 Modutrol IV Motors
Series 7, 7, and 76 Modutrol IV Motors PRODUCT DATA FEATURES APPLICATION The Series 7, 7 and 76 Modutrol IV Motors are spring return and nonspring return motors used to control dampers and valves. The
More informationEMO T. Thermal actuator for heating, ventilation and air conditioning systems
EMO T Thermal actuator for heating, ventilation and air conditioning systems Pressurisation & Water Quality Balancing & Control Thermostatic Control ENGINEEING ADVANTAGE EMO T Description The EMO T thermal
More informationPower Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationFlush-mounted room thermostats
s 3 076 RDF300, RDF300.02, RDF340 RDF400.01 RDF600 RDF600 Flush-mounted room thermostats for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units for use with compressors in DX type equipment RDF300
More informationI nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
More informationElectrically operated valves Series M-05, 3/2-, 5/2- and 5/3-way G1/8 650 and 750 Nl/min (0.661 and 0.762 Cv)
Electrically operated valves Series M-05, 3/2-, 5/2- and 5/3-way G1/8 650 and 750 Nl/min (0.661 and 0.762 Cv) Order code Series and function M-05-310-HN-442 Standard coil HN at ports 2 + 4 HN at ports
More informationOutdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
More informationAssisted lift operated 2/2-way solenoid valves Type EV250B
MAKING MODERN LIVING POSSIBLE Data sheet Assisted lift operated 2/2-way solenoid valves Type EV250B EV250B with assisted lift can operate from zero and up to 10 bar differential pressure. This 2/2-way
More information3/2-way Solenoid Valve, direct-acting, NC or NO
3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined
More informationHydraulic Control Solutions
Hydraulic Control Solutions Vexve s Hydrox hydraulic control solutions are suitable for even the most challenging installation sites and conditions. Specifically designed for district heating and district
More informationOZW30. Central Unit SYNERGYR
2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control
More informationDN [mm] [m 3 /h] Characterizing disk Dimensions / Weights see «Dimensions and weights», page 3 Motorizing
Technical data sheet R5.. Characterized control valves, 3-way, with external thread for open and closed cold and warm water systems for modulating control on the water side of air-handling and heating
More informationDXPE*J 85 320/215 ED. DIRECtIONAL CONtROL VALVE PILOt OPERAtED, WItH OBE AND FEEDBACK. Q max (see performance table) SERIES 30
85 320/215 ED DXPE*J DIRECtIONAL CONtROL VALVE PILOt OPERAtED, WItH OBE AND FEEDBACK SUBPLAtE MOUNtINg DXPE5J CEtOP P05 DXPE5RJ ISO 4401-05 (CETOP R05) DXPE7J ISO 4401-07 (CETOP 07) DXPE8J ISO 4401-08
More informationSTEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
More informationits ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
More informationInstruction Manual Differential Pressure Transmitter
DE28 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationDS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches
DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a
More informationWhale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.
Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections
More informationWE-350 Series ¼ Turn Electric Actuator
WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information
More informationElectronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
More informationSwitch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111
, GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,
More informationTechnical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.
Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling
More informationOperating Instructions. Room temperature controller
Operating Instructions 1. Area of application The room temperature controller is used to regulate the temperature in closed rooms such as flats, schools, function suites, workshops, etc. Safety instructions
More informationInfrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
More informationFLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More information4/2-Way Pneumatic Solenoid Valve
4/2-Way Pneumatic Solenoid Valve Robust servo assisted piston valve Service friendly manual override Single or block assembly Explosion-proof versions Type 5413 cam be combined with Type 2508 Cable plug
More informationPlease also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk
1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance
More informationMINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
More informationHMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
More informationDaker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
More informationINSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION
More informationELECTRIC CENTRAL HEATING FLOW BOILER
ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment
More informationTECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)
More informationPosition Transducers with Restoring Spring 10, 25, 50, 75, 100 mm TR, TRS Series
Position Transducers with Restoring Spring 10, 25, 50, 75, 100 mm TR, TRS Series Special features long life 100 x 10 6 movements outstanding linearity up to ±0.075% choice of plug or cable connection DIN
More informationIO-RM3 3-Stage Relay Module
Page 1 of 6 IO-RM3 3-Stage Relay Module Features: Benefits: Link selectable modes binary, heat/cool, staged or sequenced On/Off/Auto links for ease of commissioning DIN Rail mounting Fault finding LED
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationCombi B Alarm box. Mounting instructions
Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power
More informationADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
More information225C-024T-05. Continuous control rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators
Actuators Technical data sheet 225C-024T-05 Continuous control rotary drive without spring return Description Actuator for adjusting air dampers of 90 angle of rotation to be used in HVAC installations.
More informationPower consuption Motor (Motion) Power consuption Standby (end position) 1,0 W. Position feedback - Switching point 0...95
Actuators Technical data sheet 227S-230-05-S1 Rotary drive without spring return Description Actuator for adjusting air dampers of 90 angle of rotation to be used in HVAC installations. Torque Motor 5
More informationN20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL
N2xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL SPECIFICATIONS Supply voltage N224A / N3424A N223A / N3423A PRODUCT DATA 24 Vac 15%, 5/6 Hz 23 Vac 15%,
More informationFAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7
FAQs Conserve package Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7 FAQs Gateway Can I have someone install my system for me? If you are concerned
More informationETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
More informationProgrammable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains
Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation
More informationABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1
Product Manual ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Intelligent Installation Systems Contents Page 1 Introduction.......................................
More informationHeating Controller. Building Technologies HVAC Products
2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or
More informationData sheet ECC 12 and 22
Application ECC is an electronic room temperature controller for water-based systems. ECC can control - fan-coil units - inductions units - air conditioning systems - small ventilating systems - 2-pipe
More informationCM702 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET
CM702 PROGRAMMABLE THERMOSTAT FEATURES Attractive slim, modern styling makes it ideal for location in any type of home. 24-hour heating program. Up to 4 daily independent time and temperature level changes
More information543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationType 3353 Angle Seat Valve
Type 3353 Angle Seat Valve Application On/off valve with pneumatic piston actuator Nominal size DN 15 to 50 (NPS ½ to 2) Nominal pressure PN Temperature range 10 to 180 C Globe valve with an angle seat
More informationRVL470. Heating Controller. Building Technologies HVAC Products. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
More informationmecotron Safety relay ESTOP-2 For emergency stop monitoring
E0006 000824 Safety relay E-2 For emergency stop monitoring Description The safety module E-2 for emergency stop monitoring is used for safety breaking one or more circuits and is designed to be incorporated
More informationFlow controller with integrated control valve (PN 16, 25, 40*) AFQM, AFQM 6 - return and flow mounting
Data sheet Flow controller with integrated control valve (PN 16, 5, 40*) AFQM, AFQM 6 - return and flow mounting Description AFQM 6 DN 40, 50 AFQM DN 65-15 AFQM DN 150-50 AFQM(6) is a self-acting flow
More information33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
More informationProduct and Application Description
Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design
More informationProduct and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationCYMAQ Marking System AS200 + DS7050 N-14
CYMAQ Marking System AS200 + DS7050 N-14 Serial Number: 13716 CYMAQ www.cymaq.com INDEX 1. PRESENTATION AND GENERAL POINTS 1.1. General Points 1.2. Identification plate 2. MACHINE CHARACTERISTICS 2.1.
More informationQFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More informationTelefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual
Uni-Valve A /S VENTILER & INSTRUMENTER Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com UNI-EL Electric actuator Installation and operating manual Remote position
More information