1 SECTION DISTRIBUTION SWITCHBOARDS PART 1 GENERAL 1.01 SECTION INCLUDES A. Main switchboard RELATED SECTIONS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. B. Section / Supplemental Mechanical and Electrical General Requirements REFERENCES A. ANSI/NFPA 70 - National Electrical Code. B. ANSI/IEEE C Code for Electricity Metering. C. ANSI C Electrical Analog Indicating Instruments. D. ANSI C Instrument Transformers. E. ANSI C Guide for Transformer through Fault Duration. F. NEMA AB 1 - Molded Case Circuit Breakers and Molded Case Switches. G. NEMA KS 1 - Enclosed Switches. H. NEMA PB 2 - Deadfront Distribution Switchboards. I. NEMA PB Proper Handling, Installation, Operation and Maintenance of Deadfront Switchboards Rated 600 Volts or Less. J. NEMA PB Application guide for Ground Fault Protective Devices for Equipment SUBMITTALS A. Shop Drawings: Indicate front and side views of enclosures with overall dimensions shown; conduit entrance locations and requirements; nameplate legends; size and number of bus bars per phase, neutral, and ground; and switchboard instrument details. B. Product Data: Provide electrical characteristics including voltage, frame size and trip ratings, fault current withstand ratings, and time-current curves of all equipment and components. C. Test Reports: Indicate results of factory production tests. Perform a short circuit study to 208 volt level at the ground floor. The utility shall provide short circuit information and transformer characteristics. The contractor shall assemble DISTRIBUTION SWITCHBOARDS

2 conductor lengths and sizes from the contract drawings. Contractor shall coordinate work with the utility to provide the optimum primary fuse size for the transformer. The utility shall provide thru fault curves, transformer inrush and a time current graph to indicate compliance with ANSI (current edition) OPERATION AND MAINTENANCE DATA A. Maintenance Data: Include spare parts data listing; source and current prices of replacement parts and supplies; and recommended maintenance procedures and intervals REGULATORY REQUIREMENTS A. Conform to requirements of ANSI/NFPA 70. B. Furnish products listed and classified by Underwriters Laboratories, Inc. as suitable for purpose specified and shown DELIVERY, STORAGE, AND HANDLING A. Deliver in 48 inch maximum width shipping splits, individually wrapped for protection, and mounted on shipping skids. B. Handle in accordance with NEMA PB 2.1 and manufacturers' written instructions. Lift only with lugs provided for the purpose. Handle carefully to avoid damage to switchboard internal components, enclosure, and finish. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Square D Company. B. General Electric Corporation. C. Westinghouse Corporation. D. Siemens ITE. E. Substitutions: Under provisions of Section SWITCHBOARD A. Description: NEMA PB 2 with electrical ratings and configurations as indicated on drawings. Provide main and distribution section. B. Distribution Section and Devices: Group mounted, similar to Square D I-Line (117" of breaker mounting space). C. Auxiliary Section Devices: Group mounted. DISTRIBUTION SWITCHBOARDS

3 D. Bus Material: Copper with tin plating, 4,000 amp. E. Bus Connections: Bolted accessible from front for maintenance. F. Ground Bus: Extend length of switchboard. G. Molded Case Circuit Breakers: NEMA AB 1, integral thermal and instantaneous magnetic trip in each pole. Provide circuit breakers UL listed as Type HACR for air conditioning equipment branch circuits. H. Solid-state Molded Case Circuit Breakers: NEMA AB 1, provide with electronic sensing, timing and tripping circuits for adjustable current settings; instantaneous trip; and adjustable short time trip. Provide stationary mounting. Provide kirk key and ground fault zone selective interlocks as indicated. I. Line and Load Terminations: Accessible from the front only of the switchboard, suitable for the conductor materials and sizes indicated. J. Provide metering transformer compartment and metering as indicated on drawings. K. Future Provisions: Fully equip spaces for future devices with bussing and bus connections, suitably insulated and braced for short circuit currents. Provide continuous current rating as indicated. L. Enclosure: NEMA Sections approximately 48"L x 36"W. 2. Switchboard Height: 90 inches excluding floor sills, lifting members, and pull boxes. 3. Finish: Manufacturer's standard light gray enamel over external surfaces. Coat internal surfaces with minimum one coat corrosion-resisting paint, or plate with cadmium or zinc. M. Short Circuit Rating: Integral equipment rating of 100,000 AIC symmetrical at 480 volts AC. N. COMPONENTS 1. Components and Connections: All components shall be front accessible for both installation and maintenance. Phase and neutral terminals shall accept #12 AWG to 750 MCM wire. Ground terminals shall accept wire sizes from #8 AWG to 750 MCM. Ground bus shall be 1/4"x2" copper. No. 8 AWG wire shall be used for all internal connections from the neutral point to ground. Control connections shall be a minimum of #14 gauge. All control wire insulation shall be type SIS. All control wiring shall be labeled at each end. Wiring within the resistor assembly shall be rated for 200 o C service. 2. Structure: The unit shall be free standing and house the resistor bank within an isolated section of the structure. Access to the resistor shall be via a bolted-on cover. The control panel door shall be pad-lockable and the components on the door shall be guarded against accidental contact with energized parts. The rear cover shall be removable. The structure shall provide top and bottom cable entry points. Lifting angles shall be provided to facilitate the installation of the unit. The structure shall be suitable for moving on rollers and shall be skidded for shipment in a manner suitable for handling by a fork lift. All steel parts (except for plated parts) shall be thoroughly cleaned and phosphatized prior DISTRIBUTION SWITCHBOARDS

4 PART 3 EXECUTION AVITA BRUNSWICK to the application of the light gray ANSI No. 61 finish. A pocket shall be located on the inside of the control compartment door to store drawings and manuals. 3. Factory Assembly and Tests: The system shall be completely assembled, wired, and tested at the factory in accordance with NEMA and UL requirements. A certified production test report shall be shipped with the unit EXAMINATION A. Verify that location as indicated on drawings is ready for switchboard installation PREPARATION A. Provide concrete housekeeping pad as shown on drawings INSTALLATION A. Install switchboard in locations shown on Drawings in accordance with manufacturer's written instructions and NEMA PB 2.1. B. Tighten accessible bus connections and mechanical fasteners after placing switchboard. C. Install fuses in each switch FIELD QUALITY CONTROL A. Inspect completed installation for physical damage, proper alignment, anchorage, and grounding. B. Measure insulation resistance of each bus section phase to phase for one minute each, at test voltage of 1000 volts; minimum acceptable value for insulation resistance is 2 megohms. C. Check tightness of accessible bolted bus joints using calibrated torque wrench. D. Physically test key interlock systems to insure proper function ADJUSTING A. Adjust all operating mechanisms for free mechanical movement. B. Tighten bolted bus connections in accordance with manufacturer's instructions. C. Adjust circuit breaker trip and time delay settings to values provided by the Engineer CLEANING A. Touch up scratched or marred surfaces to match original finish. DISTRIBUTION SWITCHBOARDS

5 *** END OF SECTION *** DISTRIBUTION SWITCHBOARDS

SECTION 16425 SWITCHBOARDS. 1. Requirements for main and distribution switchboards.

SECTION 16425 SWITCHBOARDS. 1. Requirements for main and distribution switchboards. SECTION 16425 SWITCHBOARDS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Requirements for main and distribution switchboards. B. Related Sections: 1. Section 16420 - Service Entrance 2. Section 16430

More information

SECTION INCLUDES REFERENCES SUBMITTALS QUALIFICATIONS DELIVER, STORAGE, AND HANDLING MAHLUM KING'S SCHOOL KING S JUNIOR HIGH SCHOOL MODERNIZATION

SECTION INCLUDES REFERENCES SUBMITTALS QUALIFICATIONS DELIVER, STORAGE, AND HANDLING MAHLUM KING'S SCHOOL KING S JUNIOR HIGH SCHOOL MODERNIZATION PART 1 1.1 1.2 1.3 1.4 1.5 GENERAL SECTION INCLUDES A. Main Switchboard Furnish and install the Service Entrance switchboard(s) as herein specified and shown on the associated electrical drawings. B. Distribution

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

LOW VOLTAGE FRONT ACCESSIBLE MAIN SWITCHBOARD

LOW VOLTAGE FRONT ACCESSIBLE MAIN SWITCHBOARD SECTION 16323 LOW VOLTAGE FRONT ACCESSIBLE MAIN SWITCHBOARD PART 1 - GENERAL 1.01 General: Provide low voltage main switchboard, complete, as indicated, specified and required per Contract Documents. 1.02

More information

SECTION 26 24 13.19 LOW VOLTAGE INSTANT SWITCHBOARDS

SECTION 26 24 13.19 LOW VOLTAGE INSTANT SWITCHBOARDS LOW VOLTAGE INSTANT SWITCHBOARDS PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated, free-standing, deadfront-type low voltage instant switchboard(s) utilizing

More information

SECTION 164XX FUSED MAIN AND DISTRIBUTION SWITCHBOARDS

SECTION 164XX FUSED MAIN AND DISTRIBUTION SWITCHBOARDS SECTION 164XX FUSED MAIN AND DISTRIBUTION SWITCHBOARDS PART 1 GENERAL 1.1 SUMMARY A. Furnish and install main and distribution switchboards as shown on the drawings. Switchboard shall be free-standing,

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

PHYSICAL FACILITIES. 2015 Consultant s Handbook Division 26 ELECTRICAL 2413 SWITCHBOARDS. Page 1 of 11

PHYSICAL FACILITIES. 2015 Consultant s Handbook Division 26 ELECTRICAL 2413 SWITCHBOARDS. Page 1 of 11 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

SECTION 16429C ( ) GENERATOR QUICK CONNECT SWITCHBOARDS LOW VOLTAGE

SECTION 16429C ( ) GENERATOR QUICK CONNECT SWITCHBOARDS LOW VOLTAGE (26 24 13.02) GENERATOR QUICK CONNECT SWITCHBOARDS LOW VOLTAGE PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install, where indicated, a free-standing, dead-front type low voltage Generator

More information

SECTION 26 24 13.17 SWITCHBOARDS LOW VOLTAGE (COMMERCIAL METERING)

SECTION 26 24 13.17 SWITCHBOARDS LOW VOLTAGE (COMMERCIAL METERING) SWITCHBOARDS LOW VOLTAGE (COMMERCIAL METERING) PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated, free-standing, dead-front-type low voltage distribution

More information

A. Section includes switchboards, distribution panelboards, and lighting and appliance branch circuit panelboards.

A. Section includes switchboards, distribution panelboards, and lighting and appliance branch circuit panelboards. 26 24 00 PART 1 - GENERAL 1.01 SUMMARY A. Section includes switchboards, distribution panelboards, and lighting and appliance branch circuit panelboards. 1.02 PERFORMANCE REQUIREMENTS A. Seismic performance:

More information

Low Voltage 480V Switchgear

Low Voltage 480V Switchgear Low Voltage 480V Switchgear General Description Low Voltage metal-enclosed switchgear is used in electric power distribution systems for the control and protection of circuits and equipment. The switchgear

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

SECTION SWITCHBOARDS. A. Provisions of Division 01 apply to this section

SECTION SWITCHBOARDS. A. Provisions of Division 01 apply to this section SECTION 16440 PART 1 - GENERAL 1.01 SUMMARY A. Provisions of Division 01 apply to this section B. Section Includes: 1. Furnish, install and connect main switchboard, including metering facilities as required

More information

11.3 Switchboards. For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616. Contents

11.3 Switchboards. For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616. Contents .3 Switchboards Compartmentalized Switchboards Compartmentalized Feeder Sections Front View Circuit Breakers Product Description Eaton s Pow-R-Line i switchboards are engineered in a new compartmentalized

More information

A. Extent of switchboard work is indicated by Drawings and/or by requirements of this Section.

A. Extent of switchboard work is indicated by Drawings and/or by requirements of this Section. SECTION 262413 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

2. Wiring Diagrams: Power, signal, and control wiring. 3. Field quality-control test reports. 4. Operation and maintenance data.

2. Wiring Diagrams: Power, signal, and control wiring. 3. Field quality-control test reports. 4. Operation and maintenance data. SECTION 262416 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes all panelboards. 1.2 SUBMITTALS A. Product Data: For each type of panelboard, overcurrent protective device, accessory, and component

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

Engineers Specification Permanent Test & Exercise Load Bank

Engineers Specification Permanent Test & Exercise Load Bank 1 1. Generator Load Bank Provide a fan-cooled resistive load bank for permanent, on-site installation as a component of the emergency power system. The load bank is to be used for periodic, scheduled,

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

RPA PROJECT NO SECTION Page 1 of 5 BW&A NO SECTION SWITCHBOARDS

RPA PROJECT NO SECTION Page 1 of 5 BW&A NO SECTION SWITCHBOARDS RPA PROJECT NO. 2015225.00 SECTION 26-24-13 - Page 1 of 5 PART 1 - GENERAL 1.01 DESCRIPTION SECTION 26-24-13 A. All work specified in this Section shall comply with the provisions of Section 26-05-05.

More information

ARC FLASH HAZARD ANALYSIS/SHORT- CIRCUIT/COORDINATION STUDY

ARC FLASH HAZARD ANALYSIS/SHORT- CIRCUIT/COORDINATION STUDY ARC FLASH HAZARD ANALYSIS/SHORT- CIRCUIT/COORDINATION STUDY (NEW CONSTRUCTION PROJECTS) SECTION 260573.15 PART 1 GENERAL 1.01 SCOPE A. The contractor shall furnish short-circuit and protective device coordination

More information

External ABB document. 1VAL SS Advance 27 Switchgear and Breaker Sample Specification

External ABB document. 1VAL SS Advance 27 Switchgear and Breaker Sample Specification External ABB document 1VAL107002-SS Advance 27 Switchgear and Breaker Sample Specification Contents Part 1 General... 1 1.1 Scope... 1 1.2 References... 1 1.3 Submittals... 2 1.4 Submittals After Order

More information

Super Blue Pennant Switchboards Warehouse Stock

Super Blue Pennant Switchboards Warehouse Stock Warehouse Stock Features The Super Blue Pennant service entrance switchboard is designed to meet the needs of main over current protection with distribution devices for medium duty service applications.

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: 1. Across-the-line, manual and magnetic controllers.

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: 1. Across-the-line, manual and magnetic controllers. PART 1 GENERAL 1.1 1.2 1.3 SUMMARY A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: 1. Across-the-line, manual and magnetic controllers. SUBMITTALS A. Product

More information

A. Section includes transfer switches in individual enclosures.

A. Section includes transfer switches in individual enclosures. SECTION 26 28 26 ENCLOSED TRANSFER SWITCHES PART 1 - GENERAL 1.1 SUMMARY A. Section includes transfer switches in individual enclosures. B. National Electrical Manufacturers Association: 1. NEMA ICS 10

More information

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee

More information

POWER SYSTEMS STUDY SPECIFICATION

POWER SYSTEMS STUDY SPECIFICATION POWER SYSTEMS STUDY SPECIFICATION Load Flow Study Fault Study Protective Device Coordination Arc Flash Analysis THIS STUDY SPECIFICATION DOCUMENT CONTAINS METHODS AND PROCEDURES FOR CONDUCTING LOAD FLOW

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

A. Work Included: Provide automatic transfer switch work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide automatic transfer switch work as shown, scheduled, indicated, and as specified. SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

A. Work Included: Provide automatic transfer switch work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide automatic transfer switch work as shown, scheduled, indicated, and as specified. SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

Technical Data and Specifications. Table 12-153. UL 489 Interrupting Capacity Ratings. Number of Poles 2, 3 2, 3, 4 2, 3, 4 2, 3, 4.

Technical Data and Specifications. Table 12-153. UL 489 Interrupting Capacity Ratings. Number of Poles 2, 3 2, 3, 4 2, 3, 4 2, 3, 4. May 8 Typical Circuit Product Description All Eaton s Cutler-Hammer Circuit s are HACR rated. circuit breakers are available as individual components (Frame, Trip Unit, Terminals), or factory assembled

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

GROUNDING AND BONDING. Table of Contents. Minimum Size Bonding, Equipment Grounding, Grounding Electrode Conductor Table

GROUNDING AND BONDING. Table of Contents. Minimum Size Bonding, Equipment Grounding, Grounding Electrode Conductor Table GROUNDING AND BONDING Table of Contents Grounding Bonding Minimum Size Bonding, Equipment Grounding, Grounding Electrode Conductor Table Typical Residential Service Grounding and Bonding Drawing (overhead)

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

SECTION 262413 SWITCHBOARDS

SECTION 262413 SWITCHBOARDS PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 1 1.4 SUBMITTALS... 2 1.5 QUALITY ASSURANCE... 3 1.6 DELIVERY, STORAGE, AND HANDLING... 3 1.7 PROJECT CONDITIONS...

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140) 9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

ELECTRICAL ACCEPTANCE TESTS

ELECTRICAL ACCEPTANCE TESTS Scope This guideline defines the standard tests that all electrical systems and equipment must pass prior to final acceptance by the University. These tests are in addition to acceptance tests specified

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

SECTION 26 24 13 SWITCHBOARDS. A. This Section includes service and distribution switchboards rated 600 V and less.

SECTION 26 24 13 SWITCHBOARDS. A. This Section includes service and distribution switchboards rated 600 V and less. SECTION 26 24 13 PART 1 - GENERAL 1.1 SUMMARY A. This Section includes service and distribution switchboards rated 600 V and less. 1.2 SUBMITTALS A. Product Data: For each type of switchboard, overcurrent

More information

A. This Section includes service and distribution switchboards rated 600 V and less.

A. This Section includes service and distribution switchboards rated 600 V and less. SECTION 16441 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to

More information

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications Product Description Product Description The Mini Power-Zone Unit Substation from Schneider Electric is a miniaturized version of our Power-Zone Unit Substation. Included are: Circuit Breaker Sealed Step-Down

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 SUBMITTALS... 2 1.4 REFERENCES... 2 1.5 QUALITY ASSURANCE... 3 1.6 DELIVERY, STORAGE, AND HANDLING... 3 1.7 PROJECT RECORD DOCUMENTS...

More information

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Section 263xxx - Automatic Transfer Switch PART 1 GENERAL. 1.1 Scope

Section 263xxx - Automatic Transfer Switch PART 1 GENERAL. 1.1 Scope Section 263xxx - Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure an automatic transfer switch that has been prototype tested, factory built, production

More information

STANDARD AUTOMATIC TRANSFER SWITCHES TS 890 SERIES 800A 4000A

STANDARD AUTOMATIC TRANSFER SWITCHES TS 890 SERIES 800A 4000A SUGGESTED SPECIFICATION STANDARD AUTOMATIC TRANSFER SWITCHES TS 890 SERIES 800A 4000A Specification No. ES007 - TS 890 2000 2003 ES007 Rev 3 03/01/09 9087A 198 th Street, Langley, BC Canada V1M 3B1 Telephone

More information

PD-100. Single Breaker 800-4000 Amps 208-600 Volts; 50/60 Hz. Single Generator Utility- Paralleling Power System. Models: General Description

PD-100. Single Breaker 800-4000 Amps 208-600 Volts; 50/60 Hz. Single Generator Utility- Paralleling Power System. Models: General Description PD-100 Single Generator Utility- Paralleling Power System Models: Single Breaker 800-4000 Amps 208-600 Volts; 50/60 Hz General Description The single-breaker PD-100 provides an economical method of operating

More information

DRIVE ISOLATION TRANSFORMER TYPE: T

DRIVE ISOLATION TRANSFORMER TYPE: T M T E C o r p o r a t i o n DRIVE ISOLATION TRANSFORMER TYPE: T USER MANUAL PART NO. INSTR - 017 REL. 031112 Instructions for the Safe Handling, Installation, Operation and Maintenance of Ventilated Dry-Type

More information

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Learning Module 13: Panelboards and Switchboards. 101 Basic Series Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and

More information

SECTION MOTORS CONTROLLERS AND POWER FACTOR CORRECTION

SECTION MOTORS CONTROLLERS AND POWER FACTOR CORRECTION SECTION 16480 MOTORS CONTROLLERS AND POWER FACTOR A. Motor Controller Applications 1. Motor control centers shall be utilized whenever there are four (4) or more motors loads. Utilize individual motor

More information

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Transformers. Basis of Design. Design Evaluation.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Transformers. Basis of Design. Design Evaluation. Basis of Design This section applies to the design and installation of transformers. Design Criteria 13.8kV equipment shall be 15kV class. 4.16KV and 2.4kV equipment shall be 5kV class. 15KV class transformers

More information

RAY-MAX Integrated Solar Power Strip

RAY-MAX Integrated Solar Power Strip RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 DESCRIPTION A. This Section covers the general provisions, which are applicable to all electrical work and the testing of the completed electrical systems. The requirements of other

More information

GE Digital Energy Power Quality. UPS Short Circuit Withstand Rating

GE Digital Energy Power Quality. UPS Short Circuit Withstand Rating GE Digital Energy Power Quality UPS Short Circuit Withstand Rating Introduction Large UPS systems are often installed in close proximity to the power source in a facility, and are therefore more likely

More information

Instruction Bulletin. Three-Pole AC Vacuum Contactors. 3-Pole AC Vacuum Contactors Type WG, Series A Class 8502 and 8702 NEMA Size 5 FRONT VIEW

Instruction Bulletin. Three-Pole AC Vacuum Contactors. 3-Pole AC Vacuum Contactors Type WG, Series A Class 8502 and 8702 NEMA Size 5 FRONT VIEW Instruction Bulletin 3-Pole AC Vacuum Contactors Type WG, Series A Class 8502 and 8702 NEMA Size 5 Bulletin No. 30072-005-105A Raleigh, NC, U.S.A. Supersedes 30072-005-105 Dated 6/92 FRONT VIEW SIDE VIEW

More information

ASCO 920 Product Specifications

ASCO 920 Product Specifications ASCO is the global leader in power switching and controls ASCO 90 Product Specifications Only (Panelboard Mounting),,. Suitable insulation must be behind switch unit.. Suitable for bus bar mounting. Lugs

More information

PowerWave Bus System Specification

PowerWave Bus System Specification BUSWAY SYSTEM 1.0 SUMMARY 1.1 This specification covers the electrical characteristics and general requirements for a continuous opening, low voltage vertical or horizontal distribution system (busway).

More information

SECTION SWITCHBOARDS

SECTION SWITCHBOARDS SECTION 16441 - SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

CTI TECHNICAL BULLETIN Number 11: A publication of the Cable Tray Institute

CTI TECHNICAL BULLETIN Number 11: A publication of the Cable Tray Institute CTI TECHNICAL BULLETIN Number 11: A publication of the Cable Tray Institute Equipment Grounding Conductors for Cable Tray Systems Cable tray wiring systems have excellent safety and dependability records.

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Contractors Guide Central Inverter System Installation

Contractors Guide Central Inverter System Installation Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.

More information

SECTION A. UL rd Edition (2009 Revision effective 9/29/2009).

SECTION A. UL rd Edition (2009 Revision effective 9/29/2009). SECTION 16289 TRANSIENT VOLTAGE SURGE SUPPRESSION PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the materials and installation requirements for Surge Protective Devices (SPDs) and includes

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Distribution Dry Type Transformers

Distribution Dry Type Transformers 8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg

More information

SECTION (16289) - SURGE PROTECTION FOR LOW VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION (16289) - SURGE PROTECTION FOR LOW VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 26 43 13 (16289) - SURGE PROTECTION FOR LOW VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Transient Voltage Surge Suppressors for Low-Voltage Power, Control,

More information

60120 Circuit Breaker

60120 Circuit Breaker 6020 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Ordering and Shipping Information Features and Specifications

More information

A. This Section includes SPDs for low-voltage power, control, and communication equipment.

A. This Section includes SPDs for low-voltage power, control, and communication equipment. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 1 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 PROJECT CONDITIONS... 3 1.8 COORDINATION...

More information

Section 10 Electric Switchboards: 0 Through 600 Volts

Section 10 Electric Switchboards: 0 Through 600 Volts Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,

More information

IN /2014. Instruction Manual. Ventilated Dry-Type Transformers. 600 Volts & Below

IN /2014. Instruction Manual. Ventilated Dry-Type Transformers. 600 Volts & Below Instruction Manual IN-7700 4/2014 Ventilated Dry-Type Transformers 600 Volts & Below Instructions for the Safe Handling, Installation, Operation and Maintenance of Ventilated Dry-Type Transformers Table

More information

DISTRIBUTION SWITCHBOARDS

DISTRIBUTION SWITCHBOARDS DISTRIBUTION SWITCHBOARDS CUTLER-HAMMER DISTRIBUTION SWITCHBOARDS Group Mounted Distribution Switchboards Pow-R-Line C Pow-R-Line C Switchboards Cutler-Hammer Distribution Switchboards combine a space-saving

More information

SECTION TRANSFER SWITCHES

SECTION TRANSFER SWITCHES PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall provide, install, and acceptance test a complete and operable emergency transfer switch to be used in conjunction with the emergency generator

More information

Requirements for Electrical Installations

Requirements for Electrical Installations ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This

More information

E-Series. Circuit Breaker

E-Series. Circuit Breaker E-Series Circuit Breaker The E-Series hydraulic/magnetic circuit breaker is ideally suited for higher current and voltage applications. It is UL listed and CSA certified for branch circuit protection,

More information

SECTION 2. TECHNICAL REQUIREMENTS FOR SERVICE UP TO AND INCLUDING 5 kv

SECTION 2. TECHNICAL REQUIREMENTS FOR SERVICE UP TO AND INCLUDING 5 kv SECTION 2 TECHNICAL REQUIREMENTS FOR SERVICE UP TO AND INCLUDING 5 kv Section 2 201 TABLE OF CONTENTS 2.1 RESIDENTIAL...207 2.1.1 Applicability...207 2.1.2 General Requirements...207 2.1.3 Point of Delivery...208

More information

Mini Power-Zone Unit Substation

Mini Power-Zone Unit Substation Catalog 7440CT0901 2009 Class 7440 CONTENTS Description............................................. Page Product Description...........................................2 General Information...........................................3

More information

LVA Take Offs in Bid Manager

LVA Take Offs in Bid Manager Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring

More information

Cutler-Hammer. Busway Systems. Application Data Page 1. In This Section

Cutler-Hammer. Busway Systems. Application Data Page 1. In This Section Page 1 January 2001 Supersedes Application Data, pages 1-28, dated March 1996 Dimensions not to be used for construction purposes. Contact Busway Marketing to confirm dimensions. Busway Systems In This

More information

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy. Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00 Answers for energy. Unit substation solution with type SIMOSEC primary switches, dry-type transformer

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

SECTION EMERGENCY GENERATOR

SECTION EMERGENCY GENERATOR SECTION 26 32 13.13 EMERGENCY GENERATOR PART 1: GENERAL 1.01 SCOPE OF WORK A. Provide complete factory assembled generator set equipment with digital (microprocessor-based) electronic generator set controls,

More information

Installation and Maintenance Instructions for Switch Fuse, Fuse Switch and associated busbar chambers.

Installation and Maintenance Instructions for Switch Fuse, Fuse Switch and associated busbar chambers. Document No. 79001865A RevA Installation and Maintenance Instructions for Switch Fuse, Fuse Switch and associated busbar chambers. 1 Switch Fuse and Switch Fuse Disconnectors 1.1 Installation Instructions

More information