1 Reliance Electric VTAC 7 Specifications Volts Volts VARIABLE FREQUENCY DRIVES This specification should be used to detail the requirements for a 1 through 400 HP at 460 Volts and 1 through 100 HP at 208 Volt AC Variable Frequency Drive (VFD). 1.0 GENERAL A single manufacturer of both motors and drives shall provide, coordinate, and start-up a drive package to ensure both proper application of the motor to the control and of the drive package to the driven load. The Variable Frequency Drive shall be manufactured by Reliance Electric Company. A. The standard Variable Frequency Drive (VFD) and all the optional modifications shall mount within a packaged NEMA 1 or NEMA 12 ( Volts, Volts) enclosure. B. Motor and VFD shall be of the same manufacturer. C. VFD shall be current rated at 8 khz carrier frequency for VFD's HP and 4 khz for VFD's HP. In cases where motor audible noise is not critical to the driven equipment, 4 khz may be used in drives above 60 HP. All HP ratings shall meet or exceed Table of the NEC, 3 Phase Motor Full Load Currents. HP, Maximum Current, and Rated Voltage shall appear on the drive nameplate. D. VFD shall not generate damaging transistor pulses at lead lengths up to 500 feet greater than limits set by NEMA MG1 section Minimum rise time at 500 feet shall be.1 microseconds and peak voltage shall remain under 1600 volts per this standard. Motors shall also be designed to withstand this rise time and peak voltage level. 1.1 BASIC DESCRIPTION The VFD shall be a fully digital PWM using very large scale integration (VLSI) techniques as well as surface-mount technology for increased reliability. The VFD shall use two 32-bit microprocessors with 12-bit resolution to allow stepless motor control from 0.1% to 110% of motor base speed.

2 All programmable settings shall be held in non-volatile memory and shall not be affected by power outages, brownouts, power dips, etc. The VFD shall have initial programmable settings intact from the factory without the need of battery backup. the VFD shall not need to be programmed at the job site prior to being able to run a motor, but shall be ready to run a motor as soon as power connections are made. Programming at the job site to accommodate specific local applications requirements, such as frequency avoidance and preset speeds shall be available to the user. VFD multiple motor operation at the same frequency and speed shall be possible as long as the sum of the connected motor full load sine wave currents are less than or equal to 90% of the VFD maximum continuous current rating. Supply and Return Fan horsepower requirements are as stated in schedule documents. All high voltage components within the enclosure shall be isolated with steel or polycarbonate covers. 1.2 CODES/STANDARDS VFD and options shall be c UL* 508 listed. NEMA 12 enclosed VFD shall be UL ä approved for mounting in conditioned air ducts and plenums (UL 1995). The drive and options shall comply with the applicable requirement of the latest standards of ANSI, NEMA, National Electric Code NEC, NEPU-70, IEEE , FCC Part 15 Subpart J, CE 96. VFD manufacturer shall be ISO 9001 certified. 1.3 EXPERIENCE The manufacturer of the VFD described in this specification shall have a minimum of 20 years experience in the design, construction and application of adjustable frequency controls and motors. 1.4 QUALITY ASSURANCE The VFD shall be subject to but not limited to the following quality assurance controls, procedures and tests. A. The VFD's shall be designed, manufactured, and tested in the United States of America. Compliance with this specification shall be stated in writing at time of bid. A minimum 80 % US. content will be considered acceptable. B. During the Design Engineering process for the VFD the following quality assurance controls, procedures and tests shall be implemented. 1. Each new product design shall undergo a 4000 hour pre-production burn-in test. Up to ten units may be used to accumulate this entire time. Each unit shall be temperature cycled between 0 and 50ºC during this time period. 2. Digital integrated circuits shall undergo functional and reliability tests. Regulator circuits must use reliable and compact surface mount construction. These circuits

3 shall be 100% tested on computer controlled systems. Test equipment must be documented, controlled and calibrated to ISO 9001 standards. 3. Each drive power circuit shall be tested under motor load conditions. While loaded, the output waveform shall be monitored for correct PWM algorithm. Short circuit testing shall be done to UL standards and an AIC rating placed on each controller nameplate. 4. All components utilized with the basic VFD like contactors, overload relays, pushbuttons, pilot devices, and other control devices shall be UL. recognized. These components shall be manufactured by Allen Bradley Company. C. After initial product quality assurance testing, each drive shall be subjected to the following quality control procedures. 1. Every VFD shall be functionally tested under motor load. During this load test the VFD shall be monitored for correct phase current, Phase voltages, and motor speed. Correct Current Limit operation shall be verified by simulating a motor overload. 2. A HYPOT voltage test shall be performed using at least 2715 VDC. Leakage currents during this test must not exceed 100 micro amps. This test insures proper grounding procedures have been followed during manufacturing. 3. Verification of proper factory presets by scrolling through all parameters shall be performed to ensure proper microprocessor settings. The computer port should also verify that the proper factory settings are loaded correctly in the drive. 4. All options shall be functionally tested including operation of a motor in the Bypass mode if supplied. Proper heater coil installation in motor overload, if supplied, shall be verified. D. Quality control systems shall conform to the ISO9001 standard. Under this system, quality assurance for design/development, production, installation and servicing of the proposed manufactures equipment shall be certified ISO9001. Written certification of conformance to this standard shall be supplied at time of bid. 1.5 SERVICE A. The VFD manufacturer shall maintain and staff world-wide service centers. The manufacturers shall have the ability to test both the controller and the motor in these service centers. 1. Start-up shall be included for each VFD provided. 2. The service engineers shall be employed by the manufacturer or be certified by the manufacturer and provide start-up service including physical inspection of drive and connected wiring and final adjustments to meet specified performance requirements. B. Training shall be available on site by employees of the manufacturer and shall be in addition to the start-up serviced. Training shall include system concepts and basic troubleshooting. C. A reasonable supply of spare parts must be kept available for the VFD to meet ordinary repair requirements for the immediate future. In addition, spare parts shall be available within 24 hours of notification through a local Service Center, by the user.

4 2.0 VARIABLE FREQUENCY DRIVE The VFD manufacturer shall provide, at minimum the basic features, adjustments, general options and modifications as specified below. 2.1 BASIC FEATURES The VFD shall have the following basic features: A. All HP 460 Volt VFD's current ratings shall be at 8 khz carrier frequency. No derating of the drive shall be required due to increasing this switching frequency for motor noise reduction An alternate 4 khz HP 460 Volt Wall Mounted Drive may be supplied where motor audible noise is not critical to the installation. VFD's from HP 460 Volt shall maintain current ratings at 4 khz. VFD's from HP 208 Volt shall be rated at 8 khz carrier frequency. Drives that automatically reduce the carrier frequency as load is increased shall not be supplied. Operator controls shall be mounted on the door of the cabinet and consist of a membrane command center which allows manual stop/start, speed control, local/remote status indication, manual or automatic speed control selection, and run/jog selection. In addition, the command center will serve as a means to configure controller parameters such as Min Speed, Max Speed, Acceleration and Deceleration times, Volts/Hz ratio, Torque Boost, Slip Compensation, Overfrequency Limit, and Current Limit. Potentiometers will not be allowed for these settings. The controller shall have an internal means of deactivating keypad parameter adjustments to eliminate unauthorized data entry. B. A slip compensation circuit for accurate 1% speed regulation without the need of a tachometer. C. Adjustable DC braking that is programmable from the command center settable in both amplitude and duration. D. An electronic overload circuit designed to protect an AC motor operated by the VFD output from extended overload operation on an inverse time basis. This Electronic overload shall be ULä and NEC recognized as adequate motor protection. No additional hardware such as motor overload relays or motor thermostats shall be required. E. Automatic and manual torque boosts that are settable within the control to accelerate high inertia fan and pump loads. F. An LED display mounted on the door of the cabinet that digitally indicates: 1. Frequency output 2. Voltage output 3. Current output 4. Motor RPM 5. Input kw 6. Elapsed Time 7. Time Stamped Fault Indication 8. DC Bus Volts

5 G. The capability of starting into a rotating load regardless of direction without the need of a time delay upon a start command. H. Relay contacts for remote indication of drive fault or motor running for inter-wiring to other user supplied devices. I. An automatic restart circuit which is settable by number of restart attempts and time interval between restarts. J. Three critical frequency avoidance bands, which can be programmed in the field, enable the controller to avoid resonate frequencies of the driven equipment. Each critical frequency avoidance band shall have a bandwidth adjustable via keypad entry of up to 10 Hz. K. Eight programmable preset speeds which will force the VFD to a preset speed upon a user contact closure. This feature shall be set digitally by entering data via the door mounted membrane command center. These shall be utilized for user specified purge functions. L. The VFD shall have the capability of riding though power dips up to 10 seconds without a controller trip depending on load and operating condition. In this extended ride through, the drive shall use the energy generated by the rotating fan as a power source for all electronic circuits. M. Multiple Volts/Hz patterns settable in one Hz increments. N. Jog speed selection. O. RS232 Port for Configuration, Control, and Monitoring. P. An isolated electrical follower capability shall enable the Adjustable Frequency Controller to follow a 0-20mA, 4-20mA or 0-4, 0-8, 0-10 volt DC grounded or ungrounded speed signal. Q. A isolated 0-10 V or 4-20 ma output signals for computer controlled feedback signals shall be selectable for speed or current. R. For ultra-smooth acceleration and deceleration capabilities, the drive shall have a preprogrammed "S" curve ramp which can be activated locally. S. Flux Vector PWM operation with "trip free" circuitry to eliminate nuisance faults. T. IGBT transistors with a selectable carrier frequency between 4 and 8 khz 2.2 PROTECTIVE CIRCUITS AND FEATURES The VFD shall include the following protective circuits and features: 1. Motor current exceeds 200% of drive continuous current rating. 2. Output phase-to-phase short circuit condition.

6 3. Total ground fault under any operating condition. 4. High input line voltage. 5. Low input line voltage. 6. Low input line voltage. 7. Loss of input or output phase. 8. External fault. (This protective circuit shall permit wiring of remote N.C. safety contact to shut down the drive). User supplied end switches, thermal switches, firestats, freeze-stats inputs will be connected to this VFD supplied circuit. 9. Metal oxide varistors for surge suppression shall be provided at the VFD input terminals. 2.3 ADJUSTMENTS The following adjustments shall be provided: A. Maximum frequency (1-120Hz) with factory setting at 60Hz. B. Minimum frequency (5 to 60Hz). C. Acceleration (0.1 to seconds). D. Deceleration (0.1 to seconds). E. Volts/Hz ratio factory set for 460 Volts at 60Hz or 208 Volts at 60 Hz. F. Current limit (50 to 110%) drive continuous rating. 2.4 SERVICE CONDITION The VFD shall be designed and constructed to operate within the following service conditions: A. Suitable for continuous operation at an ambient temperature of 0ºC to 40ºC, elevation up to 3300 feet altitude with a relative humidity to 95% non-condensing. B. AC line variation of -10% to + 10% Voltage and +/-5 Hz Frequency. C. AC line distribution system capacity shall not exceed 30,000 Amps symmetrical available fault current. 2.5 GENERAL OPTIONS AND MODIFICATIONS The following options shall be included as specified in the document: 1. The energy efficient motor manufacturer shall performance-match and guarantee full nameplate horsepower and speed when operated on the specified VFD and also

7 provide as a minimum the mechanical design, electrical design and basic features as follows: 2. All motors shall conform to the latest applicable requirements of NEMA, IEEE, ANSI and NEC standards. 3. Motors shall be of an energy efficient design meeting NEMA efficiency table or a premium efficient design. 4. Motors shall be designed for continuous duty operation, NEMA design B. 5. Open Drip Proof Motors and Totally Enclosed Motors to be furnished with Class F insulation. 6. Motor Insulation System shall conform to all of the requirements of NEMA MG1 part 31 section for peak voltage withstand capability. 7. Stainless steel nameplates with: A. NEMA efficiency index nominal efficiency (MG b) B. AFBMA bearing numbers C. Lubrication instructions B. Isolation Transformer in a NEMA 1 enclosure, for separate mounting, for use on threephase 60Hz input power of the voltage specified to provide three-phase, 60Hz output for the Variable Frequency Drive. C. Complete Contactor ByPass shall be provided to allow motor to be safely transferred from VFD output to the AC line, or from the AC line to the VFD, while the motor is at zero speed. The contactor ByPass shall utilize two motor contactors electrically interlocked. One contactor is to open and close the connection between the VFD output and the motor. The other contactor will open and close the connection between the ByPass power line and the motor, providing "across the line" starting. Motor protection is to be provided in the "ByPass" mode by a bi-metallic Class 20 Smart Motor Protection adjustable overload relay. Relay control logic shall also be included within the VFD enclosure to allow the same "START/STOP" command to operate the motor in either mode. The relay logic shall be 115 Volts. The ByPass circuit shall include a second disconnect installed in the VFD to provide the ability to safely troubleshoot and test the controller, both energized and de-energized, while the motor is running in the "ByPass" mode. A contact closure shall be provided to indicate that the drive is in the "ByPass" mode. A Remote/Local selector switch shall also be provided to transfer control from the keypad to user wired signals. Form "C" Normally Open and Normally Closed contacts shall be provided for both Run and IET/Drive Stopped. The entire ByPass option shall be packaged with the controller enclosure and be mechanically isolated from the VFD. D. Input line fuses shall provide protection for the input rectification circuit using Class J fuses with interrupting rating of 200,000 AIC. The series interrupting rating of the VFD and fuses shall be a minimum of 30,000 AIC and shall be stated in the VFD Instruction Manual as required by UL E. A main input disconnect shall mount within the standard NEMA 1 or NEMA 12 enclosure for positive power disconnect of the VFD. It shall have the capability for door padlocking. F. A three phase 3% impedance Input Line Reactor shall be provided to minimize drive harmonics on the AC line and protect the drive from damaging electrical system transients. G. In units from 1-40 HP a door interlocked main input disconnect shall be provided. This disconnect shall also increase the short circuit interrupting capacity from 30,000 to 85,000

8 amps symmetrical fault current. This high fault current option shall be UL listed and suitable for use on distribution systems feeds up to 4,000 KVA with 5% minimum impedance. To rate the drive at 85,000 AIC, a three phase Line Reactor must be provided with the appropriate disconnect. H. Provide harmonic measurements at the specified Point of Common Coupling (PCC). This study will provide the user with data on the actual power system waveforms. Upstream transformers maximum load current shall be the unity factor for all data supplied in percentages. Data shall include total harmonic voltage and current distortion as required by IEEE standard. Additionally, individual current harmonic data shall be included to the 13th harmonic. I. I/O Expansion Interface Card with the following features: 1. PI regulator for setpoint pressure control 2. Four Isolated 24 VDC programmable digital inputs 3. An additional analog input for speed feedback to PI regulator 4. One Frequency Input (0 to 200 Hz) for digital control of current limit 5. Four programmable Isolated Digital Outputs (24 VDC rated) 6. One Form A output relay rated at 250 VAC or 24 VDC 7. Two NO/NC programmable output relays rated at 250 VAC or 24 VDC Additional control digital and analog signals can be activated through the standard keypad for customized interface with specific Building Automation Systems. J. Johnson Controls Metasys(tm) option card allows direct connection from the VTAC 7 to the Johnson N2 bus architecture. All configuration and control functions can be accessed through this card. Allows direct communication between the VTAC 7 microprocessor and the host Johnson system. Fault diagnostics, start/stop, speed commands, and all drive feedback's shall be available over a single RS485 communication connection. Discrete signals such as ByPass Run or Interlock Open shall also be mapped through the drive terminal strip to the Metasys system. The card shall have the ability to be used in a "monitor only" mode where control shall be from a AHU or similar type controller directly wired to the drive. Reliance document VTAC-409 January 1998 Copyright 2002 Rockwell Automation For more information call

Variable Freq Drives

Variable Freq Drives Variable Freq Drives 26 29 23 The following information shall be included in specifications prepared for use on all University of Cincinnati construction and renovation projects. This information is supplemental

More information

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications Product Name: Enclosed Adjustable Frequency Drive - Class 8839 E-Flex AC Drive for Variable Torque HVAC and Pumping Applications (1-100 hp, 460 V and 1-50 hp, 208/230 V) SECTION 15 Enclosed Adjustable

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

SECTION MOTORS CONTROLLERS AND POWER FACTOR CORRECTION

SECTION MOTORS CONTROLLERS AND POWER FACTOR CORRECTION SECTION 16480 MOTORS CONTROLLERS AND POWER FACTOR A. Motor Controller Applications 1. Motor control centers shall be utilized whenever there are four (4) or more motors loads. Utilize individual motor

More information

HV Series Uninterruptible Power Systems 7.5 KVA - 25 KVA. General Specification

HV Series Uninterruptible Power Systems 7.5 KVA - 25 KVA. General Specification 5/13/16 Rev2 HV Series General Specification 7.5 KVA to 25 KVA 1.0 General HV Series Uninterruptible Power Systems 7.5 KVA - 25 KVA General Specification This specification describes the features and design

More information

VARIABLE FREQUENCY DRIVES. 1. Variable Frequency Motor Drives

VARIABLE FREQUENCY DRIVES. 1. Variable Frequency Motor Drives 262923 VARIABLE FREQUENCY DRIVES PART 1: GENERAL 1.01 SUMMARY A. Section Includes: 1. Variable Frequency Motor Drives B. Related Sections: 1. Section 230000 - Basic HVAC Requirements 2. Section 230900

More information

Section 263xxx - Automatic Transfer Switch PART 1 GENERAL. 1.1 Scope

Section 263xxx - Automatic Transfer Switch PART 1 GENERAL. 1.1 Scope Section 263xxx - Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure an automatic transfer switch that has been prototype tested, factory built, production

More information

VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems

VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems SECTION 23 81 07 - VARIABLE FREQUENCY DRIVES PART 1 - GENERAL 1.1 SUMMARY A. This section includes all variable frequency drives. All standard and optional features shall be included within the VFD panel

More information

VLT HVAC Drive. Variable Frequency Drive Guide Specification. Section 15172

VLT HVAC Drive. Variable Frequency Drive Guide Specification. Section 15172 I. PART 1- GENERAL A. DESCRIPTION VLT HVAC Drive Variable Frequency Drive Guide Specification Section 15172 1. This specification covers complete a variable frequency drives (VFDs) designated on the drawing

More information

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA

More information

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications Product Name: Enclosed Adjustable Frequency Drive - Class 8839 M-Flex AC Drive for Variable Torque HVAC and Pumping Applications (1-100 hp, 460 V and 1-50 hp, 208/230 V) SECTION 15 Enclosed Adjustable

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Focus 3. Rugged and Robust. Conveyor Rugged. Focus 3. Focus Chassis. Overview

Focus 3. Rugged and Robust.  Conveyor Rugged. Focus 3. Focus Chassis. Overview www.emersonct.com Rugged and Robust Overview The is a single-phase analog drive for DC motors with power ranges from 1/4 to 5 HP. Years of proven engineering design matched with surface mount technology

More information

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect

More information

SECTION ( ) ENCLOSED ADJUSTABLE FREQUENCY DRIVES (1 to 500 HP)

SECTION ( ) ENCLOSED ADJUSTABLE FREQUENCY DRIVES (1 to 500 HP) Specification Number: 16420-4.1 (26 29 23.10) Product Name: ENCLOSED ADJUSTABLE FREQUENCY DRIVES (1-500 HP) SECTION 16420-4.1 (26 29 23.10) ENCLOSED ADJUSTABLE FREQUENCY DRIVES (1 to 500 HP) PART 1 GENERAL

More information

Transfer Switch Features

Transfer Switch Features 1-1 Product Description The Automatic Transfer Switch Option may be added to any FD type Fire Pump Controller whenever automatic transfer from normal to alternate power is required. The automatic Transfer

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

PART 1: GENERAL PART 2: PRODUCT. Phone: Fax: Web: -

PART 1: GENERAL PART 2: PRODUCT. Phone: Fax: Web:  - Specification Number: 23 09 33 Product Name: FRENIC-HVAC AC Drives for Variable Torque Fan & Pump Applications (1-125Hp at 208/230Vac, 1-1000Hp at 460Vac, 1-300Hp at 575Vac) PART 1: GENERAL 1.01 SUMMARY

More information

VFD 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

VFD 101 Lesson 3. Parts of a Variable Frequency Drive (VFD) VFD 101 Lesson 3 Parts of a Variable Frequency Drive (VFD) This lesson covers the parts that make up the Variable Frequency Drive (VFD) and describes the basic operation of each part. Here is the basics

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

BDI 1100 Frequency Inverter

BDI 1100 Frequency Inverter $25.00 BDI 1100 Frequency Inverter Installation and Operating Manual 12/96 MN71100 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................

More information

ADJUSTABLE SPEED DRIVES. Q7 flow

ADJUSTABLE SPEED DRIVES. Q7 flow ADJUSTABLE SPEED DRIVES Q7 flow TM Unsurpassed Quality Toshiba is known throughout the world for high quality products. Manufactured in our state-of-the-art ISO 9001 plant in Houston, Texas, the Q7 is

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

SECTION TRANSFER SWITCHES

SECTION TRANSFER SWITCHES PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall provide, install, and acceptance test a complete and operable emergency transfer switch to be used in conjunction with the emergency generator

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

MC Series Drives. Flexible, simple, rugged, robust! Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.

MC Series Drives. Flexible, simple, rugged, robust! Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives. Drives Flexible, simple, rugged, robust! Our promise Commitment to Price Leadership Price leadership is serious business. It takes continuous life cycle management to make price leadership a sustainable

More information

Variable Frequency Drives

Variable Frequency Drives Purchasing Tips Analyse the System as a Whole Variable Frequency Drives Since the process of converting incoming power from one frequency to another will result in some losses, energy savings must always

More information

Guide Specification for Siemens BT300 HVAC Variable Frequency Drives Division 23/26/29

Guide Specification for Siemens BT300 HVAC Variable Frequency Drives Division 23/26/29 May, 2016 Guide Specification for Siemens BT300 HVAC Variable Frequency Drives Division 23/26/29 PART 1 - GENERAL 1.01 Description A. This specification covers the complete Variable Frequency Drive (VFD)

More information

Uninterruptible Power System (UPS)

Uninterruptible Power System (UPS) Description: The purpose of the section is to provide guidelines for the UMCP Design Standards for design, selection, and installation of uninterruptible power systems (UPS) at the UMCP campus. Related

More information

GPD 506/P5 Start-up Procedure and Checklist

GPD 506/P5 Start-up Procedure and Checklist GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the

More information

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and

More information

ZENITH ZTS-MV MEDIUM VOLTAGE TRANSFER SWITCHGEAR

ZENITH ZTS-MV MEDIUM VOLTAGE TRANSFER SWITCHGEAR ZENITH ZTS-MV MEDIUM VOLTAGE TRANSFER SWITCHGEAR 1 RATING 1.1 The automatic switchgear shall be rated for a line voltage of, phase,, wire, Hertz with a maximum ampere rating of, interrupting current rating

More information

SERIES 300 AUTOMATIC TRANSFER SWITCH

SERIES 300 AUTOMATIC TRANSFER SWITCH SERIES 300 AUTOMATIC TRANSFER SWITCH SERIES 300 AUTOMATIC TRANSFER SWITCH ASCO Series 300 automatic transfer switches are suitable for emergency and standby power system applications. Sizes 30 through

More information

E7 Drive and E7 Bypass Packages

E7 Drive and E7 Bypass Packages E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications 1/2 to 500 Horsepower E7 Drive Design Benefits The E7 drive is an application-specific, variable torque, ac drive designed to meet the

More information

SUGGESTED SPECIFICATION for Automatic Transfer Switches

SUGGESTED SPECIFICATION for Automatic Transfer Switches SUGGESTED SPECIFICATION for Automatic Transfer Switches Division 16 - Electrical Standby Power Generator Systems PART 1 GENERAL 1.01 Scope A. Furnish and install automatic transfer switches (ATS) with

More information

ATV32HU75N4437 variable speed drive ATV32-7.5kW 400 V - 3P - Bluetooth built-in - w heat sink

ATV32HU75N4437 variable speed drive ATV32-7.5kW 400 V - 3P - Bluetooth built-in - w heat sink Characteristics variable speed drive ATV32-7.5kW 400 V - 3P - Bluetooth built-in - w heat sink Main Range of product Altivar 32 Product or component type Product destination Product specific application

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

UPS 500iG SERIES FLYWHEEL MULTI MODULE SYSTEM 250 kva / 225 kw, 50 Hz 500 kva / 450 kw, 50 Hz

UPS 500iG SERIES FLYWHEEL MULTI MODULE SYSTEM 250 kva / 225 kw, 50 Hz 500 kva / 450 kw, 50 Hz UPS 500iG SERIES FLYWHEEL MULTI MODULE SYSTEM 250 kva / 225 kw, 50 Hz 500 kva / 450 kw, 50 Hz FEATURES PRODUCT FEATURES Smallest available footprint 98% total system efficiency Simple cost-effective installation

More information

UL-506 File #E53094 (lamp through 1200 amps) UL-508 File #El80243 (1 amp through 1200 amps)

UL-506 File #E53094 (lamp through 1200 amps) UL-508 File #El80243 (1 amp through 1200 amps) Benefits of Using Line/Load Reactors Guard-AC line/load reactors help keep your equipment running longer by absorbing many of the power line disturbances which otherwise damage or shut down your inverters,

More information

Built-in features Built-in simplicity Built-in ruggedness

Built-in features Built-in simplicity Built-in ruggedness GE Energy Built-in features Built-in simplicity Built-in ruggedness AF-650 GP Panel for Constant Torque Applications imagination at work AF-650 GP Constant Torque Drives Built for constant torque The AF-650

More information

Fractional to 2 HP DC Drives for Both Non-Regenerative and Regenerative Applications

Fractional to 2 HP DC Drives for Both Non-Regenerative and Regenerative Applications DC3 DC Drives Fractional to 2 HP DC Drives for Both Non-Regenerative and Regenerative Applications The Reliance Electric DC3 family of drives provides cost-effective variable speed control and operates

More information

Series DRWS: driver for Stepper motors, one size/version Series DRWB: driver for Brushless motors, sizes in power classes 100, 400 and 750 W

Series DRWS: driver for Stepper motors, one size/version Series DRWB: driver for Brushless motors, sizes in power classes 100, 400 and 750 W C_Electrics > 206 > Series DRWS and DRWB drivers for the control of electric actuation Series DRWS and DRWB drivers for the control of electric actuation Series DRWS: driver for Stepper motors, one size/version

More information

MTE RLW Reactors Price book

MTE RLW Reactors Price book Table of Contents TABLE OF CONTENTS...1 STANDARD DELIVERY SCHEDULE...2 SELECTION & APPLICATION GUIDE...3 SPECIFICATION DATA...4 SERVICE FACTOR...4 AMBIENT TEMPERATURE...4 APPROVALS...4 ENCLOSURES:...4

More information

Z1000 HVAC Drive. 3 HP to 500 HP Fan and Pump Applications. Specifications

Z1000 HVAC Drive. 3 HP to 500 HP Fan and Pump Applications. Specifications Z1000 HVAC Drive 3 HP to 500 HP Fan and Pump Applications The Z1000 variable speed drive is designed for building automation applications such as fans, pumps, and cooling towers through 500 HP. The Z1000

More information

UNINTERRUPTIBLE POWER SUPPLIES >7011AU P S 011A

UNINTERRUPTIBLE POWER SUPPLIES >7011AU P S 011A UNINTERRUPTIBLE POWER SUPPLIES >7011AU P S U N I N T E R R U P T I B L E POWER S U P P L I E S 011A Power Failures Strike at the Heart of Critical Operations 7011A Series Product Line True On-Line, Double

More information

2.2. Adjustable Frequency Drives. Contents

2.2. Adjustable Frequency Drives. Contents . Adjustable Frequency Drives Contents Selection................ Product Selection....................... Accessories........................... Technical Data and Specifications.......... Dimensions...........................

More information

ABB Drives for HVAC ACH to 550 HP with Harmonic Filter

ABB Drives for HVAC ACH to 550 HP with Harmonic Filter ABB Drives for HVAC ACH550 7.5 to 550 HP with Harmonic Filter ABB is in the business of serving your HVAC Drive needs. When adding a drive to a power system in a commercial facility, ABB is well acquainted

More information

Compact Variable Frequency Drive INSTALLATION GUIDE

Compact Variable Frequency Drive INSTALLATION GUIDE Compact Variable Frequency Drive INSTALLATION GUIDE 62-0269 01 Honeywell Technical Support 888-516-9347 Honeywell Customer Web-site: customer.honeywell.com VFD technical data can be accessed via: customer.honeywell.com/vfd

More information

AC Drive Theory and Application

AC Drive Theory and Application AC Drive Theory and Application Application Guide AP4145E Effective May 28 Introduction Adjustable Frequency AC Drive System Description An adjustable frequency AC drive system consists of an ordinary

More information

MC1000 Series Installation and Operation Manual

MC1000 Series Installation and Operation Manual MC1000 Series Installation and Operation Manual NOTE! The manual covers software version M108314 and above. Refer to parameter 63 for the software version of the drive you are working with. If you are

More information

Operation and Performance of a Flywheel-Based Uninterruptible Power Supply (UPS) System

Operation and Performance of a Flywheel-Based Uninterruptible Power Supply (UPS) System Operation and Performance of a Flywheel-Based Uninterruptible Power Supply (UPS) System White Paper 108 2128 W. Braker Lane, BK12 Austin, Texas 78758-4028 www.activepower.com Objective This paper describes

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

Motor Controllers Variable Frequency AC Drives Type VariFlex 2 RVCF

Motor Controllers Variable Frequency AC Drives Type VariFlex 2 RVCF Type VariFlex 2 RVCF Product Description VariFlex 2 RVCF is a simple, compact general purpose AC variable speed drive for use with AC induction motors. A full range of power rating is available from 0.4kW

More information

Fuji Electric Corp. of America (FECOA) Variable Frequency Drives HVAC Systems. Submittal Summary Data Form NEMA 12 Ventilated Non Bypass Systems

Fuji Electric Corp. of America (FECOA) Variable Frequency Drives HVAC Systems. Submittal Summary Data Form NEMA 12 Ventilated Non Bypass Systems Submittal Summary Fuji Electric Corp. of America (FECOA) Variable Frequency Drives HVAC Systems Submittal Summary Data Form NEMA 12 Ventilated Non Bypass Systems Project: Architect: Engineer: Contractor:

More information

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com 13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer tsi@mbesi.com Rotating Machinery Diagnostics & Instrumentation

More information

REGAL-BELOIT. Installation and Operation Manual. Variable Speed AC Motor Drives. Micro and PowerWash Series

REGAL-BELOIT. Installation and Operation Manual. Variable Speed AC Motor Drives. Micro and PowerWash Series REGAL-BELOIT Variable Speed AC Motor Drives Micro and PowerWash Series Installation and Operation Manual Manual Number: SB184 TABLE OF CONTENTS 1.0 GENERAL................................................1

More information

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)

More information

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 Instruction Manual D2-3405-2 The information in this manual is subject to change without notice. Throughout this manual, the following

More information

Fundamentals of Electric Actuator Control A VIEW OF THE ELECTRICAL FUNCTIONS OF A MOTOR ACTUATOR

Fundamentals of Electric Actuator Control A VIEW OF THE ELECTRICAL FUNCTIONS OF A MOTOR ACTUATOR FA L L 2 0 0 6 V O LU M E 1 8, N O. 4 PLUS: Market Outlook '07 Evolution of the Valve Industry Back to Basics: Relief Valves Desuperheating for Temperature Control Castings or Forgings? Fundamentals of

More information

INSTRUCTION MANUAL PHOENIX DX 3 TO 3500 HP SENSORLESS VECTOR AC DRIVE

INSTRUCTION MANUAL PHOENIX DX 3 TO 3500 HP SENSORLESS VECTOR AC DRIVE INSTRUCTION MANUAL PHOENIX DX 3 TO 3500 HP SENSORLESS VECTOR AC DRIVE Thank You We at US Drives would like to say thank you for purchasing our product. We believe the Phoenix AC Drive Series is the most

More information

EI-9001 Series 220V Class Specifications

EI-9001 Series 220V Class Specifications EI-9001 Series 220V Class Specifications Inverter Model EI-9001 001L -002L -003L -005L -007L -010L -015L -020L -025L -030L -040L -050L -060L -075L -100L -150L Max. applicable motor output (kw) 0.75 1.5

More information

Number 1 in efficiency

Number 1 in efficiency PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter Why

More information

KBN2 DIGITAL AC ADJUSTABLE SPEED DRIVES

KBN2 DIGITAL AC ADJUSTABLE SPEED DRIVES INSTALLATION AND OPERATION MANUAL KBN2 DIGITAL AC ADJUSTABLE SPEED DRIVES for Use with 1/2-30 HP Inverter Duty, TEFC and TENV 3-Phase Induction Motors 208/230 or 380-460 Volts, 50/60 Hz, 1 & 3 Phase AC

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

Fan and Pump AC Inverter

Fan and Pump AC Inverter Fan and Pump AC Inverter Key Features for Fan and Pump Applications PID and Auto Energy Saving Functions. Input Phase Loss and Output Phase Loss Protection. LCD Keypad can be used to copy parameter settings

More information

Unitary Controller. Features. Description. Technical Specification Sheet Document No. 149-188P25 Rev. 6 March, 2000

Unitary Controller. Features. Description. Technical Specification Sheet Document No. 149-188P25 Rev. 6 March, 2000 Technical Specification Sheet Document No. 149-188P25 Rev. 6 March, 2000 Unitary Controller The Unitary Controller can operate as an independent stand-alone controller, or can be connected to the APOGEE

More information

Multipump System CFW-08

Multipump System CFW-08 Multipump System CFW-08 Software Version V5.0X Language: English Document: 0899.5547 / 02 Installation, Configuration and Operation Guide CFW-08 Frequency Inverter Multipump System INDEX 1. About the

More information

T1000 Series Single Phase Uninterruptible Power Systems Product Specifications Rev 1.0 May VA (5400W) 1.0 Scope

T1000 Series Single Phase Uninterruptible Power Systems Product Specifications Rev 1.0 May VA (5400W) 1.0 Scope 1.0 Scope This specification document describes the Toshiba T1000 Series. The T1000 is continuous duty, singlephase, on-line, solid-state uninterruptible power supply system hereafter referred to as the

More information

first class ride with vacon ac drive

first class ride with vacon ac drive first class ride with vacon ac drive vacon ac drives - lift your elevators to excellence Vacon is focused on vertical transportation and is dedicated to absolute elevator control. Our products possess

More information

RLW Reactors Technical Reference Manual

RLW Reactors Technical Reference Manual Form: RLW-TRM-E Rel: March 2011 Form RLW-TRM-E March 2011 Page 1 Table of Contents STANDARD DELIVERY SCHEDULE... 3 SELECTION & APPLICATION GUIDE... 4 MODEL CODE PART NUMBER CONFIGURATION... 5 RL REACTOR

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

A. This Section includes SPDs for low-voltage power, control, and communication equipment.

A. This Section includes SPDs for low-voltage power, control, and communication equipment. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 1 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 PROJECT CONDITIONS... 3 1.8 COORDINATION...

More information

PowerFlex 700 and 700H Packaged Drives. Technical Data

PowerFlex 700 and 700H Packaged Drives. Technical Data PowerFlex 700 and 700H Packaged Drives Technical Data Overview The heart of every PowerFlex 700/700H packaged drive package is a PowerFlex Adjustable Frequency Drive. The packaged drives program provides

More information

EnVisioneering. www.danfossdrives.com

EnVisioneering. www.danfossdrives.com EnVisioneering As a world leader in components and solutions, Danfoss meets our customers challenges through EnVisioneering. This approach expresses our views on engineering innovation, energy efficiency,

More information

Transfer Switches GTEC Amp 2 Pole, 3 Pole and 4 Pole

Transfer Switches GTEC Amp 2 Pole, 3 Pole and 4 Pole Transfer Switches GTEC 63-1250 Amp 2 Pole, 3 Pole and 4 Pole Description GTEC series transfer switches provide normal and generator set source monitoring, generator set starting, and load transfer functions

More information

City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION

City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power

More information

August 2004. www.danahermotion.com SECO DC DRIVES. Table of Contents

August 2004. www.danahermotion.com SECO DC DRIVES. Table of Contents SECO DC DRIVES SECO AC/DC DC Drives DRIVES Table of Contents August 2004 www.danahermotion.com Tel : 800 554 8466 Web site : www.danahermotion.com Mechanical and Electro-Mechanical Product Solutions by

More information

Matrix AP 400V 690V TECHNICAL REFERENCE MANUAL. Quick Reference

Matrix AP 400V 690V TECHNICAL REFERENCE MANUAL. Quick Reference Matrix AP 400V 690V TECHNICAL REFERENCE MANUAL FORM: MAP-TRM-E REL. September 2015 REV. 019 2015 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Cat UPS 1200Z Series Multi Module Systems

Cat UPS 1200Z Series Multi Module Systems Cat UPS 1200Z Series Multi Module Systems 300 kva/240 kw, 60 Hz 600 kva/480 kw, 60 Hz 900 kva/720 kw, 60 Hz 1200 kva/960 kw, 60 Hz Caterpillar is leading the power generation marketplace with power quality

More information

Voltage Influence on Typical Protection and Controls for Motors, Power Electronics, and Other Common Loads

Voltage Influence on Typical Protection and Controls for Motors, Power Electronics, and Other Common Loads Voltage Influence on Typical Protection and Controls for Motors, Power Electronics, and Other Common Loads Presentation to: WECC Modeling and Validation Work Group March 3, 2011 John Kueck The Study Examines

More information

Series 10 Inverter Control

Series 10 Inverter Control AC INVERTER Series 10 Inverter Control Installation and Operating Manual 6/98 MN710 Table of Contents Section 1 General Information.............................. 1-1 Limited Warranty................................

More information

What is a transformer and how does it work?

What is a transformer and how does it work? Why is a transformer needed? A control transformer is required to supply voltage to a load which requires significantly more current when initially energized than under normal steady state operating conditions.

More information

SECTION PROCESS INSTRUMENTATION AND CONTROL SYSTEM PROGRAMMABLE LOGIC CONTROLLERS

SECTION PROCESS INSTRUMENTATION AND CONTROL SYSTEM PROGRAMMABLE LOGIC CONTROLLERS SECTION 13311 - PROCESS INSTRUMENTATION AND CONTROL SYSTEM PROGRAMMABLE LOGIC CONTROLLERS PART 1 - GENERAL 1.01 WORK INCLUDED A. This Section covers work related to the Programmable Logic Controllers (PLC)

More information

I/O modules meets requirements for applications from V ac. These modules exhibit long life (20 million to over 100 million operations).

I/O modules meets requirements for applications from V ac. These modules exhibit long life (20 million to over 100 million operations). . Allen-Bradley digital ac I/O modules interface to ON/OFF devices such as limit switches, pushbuttons, motor starters, pilot lights, and annunciators. These modules are compatible with all current Allen-Bradley

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality

More information

SPEEDMASTER Micro Series Compact Inverters Installation and Operation Manual

SPEEDMASTER Micro Series Compact Inverters Installation and Operation Manual SPEEDMASTER Micro Series Compact Inverters Installation and Operation Manual A Regal Brand TABLE OF CONTENTS 1.0 GENERAL... 4 PRODUCT CHANGES... 4 WARRANTY... 4 RECEIVING... 4 CUSTOMER MODIFICATION...

More information

Capacitor Bank Controls

Capacitor Bank Controls Capacitor Bank Controls CBC-8000 Capacitor Bank Controller Device Functional Specification Guide 1. Capacitor Bank Controllers (CBCs) 1.1. The Capacitor Bank Control (CBC) shall be designed to control

More information

TECHNICAL DATA SHEET INIFINITY EVO kva 3Ph(In) 1Ph(Out)

TECHNICAL DATA SHEET INIFINITY EVO kva 3Ph(In) 1Ph(Out) TECHNICAL DATA SHEET INIFINITY EVO 3100 10 15 20 kva 3Ph(In) 1Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cosϕ 0.9) kva 10 15 20 Nominal output power (Cosϕ 1.0)

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA)

POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA) POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA) A55-00017 SEC PLUS 8-10 KVA MAREKTING SPECS REV. A 9/10 8kVA, 10kVA POWERVAR Isolated On-Line UPS Specifications Index 1.0 General

More information

GE Consumer & Industrial. Product description. Digital Energy Uninterruptible Power Supply VH Series UPS VA

GE Consumer & Industrial. Product description. Digital Energy Uninterruptible Power Supply VH Series UPS VA GE Consumer & Industrial Product description Digital Energy Uninterruptible Power Supply VH Series UPS 700-1000 - 1500-2000 - 3000VA Contents: 1. Introduction... 2 2. Functional explanation... 2 2.1 Principles

More information

AE8-1328 R5 March 2011. Copeland Digital Compressor Controller AE8-1328 R5. Specifications

AE8-1328 R5 March 2011. Copeland Digital Compressor Controller AE8-1328 R5. Specifications AE8-1328 R5 March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the Copeland

More information

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN UNINTERRUPTIBLE POWER SYSTEMS PF >0.98 G8000MM Series 100 to 750 KVA UPS IGBT DESIGN 94% Efficiency Main Features State-of-the-Art Modular Design Provides Maximum Flexibility The Toshiba G8000MM Uninterruptible

More information