Solution Specifications Freight Elevator
|
|
- Stephany Blake
- 7 years ago
- Views:
Transcription
1 Solution Specifications Freight Elevator Technical Equipment Data Equipment-No. Freight #1 Rated Load lb Rated Speed 150 fpm Travel Height 40 ft 0 in Number of floors All Proposals offered shall be comprised of design, manufacturing, supply and installation of following unit(s). Besides the technical specification we would highlight the key inclusions mentioned below. Offered Components Power Freight Traction Controller Hoist Motor Miscellaneous Existing freight doors to be retained and reused, new door interlocks to be provided as needed. Provide microprocessor-based control system to perform the functions of safe elevator motion. Included shall be all of the hardware required to connect, transfer and interrupt power, and to protect the motor against overloading. Each controller cabinet containing memory equipment shall be properly shielded from line pollution. The microcomputer system shall be designed to accept reprogramming with minimum system down time. All high voltage (110V or above) contact points inside the controller cabinet shall be protected from accidental contact in a situation where the controller doors are open. A new hoist motor shall be provided. The motor will be designed to stand the loads encountered for elevator service, sufficient capacity to operate with the contract load and speed without overheating, and will be rated in accordance with the standards of the IEEE. New Traveling Cable, Hoistway Wiring, Car Top Handrail Guides Governor New roller guides shall be provided. The car safety will be activated by a new speed governor located overhead, driven by a governor rope suitably connected to the car safety. The governor will be equipped with rope grip jaws designed to clamp the governor rope so as to actuate the car safety upon a predetermined over speed downward. The governor will be set at not less than 115% of specified rated car speed and not more than the maximum governor tripping speed specified in the code for the specified rated car speed. The rope grip jaws must be positively tripped within the permitted range of speed. The governor rope-tripping device will be so designed that no appreciable damage to or deformation of the governor rope will result from the stopping action of the device in operating the car safety. The governor over speed switches will conform to ANSI
2 A17.1 Code requirements and be so located and enclosed that excess lubricant will not enter the switch enclosure. Upon activation of the safety switch, the switch will remain in the open position until manually reset. The governor will be accurately adjusted and sealed with tripping speed specified. Date tags indicating the test date will be applied. Governor Ropes Hoist Ropes Rope Gripper Signalization Included Options A new governor cable(s) compatible with the specifications for the new governor will be provided. The governor cable is to pass over the governor sheave and under a weighted tension device at the bottom of the hoist way. During normal operation of each elevator, the governor rope will run free and clear of the governor gripping jaws, cable guards and all other stationary parts. A metal tag will be attached to the top of the car-releasing carrier, giving the diameter, material of cable, and with date of cable installation. Tags will be attached in an approved manner. New hoist cables shall be provided. The hoisting cables will be designed for elevator service, compatible with the hoist machine, and having a factor of safety at least equal to that specified in the ANSI Code. A new rope gripper over speed device shall be provided. The rope gripper shall prevent the car from striking the hoistway overhead structure due to a failure in the hoist motor, brake, coupling, shaft, gearing or control system. The rope gripper will be set to detect an ascending car over speed condition at a speed not greater than 10% higher than the speed at which the car governor is set to actuate. The device will also detect unintended car movement away from the landing with the hoistway door not in the locked position and the car door not in the closed position. The rope gripper will be designed so that no appreciable damage to, or deformation of, the cables will result from the stopping action of the device. Once activated by unintended movement or car over speed the device will remain activated until manually reset. New signalization in the hall and car shall be provided as required. 1 pc. Mechanical Layout Engineering - Machine Room Only Project Notes Handover Date Elevator Installation Permit provided by Contractor Mutually agreeable project schedule will be determined at time of proposal acceptance. Specify delivery lead time in proposal. Downtime period Specify down time per unit in proposal. CLARIFICATIONS
3 Contractors shall be responsible for all Permitting. All elevator equipment provided shall meet all applicable ASME A17.1 code requirements including all emergency phone requirements. Proposals shall include all inspections and testing as required by the Authority Having Jurisdiction as well as the fees associated with them.
4 Solution Specifications Passenger Elevator Upgrade Technical Equipment Data Equipment-No. Passenger #1 Rated Load 2500 lb Rated Speed 150 fpm Travel Height 40 ft 0 in Number of floors 2 All Proposals offered shall be comprised of design, manufacturing, supply and installation of following unit(s). Besides the technical specification we would highlight the key inclusions mentioned below. Offered Components Power Passenger: Existing doors to be retained and reused, new door interlocks to be provided Traction Controller Provide microprocessor-based control system to perform the functions of safe elevator motion. Included shall be all of the hardware required to connect, transfer and interrupt power, and to protect the motor against overloading. Each controller cabinet containing memory equipment shall be properly shielded from line pollution. The microcomputer system shall be designed to accept reprogramming with minimum system down time. All high voltage (110V or above) contact points inside the controller cabinet shall be protected from accidental contact in a situation where the controller doors are open. Hoist Motor A new hoist motor shall be provided. The motor will be designed to stand the loads encountered for elevator service, sufficient capacity to operate with the contract load and speed without overheating, and will be rated in accordance with the standards of the IEEE. Power Unit: Power unit will be replaced with a new hydraulic power unit. Fixtures: New fixtures will be installed to replace obsolete vector fixtures Infrared Door Edge: Install a new infrared door edge Door Operator: A new door operator will be installed with all necessary accessories. Car Fan: A new car fan will be installed. Cab Refurbishment: SCOPE OF SUPPLY: ELEVATOR INTERIOR (2500Lb Cab) 1. Prepare the existing walls to receive a new interior. 2. Supply and install #4 satin stainless steel 5 x1 L shape baseboard for the rear and two sidewalls. 3. Supply and install eight (10) vertical #4 satin stainless steel reveals that will be mounted between the wall panels and in all four corners. 4. Supply and install a true suspended ceiling faced with #4 Satin Stainless Steel finish divided into six (6) sections. The recessed downlights will be low voltage SoloBeam LEDs with black trim. 5. Supply and install seven (7) panels for the rear and two sidewalls faced and edged with standard horizontal grate laminate. Substrate to be ½ firerated flake. (see note 5) 6. Supply and install three (3) 3/8 x 2 #4 satin stainless steel flat bar handrails for the rear and two sidewalls. 7. Clean up as required.
5 SCOPE OF SUPPLY ELEVATOR INTERIOR CLADDING (2500LB CAB) 1. Prepare the front returns and header for cladding. 2. Clad the front returns and header with #4 satin stainless steel. Clean up as required. Signalization New signalization in the hall and car shall be provided as required. Included Options 1 pc. Mechanical Layout Engineering - Machine Room Only Project notes: contractor Elevator Installation Permit provided by Handover Date Mutually agreeable project schedule will be determined at time of proposal acceptance. Specify delivery lead time in proposal. Downtime period Specify down time per unit in proposal. CLARIFICATIONS Contractors shall be responsible for all Permitting. All elevator equipment provided shall meet all applicable ASME A17.1 code requirements including all emergency phone requirements. Proposals shall include all inspections and testing as required by the Authority Having Jurisdiction as well as the fees associated with them.
Roped Hydraulic Residential Elevator Specifications
January 1, 2004 Roped Hydraulic Residential Elevator Specifications P.O. Box 749, 5191 Stump Rd., Plumsteadville, PA 18949 Toll Free: 888-443-2800, Phone: 215-766-3380, Fax: 215-766-3385 CONTENTS Part
More informationSECTION 14 20 10 - FREIGHT & PARKING GARAGE ELEVATORS PART I - GENERAL
SECTION 14 20 10 - FREIGHT & PARKING GARAGE PART I - GENERAL 1.1 SECTION INCLUDES [NOTE to AE: The following lists requirements that are specific to freight elevators. These requirements are in addition
More informationCITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS
Subject: SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS Reference: Denver Fire Code Section 105.7.29 Approved: Joseph L. Gonzales, Division Chief, Fire Prevention Division Number: 105-1 Effective
More informationITEM DESCRIPTION SPECIFICATION TENDER OFFER
TECHNICAL SPECIFICATIONS PL1 & PL2 PLEASE TICK IF YOU COMPLY. SPECIFY YOUR OPTION IF YOU DON'T. ITEM DESCRIPTION SPECIFICATION TENDER OFFER Make (please specify) 1.0 Type Duplex Passenger Lift 2.0 Minimum
More informationV1504 Vertical Platform Lift OWNER S MANUAL
V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 01-m03-2016 2 IMPORTANT Ensure that only an authorized Savaria Dealer
More informationAssessment of Elevator and Escalator Maintenance & Repair Program Final Elevator Audit Submission Bethesda Station - Escalator A09X04 (Station)
Bethesda Station - Escalator A09X04 (Station) Ride Quality Test Results The Parametricoder is a time and displacement encoding system that measures mechanical performance characteristics on escalators.
More informationDEPARTMENT OF CORRECTIONS
Elevator Consulting, LLC. Post Office Box 464 Mequon, WI 53092-0464 Voice/Fax: 262-242-3077 Mobile No: 262-853-1054 E-mail: PerformElevCons@wi.rr.com DEPARTMENT OF CORRECTIONS MILWAUKEE SECURE DETENTION
More informationCLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
More informationV1504 Vertical Platform Lift OWNER S MANUAL
V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 03-m12-2013 2 IMPORTANT Ensure that only an authorized Savaria Dealer
More informationHOLLISTER-WHITNEY ROPE GRIPPER
HOLLISTER-WHITNEY ROPE GRIPPER Instructions for Model #620GA1, 620GA2 (Patented worldwide, other patents pending) WARNING: KEEP HANDS CLEAR OF ROPE GRIPPER. FORCES CREATED CAN CRUSH FINGERS. Figure 1 ROPE
More informationInterfacing Elevators with Fire Alarm and Sprinklers
Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes? Applicable Codes NFPA
More informationCLEAR-DIVISIONS VARIOFOLD
CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the
More informationCLEAR-DIVISIONS APERTO
CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the
More informationSchindler 5500 Efficiency. Flexibility. Performance.
Efficiency. Flexibility. Performance. Schindler Passenger Elevators Key figures Capacity 2100 lb (950 kg) to 5000 lb (2270) kg Travel height Up to 350 ft (107 m) Door width Up to 4 6 Door height Up to
More informationDIVISION H VERTICAL TRANSPORTATION REQUIREMENTS INDEX H.1 INTRODUCTION...2 H.2 GENERAL... 2 H.3. PRODUCTS...4 H.4 PASSENGER ELEVATORS...
DIVISION H VERTICAL TRANSPORTATION REQUIREMENTS INDEX H.1 INTRODUCTION........2 H.2 GENERAL......... 2 H.3. PRODUCTS............4 H.4 PASSENGER ELEVATORS..........5 H.5 FREIGHT AND COMBINATION PASSENGER/FREIGHT
More informationP.A.L. S SPECIFICATIONS
PART 1- GENERAL 1.1 SCOPE To furnish all labor, materials and equipment necessary or required to complete the installation of the lift as indicated on the Drawings and Specifications. This specification
More informationUBC Technical Guidelines Division 14 2016 Edition CONVEYING EQUIPMENT Page 1 of 1 INDEX. Section 14 40 00
UBC Technical Guidelines Division 14 2016 Edition CONVEYING EQUIPMENT Page 1 of 1 INDEX Section 14 20 00 Section 14 40 00 Elevators Lifts Page 1 of 14 1.0 GENERAL 1.1 Related UBC Guidelines.1 Division
More informationTechnical Investigation Report on Lift Incident. at 478-480 King s Road, North Point, Hong Kong
Technical Investigation Report on Lift Incident at 478-480 King s Road, North Point, Hong Kong Electrical and Mechanical Services Department July 2013 CONTENTS Page Executive Summary 3 1. Objectives 4
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationPlanning Information. Passenger and Freight Elevators.
A company of ThyssenKrupp Elevator Thyssen Aufzüge tk This planning information will give you an overview of the most important planning criteria of passenger and freight elevators. However you should
More informationSECTION 14 21 00 TRACTION ELEVATORS
SECTION 14 21 00 TRACTION ELEVATORS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Provide passenger and service traction elevators. 2. Due to maintenance area concerns, MRL elevators will be considered
More informationOregon Specialty Lift Code
2005 OREGON SPECIALTY LIFT CODE Effective January 1, 2012 Oregon Specialty Lift Code Based on: 2003 Vertical Reciprocating Lifts Part I 2003 Portable Wheelchair Lifts Part II Revised in 2005 Effective
More informationSchindler 3100 Simple and practical. Our passenger elevator for small residential buildings really gets you moving.
Simple and practical. Our passenger elevator for small residential buildings really gets you moving. Schindler Passenger Elevators 2 We keep what we promise. And we promise alot. A sensible choice Are
More informationMACHINE ROOM-LESS PERFORMANCE IN A HYDRAULIC ELEVATOR HOISTWAY. KONE EcoSpace
MACHINE ROOM-LESS PERFORMANCE IN A HYDRAULIC ELEVATOR HOISTWAY KONE EcoSpace The revolutionary machine room-less elevator concept KONE s machine room-less (MRL) technology eliminates the need for a machine
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationPremier & Deluxe 3-Season Room Sliding Glass Door
DTSSGD-11 Premier & Deluxe 3-Season Room Sliding Glass Door Installation Instructions Screen Door Seal Left Side Track Top Track Assembly Right Side Track Right Side Trim Sliding Glass Door Sliding Screen
More informationLift and Escalator Installations
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-29 Lift and Escalator Installations Building Works Requirements The
More informationHYDRAULIC FREIGHT ELEVATOR PACKAGES
HYRAULIC FRIGHT LVATOR PACKAGS Leistritz offers its customers a complete selection of freight elevators to meet a wide range of heavy-duty, freight handling applications. In addition to the cylinders,
More informationBUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
More informationSECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF)
SECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF) PART 1-GENERAL 1.01 RELATED WORK SPECIFIED IN OTHER SECTIONS A. Electrical connections see electrical specifications. 1.02 SUBMITTALS A.
More informationSECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
More informationGlossary of Common Crane Ter ms:
Glossary of Common Crane Ter ms: 26 Adjustable brakes: Electro-mechanical device to control crane deceleration. Bridge beam: Traveling beam connected to end trucks - supports trolley hoist and load. Bumpers:
More informationLOAD TEST PROCEDURE. Bridge, Gantry and Jib Cranes & Monorail Systems B001-R05/07
LOAD TEST PROCEDURE Bridge, Gantry and Jib Cranes & Monorail Systems B001-R05/07 Introduction: Load testing and inspection of overhead cranes is required by many safety regulations, national consensus
More information-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
More informationSchindler 400AE Machine Room-less Elevator Dynamic. Durable. Distinguished.
Schindler 400AE Machine Room-less Elevator Dynamic. Durable. Distinguished. Schindler Passenger Elevators 2 Streamlined MRL design. Enhanced with PORT Technology. The streamlined Schindler 400 Advanced
More information800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
More informationElectrical Wiring Technical Bulletin
Electrical Wiring Technical Bulletin Overview In general, SIP construction is easier and more cost effective when things are planned and thought out before the panels are manufactured. This process will
More informationStandard Design TKLP Cab
Standard Design TKLP Cab ThyssenKrupp Elevator s Laminated Plastic cabs are a beautiful blend of style and functionality. The standard cab, as included with our Pre-engineered and SPF elevator packages,
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationHAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 8 DIVISION OF OCCUPATIONAL SAFETY AND HEALTH CHAPTER 232
HAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 8 DIVISION OF OCCUPATIONAL SAFETY AND HEALTH CHAPTER 232 PERSONNEL HOISTS 12-232-1 Definitions 12-232-2 General
More informationLOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.
LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and
More informationQUOTATION FOR UPGRADING OF LIFT AT BINJA SAN DAVID, TRIQ SAN DAVID, MTARFA
Housing Authority AWTORITÀ TAD-DJAR HOUSING AUTHORITY 22, Pietro Floriani Street, Floriana Telephone: (356) 22991000 Fax: (356) 21243284 E-mail: procurement.ha@ha.gov.mt Website: http://www.housingauthority.gov.mt/
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More informationOwner s Manual Gantry Cranes
Owner s Manual Gantry Cranes Fixed Height Gantry Crane MODEL NUMBER: SERIAL NUMBER: CAPACITY IN TONS: Telescoping Gantry Crane Bushman AvonTec 262-790-4200, 800338-7810, Fax 262-790-4200 www.bushmanavontec.com
More informationBLR s Safety Training Presentations
BLR s Safety Training Presentations Machine Guarding 29 CFR 1910.211 to 1910.219 Machine guarding is an integral part of any safety and health program. As statistics can demonstrate, it is also one aspect
More informationSECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES
SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationThe Passenger and Freight Elevator Regulations, 2003
PASSENGER AND FREIGHT ELEVATOR, 2003 P-4 REG 2 1 The Passenger and Freight Elevator Regulations, 2003 being Chapter P-4 Reg 2 (effective January 1, 2004) as amended by Saskatchewan Regulations 80/2008.
More information1.1 DIMENSIONS AND WEIGHT PAG. 2 1.2 LOAD CENTRE FOR LIFTING PAG. 2 1.3 STORAGE CONDITIONS PAG. 2
TRANSPORT AND INSTALLATION. DIMENSIONS AND WEIGHT PAG.. LOAD CENTRE FOR LIFTING PAG..3 STORAGE CONDITIONS PAG. STARTING. INSTALLATION PAG.. SPACE REQUIREMENTS PAG. 3.3 ELECTRIC CONNECTION PAG. 3 3 DESCRIPTION
More informationJANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator
JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator The Janus Pantheon mini operator does not typically require the provision of any additional site requirements other than
More informationAutomatic Door Selection Guide
Automatic Door Selection Guide AAADM 1300 Sumner Avenue Cleveland, OH 44115 P: 216-241-7333 F: 216-241-0105 aaadm@aaadm.com Automatic Door Selection Guide General: The members of AAADM manufacture an assortment
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationEXCAVATOR SAFETY TRAINING
EXCAVATOR SAFETY TRAINING INSPECTION CHECKLIST INSPECTION AREA INSPECTION RESULTS Sat. Unsat. N/A Comments Carrier & Car Body Rotation system Tracks Rollers Frame, welds, bolts Drive system Upper Structure
More informationSWIMMING POOL, SPA, & HOT TUB GUIDELINES
SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015
More informationWalking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
More informationCluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11
Cluster Box Units (CBU s) continued on pages 7-11 CLUSTER BOX UNITS FRONT LOADING Made of heavy duty aluminum and stainless steel hardware, Salsbury 3300 series U.S.P.S. approved Cluster Box Units (CBU
More informationMaxi-Stamper. 200 to 1,000 Tons STAMPING OUT DOWNTIME
TM Maxi-Stamper 200 to 1,000 Tons STAMPING OUT DOWNTIME Standard Features Steel Fabricated Construction Drive Capacity Rated 1/2 Above Bottom of Stroke Self-Diagnostic Solid State Controller Moveable Operator
More informationRecommendations to improve the safety of existing lifts
Recommendations to improve the safety of existing lifts Lift & Escalator Industry Association Lift Safety an introduction Lifts are amongst the very few modes of transport available for continuous unsupervised
More informationHydraulic Controllers, PHC, HS
General In This Section PHC HS Hydraulic Controllers, PHC, HS General Model HMC-1000 controllers, industry recognized for over a decade, provide field proven reliability for all hydraulic elevator applications.
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationDisplay hidden notes to specifier. (Don't know how? Click Here) A. Advanced Upcoiling Security Grilles, power operated.
SECTION 08333 ADVANCED UPCOILING SECURITY GRILLE MODEL 600 ADV Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Advanced Upcoiling Security Grilles,
More informationDaily Operator Checks. Monthly Maintenance
CUSTOMER DATE OF INSPECTION SERIAL # RSF # UI Rev # PLC Project # SERVICE REPRESENTATIVE Daily Operator Checks Verify that all safety guards are in place. Verify that all safety signs are in proper location
More informationInstruction Manual Model #2343PXJ, 2344PXJ, 2345PXJ
Part No. 39598EXJ Revised March 2002 Instruction Manual Model #2343PXJ, 2344PXJ, 2345PXJ Proctor Companies 10497 Centennial Road Littleton, Colorado 80127 USA Phone: (303) 973-8989 Fax: (303) 973-8884
More informationknow-how Giant in distributing electricity for industry Prisma GK
Prisma GK Giant know-how in distributing electricity for industry Installation system up to 630A for electrical power distribution and circuit control. Prisma GK: technology and innovation for an IP55
More informationThe UPLANDS at ORO VALLEY Sterling Features
The UPLANDS at ORO VALLEY Sterling Features STERLING FEATURES Enhanced Air Quality System 2x6 Exterior Walls in Living Area Engineered Post Tension Concrete Slab Dual Pane Low-E Windows Covered Patio Gated
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationGENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
More informationReduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U
Reduced depth High Density Cabinet HDC with 19 swing frame 36, 40 and 45 U Applications The High Density Cabinets are suitable for Central Offices and can be used as fiber nodes and termination points
More informationJABATAN KESELAMATAN DAN KESIHATAN PEKERJAAN MALAYSIA (JKKP)
APPENDIX 1 Department of Occupational Safety and Health JABATAN KESELAMATAN DAN KESIHATAN PEKERJAAN MALAYSIA (JKKP) DEPARTMENT OF OCCUPATIONAL SAFETY AND HEALTH, MALAYSIA (DOSH) Aras 2, 3 & 4 Blok D3,
More informationCable Installation Notes
Cable Installation Notes June 2006 Table of Contents Cable Pulling... 2 Bending Radius... 2 Pulling Tension... 3 Friction... 3 Installation with Rollers... 4 Installation without Rollers... 4 Pulling Tension
More informationAndersen Electric Window Opener for Andersen Awning and Roof Windows
W A Electric Window Opener Electric Window Opener for Awning and Roof Windows Congratulations! You have just purchased one of the many fine products. For ease of installation and continued enjoyment of
More informationSchindler 3300 AP A remarkable style that suits the building. The machine room-less passenger elevator that unifies form and function.
A remarkable style that suits the building. The machine room-less passenger elevator that unifies form and function. Schindler Passenger Elevators Key figures Capacity Travel height One- or two-sided entrance*
More information39HQ Airovision Air Handling Units
39HQ Airovision Air Handling Units Mounting instructions CONTENTS 1 - TRANSPORT AND LIFTING INSTRUCTIONS... 3 1.1 - General... 3 1.2 - Transport and storage... 3 1.3 - Roof edge protection during transport
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationInstallation Instructions Avalanche XUV Cap IMPORTANT! IMPORTANT!
Installation Instructions Avalanche XUV Cap IMPORTANT! Read all instructions carefully before commencing any work. Always wear safety equipment. Some installation steps will require two or more installers.
More informationWE-350 Series ¼ Turn Electric Actuator
WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information
More informationPRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133
More informationC. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE
More informationProduct Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
More informationELECTRIC KNIFE SHARPENER
PRODUCT MANUAL- M109 MODEL 401 ELECTRIC KNIFE SHARPENER Please read thoroughly before operation and keep for future reference Model 401 Knife Sharpener Specifications Model No. #401 Power Requirements
More informationTOP AND CABINET PARTS
TOP AND CABINET PARTS AUTOMATIC WASHER 10 10 Litho in U.S.A. (drd) (psw) 1 Part No. W10337313 Rev. C TOP AND CABINET PARTS 1 Literature Parts Installation Instructions W10240509 English/French W10240510
More informationfreight elevators 2008 planning guide ThyssenKrupp Elevator Americas Business Unit
freight elevators 2008 planning guide ThyssenKrupp Elevator mericas usiness Unit TK Our ommitment To You ependable. Tough. Efficient. The qualities you need in your freight elevators are the qualities
More informationCan you design a frameless shower enclosure that doesn't leak?
Can you design a frameless shower enclosure that doesn't leak? With proper design and installation frameless shower enclosures should not have any problems with water leakage, but they are not 100 percent
More informationFG MOISTURE MONITOR Installation & Operation Manual
FG MOISTURE MONITOR Installation & Operation Manual Issue 3.0 7/20/10 1 Contents SERVICE AND TECHNICAL SUPPORT... 2 INSTALLATION:... 3 MOISTURE SENSOR INSTALLATION:... 3 SENSOR CONNECTOR:... 5 MONITOR
More informationSECTION 807 PUMP STATION REHABILITATION
SECTION 807 PUMP STATION REHABILITATION 807-1 DESCRIPTION: Rehabilitation of pump stations shall be defined as the cleaning, removal, repair and/or replacement of any and/or all components including but
More informationDoc 10. UTM Standards: Card Access Security System
Doc 10 UTM Standards: Card Access Security System 1. GENERAL... 2 1.1. GENERAL REQUIREMENTS.... 2 1.2. SUMMARY OF WORK INCLUDED... 2 1.3. OVERVIEW... 2 1.4. MANDATORY REQUIREMENTS... 3 1.5. ACCESS CONTROL
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationCooking at the Speed of light!
Cooking at the Infrared Cooking & Colouring Infrabaker is a modular infrared continuous cooking system developed by Infrabaker International. The machine is designed to cook and/or put colour on a wide
More informationSection 7: Elevators and Lifts. Main Entry Floor Outside the Elevator
Section 7: Elevators and Lifts Questions Yes No Data Main Entry Floor Outside the Elevator 1. If an elevator is required to arrive at the voting area, is it on an accessible path of travel? 2. Is there
More informationTS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
More informationTube Type Oil Skimmer Comparison
Process Overview- Tube Type Oil Skimmers Oil flows down the face of the skimmer and into a sludge pan that is plumbed to a barrel. Model BG01 & BG34 or 6V Oil Skimmer 1.0 or 3/4 Diameter Collector Tube
More informationHorizontal Cable Systems
Safety From The Top Down Suspended Access Systems and Fall Protection Overview Horizontal cable systems are generally installed as a permanent fall protection system, typically consisting of two terminating
More informationETZGAR CONVEYOR COMPANY Controls Section v12.05
Section 7 Controls Page Description 7-1 Controls Index 7-2 Motor Data, Enclosure Rating and Abbreviations 7-3 Controls Safety Guidelines 7-4 Fixed Speed Controls Packages 7-5 Three Phase AC Variable Speed
More informationOccupational Safety and Health Admin., Labor 1910.68
Occupational Safety and Health Admin., Labor 1910.68 (vii) The brakes shall be set and outriggers, when used, shall be positioned on pads or a solid surface. Wheel chocks shall be installed before using
More informationUniversal Mount Industrial Monitors
Universal Mount Industrial Monitors Tu Sitio de Automatización! VESA Mount Options Yoke Mount Options Pedestal Mount Options VESA Mount Options Radial Arm Wall Mount Bracket Benchtop Stand Radial Arm Mount
More informationIntroduction... 2. Body Specifications... 3. Technical Data... 4. Body... 5. Interior Rear Seats... 6. Center Arm Rest... 7. Child Seat Restraint...
Table of Contents Subject Page Introduction.......................................... 2 Body Specifications.................................... 3 Technical Data........................................
More informationrpsa FIRE PROTECTION ENGINEERS www.rpsa-fire.com
www.-fire.com R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, MA 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator Power Shutdown Disclaimer:
More informationFAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com
FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,
More informationLIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
More information