PART 0 DESIGN STANDARDS 0.01 USE OF THIS STANDARD

Size: px
Start display at page:

Download "PART 0 DESIGN STANDARDS 0.01 USE OF THIS STANDARD"

Transcription

1 PART 0 DESIGN STANDARDS 0.01 USE OF THIS STANDARD A. Due to the extent of detail provided in this standard, the A/E may choose to edit this standard and incorporate portions of this standard in the construction documents. To obtain an electronic copy of this standard in Microsoft Word format, contact the DPS Project Manager GENERAL DESIGN REQUIREMENTS A. New facilities and facilities to be substantially renovated must include a fire alarm system. 1. Exceptions include very small single story buildings, sheds, and temporary facilities where coderequired systems are not mandatory and the occupancy does not warrant a system. B. Renovations affecting existing systems shall be handled on a case-by-case basis with direct input from DPS. C. This standard covers new fire alarm systems. D. Inspections and testing by others do not relieve the A/E of contract responsibilities. Conduct necessary observations and inspections including, but not limited to, rough-in observations and punch list preparation and backchecking. Provide reports DESIGN CRITERIA A. General: 1. The following guide spec is to provide the A/E with the information needed to specify and design fire alarm systems for DPS. This guide spec provides the types of systems and detectors to be used, shop drawing requirements, annunciator requirements, sequence of operations, A/Eing drawing requirements, and the A/E's duties. 2. The A/E should avoid specifying proprietary features of specific manufacturers. B. Existing Systems: 1. On projects where existing systems are revised or expanded, the A/E shall meet with the Contractor and the DPS Project Manager to verify the operating condition of the existing system before the Contractor begins work on the system (i.e., is the existing system functioning properly, etc.). The A/E shall include this requirement in the project specifications. 2. Where a new system is being installed to replace an existing system, the existing fire alarm systems shall remain fully operational until the new work is completed and the entire new system is functional and accepted by the Fire Department. 3. Where a new system is being installed to replace an existing system, the A/E shall require the Contractor to field verify and show the locations of sensors. C. Circuits and Raceway: 1. Fire alarm system wire and cable shall be located in concealed metal conduit regardless of code exceptions. Location and routing shall take advantage of areas easily accessed by DPS Maintenance personnel (hallways/corridors) and shall consider future modification and/or extension wherever practical. 2. Raceway fill shall be less than 40% per NEC. Calculations proving this will need to be submitted for review. Raceway capacity between control panels and terminal cabinets shall be sufficiently sized to accept additional circuits in the future. A/Es are encouraged to show a minimum size that would accommodate future work. 3. Circuits shall be laid out to serve a specific geographical area (zone) per floor. 4. Field located transponders and power supply panels may be used. Good access must be provided for testing and maintenance requirements Page 1 of 23

2 5. Provide 25% spare capacity on all circuits, considering both circuit and panel limitations. This includes device count, circuit length, voltage drop, and panel capacity. Other spare capacity should be specified. 6. Balance all circuits for equal loading and spare capacity. D. Device and Appliance Layout: 1. The design shall include complete smoke detection throughout public corridors, classrooms, offices, toilets and all spaces as dictated by applicable codes. Coordinate detector locations with ceiling diffusers; none may be closer than 3 feet. 2. Smoke detectors shall be provided at all elevator lobbies. 3. A smoke detector shall be provided above the fire alarm panel. 4. Smoke detectors shall be placed to avoid dirty environments that would be prone to false alarm. 5. Heat sensors located in attics and crawl spaces shall be spaced in accordance with their listing with the following exceptions: a) The sensors must be accessible from catwalks or access doors. In existing buildings, the sensors should be located over existing catwalks, if allowed by the AHJ. It is not required to add catwalks simply to meet spacing requirements. b) Spacing may be modified in order to locate sensors where they will be accessible. c) In crawl spaces or attics with limited access, heat sensors are to be located at the access to the space and at any equipment located in the space. 6. Provide fire alarm manual pull stations at all building exits in the direct path of egress. Pull stations shall be provided on individual floors at the entrance to the exit stair. Additional devices in corridors and in stairs are not required or desired, as they become a maintenance burden. 7. Fire alarm audibility and visual notification is required throughout the building. Provide horn/strobes in all classrooms. 8. Visual notification must be in compliance with NFPA 72, including minimum candela intensity throughout all public spaces including but not limited to corridors, classrooms, conference rooms and restrooms. Strobe design must include candela rating on the individual device and a template should be used to ensure sufficient intensity to provide coverage to all required areas. Synchronize visual notification devices when multiple devices are in the line of sight. Synchronize the circuit at the individual floor terminal cabinet. 9. Devices shall be combination horn/strobe. Individual strobes are also acceptable where appropriate (i.e. small restrooms and conference rooms that receive adequate audibility from adjacent area horns). Horn/strobes are also required in acoustic (sound) rooms, coolers, environmental rooms and other areas resistant to sound transmission that are regularly occupied. The use of ceiling mounted horn/strobes is encouraged for discouraging vandalism. Provide only a horn for dark rooms. 10. Provide 110VAC horn/strobe on exterior of building within 10 feet vertically above the fire department connection. This horn/strobe shall be activated by a water flow alarm. 11. Provide two-way firefighter phone jacks and speakers in spaces with occupancy of 1000 or more. E. Auxiliary Controls: 1. Coordinate auxiliary controls for fans, dampers, fire sprinklers, elevator and door control. Include all necessary components and relays to make an operational system. 2. Control fire smoke dampers from the FACP via a supervised relay serving a number of dampers. Relays must be labeled and shall be accessible for maintenance. Electric 110 VAC actuated dampers must be specified. The FACP must not provide power for dampers Page 2 of 23

3 3. To minimize duct over-pressurization, damper interface from the FACP shall include a 30 second delay programmed into the FACP to ensure fan blades have stopped rotating. 4. Include interface with all necessary fire sprinkler components, water flow devices and valve supervision. 5. Provide fire alarm circuits to elevator controller. Provide two supervised relays in the elevator machine room. 6. Coordinate door hold open requirements with the Architect. Door hold open release shall occur upon any alarm. 7. Provide manual door hold open release button in each classroom, located by the room light switch. Provide Carling switch model #170 - Normally Closed SPST. 8. For remodel projects only, provide 10-gauge metal plate, 10"x10" to mount magnetic door holder unless they are flush mounted. If mounted on a corner, make the plate 10 x20 bent at a 90 degree angle to go around the corner NEW SYSTEM REQUIREMENTS A. Control Panels: 1. New fire alarm and detection systems should be microprocessor-based with intelligent addressable smoke and heat sensors, and addressable contact monitoring devices for initiating devices such as manual fire alarm boxes, water flow switches, tamper switches, etc. Systems other than addressable systems that meet the current Denver Building Code may be considered upon prior approval from the DPS Project Manager. 2. For an addressable system, the FACP shall contain a keypad, function buttons, and backlit LCD display. The FACP shall contain an integrated printer. 3. The fire alarm system shall allow for loading and editing of special instructions and operating sequences. The system is to be capable of on-site programming. All software operations are to be stored in non-volatile programmable memory. The vendor shall provide software documentation that details procedures and precautions required for software modification. 4. The system shall log and print all events on the system. Real time and date shall accompany all history event recording. 5. If allowed by the AHJ, the system shall have an alarm verification feature that can be set by individual sensor or for a group of sensors. The verification time shall be adjustable from 0 to one (1) minute. The specifications shall require that alarm verification be set at 30 seconds. Special conditions may dictate that specific detectors have a different verification period. 6. The system shall use smoke sensors that measure smoke density and heat sensors that measure temperature, and report the condition to the control panel. The control panel shall determine if an alarm condition exists by comparing the sensor value to stored values. If allowed by the AHJ, the alarm point shall be adjustable manually or automatically from the control panel. The system shall be programmed to set the sensitivity to the lowest level during school hours and then reset to a higher sensitivity when the building is unoccupied. 7. The system shall have the capability to cancel, through software modification, the detector polling light during normal operation of the system. 8. The system shall automatically compensate the sensitivity level of smoke sensors for dusty or dirty conditions. At a preset level, the system shall identify that a smoke sensor requires maintenance. 9. The system shall be a complete UL-listed, supervised fire alarm system that incorporates the following functions: a) The actuation of any initiating device shall automatically cause all audible and visual alarms to activate continuously. The audible signals shall sound a temporal pattern until the system Page 3 of 23

4 is silenced or reset. The visual alarms shall continue to flash until the system is reset. The silencing of audible signals shall be a separate function from reset. b) Activation of any sprinkler or standpipe valve tamper switch shall activate the system supervisory alarm and illuminate the supervisory LED on the control panel. c) In the event of an open or ground in a circuit or an off-normal condition, a trouble alarm shall sound and the trouble LED on the control panel shall be illuminated. Acknowledgement of the trouble or operation of the trouble silence switch shall cause the audible alarm to silence. The trouble condition shall remain on the system until the trouble is corrected. Once the trouble is corrected, the trouble alarm shall self-restore. d) Include any modifications to the security system to monitor these points. Trouble and supervisory alarms are not to be transmitted to the City Fire Alarm Headquarters. 10. Automatically transmit a coded signal to the City Fire Alarm Headquarters through a G. H. Harlow radio transmitter. It shall be possible to disable the transmitter for testing and maintenance purposes. Disabling the signal to the City shall cause a trouble alarm to sound. Silencing the trouble alarm shall leave a trouble light until the system is restored to on-line status. The system shall transmit to the radio transmitter those alarms required by the AHJ. The radio transmitter will then send the alarms to the Fire Alarm Headquarters. For schools with a swimming pool, an additional "drowning alarm," activated by a separate manual box in the pool area, shall be transmitted. The drowning alarm sounds a different sound (not temporal pattern) in the pool area only, not as a general alarm throughout the building. The pull station will be yellow and be labeled as Drown Alarm. Special systems such as kitchen hoods, etc. shall be transmitted as separate alarms. Use existing Bronco panel for renovations to existing systems. The interface panel and radio transmitter are limited to seven (7) zones. If more than seven zones are required, additional interface panels and transmitters will be required. 11. Provide an 8-point relay card in the FACP (FACP) and program FACP to send discrete signals to the transmitter. 12. Each device within the building will be programmed to report to one of the transmitter zones. Duct Detector, Supervisory, and Trouble alarms shall not be transmitted. 13. The DPS Project Manager will coordinate with the Denver Fire Prevention Bureau and will provide a listing of devices to be programmed to each transmitter zone. 14. A double-contact pull station shall be located adjacent to the FACP. One contact will provide alarm directly through the transmitter (even when the fire alarm system is disabled or off line). It will also override all disabled points on the FACP including horn/strobes. Location of this pull station shall be determined by the AHJ. B. Power Supply: 1. The system shall be provided with a Transient Voltage Surge Suppression (TVSS) device on the incoming 120-volt power. 120-volt power shall be provided from a convenient branch circuit dedicated to the fire alarm. If the building is equipped with a standby generator, the fire alarm system shall be connected to a dedicated branch circuit connected to the generator. 2. The fire alarm system power supply shall be UL-listed with secondary power capable of operating the system, including the printer, as required by code. C. Devices: 1. Magnetic door hold-opens and door closers with an electric hold-open feature shall be connected to the building electrical system. Hold-opens shall not obtain their power from the fire alarm system. 2. The fire alarm system shall incorporate manual fire alarm boxes, photoelectric smoke sensors, photoelectric duct smoke sensors, heat sensors, magnetic door holders, remote indicating lights and other devices required to meet the requirements of this standard Page 4 of 23

5 a) Manual fire alarm boxes shall be located and provided per code. b) Provide photoelectric smoke sensors in toilet rooms. c) Fixed-temperature heat sensors shall be located in: i) Boiler rooms. ii) Kitchens. iii) Exterior storage (verify with DPS). d) Smoke sensors located in gymnasiums shall have metal guards installed over the detectors for physical protection. The sensor manufacturer shall warrant that the guard does not affect the sensor operation. e) Smoke and heat sensors shall incorporate a lamp or LED that will light continuously while the sensor is in alarm. Do not use polling systems. f) Visual alarm strobes shall be mounted inches above the finished floor level within a space or six (6) inches below the ceiling, whichever is lower. In general, visual alarm strobes shall be no more than 50 feet from any point in a room or corridor. Do not install strobes in small toilets that are normally supervised (e.g., toilets in kindergarten classrooms). Strobes shall be UL 1971-listed. D. Annunciation: 1. Provide an alphanumeric backlit LCD annunciator that shows the device address and a descriptor for the type of device and its location. In addition to the LCD annunciator, provide a hard copy printer that prints out each device in alarm and/or in trouble state. Provide a graphic zone map mounted on the wall next to the LCD annunciator and printer. The LCD annunciator and printer shall clearly indicate the location of each alarm-initiating device. The descriptor shall contain the general area, the specific area, the room, the room number, and the device. For example, "THIRD FLOOR EAST WING CLASSROOM 301-SMOKE DETECTOR." The building shall be zoned by level and by logical building feature, i.e., west wing, athletic wing, auditorium, etc. The maximum size of any zone should be approximately 20,000 square feet. Provide additional graphic zone maps in multilevel buildings. The additional zone maps shall be located on the other levels from where the main zone map is located. These zone maps shall represent only the level on which they are located. See drawing Remote Light Configurations for example of map with remote indicating lights. 2. Graphic zone maps shall be constructed of a black and color image on white plasticized photographic paper mounted on a rigid backing. The map shall be covered with a 1/8" clear antiglare acrylic. The assembly shall be mounted in an anodized aluminum frame with a concealed security hanging system. The graphic zone map shall depict the building features such as walls, doors, stairs, etc. in black. The location of the FACP, main zone map and other zone maps shall be shown in red with "You are Here" in red. The location of the transmitter and fire department connection shall be indicated in red. Initiating devices are to be shown in red. Locations of special systems shall be shown in red. Room numbers shall be shown in blue. Show street names and the locations of hydrants, main gas shutoff, main water shutoff, sprinkler shutoff, and main electrical shutoff in green A/EING DOCUMENT REQUIREMENTS A. As part of the construction documents, the A/E shall provide separate drawings for the fire alarm system in accordance with Method C of the Building Inspection Division Policy B-049, dated December 17, These requirements are for documents for expansions and revisions to existing systems, as well as new systems. B. The A/E's drawings shall: 1. Be on separate sheets from lighting, power and special systems Page 5 of 23

6 2. Be to scale, showing room numbers and room occupancy descriptions. 3. Show the placement of all alarm initiating devices and alarm notification appliances. The type of alarm initiating device, such as smoke sensor, rate-of-rise or fixed temperature heat sensor, duct sensor, etc., shall be shown. 4. Show the location of the FACP, annunciators, zone maps, interface panel, transmitter, transmitter antenna, and risers. The A/E shall meet with the Fire Department and DPS Project Manager before submitting drawings and get approval on the locations of control panels, annunciators, etc. Indicate on the drawings the date of that meeting and persons present. 5. Show a detail of the graphic annunciator panel or graphic zone map. The detail shall show the layout of the different floor plans, the location and labeling of any LEDs and the zones in which the building is being divided. The detail is not required to be actual size. 6. Include the Sequence of Operation, even if the Sequence is included in the specifications. 7. Include a zone schedule indicating the grouping of addressable devices for the annunciator. 8. Include a schematic system one-line diagram. PART 1 GENERAL 1.01 SECTION INCLUDES A. This section of the specification includes the furnishing, installation, connection and testing of the fire alarm equipment required to form a complete, operative, coordinated system. It shall include, but not be limited to, alarm initiating devices, alarm notification appliances, evacuation equipment, FACP (FACP), auxiliary control devices, annunciators, auto-dialers, power supplies, and wiring as shown on the drawings and specified herein ALTERNATES/ALTERNATIVES A. Project alternates are to be used only with the approval of DPS. Work identified as "Alternates" shall be subject to the review and evaluation of the DPS Project Manager and may be selected for addition to or deletion from the Contract for Construction. Comply with requirements of Section Alternates/Alternatives PRODUCT OPTIONS AND SUBSTITUTIONS A. No requests for substitutions will be considered after the Bid Opening. B. Contractors and/or suppliers may submit requests for approval of equal products or materials. Written requests shall be submitted to the A/E for review within the specified time BEFORE THE BID SYSTEM DESCRIPTION A. Design Requirements: 1. The fire alarm system shall comply with requirements of 1996 NFPA Standard 72 for Protected Premises Signaling Systems except as modified and supplemented by this specification. The system shall be electrically supervised and monitor the integrity of all conductors. 2. The system and its components shall be Underwriters Laboratories, Inc. listed under the appropriate UL testing standard for fire alarm applications and the installation shall be in compliance with the UL listing. B. Performance Requirements: 1. The installing company shall employ NICET (minimum Level II Fire Alarm Technology) technicians on site to guide the final checkout and to ensure system integrity. 2. The connection between network control panels shall be a recognized network communication scheme and shall be wired in a Class A, Style 7 fashion Page 6 of 23

7 3. Alarm, trouble and supervisory signals from all intelligent reporting devices shall be encoded on NFPA Style 4 (Class B) Signaling Line Circuits (SLC). 4. Initiation Device Circuits (IDC) shall be wired Class B (NFPA Style B) as part of an addressable device connected by the SLC Circuit. 5. Notification Appliance Circuits (NAC) shall be wired Class B (NFPA Style Y). Power for initiating devices and notification appliances must be from the main FACP or from a Field Charging Power Supply (FCPS). 6. A single ground fault or open circuit on the system Signaling Line Circuit shall not cause system malfunction, loss of operating power or the ability to report an alarm. 7. Alarm signals arriving at the main FACP shall not be lost following a primary power failure (or outage) until the alarm signal is processed and recorded. 8. Provide 25% spare capacity on each circuit and for panel points, considering both circuit and panel limitation. This includes device count, circuit length, voltage drop, and panel capacity. 9. Balance all circuits for equal loading and spare capacity SUBMITTALS A. General: 1. Shop drawings shall be submitted under provisions described in Division 1, Section Submittals shall include specification (cut) sheets for each device utilized in the fire alarm system. 3. When the drawings are submitted to the Fire Department for review for a permit, the A/E shall be responsible to ensure that a third set of the fire alarm A/Eing drawings are submitted. The Fire Department will return this third set to the Contractor to be returned to the DPS as their record approved submittal. B. Shop Drawings: 1. Shop drawings shall be submitted per Section for review to the Architect/A/E and the DPS Project Manager before being submitted to the Fire Department. The shop drawings shall include the following: a) Sufficient information, clearly presented to determine compliance with drawings and specifications. b) Architectural floor plans (scale as depicted on contract documents) showing location of FACP, all alarm initiating devices, all alarm notification appliances and sources of all electric power for the system. c) Equipment layout and device arrangement. d) Complete point-to-point wiring diagrams detailing internal and interconnecting wiring for power, signal and control that distinguishes between field installed and factory installed wiring. e) Fire alarm symbols shall match those shown on contract documents (NFPA 170). f) FACP cabinet layout. g) Remote Supervising Station connection. h) Graphic map plan shall be submitted at actual size and depict the following: i) i) architectural floor plan (black) ii) room names and numbers (blue) iii) fire alarm initiating devices (red) with custom message number iv) FACP (red) Page 7 of 23

8 v) graphic map location with you are here arrow (red) vi) north arrow (black) vii) legend viii) adjacent street names (green) ix) locations of hydrants, fire department connection and DFD transmitter (red) x) locations of main shutoffs for gas, water, electric, and fire sprinkler (green) i) Standby battery calculations. j) Voltage drop calculations for horn and visual devices. k) Sequence of operation. (Manufacturer s standard descriptions for generic systems are not acceptable) l) Riser diagram. Typical riser diagrams are not acceptable. The riser diagram shall be specific to each building and include exact quantities of notification appliances. Riser diagram showing each circuit emanating from the control panel, auxiliary equipment such as printers, and every device on the system. Devices shall be located on the circuits they are connected to in the same relation as shown on the floor plan. m) Wire list including FACP manufacturer s recommended wire, size and color-coding. n) 3:1 scaled elevation drawing of network graphical user interface station placement and layout of all equipment required therein. o) All shop drawings shall be produced on AutoCAD per Section p) Specifications and highlighted cut sheets on each piece of equipment proposed. q) Drawings showing the layout of the floors and location of each item of equipment. These drawings may be a re-submittal of the "approved" A/E's drawings as per Method C or may be drawings prepared by the Contractor. If the Contractor prepares new floor plans, the "approved" A/E's drawings must still be submitted. r) Elevation drawings of walls on which control panels, interface panel, transmitter and annunciator panels are to be mounted. Elevations should be fully dimensioned to show location of each piece of equipment. C. Product Data: Manufacturer's name(s), model numbers, ratings, power requirements. D. Quality Assurance Data: Together with the shop drawing submittal, submit a certification from the major equipment manufacturer indicating that the distributor is an authorized representative of the major equipment manufacturer. Include names and addresses in the certification. E. Provide three (3) copies of as-built drawings and specifications to A/E before Final Inspection. F. Operation and Maintenance Data: 1. Submit as-built shop drawings with complete operation and maintenance manuals listing the manufacturer s name(s), including technical data sheets per Section Wiring diagrams shall indicate internal wiring for each device and the interconnections between the items of equipment. 3. Provide a clear and concise description of operation that gives, in detail, the information required to properly operate the equipment and system. G. Software Modifications: 1. Provide the services of a factory trained and authorized technician to perform all system software modifications, upgrades or changes. Response time of the technician to the site shall not exceed four hours Page 8 of 23

9 2. Provide all hardware, software, programming tools and documentation necessary to modify the fire alarm system on site. Modification includes addition and deletion of devices, circuits, zones and changes to system operation and custom label changes for devices or zones. The system structure and software shall place no limit on the type or extent of software modifications on-site. Modification of software shall not require power-down of the system or loss of system fire protection while modifications are being made QUALITY ASSURANCE A. Qualifications: 1. Shop drawing preparation shall be by a NICET Level III A/Eing Technician or a qualified Professional A/E and shall have 5 years experience in designing fire alarm systems with at least three systems greater than 200,000 sq. ft. in the City and County of Denver within the last two years. 2. Bidder shall have 5 years experience in designing and installing fire alarm systems with at least three systems greater than 200,000 sq. ft. in the City and County of Denver within the last two years. B. Certifications: Together with the shop drawing submittal, submit a certification from the major equipment manufacturer indicating that the distributor is an authorized representative of the major equipment manufacturer. Include names and addresses in the certification. C. Approvals: The system shall have proper listing and/or approval from Underwriters Laboratories Inc. (UL). The FACP shall meet UL Standard 864 (Control Units). D. Modular Labeling: The FACP shall meet the modular labeling requirements of Underwriters Laboratories, Inc. Each subassembly, including all printed circuits, shall include the appropriate UL modular label. Systems, which do not include modular labels, may require return to the factory for system upgrades, and are not acceptable WARRANTY A. All work performed and all material and equipment furnished under this contract shall be free from defects and shall remain so for a period of at least twenty-four (24) months from the date of acceptance. The full cost of maintenance, labor and materials required to correct any defect during this period shall be included in the submittal bid. B. If at any time during the construction of this project, the Denver Fire Department determines that a fire watch is required due to contractor s delays or methods of construction sequence, the contractor shall be responsible for the cost of such watch and obtain all permits required. PART 2 PRODUCTS 2.01 MATERIAL AND EQUIPMENT, GENERAL A. All equipment and components shall be new, and the manufacturer's current model. The materials, appliances, equipment and devices shall be tested and listed by a nationally recognized approvals agency for use as part of a protective signaling system, meeting the National Fire Alarm Code. The authorized representative of the manufacturer of the FACP shall be responsible for the satisfactory installation of the complete system CONDUIT AND WIRE A. Conduit: 1. Conduit shall be in accordance with The National Electrical Code (NEC), and Section Raceways. 2. Cable must be separated from any open conductors of power, or Class 1 circuits, and shall not be placed in any conduit, junction box or raceway containing these conductors, per NEC Article Page 9 of 23

10 3. The contractor may reuse existing conduit that meets the above requirements. 4. Provide 25% spare capacity for all circuit runs. 5. Wiring for 24 volt DC control as related to the fire alarm system, alarm notification, emergency communication and similar power-limited auxiliary functions may be run in the same conduit as initiating and signaling line circuits. 6. All circuits shall be provided with transient suppression devices and the system shall be designed to permit simultaneous operation of all circuits without interference or loss of signals. 7. Conduit shall not enter the FACP, or any other remotely mounted control panel equipment or back boxes, except where conduit entry is specified by the FACP manufacturer. 8. Conduit shall be 3/4-inch (19.1 mm) minimum EMT. Conduit runs to single device locations may be 1/2-inch minimum EMT. Existing conduit meeting these requirements may be reused. 9. All conduit, junction boxes, conduit supports and hangers shall be concealed in finished areas and may be exposed in unfinished areas. 10. All fire alarm conduits shall be identified by spraying with red paint or applying red self-adhesive tape at least every 3 feet at all changes in direction. B. Wire: 1. All fire alarm system wiring shall be new. 2. Wiring shall be in accordance with local, state and national codes (e.g., NEC Article 760) and as recommended by the manufacturer of the fire alarm system. Number and size of conductors shall be as recommended by the fire alarm system manufacturer, but not less than 16 AWG (1.02 mm) for Initiating Device Circuits and Signaling Line Circuits, and 14 AWG (1.63 mm) for Notification Appliance Circuits. 12 AWG will not be allowed to be directly connected to notification appliances. 3. All wire shall be solid copper. 4. All wire and cable shall be listed and/or approved by a recognized testing agency for use with a protective signaling system. 5. Wire and cable not installed in conduit shall have a fire resistance rating suitable for the installation as indicated in NFPA 70 (e.g., FPLR). 6. The design of the system shall permit use of IDC and NAC wiring in the same conduit with the SLC communication circuit. 7. All field wiring shall be electrically supervised for open circuit and ground fault. 8. Initiating circuits shall be arranged to serve like categories (manual, smoke, water flow). Mixed category circuitry shall not be permitted except on signaling line circuits connected to intelligent reporting devices. 9. FACP primary power wiring shall be 12 AWG TERMINAL BOXES, JUNCTION BOXES AND CABINETS A. All boxes and cabinets shall be UL listed for their use and purpose. Comply with Section Cabinets and Enclosures. B. All fire alarm junction and back boxes shall be identified by spraying at least one surface with red paint or applying red self-adhesive tape to the surface. Mask adjacent surfaces when spray-painting to obviate over-spray. C. The control panel cabinet shall be grounded securely to either a cold water pipe or grounding rod DENVER FIRE DEPARTMENT RADIO TRANSMITTER Page 10 of 23

11 A. Electrical Contractor shall provide and install radio transmitter G.H. Harlow Model #GHR02AX08S- 72M MAIN FACP A. Each FACP shall be a microprocessor based Central Processing Unit (CPU). The CPU shall communicate with and control the following types of equipment used to make up the system: intelligent addressable smoke and thermal (heat) detectors, addressable modules, temporal coded horn evacuation equipment, emergency voice evacuation equipment, annunciators, network graphic interface stations at the fire command center and back-up fire command center, and other system controlled devices. B. Operator Control: 1. Acknowledge Switch: Activation of the control panel acknowledge switch in response to new alarms and/or troubles shall silence the local panel piezo electric signal and change the alarm and trouble LEDs from flashing mode to steady-on mode. If multiple alarm or trouble conditions exist, depression of this switch shall advance the 80-character LCD display to the next alarm or trouble condition. Depression of the Acknowledge switch shall also silence all remote annunciator piezo sounders. 2. Alarm Silence Switch: Activation of the alarm silence switch shall cause all programmed alarm notification appliances and relays to return to the normal condition during an alarm condition. The selection of notification circuits and relays that are silenceable by this switch shall be fully field programmable within the confines of all applicable standards. The FACP software shall include silence inhibit and auto-silence timers. 3. Alarm Activate (Drill) Switch: The Alarm Activate switch shall activate all notification appliance circuits. The drill function shall latch until the panel is silenced or reset. 4. System Reset Switch: Activation of the System Reset switch shall cause all electronically-latched initiating devices, appliances or software zones, as well as all associated output devices and circuits, to return to their normal condition. 5. Lamp Test: The Lamp Test switch shall activate all system LEDs and light each segment of the liquid crystal display. C. The FACP shall include a full-featured operator interface control and annunciation panel that shall include a backlit Liquid Crystal Display (LCD), individual color-coded system status LEDs, and an alphanumeric keypad for the field programming and control of the fire alarm system. D. Provide means of minor programming changes by DPS personnel. E. The system shall allow the programming of any input to activate any output or group of outputs. Systems, which have limited programming (such as general alarm) or have complicated programming (such as a diode matrix), are not considered suitable substitutes. F. The FACP shall provide the following features: 1. Drift compensation to extend detector accuracy over life. Drift compensation shall also include a smoothing feature, allowing transient noise signals to be filtered out. 2. Detector sensitivity test, meeting requirements of NFPA 72, Chapter Maintenance alert to warn of excessive smoke detector dirt or dust accumulation. 4. A minimum of seven sensitivity levels for alarm, selected by detector. The alarm level range shall be 1 to 2.35 percent per foot for photoelectric detectors and 0.5 to 2.5 percent per foot for ionization detectors. The system shall also include pre-alarm, selected by detector, to indicate to maintenance personnel of impending alarms. 5. The ability to display or print system reports Page 11 of 23

12 6. Alarm verification, with counters and a trouble indication to alert maintenance personnel when a detector enters verification 20 times. 7. PAS presignal, meeting NFPA requirements. 8. Rapid manual station reporting (under 3 seconds). 9. Non-alarm points for general (non-fire) control. 10. Periodic detector test, conducted automatically by the software. 11. Self-optimizing pre-alarm for advanced fire warning, which allows each detector to learn its particular environment and set its pre-alarm level to just above normal peaks. 12. Cross zoning with the capability of counting: two detectors in alarm, two software zones in alarm, or one smoke detector and one thermal detector. 13. Walk test, with a check for two detectors set to same address. 14. Control-by-time for non-fire operations, with holiday schedules. 15. Day/night automatic adjustment of detector sensitivity. 16. UL-1076 security monitor points. 17. Provide 25% spare capacity on all cards. 18. Provide an 8-point relay card in the FACP (FACP) and program FACP to send discrete signals to the transmitter. G. The FACP shall be capable of coding notification circuits in temporal pattern (NFPA 72 A ), and California code. H. Central Microprocessor: 1. The microprocessor shall be a state-of-the-art, high speed, device and it shall communicate with, monitor and control all external interfaces. It shall include an EPROM for system program storage, non-volatile memory for building-specific program storage, and a watchdog timer circuit to detect and report microprocessor failure. 2. The Microprocessor shall contain and execute all control-by-event programs for specific action to be taken if an alarm condition is detected by the system. Control-by-event equations shall be held in non-volatile programmable memory, and shall not be lost even if system primary and secondary power failure occurs. 3. The microprocessor shall also provide a real-time clock for time annotation of system displays, printer, and history file. The time-of-day and date shall not be lost if system primary and secondary power supplies fail. The real time clock may also be used to control non-fire functions at programmed time-of-day, day-of-week, and day-of-year. 4. A special program check function shall be provided to detect common operator errors. I. Display: 1. The display shall provide the controls and indicators used by the system operator and may also be used to program system operational parameters. 2. The display shall include status information and custom alphanumeric labels for all intelligent detectors, addressable modules, internal panel circuits, and software zones. 3. The display shall include an 80-character backlit alphanumeric Liquid Crystal Display (LCD). It shall also provide 8 Light-Emitting-Diodes (LEDs), that indicate the status of the following system parameters: AC POWER, FIRE ALARM, PRE-ALARM WARNING, SECURITY ALARM, SUPERVISORY SIGNAL, SYSTEM TROUBLE, DISABLED POINTS and ALARM SILENCED. 4. The display shall include the following operator control switches: ACKNOWLEDGE, ALARM SILENCE, ALARM ACTIVATE (drill), SYSTEM RESET and LAMP TEST Page 12 of 23

13 5. The system shall support an optional battery ammeter/voltmeter display. J. Signaling Line Circuits (SLC): 1. Each SLC interface shall provide power to and communicate with intelligent detectors (ionization, photoelectric or thermal) and intelligent modules (monitor or control). Each SLC shall be NFPA 72 Style 4 (Class B) wiring and shall support T-tapping. T-tapping shall be allowed only with written approval of the DPS Project Manager. 2. The Loop Interface Board (LIB) shall receive analog information from all intelligent detectors to be processed to determine whether normal, alarm, pre-alarm, or trouble conditions exist for each detector. The software shall automatically maintain the detector's desired sensitivity level by adjusting for the effects of environmental factors, including the accumulation of dust in each detector. The analog information shall also be used for automatic detector testing and for the automatic determination of detector maintenance requirements. 3. The detector software shall meet NFPA 72, Chapter 7 requirements and be certified by UL as a calibrated sensitivity test instrument. 4. The detector software shall allow manual or automatic sensitivity adjustment. K. Serial Interfaces: The system shall include serial EIA-232 interfaces. Each interface shall be a means of connecting UL Listed Electronic Data Processing (EDP) peripherals. L. Notification Appliance Circuit (NAC) Module: 1. The Notification Appliance Circuit module shall provide fully supervised Class B (NFPA Style Y) notification circuits. An expansion circuit board shall allow expansion to eight circuits per module. 2. The module shall not affect other module circuits in any way during a short circuit condition. 3. The module shall also provide a momentary switch per circuit that may be used to manually turn the particular circuit on or off or to disable the circuit. 4. Each notification circuit shall include a custom label inserted to identify each circuit s location. Labels shall be created using a standard typewriter or word processor. 5. The notification circuit module shall be provided with removable wiring terminal blocks for ease of installation and service. The terminal strips shall be UL listed for use with up to 14 AWG wire. 6. Each circuit shall be capable of, through system programming, deactivating upon depression of the signal silence switch. M. Control Relay Module: 1. The control relay module shall provide four Form-C auxiliary relay circuits rated at 2 amperes, 28 VDC. An expansion circuit board shall allow expansion to eight Form-C relays per module. 2. Each relay circuit shall be capable of being activated (change in state) by any initiating device or from any combination of initiating devices. 3. The module shall provide a momentary switch per relay circuit that may be used to manually turn the relay ON/OFF or to disable the relay. 4. Each relay circuit shall include a custom label inserted to identify its location. Labels shall be created using a standard typewriter or word processor. The contractor shall provide all labels. 5. The control relay module shall be provided with removable wiring terminal blocks for ease of installation and service. The terminal blocks shall be UL listed for use with up to 14 AWG wire. N. Enclosures: 1. The control panel shall be housed in an UL-listed cabinet suitable for surface or semi-flush mounting. The cabinet and front shall be corrosion protected, given a rust-resistant prime coat, and manufacturer's standard finish. The Owner shall select the color of the cabinet from choices provided by the equipment supplier Page 13 of 23

14 2. The back box and door shall be constructed of steel with provisions for electrical conduit connections into the sides and top. 3. The door shall provide a key lock and shall include a glass or other transparent opening for viewing of all indicators. O. Voice Command Center (VCC): 1. The Voice Command Center (VCC) shall contain equipment required for all audio control, telephone system control, signaling and supervisory functions. This shall include amplifiers, tone generators, digital voice units, a microphone and a main telephone handset. The voice command center shall be an integral part of the fire alarm system. Systems, which require separate, non-integrated voice systems, are not considered suitable substitutes. 2. Function: The voice command center equipment shall perform the following functions: a) Operate as a supervised dual channel emergency voice communication system. b) Provide automatic custom digital recorded voice message and tone generation. c) Provide a hand held microphone with priority push-to-talk switch. d) Provide an all-call switch and indicator to quickly activate all speaker circuits. P. Power Supply: 1. The main power supply for the FACP shall provide a minimum 6.0 amps of available power for the control panel and peripheral devices. 2. Provisions will be made to allow the audio-visual power to be increased as required by adding modular expansion audio-visual power supplies. 3. Positive-Temperature-Coefficient (PTC) thermistors, circuit breakers, or other over-current protection shall be provided on all power outputs. The power supply shall provide an integral battery charger for use with batteries up to 55 AH or may be used with an external battery and charger systems. Battery arrangement may be configured in the field. 4. The main power supply shall continuously monitor all field wires for earth ground conditions, and shall have the following LED indicators: a) Ground Fault LED b) Battery Fail LED c) AC Power Fail LED 5. The main power supply shall operate on 120 VAC, 60 Hz, and shall provide all necessary power for the FACP. The FACP shall be connected to a separate dedicated branch circuit, maximum 20 amperes. This circuit shall be labeled at the main power distribution panel as FIRE ALARM. 6. The main power supply shall provide a battery charger for 24 hours of standby using dual-rate charging techniques for fast battery recharge. 7. The main power supply shall provide a very low frequency sweep earth detect circuit, capable of detecting earth faults. 8. The main power supply shall provide meters to indicate battery voltage and charging current. 9. All circuits shall be power-limited, per 1995 UL864 requirements. Q. Field Charging Power Supply: 1. The FCPS is a device designed for use as either a remote 24-volt power supply or used to power Notification Appliances. 2. The FCPS shall offer up to 6.0 amps (4.0 amps continuous) of regulated 24-volt power. It shall include an integral charger designed to charge 7.0 amp hour batteries and to support 60-hour standby Page 14 of 23

15 3. The Field Charging Power Supply shall have two input triggers. The input trigger shall be a Notification Appliance Circuit (from the FACP) or a relay. Four outputs (two Style Y or Z and two style Y) shall be available for connection to the Notification devices. 4. The FCPS shall include an attractive surface mount back box. 5. The Field Charging Power Supply shall include the ability to delay the AC fail delay per 1993 NFPA requirements. 6. The FCPS include power limited circuitry, per 1995 UL standards. R. System Circuit Supervision: 1. Each FACP node shall supervise all circuits to intelligent devices, annunciators and peripheral equipment and annunciate loss of communications with these devices. The FACP CPU shall continuously scan the above devices for proper system operation and upon loss of response from a device shall sound an audible trouble, indicate which device or devices are not responding and print the information on the printer. 2. Sprinkler system valves, standpipe control valves, PIV, and main gate valves shall be supervised for off-normal position. 3. All notification circuits shall be supervised for opens and shorts. S. Audio Amplifiers: 1. The audio amplifiers will provide audio power for distribution to the speaker circuits. 2. Multiple audio amplifiers may be mounted in the FACP using additional cabinets if necessary. Each FACP shall have a primary and a back-up amplifier. 3. The audio amplifiers shall include an integral power supply, and shall provide the following controls and indicators: a) Normal Audio Level LED b) Incorrect Audio Level LED c) Brownout LED d) Battery Trouble LED e) Amplifier Trouble LED f) Audio Amplifier Gain Adjust 4. Adjustment of the correct audio level for the amplifier shall not require any special tools or test equipment. 5. All terminal blocks for the connection of field wiring shall have a removable plug-in and be hardwired to allow for ease of field wire installation in a cabinet or at a remote location. 6. The amplifier shall include audio input and amplified output supervision, backup input, and automatic switchover to back up (if primary amplifier should fail). T. Specific System Operations: 1. Smoke Detector Sensitivity Adjust: A means shall be provided for adjusting the sensitivity of any or all addressable intelligent detectors in the system from the system keypad. Sensitivity range shall be within the allowed UL window and have a minimum of 7 levels. 2. Alarm Verification: Each of the intelligent addressable smoke detectors in the system may be independently selected and enabled to be an alarm verified detector. The alarm verification delay shall be programmable from 5 to 30 seconds and each detector shall be able to be selected for verification. The FACP shall keep a count of the number of times that each detector has entered the verification cycle. These counters may be displayed and reset by the proper operator commands Page 15 of 23

16 3. Point Disable: Any addressable device or conventional circuit in the system may be enabled or disabled through the system keypad. 4. Point Read: The system shall be able to display or print the following point status diagnostic functions: a) Device status b) Device type c) Custom device label d) View analog detector values e) Device zone assignments f) All program parameters 5. System Status Reports: Upon command from an operator of the system, a status report will be generated and printed, listing all system status. 6. System History Recording and Reporting: The FACP shall contain a history buffer that will be capable of storing up to 1000 events. Up to 200 events shall be dedicated to alarm and the remaining events are general purpose. Each of these activations will be stored and time and date stamped with the actual time of the activation. The contents of the history buffer may be manually reviewed, one event at a time, or printed in its entirety. The history buffer shall use nonvolatile memory. Systems that use volatile memory for history storage are not acceptable substitutes. 7. Automatic Detector Maintenance Alert: The FACP shall automatically interrogate each intelligent detector and shall analyze the detector responses over a period of time. If any intelligent detector in the system responds with a reading that is above or below normal limits, then the system will enter the trouble mode, and the particular detector will be annunciated on the system display, and printed on the optional printer. This feature shall in no way inhibit the receipt of alarm conditions in the system, nor shall it require any special hardware, special tools or computer expertise to perform. 8. The FACP shall include a walk test feature. It shall include the ability to test initiating device circuits and notification appliance circuits from the field without returning to the panel to reset the system. Operation shall be as follows: 9. Alarming an initiating device shall activate programmed outputs, which are selected to participate in walk test, for 3 seconds. 10. Introducing a trouble into the initiating device shall activate the programmed outputs for 8 seconds. 11. Walk test shall be selectable on a per device/circuit basis. All devices and circuits which are not selected for walk test shall continue to provide fire protection and if an alarm is detected, will exit walk test and activate all programmed alarm functions. 12. All devices tested in walk test shall be recorded in the history buffer. U. Waterflow Operation: 1. An alarm from a water flow detection device shall activate the appropriate alarm message on the 80-character display, turn on all programmed notification appliance circuits and shall not be affected by the signal silence switch. 2. An alarm from a water flow detection device shall activate the exterior horn/strobe. The exterior horn/strobe shall be electrically supervised. V. Supervisory Operation: An alarm from a supervisory device shall cause the appropriate indication on the 80 character display, light a common supervisory LED, but will not cause the system to enter the trouble mode Page 16 of 23

SECTION 16700 FIRE ALARM SYSTEM

SECTION 16700 FIRE ALARM SYSTEM SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

INTRUSION DETECTION SYSTEM Section 281600

INTRUSION DETECTION SYSTEM Section 281600 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS

More information

FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM

FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM PART 1.0 - GENERAL 1.1 DESCRIPTION: A. This section of the specifications includes the furnishing, installation, and connection of a multiprocessor controlled,

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

Fire Alarm Systems Permit Packet. City of Greer Fire Department

Fire Alarm Systems Permit Packet. City of Greer Fire Department Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 50 - POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 50 - POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 50 - POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines

More information

A. This Standard outlines the requirements for an addressable fire detection and alarm system.

A. This Standard outlines the requirements for an addressable fire detection and alarm system. 1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14 City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM

SECTION 28 31 00 FIRE DETECTION AND ALARM SECTION 28 31 00 PART 1 - GENERAL 1.1 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a complete coordinated

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC 1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

FIRE ALARM SYSTEM Section 16750 Page 1

FIRE ALARM SYSTEM Section 16750 Page 1 FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract

More information

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating

More information

JULY 2013 UCB STANDARDS 16720-1

JULY 2013 UCB STANDARDS 16720-1 SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying

More information

Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions. EPROM Electrically Programmable Read Only Memory

Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions. EPROM Electrically Programmable Read Only Memory Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions EPROM Electrically Programmable Read Only Memory EVAC Emergency Visual Audio Control FACP Fire Alarm Control Panel HVAC

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE

More information

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION 16610 FIRE DETECTION AND ALARM SYSTEM

SECTION 16610 FIRE DETECTION AND ALARM SYSTEM SECTION 16610 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

FIRE ALARM APPLICATION

FIRE ALARM APPLICATION FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm System Monitoring - CAN/ULC-S561-03 Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material

More information

SECTION 16721 MULTI-FIRE ALARM SYSTEM

SECTION 16721 MULTI-FIRE ALARM SYSTEM PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.

More information

SECTION 16620 FIRE ALARM SYSTEM

SECTION 16620 FIRE ALARM SYSTEM SECTION 16620 PART 1 GENERAL FIRE ALARM SYSTEM 1.01 SUMMARY A. Work included: Labor, materials and equipment necessary to complete the installation required for the item specified under this Division,

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

The Benefits of ADDRESSABLE Fire Alarm Technology

The Benefits of ADDRESSABLE Fire Alarm Technology The Benefits of ADDRESSABLE Fire Alarm Technology NOTICE: If you were born after 1990 or if you lived through the 60 s and can t remember what happened since, you may be surprised to learn that fire alarm

More information

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2017-12NDS Network Fire Alarm Control Unit offers modular components to meet a

More information

Life Alarm Fire Alarm Controls

Life Alarm Fire Alarm Controls FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six

More information

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the

More information

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems.

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for Fire Detection and Alarm. B. The design guidelines contained

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00 SECTION 28 31 00 FIRE DETECTION AND ALARM GENERAL This section deals with the fire alarm system, including the control panel and integral equipment, wiring and circuitry, initiating devices, indicating

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms.

A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms. SECTION 283111 - PART 1 - GENERAL 1.1 SUMMARY A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms. 1.2 GENERAL REQUIREMENTS

More information

A. Product Data: For each type of product, including furnished options and accessories.

A. Product Data: For each type of product, including furnished options and accessories. SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Non-system

More information

The Mission Critical Fire Protection Experts

The Mission Critical Fire Protection Experts The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure

More information

B. Equipment shall be furnished and installed as specified. No substitutions will be allowed.

B. Equipment shall be furnished and installed as specified. No substitutions will be allowed. CLASSROOM SOUNDFIELD DISTRIBUTION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information