Looking for low voltage transformer solutions?
|
|
- Joseph McDowell
- 7 years ago
- Views:
Transcription
1 Looking for low voltage transformer solutions? Select the best from the industry leader. Square D Low Voltage Dry Type Transformers Make the most of your energy SM
2 Special Transformers This application guide is designed to provide a handy pocket reference for those who need to select and apply dry-type transformers in the course of their vocation. The information is also of use in all electrical work. Because it is a pocket guide, the information is brief and abbreviated. Schneider Electric will build most special dry type transformers your application requires. Your Square D field sales representatives, or transformer headquarters, will be happy to assist you in selecting the proper transformer. Data required to help you is: kva or load amperage, primary voltage, secondary or load voltage, phase, frequency, taps, insulation class and temperature rise, type of enclosure, sound level, physical limitations accessories required. Transformers available from your distributor s stock Single Phase s Voltage: 2 x 480-1/2 Ratings: kVA Voltage: 480-1/2 Ratings: 3-kVA Voltage: 600-1/2 Ratings: kVA Three Phase s Voltage: Ratings: Voltage: Ratings: Voltage: Ratings: 480r-280Y/1 3-0kVA 480r-2r with 1V center trap kVA 600r-280Y/1 6-kVA Buck and Boost (Single Phase) Voltage: 1 x 2-12/24 or 16/32; 2 x /48 Ratings:.050-3kVA Full Current in Amperes Single Phase Low Voltage Dry Type Transformers Rated Line-to-Line Voltage kva Formula: Single Phase kva Volts x Amperes/0 Three Phase Low Voltage Dry Type Transformers Rated Line-to-Line Voltage kva Formula: Three Phase kva Volts x Amperes x 1.73/0 2 3
3 The following tables have been reproduced through the courtesy of the National Fire Protection Association from the National Electric Code 08 Edition. Table Allowable Amapacities of Insulated Conductors Rated 0 Through 00 Volts, 60 C Through 90 C (1 F Through 194 F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of C (86 F) Size Temperature Rating of Conductor (See Table (A).) Size AWG or kemil * 12* 10* /0 2/0 3/0 4/ Ambient Temp. ( C) 60 C (1 F) TW, UF C (167 F) RHW, THW, THWN, USE, ZW Copper C (194 F) TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THW-2, THWN-2, USE-2, XHH, XHHW-2, ZW C (1 F) TW, UF C (167 F) RHW, THW, THWN, USE 90 C (194 F) TBS, SA, SIS, THHN, THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW-2, ZW-2 Aluminum or Copper-Clad Aluminum Correction Factors For ambient temperatures other than C (86 F), multiply the allowable ampacities shown above by the appropriate factor shown below AWG or kemil 12* 10* /0 2/0 3/0 4/ Ambient Temp. ( F) * See 2.4(D) 08 NEC. Table 450.3(B) Maximum Rating or Setting of Overcurrent Protection for Transformers 600 Volts and Less (as a Percentage of Transformer-Rated Current) Protection Method Primary only protection Primary and secondary protection Currents of or More 1% (See Note 1.) 0% (See Note 3.) Primary Protection Currents Less Than Currents Less Than 2 Amperes Secondary Protection (See Note 2.) Currents of or More Currents Less Than 167% 0% Not required Not required 0% (See Note 3.) 0% (See Note 3.) 1% (See Note 1.) NOTES: 1. Where 1 percent of this current does not correspond to a standard rating of 167% a fuse or nonadjustable circuit breaker, a higher rating that does not exceed the next higher standard rating shall be permitted. 2. Where secondary overcurrent protection is required, the secondary overcurrent device shall be permitted to consist of not more than six circuit breakers or six sets of fuses grouped in one location. Where multiple overcurrent devices are utilized, the total of all the device ratings shall not exceed the allowed value of a single overcurrent device. If both breakers and fuses are utilized as the overcurrent device, the total of the device ratings shall not exceed that allowed for fuses. 3. A transformer equipped with coordinated thermal overload protection by the manufacturer and arranged to interrupt the primary current shall be permitted to have primary overcurrent protection rated or set at a current value that is not more than six times the rated current of the transformer for transformers having not more than 6 percent impedance and not more than four times the rated current of the transformer for transformers having more than 6 percent but not more than 10 percent impedance. NEMA TP 1-02 NEMA Class I Efficiency Levels for Dry Type Distribution Transformers Low Voltage Reference Condition: C and 35% Single Phase Three Phase kva % Efficiency kva % Efficiency Sound Levels Square D Dry Type Transformers are the quietest available, whether standard or special sound level limits are ordered. Testing is done in accordance with NEMA standards. Sound Levels 600 Volts and Below NEMA Standard Sound kva Levels 09 db db db db 0 60 db db db NOTE: Lower sound levels than those shown above are available at a slight additional charge. 4 5
4 Buck and Boost The nameplate rating on buck and boost transformers indicates the load they will handle as an isolation transformer. (Pri. 1 x 2, Sec. 12/24*, Ex.: A 1kVA buck and boost will reduce 1 or 2V to 12 or 24V and be able to carry a continuous load of 1kVA.) The majority of buck and boost transformers sold, however, are used to boost 8V to either 2V or 2V, or buck these voltages down to 8V. To use these transformers in this way, the primary and secondary windings are connected to form an auto transformer as follows: Single Phase Connect H2 to H3 X1 to H4 X2 to X3 Connect 8V to H1 and H4-X1 Connect 2V or 2V to H1 and X4 Buck/Boost Secondary kva Capacity /24 10 x nameplate rating / x nameplate rating Three Phase, Open Delta Power-s Only (Use 2 s) Connect On each unit X3 to X2 X1 to H4 H3 to H2 Then connect H1 s from each unit. Connect 8V to X1-H4, H1-H1, H4-X1 Connect 2V or 2V to X4, H1-H1, X4 X4 H1 H2 H3 H4 X1 X2 X3 X4 2 V or 2 V NOTE: This connection for power loads only. Three phase lighting loads require (3) transformers and source neutral must be carried through to load. X3 X2 X1 H4 H3 H2 H1 H1 H2 H3 H4 X1 X2 X3 X4 2 V 2 V Single phase connections Note: Non-standard ratings increase to next larger standard. Single Phase 2 x 480 to 1/2V Primary Connections 2V Service 2 V Line H1 H3 H2 H4 Connect H1 & H3 Connect H2 & H4 Connect lines to H1-H3 & H2-H4 Secondary Connections 1V 2-Wire Circuit X1 X2 X3 1 V Connect X1 & X3 Connect X2 & X4 Connect to X1-X3 & X2-X4 X4 1/2V 3-Wire Circuit 480V Service 480 V Line H1 H3 H2 H4 Connect H3 & H2 Connect H1 & H4 Connect lines to H1 & H4 2V 2-Wire Circuit 2 V Connect X3 & X2 Connect to X1 & X4 2 V or 2 V Three Phase kva Rating Buck/Boost Secondary kva Capacity /24 nameplate kva x 1.73 x /32 nameplate kva x 1.73 x 7.5 NOTE: When used as an auto transformer, the buck and boost unit will carry greater loads than shown on the nameplate. For other uses and connections, ask your distributor for a copy of the Product Data Bulletin (7414SP9901) or a Buck-Boost Slide Rule or use the online calculator. Visit and search for Buck and Boost. Check local codes relative to the use of auto transformers before applying buck and boost transformers. 1 V 1 V 2 V The junction of X3-X2 may be used as the neutral of a 3-wire system and must be bonded to the nearest earth ground per NEC requirements. 6 7
5 Note: Non-standard ratings increase to next larger standard. The following diagrams show special ways that standard 2 x 480-1/2 single phase transformers can be connected for special applications. LV LV Single Unit Connected 2 V H1 H3 H2 H4 as Auto Transformer 2V to 480V kva Capacity 480 V 2 x Nameplate kva HV HV kva 2 Single Unit Connected as Auto Transformer 480V to 600V kva Capacity 5 x Nameplate kva kva 5 kva Rating of Transformer Required kva Rating of Transformer Required Two unit transformers connected in Hoppy Hookup for single phase lighting and single phase power loads from three phase supply. This connection allows changeover of existing single phase service to three phase service without changing existing lighting panels or secondary neutrals. The neutral current will be the same as with the original single phase service rather than increasing by the factor of 1.73 ( 3 ). H1 H3 H2 H4 H1 H3 H2 H4 1 V 1 V * NOTE: The primary common current will be the in the other two lines. 3 x the current For 480V Primary Connect H2 to H3 in Each Unit For 2V Primary Connect H3 to H1 and H2 to H4 in Each Unit Secondary kva Capacity Total Nameplate kva of Both Transformers * Secondary voltage is 1/8V, 3-wire only. NOT 1/2V, 3-wire. Three Phase Connections Note: For non-standard kva ratings increase to next larger standard kva, using single phase 2 x 480 to 1/2. Three Units Connected Delta-Wye, for Three Phase Operation H1 H3 H2 H4 H1 H3 H2 H4 H1 H3 H2 H4 Neutral For 480V Delta Primary Connect H3 to H2 in For 2V Delta Primary Connect H3 to H1 and H2 to H4 in For 416Y/2V Secondary Connect X3 to X2 in For 8Y/1V Secondary Connect X3 to X1 and X2 to X4 in Three Phase kva Capacity Total kva of Three Units Three Units Connected Delta-Delta, for Three Phase Operation H1 H3 H2 H4 H1 H3 H2 H4 H1 H3 H2 H4 For 480V Delta Primary Connect H3 to H2 in For 2V Delta Primary Connect H3 to H1 and H2 to H4 in For 2V Delta Secondary Connect X3 to X2 in For 1V Delta Secondary Connect X3 to X1 and X2 to X4 in Three Phase kva Capacity Total kva of Three Units Two Units Connected Open-Delta, for Three Phase Operation H1 H3 H2 H4 H1 H3 H2 H4 For 480V Delta Primary Connect H3 to H2 in For 2V Delta Primary Connect H3 to H1 and H2 to H4 in For 2V Delta Secondary Connect X3 to X2 in For 1V Delta Secondary Connect X3 to X1 and X2 to X4 in Three Phase kva Capacity Total kva of Two Units x 0.86 kva
6 Note: For non-standard kva ratings increase to next larger standard kva, using single phase 2 x 480 to 1/2. Two Units Connected as Open Delta Auto Transformer for Three Phase Operation for 2480; 4802 Three Phase kva Capacity (Total kva of Both Units x 2) x.86 HV HV HV H1 H3 H2 H4 H4 H2 H3 H1 X4 X2 X3 X1 LV LV LV kva 3.44 Two Units Connected as Open-Delta Auto Transformer for Three Phase Operation for ; ; ; kva Capacity ; kva 8.6 kva Capacity ; kva 6.88 The following diagram shows special ways that standard 600-1/2 single phase transformers can be connected for special applications. Two Units Connected as Open-Delta Auto Transformer for Three Phase Operation for 5480 or kva kva
7 Energy Efficient Transformers Square D general purpose and lighting transformers are known as the industry standard. Harmonic Mitigating and Non-Linear Transformers Schneider Electric expertise in power management is evident with the broad line of transformers for non-linear loads. Control Power Transformers Schneider Electric s complete line of control power transformers offer a variety of options for panel builders and OEMs. Schneider Electric North American Operating Division 1415 S. Roselle Road Palatine, IL Tel: Fax: HO9501R6/ Schneider Electric. All rights reserved.
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationBuck - Boost Transformers
Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single
More informationElectrical Design Training Class Ampacity WSDOT Winter 2008 BZA
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions
More informationConductor Sizing and the National Electrical Code
Conductor Sizing and the National Electrical Code The National Electrical Code requirements for conductor sizing and overcurrent protection have always been confusing and complex. Factors that must be
More informationHPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More informationCHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
More informationBRANCH CIRCUIT AND FEEDER REQUIREMENTS
CHAPTER 36 BRANCH CIRCUIT AND FEEDER REQUIREMENTS SECTION E3601 GENERAL E3601.1 Scope. This chapter covers branch circuits and feeders and specifies the minimum required branch circuits, the allowable
More informationTRANSFORMERS. Unit 14 OBJECTIVES
Unit 14 TRANSFORMERS OBJECTIVES After studying this unit, the student will be able to state the purpose of a transformer. explain the principle of mutual induction. determine the output voltage of a transformer
More informationLow Voltage Transformer Through-Fault Protection: A System Approach
Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and
More informationJEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual
JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual Revised on February 15, 2012 Table of Contents I. Introduction... 2 II. Choosing the Proper Transformer... 2 III. Rapid Selector Charts...
More informationDistribution Dry Type Transformers
Distribution Dry Type s Sentron Power Centers Bolt-in Breaker Option The same economical space saving package, NEMA 3R rated enclosure, and UL listed transformer of the original Sentron Power Center but
More informationMotor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
More informationHistory and Overview. Manual Motor Protectors & Combination Motor Controllers
Manual Motor Protectors & Application te May 2005 Supersedes, April 2004 Applications: Manual Motor Starter Manual Motor Disconnect IEC Circuit Breaker (European Market) NEC Group Installation Motor Starter
More information6 Buck Boost Transformers
6 uck oost Transformers uck-oost transformers are small, single phase, dry type distribution transformers designed and shipped as insulating/isolating transformers. They have a dual voltage primary and
More informationDepartment of Labor and Industry Electrical Licensing
Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants
More informationCONDUCTOR SHORT-CIRCUIT PROTECTION
CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating
More informationElectrical Drawings - Table of Contents
Electrical Drawings - Table of Contents E1.0 Lighting Plan E1.1 Power Plan E2.0 Electrical Specifications E2.1 Electrical Specifications E3.0 Panel Schedule E3.1 Load Summary 1 2 1 Panel Schedule LP1
More informationRecommended Practices for Designing and Installing Copper Building Wire Systems
Recommended Practices for Designing and Installing Copper Building Wire Systems CDA - CWIS Committee December 3, 2013 Developed by the Copper Development Association Inc. www.copper.org Foreword This document
More informationACME ELECTRIC CORPORATION PDPD-01
4815 West Fifth Street Lumberton, NC 28358 (910) 738-1121 Inside NC (800) 334-5214 Outside NC (910) 739-0024 Fax www.acmepowerdist.com ACME ELECTRIC CORPORATION PDPD-01 ATD-101-1001 Revised-02/ 06 Printed
More information3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
More informationSimple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
More information600 Volt Class Transformers
Transformers ISO 9001:2008 REGISTERED 11 11 Table of Contents - Transformers Page Full Load Current Tables... 12 General Information, Standards, Testing... 13 Selection and Application Considerations...
More information2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
More informationUNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT 06387 Phone: 860.774.4812 Fax: 860.774.7330 www.cmcorporation.
UNDERSTANDING UNDERSTANDING NFPA 79 By Ned Lloyd and Mike Levesque NFPA-79 is the electrical standard that has been developed by the National Fire Protection Association (NFPA) and is intended to minimize
More informationMETER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
More informationSingle Phase Three Phase Single Phase Export Model Transformers Single Phase Buck and Boost Transformers Stainless Steel Enclosed Transformers
Transformers Selection Guide Description Page Three Phase Single Phase Aluminum, Copper, 150 Degree Rise Aluminum, Copper, 115 Degree Rise Aluminum, Copper, 80 Degree Rise Epoxy Encapsulated Aluminum,
More informationFirst Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897
OCA #230100 First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 AN ORDINANCE AMENDING SECTIONS 4.A.080, 4.1.020, 4.1.110, 4.2.010, 4.2.070, 4.2.125, 4.2.170, 4.2.175 AND 4.2.220;
More informationCorner-Grounded Delta (Grounded B Phase) Systems
Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems
More informationData Bulletin Variable Frequency Drives and Short-Circuit Current Ratings
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is
More informationGuidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
More informationAMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationNEC Class 2 Power Circuits and Power Supplies
NEC Class 2 Power Circuits and Power Supplies Abstract: The NEC (National Electrical Code) is a North American standard, which can be regarded as a law in most of the North American states. Among others,
More informationBranch Circuit Calculations
Branch Circuit Calculations by Gerald Newton October 31, 1999 1. A 20 ampere, 120 volt, 2-wire branch circuit has a maximum load capacity of watts or volt-amperes. Reference: Using the following for Single
More informationGENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
More informationEast Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
More informationWhite Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
More informationThe National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
More informationUL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved.
UL 508A Industrial Control Panels Power Distribution and Control Lunch & Learn Training 2002 Eaton Corporation. All rights reserved. Agenda Who is UL and what role do they play? What is the UL 508A Standard?
More informationVoltage Drop (Single-Phase)
Voltage Drop (Single-Phase) To Find: To Find Voltage Drop Formula: 2 x K x L x I V.D. = ------------------- C.M. Variables: C.M. = Circular Mill Area (Chapter 9, Table 8) To Find Voltage Drop Percentage
More informationDistribution Dry Type Transformers
8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg
More informationApplication Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
More informationSERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp
SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS
More informationDirection of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
More informationMOTOR PROTECTION AGAINST SINGLE-PHASING
THE SINGLE-PHASE DILEMMA: FACT OR FICTION PROTECTION AGAINST SINGLE-PHASING Bulletin PSP The Single-Phasing Issue: Fact or Fiction Overview Before discussing SINGLE-PHASING, let s take a look at some of
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationEngineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
More informationMODEL 5060 USER S GUIDE ELECTRICALC PRO. Set. Stor. Rcl. Off. On/C #THHN #THW VD% Length. DEFuse. ParSz. kilo. WireSz. Grnd. HPth. Watts. Volts.
USER S GUIDE ELECTRICALC PRO MODEL 5060 3O 60 Cu VD WIRE SIZE 125% CONSTRUCTION MASTER ELECTRICALC PRO Cond Type Off On/C CondSz #THW #XHHW #THHN VD% Starter SEFuse InsTrip M Type Wire Res HPmotor DEFuse
More informationThe following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
More informationLine Loss WSDOT Winter 2008 BZA
Electrical Design Training Class Line Loss WSDOT Winter 2008 BZA Presented by: Keith Calais 1 OHM S LAW P = Watts (Power) I = CURRENT (AMPERES) R = RESISTANCE (OHMS) E = ELECTROMOTIVE FORCE (VOLTS) P =
More informationMotor Circuit Protection Tables
NEC Article 40 and Tables Explanation Columns & 2 Motor horsepower ratings are listed in Column. Full load amps from Tables 40.247 through 40.250 are provided in Column 2. Column Various fuse types are
More informationApplication of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
More informationVariable Transformers Product Design & Engineering Data
Variable Transformers Product Design & Engineering Data Product Design & Engineering Data Type 1010B Cutaway General Information STACO ENERGY PRODUCTS CO. is a leading manufacturer of variable transformers,
More informationElectrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
More informationMultiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained
Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase
More informationInstruction Manual. A DIVISION OF A. O. SMITH CORPORATION RENTON, WASHINGTON www.hotwater.com
Instruction Manual COMMERCIAL ELECTRIC WATER HEATERS MODELS DSE-5 THRU DSE-120 INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY A DIVISION OF A. O. SMITH CORPORATION RENTON, WASHINGTON
More informationHIGH VOLTAGE CALCULATIONS / EVALUATIONS. West Virginia Office of Miners Health, Safety & Training
HIGH VOLTAGE CALCULATIONS / EVALUATIONS West Virginia Office of Miners Health, Safety & Training Helping You To Work More Safely In The Mining Industry DISCLAIMER The West Virginia Office of Miners Health,
More informationThree Phase Transformers
Three Phase Transformers ontents Three Phase - General Purpose... 26 Three Phase - General Purpose Scott ed... 30 Three Phase - dditional ombinations vailable... 31 Three Phase - ion Diagrams... 32 Series
More information101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module
More informationMini Power-Zone Unit Substation
Catalog 7440CT0901 2009 Class 7440 CONTENTS Description............................................. Page Product Description...........................................2 General Information...........................................3
More informationSOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
More informationUsing Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A.
WHITEPAPER Using Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A. January 1 st, 2014 Sources: UL508A: UL Standard for Safety for
More informationDC disconnects for solar photovoltaic installations. Connecting the. power of the sun
DC disconnects for solar photovoltaic installations Connecting the power of the sun Solar energy is heating up Interest in renewable energy sources has never been greater, and the fastest growing of these
More informationTips for connecting 24-volt power
Digital Designer s Guide Application NoteAN0604D Revision B Tips for connecting 24-volt power This application note covers choosing a transformer and connecting 24 volt AC power to a KMC Controls DDC controller.
More informationBussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
More informationConnecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations
Connecting the Power of the Sun DC Disconnects for Solar Photovoltaic Installations DC disconnects for solar photovoltaic installations Solar energy is heating up Interest in renewable energy sources has
More informationLEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
More informationCity of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
More informationThe Service Entrance. Technical Terms Drip loop Insulator Meter Meter enclosure
This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. 10 The Entrance Objectives Information in this chapter will enable you to: List the components
More informationENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613
ENGINEERING REPORT XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613 PERFORMED BY: MIDWEST ELECTRICAL CONSULTANTS, INC 18055 UPLAND DRIVE TINLEY PARK, ILLINOIS 60487 (708) 444-0001 fax: 444-0003
More informationMTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
More informationUL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL
UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller
More informationHow To Wire A Three Phase, Single Phase, Wye Transformer
Three-Phase Transformers When more power is needed - three transformers can be tied together. This is called three-phase. Here s a simple way of comparing single-phase to threephase power. Single-Phase
More informationBASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
More informationCITY OF LOS ANGELES CALIFORNIA
BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI
More information2.2 NEMA Premium and E3 Super Efficient Transformers NEMA Premium Efficient Transformers... E3 Super Efficient Transformers...
Dry- Transformer Family.1 NEMA TP-1 Energy-Efficient Transformers Product Description....................................... Application Description.................................... Features, Benefits
More informationAC Module Installation Guide Content
AC Module Installation Guide Content for ET-P660250AC May 9, 2012 2011-2012 ET Solar Group All Rights Reserved. No part of this publication may be reused in any manner nor in any form or format without
More informationPower Management Module 2. Installation
Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...
More informationRotary Phase Converters
FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More informationmisconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
More information3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationLoading Considerations When Paralleling Transformers
Application Guide 7400DB0701 02/2007 Nashville, TN, USA Loading Considerations When Paralleling Transformers Class 7400 Retain for future use. Introduction Principles of Paralleling This application guide
More information21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
More informationNational Craft Assessment and Certification Program S P E C I F I C A T I O N S
National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret
More informationProduct Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
More informationTransformer Questions & Answers
Transformer Questions & Answers. What is a transformer and how does it work? A transformer is an electrical apparatus designed to convert alternating current from one voltage to another. It can be designed
More informationINTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS
CHAPTER 3 WIRING METHODS AND MATERIALS INTRODUCTION TO CHAPTER 3 WIRING METHODS AND MATERIALS Chapter 2 provided the general rules for wiring and protection of conductors, and was primarily concerned with
More information12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST
12VDC MAGNETIC ED DIMMABE POER SUPPIES SPEC SEET DIGEST TM-30-DIM TM-50-DIM T-60-DIM TM100-DIM TM200-DIM TM300-DIM iring Diagram for TM-50-DIM and TM-100-DIM ED 12VDC MAGNETIC DIMMABE 30 POER SUPPY Smallest
More information12V Dimmable Driver EL-TMDRVR
Elemental LED, LLC website: elementalled.com 11 9 5 P a r k A v e., S u i t e 2 11 Emeryville, CA 94608 toll free 877.564.5051 fax 510.740.4457 12V Dimmable Driver EL-TMDRVR ETL Listed #4001928 CSA Listed
More informationRule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
More informationAC and DC Drive System Installation Information
Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS
More informationThermal-Magnetic / Magnetic Only Molded Case Circuit Breakers
Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog 2004 Class 601 CONTENTS Description..............................................Page INTRODUCTION.............................................
More informationMini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection
Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional
More informationIndustrial Control Transformers
Industrial Control Transformers Sizing...158 Selection Chart...159 SBE 55 C ise, Copper, Encapsulated, 50 VA - 1000 VA... 161 5 SBE Accessories... 165 SBE 55 C ise, Copper Open Style, 1500 VA - 5000 VA...
More informationCURRENT TRANSFORMERS INSTALLATION GUIDE
CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright
More informationSIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
More informationElectrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
More information