C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Continuity of Protective Conductors
|
|
- Archibald Knight
- 7 years ago
- Views:
Transcription
1 C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Continuity of Protective Conductors 1
2 Outcomes of this Session State the requirements which need to be considered for protective conductors in terms of earthing conductors, protective bonding conductors and circuit protective conductors describe the need for, and methods of verifying, the continuity of protective conductors state the relationship between conductor length, cross-sectional area and resistance state the effect of temperature on a conductor state the effect on measured resistance when cables are connected in parallel describe the need for, and methods of, verifying the continuity of ring final circuit conductors explain how the results of the tests should be analysed.
3 Continuity testing All protective and bonding conductors must be tested to ensure that they are electrically continuous, electrically safe and correctly connected. Prior to the testing of continuity in either radial circuits or ring final circuits, you must check three things: 1. That the instrument has batteries that are adequate for the task. They must be replaced regularly to maintain the current we require. 2. The connecting leads and the instrument must be nulled/zeroed. 3. A current calibration certificate or a current record of the accuracy of the test instrument.
4 Continuity of protective conductors
5 Continuity of protective conductors This test is carried out to ensure that the protective conductor links together all exposed conductive parts to the main earthing terminal (MET). A circuit protective conductor (cpc) must be present at all points in the wiring system ( ) In a ring final circuit, the cpc must also be wired in a RING configuration!
6 Continuity of protective conductors Firstly, it is to ensure that any earthing system is a continuous and a low resistance path to allow the passage of fault currents of sufficient magnitude to operate the protective device during fault conditions within the required disconnection time. Secondly, confirmation of the zero potential between metal parts, both extraneous and exposed-conductive-parts, within an installation to reduce the effects of electric shock for the user of the electrical installation. Thirdly, that the conductors, including all line and neutral conductors, are connected in the correct sequence for safety and for operational purposes.
7 Continuity of protective conductors The GN3 recommended maximum resistance between accessible exposed conductive parts should be 0.05Ω. (p.35 GN3)
8
9
10
11 Parallel Paths The continuity test(s) test must be carried out prior to the connection of any supplementary bonding conductor or main bonding conductor. If there are either supplementary bonding conductors or main bonding conductors connected, then you may not be testing just the circuit protective conductor, you may also be testing a parallel combination of earthing conductors. This will lead to a different readings.
12 Continuity Testing of Radial Circuits Regulation requires testing for continuity. As far as the continuity test is concerned, the earthing conductor, the main bonding conductors, the supplementary bonding conductors and the circuit protective conductors must all be tested. There are two methods for testing the continuity of protective conductors. These are called Method 1 and Method 2. Method 1 (R1 + R2) is generally used for circuits. Method 2 (long wander lead) is generally used for single conductors, such as bonding conductors.
13 Method 1 Now for the test itself: Where necessary, first prove that the installation or circuit is dead. If the circuits that are supplied from the same distribution board cannot be made safe (i.e. dead) then you should not carry out this test. Connect the line conductor to the protective conductor at the distribution switchboard using a temporary test link. Test between the line and circuit protective conductor at the remote appliance. The measurement of (R 1 +R 2 ) should be recorded in Ohms (Ω). You don t need to test every point, just the furthest points. If there is a need (although unlikely) to determine the resistance of the circuit protective conductor R 2 as a value then the following can be used; R 2 = R R x A 1 A 1 + A 2 OR R 2 = (R 1 +R 2 ) x CSA line CSA line + CSA cpc
14 Readings From Test Instruments Regulation requires that we compare our results with relevant criteria. It is unacceptable to simply just record a result! It needs to be reasonable! In different circumstances, protective devices must operate within set times. A higher fault current may be needed to make the protective device operate in 0.2 s as opposed to 5 s. The cpc must be capable of withstanding the rise in temperature, due to the fault current for the set time. (Time/Current Characteristics). Current increase = Temperature increase. Will the resistance reading of the continuity test allow you to make a reasonable judgement, in accordance with BS 7671, about the time it takes to clear the fault? Can you guarantee the cpc will not open circuit before the protective device operates? If this last question can be answered with a YES, then the results will be acceptable.
15 What happens if the test is unsatisfactory? First find the type of fault. Open circuit on a cpc A cable could have been cut by another person A nail could have split the cpc The connections are not tightened up adequately and the cpc could have worked free. Borrowed cpc This could happen if the electrician has used a cpc from another circuit to provide an earth for a circuit. This is not acceptable! Borrowed neutral This is an all too common fault when electricians take a neutral from one circuit to give to another circuit. This breaches Regulation and is extremely dangerous practice!
16 Continuity of ring final circuit conductors This test is carried out to verify the continuity of the line, neutral and protective conductors and correct wiring of every ring final circuit. The test results show if the ring has been broken or interconnected to create an apparently continuous ring circuit which is in fact broken or connected as a figure of eight configuration. (GN ) End of chapter 4a
Polarity. Electrical Quals 2007 1
Polarity Electrical Quals 2007 1 Polarity testing Introduction The polarity test is the 8th test in the sequence. Some people will think of it as the 4th test, (which to a certain extent they are correct).
More informationDOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
More informationPROTECTION AGAINST ELECTRIC SHOCK by John Ware
16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created
More informationCHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
More informationBy Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.
16 Operation of portable generators Operation of portable generators By Mark Coles This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.
More informationELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
More informationchapter8 Testing and commissioning Unit 2 outcome 2
Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.
More informationELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE
More informationA Guide to 17th Edition Testing
Seaward, Bracken Hill, South West Industrial Estate, Peterlee, County Durham, SR8 2SW United Kingdom Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227 Email: sales@seaward.co.uk Web: www.seaward.co.uk
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationCSA Z32 TESTING GUIDELINE AND PROCEDURES
PO Box 20020 Red Deer, AB T4N 6X5 Phone: 403.986.2939 Web: www.908eng.com July 9, 2012 CSA Z32 TESTING GUIDELINE AND PROCEDURES This document is intended to outline the various tests, procedures and preparations
More informationElectrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
More informationPontyclun Electrotechnical Training Ltd. (P.E.T. Ltd.)
Pontyclun Electrotechnical Training Ltd. (P.E.T. Ltd.) Our highly-skilled and knowledgeable staff boast extensive industry experience as well relevant teaching qualifications. We are fully accredited by
More informationElectrical Safety Tester Verification
Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that
More informationCircuit Electrical Testing
Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved
More informationCandidate Self-Assessment Checklist
General Information This is a compulsory document which must be completed by all candidates due to undertake the AM2 Assessment of Occupational Competence and provided to the assessment centre prior to
More information12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
More informationSection B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
More informationA Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
More informationA B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898
NAPIT Electrical Test Continuation Sheet Requirements for Electrical Installations BS 767 [IEE Wiring Regulations] and for Please complete all the unshaded areas. This sheet forms part of *Inspection Report
More informationFAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
More informationExperiment NO.3 Series and parallel connection
Experiment NO.3 Series and parallel connection Object To study the properties of series and parallel connection. Apparatus 1. DC circuit training system 2. Set of wires. 3. DC Power supply 4. Digital A.V.O.
More informationDouglas J. Reinemann, Ph.D. University of Wisconsin-Madison, Department of Agricultural Engineering Madison, Wisconsin. and
Paper o. 953623 An ASAE Meeting Presentation ELECTRICAL SERVICE TO AGRICULTURAL BUILDIGS: FOUR- WIRE AD THREE-WIRE SYSTEMS by Mark A. Cook, Daniel M. Dasho P. E., and Richard Reines Public Service Commission
More information13.10: How Series and Parallel Circuits Differ pg. 571
13.10: How Series and Parallel Circuits Differ pg. 571 Key Concepts: 5. Connecting loads in series and parallel affects the current, potential difference, and total resistance. - Using your knowledge of
More informationBuilding Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24
1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition
More informationTutorial on Safety Standard Compliance For Hipot Testing
Chroma Systems Solutions, Inc. Tutorial on Safety Standard Compliance For Hipot Testing 19071, 19073 Hipot Testers Keywords: Safety Issues, Electrical Shock, Fire, Hipot (Dielectric Withstand), Leakage
More informationTrouble-shoot and repair faults in low voltage electrical apparatus and circuits
UEENEEG108A Trouble-shoot and repair faults in low voltage electrical apparatus and circuits AS3000:2007 & AS3017:2007 Summary MANUFACTURING AND ENGINEERING DIVISI M & E UEENEEG108A TESTING Before any
More informationBypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
More informationGroundRod AC Substation Earthing Tutorial
1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities
More informationNEW Practical Courses for the Electrical Industry
NEW Practical Courses for the Electrical Industry Practical application of the wiring regulations 0800 028 28 28 We are here to help, call 0800 028 28 28 2 3 Welcome to our courses for the Electrical Industry
More information2 Wire Electronic Time Delay Switch. 2 Wire Slave Switch. 3 Wire Electronic Time Delay Switch
2 Wire Electronic Time Delay Switch Cat No. DS1 2 Wire Slave Switch Cat No. DSS 3 Wire Electronic Time Delay Switch Cat No. DS2 Installation & Operating Instructions DS1/DSS Instructions for Installation
More informationParallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected
This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. Electricity Objectives After studying this chapter, you will be able to answer these questions:.
More informationIntroduction to Data Centre Design
Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09 Earthing what s the point Safety from electrical hazards Reliable signal reference within
More informationSTREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
More informationGUIDE TO THE AM2 EXAM
AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test
More informationGrounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
More information6.0 Electrical Installations
6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is
More information6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20
USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure
More informationWhat are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
More informationEnphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance
WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new
More informationDEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
More informationMobile Device Power Monitor Battery Connection Quick Start Guide
Mobile Device Power Monitor Battery Connection Quick Start Guide Distributed By: Monsoon Solutions, Inc. www.msoon.com Introduction The Power Tool software and the Mobile Device Power Monitor hardware
More informationInstruction Bulletin. MCS025 Sync-Check Module Installation Sheet
Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical
More informationElectrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
More informationInsulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationTHREE PHASE CIRCUITS
THREE PHASE CIRCUITS A. PREPARATION 1. Three Phase Voltages and Systems 2. The Determination of Phase Sequence 3. Blondel's Theorem and Its Consequences 4. References B. EXPERIMENT 1. Equipment List 2.
More informationProject Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1
Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to
More informationHIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
More informationEARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
More informationMEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV
MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects
More informationFire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
More informationOPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
More informationLightning Protection Introduction
Lightning Protection Introduction Structural lightning protection design considerations BS 6651 (Protection of structures against lightning) clearly advises strict adherence to the provision of a conventional
More informationElectrical test equipment for use on low voltage electrical systems
Electrical test equipment for use on low voltage electrical systems Guidance Note GS38 (Fourth edition) This general series guidance note is aimed at people (including electricians, electrical contractors,
More informationD. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
More informationPXL-250: Network Wiring
This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification,
More information3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS
3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS Pierre FRISTOT Olivier CONSTANT Catherine MONCET Omegawatt - France Omegawatt - France SDET - France pierre.fristot@omegawatt.fr
More informationemployed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
More informationFundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
More informationAbout the HotWire 7900 10-Slot Standalone Shelf
TM HotWire Model 7900 10-Slot Standalone Shelf Installation Instructions Document Number 7900-A2-GN10-10 About the HotWire 7900 10-Slot Standalone Shelf The HotWire 7900 10-Slot Standalone Shelf is designed
More informationNovember 2014. Stray Voltage Test Procedure for Electrical Contractors
Stray Voltage Test Procedure for Electrical Contractors 1 LIMITATION OF LIABILITY AND DISCLAIMER Any person who uses, relies on, or otherwise deals with this document and the information herein, does so
More informationTechnical Update TAA.TU.11093 Rev. 1
http://www.gambro.com/en/usa_tech/ 800-525-2623 303-222-6500 Technical Update TAA.TU.11093 Rev. 1 Effective: 05 APR 2013 CO# 13084 Product: Subject: From: Phoenix Dialysis System Required Electrical Safety
More information1. Electrical Equipment A) Transformer
Standards and Basic Equipment Date : 15 November 2010 1. Electrical Equipment 2. Terminology 3. Code & Standard 1. Electrical Equipment A) Transformer A1) One Transformer and 11kV Switchgear in High Rise
More informationInterface between Eircom Network and Additional Telephone Equipment
Interface between Eircom Network and Additional Telephone Equipment External Terminating Unit The ETU (small cabinet, 230mm x 150mm x 150mm) is fitted by the customer on an exterior wall, at a point approx
More informationchapter6 Basic electrical circuitry and applications Unit 2 Outcome 3
Basic electrical circuitry and applications chapter6 Unit 2 Outcome 3 The primary role of an electrician is the installation of electrical circuits and applications. In order to install any type of application,
More informationWhite Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
More informationInstallation instructions for Series NRX INCOM communications adapter module
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply
More informationBC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
More informationSolar Photovoltaic (PV) Systems
ARTICLE 690 Solar Photovoltaic (PV) Systems INTRODUCTION TO ARTICLE 690 SOLAR PHOTOVOLTAIC (PV) SYSTEMS You ve seen, or maybe own, photocell-powered devices such as night lights, car coolers, and toys.
More informationLoad Cell Troubleshooting
VPG TRANSDUCERS Load Cells and Weigh Modules Technical Note VPGT-08 Scope Load cells are designed to sense force or weight under a wide range of adverse conditions; they are not only the most essential
More informationConstruction Electrical Terminology. Electricians
Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.
More informationIEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439
More informationThe Do s and Don ts of Pressure Transducers
The Do s and Don ts of Pressure Transducers ABSTRACT When specifying a pressure transducer for a process measurement, a number of items have to be considered. Some of the more important ones are discussed
More informationOPERATING INSTRUCTIONS
OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MAG & Electric Blue Amplifier Heads and Combos Thank you for purchasing your Ashdown Engineering Amplifier. If you live in the UK, please register your purchase
More informationLocoNet, the Digitrax Difference
LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on
More information1 Introduction. 2 Hazards From Electricity
Risk Assessment Application to Electrical Rigs A guide to assist the Competent Named person who will verify the safety of rigs consisting mainly of electrical equipment. 1 Introduction Every employer shall
More informationChapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
More informationINSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES
1 By kind permission of MK INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES By Mark Coles The IEE receives many enquiries relating to the inspection and testing of electrical
More informationAtlanta Chapter IEEE Industry Applications Society
Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.
More informationR22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
More informationNZQA registered unit standard 15848 version 6 Page 1 of 5. Demonstrate and apply knowledge of safeguards for use with portable electrical appliances
Page 1 of 5 Title Demonstrate and apply knowledge of safeguards for use with portable electrical appliances Level 2 Credits 3 Purpose This unit standard covers knowledge of safeguards used in conjunction
More informationGrounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
More informationApplication of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
More informationIntroduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory
Introduction to Electricity & Magnetism Dr Lisa Jardine-Wright Cavendish Laboratory Examples of uses of electricity Christmas lights Cars Electronic devices Human body Electricity? Electricity is the presence
More informationPAT400 Series. Portable Appliance Testers. User Manual
M PAT400 Series Portable Appliance Testers User Manual Thank you for purchasing the Megger PAT400 portable appliance tester. For your own safety and to get the maximum benefit from your instrument, please
More informationElectrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?
Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are
More informationWIRING MATTERS. EARTHING: Your questions answered. Electrical installations outdoors Ongoing accuracy of test instruments PAT testing of equipment
WIRING MATTERS Autumn 2005 Issue 16 EARTHING: Your questions answered Electrical installations outdoors Ongoing accuracy of test instruments PAT testing of equipment OUTBUILDINGS 1 IN THIS EXAMPLE, the
More informationTroubleshooting Guide, Freedom and Fleet Power Inverter/Chargers
Technical Note Freedom/Fleet Power 512-0084-01-01 Rev 1 Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers Overview This document is a guide for troubleshooting inverters, battery chargers,
More informationGround Resistance Clamp On Tester
USER MANUAL Ground Resistance Clamp On Tester MODEL 382357 Introduction Congratulations on your purchase of Extech s 382357 Ground Resistance Tester. This Clamp on device allows the user to measure ground
More informationGuidance notes for the installation of electrical supply in mobile trailers for breast screening
NHS Breast Cancer Screening Programme Cancer Screening Programmes Guidance notes for the installation of electrical supply in mobile trailers for breast screening B Mansfield, CP Lawinski NHSBSP PUBLICATION
More informationCAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
More informationCITY OF LOS ANGELES CALIFORNIA
BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI
More informationELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
More informationDirection of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
More informationStrength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines
Strength and Durability for Life CORROSION CONTROL The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines Last Revised: May 2016 Sharing of rights-of-way by AC power lines and buried
More information2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
More informationESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
More informationExperiment #3, Ohm s Law
Experiment #3, Ohm s Law 1 Purpose Physics 182 - Summer 2013 - Experiment #3 1 To investigate the -oltage, -, characteristics of a carbon resistor at room temperature and at liquid nitrogen temperature,
More informationIndustrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards
Redundancy = Protection from Network Failure. Redundancy Standards WP-31-REV0-4708-1/5 Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards For a very
More information