1 Lighting Control

2 Table of Contents 1 General Conventional Brightness Control: Sun shines Light switches off Principle Constant Lighting Control Constant Lighting Control: Areas of Application, Objective Types of Closed-loop Control Usable Bus Devices Characteristics of Sensors and Actuators Sensors Closed-loop Controller types Actuators Parameterisation Notes, Flags, Possible Errors, Bus Load etc Parameterisation Example Functions Example Parameters Group Addresses Linking of Sensor and Actuator Objects, Operation Additional Notes Installation Notes Alignment of the Measuring Sensor Several Light Strips with a Varying Proportion of External Light: Fundamental Mismatch Brightness Control Areas of Application, Objective Types of Open-loop Lighting Control Continuous Control Two-step Control Usable Bus Devices General Sensors Actuators Controllers Parameterisation Notes, Flags, Bus Load etc Parameterisation Example Installation Notes Brightness Control, combined with Master/Slave Control Objective Principle...25 Lighting Control Lighting Control_E0310a 2/34

3 6.3 Available Devices Parameterisation Example Installation and Solution Notes Appendix Tasks Task 1: Lighting Control dependent on External Light Task 2: Lighting Closed Loop Control Master-Slave with separate Actuator General hints for the calibration of lighting closed loop control...34 Lighting Control Lighting Control_E0310a 3/34

4 1 General The lighting in modern buildings is generally no longer switched manually. The users in principle demand the implementation of intelligent open- and closed-loop lighting control systems. This should result in the efficient operation of the lighting. Efficiency has three meanings in this context: firstly, there should be an obvious saving of energy; secondly, intelligent lighting systems should largely prevent lights from being switched on unnecessarily which should lead finally to an automatic protection of resources! 2 Conventional Brightness Control: Sun shines Light switches off If dimmed fluorescent lamps are used for example instead of switched lamps, the service life of the fluorescent material is lengthened considerably even when the maximum power is reduced by only 10%. This again results in cost savings and protection of the environment. A well-designed lighting control system also means a more pleasant working environment for the user e.g. from office workstations. It is also worth mentioning in this context that closed-loop lighting control should where possible use existing (free) external light which results in a two-fold energy saving, particularly during the warmer seasons of the year. A reduced level of artificial light means less electrical power, less waste heat and thus also a lower cooling capacity if the rooms are air-conditioned. Moreover, scientific studies have proven, that an integrated blinds and illumination automation will reduce the sun induced heat energy into a building up to 80%, Thus even a 4-fold saving can be made, perhaps in certain buildings avoid to install air condition at all. Lighting Control Lighting Control_E0310a 4/34

5 Light strip 1 Light strip 2 Light strip 3 ~ 26 % ~ 48 % ~ 70 % Receiver Receiver Receiver 500 lux required light intensity Necessary artificial light Existing daylight Goal: Brightness control optimised for all areas of the room 3 Principle Closed-loop and open-loop lighting control systems are based on the modulation of the lighting level inside the room by the measurement of either the level of external light (independent variable) or the measurement and feedback of the level of internal light (dependent variable) which contains a variable proportion of external light. In both variants, the primary goal is to maintain a required level of internal light as constant as possible. In general, it is a feature of a distributed system such as KNX that the individual tasks in the closed-loop or open-loop control systems are distributed among different devices: sensors, actuators and controller modules. This has both benefits and disadvantages as outlined below in detail. 4 Constant Lighting Control A closed-loop control circuit is used for constant lighting control. The required level of brightness in the room or the level of lighting at the desk is measured as a controlled variable together with the interference from the external light and then fed back to the actuators in the appropriate manner. Controlling system Controlled system Z W Controller Y Actuator Contr. variable X X+Z - + Measuring device Brightness sensor W... Reference variable (e.g. brightness, setpoint) Y... Control value (dimming value 1-100%) Z... Interference (level of external light) X... Actual value (lux value at workstation) Figure 1: Constant lighting control Lighting Control Lighting Control_E0310a 5/34

6 4.1 Constant Lighting Control: Areas of Application, Objective This type of control system is mainly used in commercial installations where it is important to adhere to certain regulations such as those governing the workplace but not to make more light available than necessary. The aim is to create optimum working conditions while at the same time saving costs. The user should also be offered an optimum level of convenience and the internal room controller should operate independently of other parameters which cannot be detected here. 4.2 Types of Closed-loop Control A distinction is made between Closed-loop Control and the so-called Integral Reset. In the first control system, the control value is directly influenced by the setpoint/actual value differential. For example, an absolute dimming value is sent to the actuators via a feedback function (dependent on the measured lighting level but with a variable proportion of external light). The negative feedback of the control value on the comparison point of the closed-loop control circuit as well as the system deviation with forward gain are governed by one function. The greater the influence on the control value, the higher the failure rate of the system deviation. Integral Reset on the other hand operates according to the two-step principle. The control value for the brightness level of the actuators is modified indirectly or gradually, namely via relative dimming telegrams. After this type of dimming process, the lighting sensor measures the surface again that is to be constantly illuminated, compares it with the setpoint and then decides again in which direction further dimming should take place. The respective level of change carried out to the control value remains constant at each new activation. It is not dependent on the degree of system deviation Two-step control is actually not a proper closed-loop control system as it rarely achieves the required setpoint. This type of control only has an opening/closing point instead of continuous dimming processes which must be provided with a sufficiently large hysteresis to prevent the triggering of continuous opening/closing operations. This type of lighting control is described in more detail under the section Brightness control. Lighting Control Lighting Control_E0310a 6/34

7 4.3 Usable Bus Devices Since we are specifically discussing the maintenance of a constant level of illuminance, only actuators that allow variable illumination are permitted. They must therefore be dimming actuators. A required characteristic of KNX dimming actuators is that it must be possible to control them in three different ways: switching, relative dimming via 4 bit information and absolute dimming via 8 bit information. Sensors for this control system must first only be able to measure the actual brightness value with sufficient accuracy and frequency without supplying upper limit values in the required band width. As regards accuracy, the sensor that offers a logarithmic resolution is the most beneficial. This means that is must be able to carry out more precise measurements in the lower range than in the upper range as the human eye reacts less to absolutely identical changes with an increasing level of brightness. When judging whether a closed-loop control system is better or worse than another type of system, only a relative estimation of accuracy is necessary. If an adjustment to 1500 lux is required for example and the maximum system deviation is +/- 150 lux i.e. 10 %, this is equivalent to an adjustment to 500 lux at an absolute value of +/- 50 lux. The third component of this control system is a controller which takes over the actual control task. It receives the measured brightness value as an input and compares it with the setpoint which is available e.g. as a parameter (fixed value) or as an object value (can be modified at any time via the bus). From these two values, it can determine the output (control value) according to the implemented algorithm (control function) and send it to the actuator. In practice, particularly due to cost and space restrictions, the manufacturers of these types of components decide to integrate the controllers into the sensors or even to build the entire controller and sensor component into the actuator. 4.4 Characteristics of Sensors and Actuators Sensors As stated above, brightness sensors that are used for lighting control should have a measured-value resolution available that is adapted to the setpoint. A system deviation below approx. +/- 15% is still not noticed by the user. The accuracy or tolerance of the measuring sensor as well as the losses caused by A/D conversion in the KNX sensor must be added together i.e. lie below this figure. Example: The setpoint is 600 lux; the tolerance is therefore +/- 90 lux. The individual possible measured values must thus be separated by less than 90 lux. The fact that indirect measurements are always carried out causes a problem. It is not the luminous flux of the lamp that is measured, but the reflected light output from the reflected surface. It is easy to imagine that a dark surface is less reflective than e.g. a white desk. The structure of the surface can also influence the recording of the measured value. In principle, it can be said that the light is scattered to a greater or lesser degree and the measured value of the sensor is lower than for direct measurement. Due to the varying reflectance factors, sensor heads must have a variable gain available which can be adapted to the respective requirements. This gain must be carried out in front of the A/D converter as otherwise the resolution is reduced by the gain factor and the control precision decreases. The measured value can thus be adapted via this gain factor under the named requirements in the course of a calibration procedure so Lighting Control Lighting Control_E0310a 7/34

8 that it can be used simultaneously as a lux value that can be displayed. The correct measured brightness value is generally sent cyclically by the sensor. The value differential and time interval that are used for sending can be set in a wide range in most cases for the available devices. In addition to the cyclical sending variant, it is also possible to react quicker with event control if the measured brightness value changes significantly Closed-loop Controller types The example outlined above now requires a closed-loop controller, which uses the setpoint/actual value comparison to determine how the control value must be modified in order to return to the desired equilibrium of setpoint = actual value. The details of this control technology will not be discussed here, only the feasible alternatives. This so-called closed-loop procedure can contain proportional, integral and differential feedback components. This means: proportional: a direct control output y is calculated for the dimming actuator from the setpoint/actual value differential x via simple, linear conversion function according to the function y = a. x integral: the control output is integrated with a specific rate i.e. it is zero at the beginning and reaches the calculated value y = a. x. t only after a certain period differential: the control output is determined from the rate of change of the system deviation y = x/t Only the P controller can be used directly by these basic functions of control technology. The use of a P controller however leads to a systematic deviation which cannot be reduced due to the requirement to avoid oscillations. Only an integrating controller would function better in our case as it finds a stable state after a certain period in which it remains while there are no changes to the external light intensity. The D controller reacts very quickly if there is a substantial change in the parameters. The response to this change dies down again after a certain period. Apart from the continuous control of the setpoint, it is now important for an optimum lighting control system that the change in the brightness level runs almost imperceptibly for the user. Extreme external variations in the lighting should also not influence the control output at such a rate that it causes an imbalance. P and D controllers are therefore rarely used for lighting control systems. Only integral action control is in practice sufficient to fulfil the requirements of the user. In most cases, the integral action control has an indirect rather than direct influence on the control output. We are then using the integral reset procedure. In practice, this means that the closed-loop controller modifies the control output stepwise and indeed always by the same amount per temporal unit, which is a modification of a true integral controller, since the steps are always of the same size. In the KNX system, 4 bit dimming telegrams (DPT 3.007) are predestined for this as they transfer these constant changes in value that do not contain any different values (apart from the sign) as is the case with an absolute 8 bit control output. Any considerable variations in the parameters always cause the same rate of change. Since the change in brightness should take place gradually, only the step widths 1/64 (1.6%) or 1/32 (3.2%) are recommended for DPT bit dimming telegrams are sent continually at a certain rate, provided that the actual value does not meet the setpoint within the hysteresis. If the hysteresis range is reached, the controller stops. Lighting Control Lighting Control_E0310a 8/34

9 Figure 2: Example of a closed-loop controller with an integrated sensor In the objects of figure 1, it is possible to detect that further possibilities can be implemented apart from the actual dimming function (= control value). These options enable a very convenient use of the control system: Setpoint adjustment via absolute (direct) value control Master /slave function for additional lighting circuits Toggling between manual and automatic mode via all operator functions which the dimming actuator is aware of (i.e. switching, dimming and value setting) The previous statements about the procedure used by DPT do not however mean that an integral reset can only be carried out with DPT only. This procedure can also be implemented with DPT telegrams. The controller thus starts with an initial value, mainly 0 or 255, and sends further telegrams as with DPT 3..07, which now contain 8 bit values that are reduced or increased by a constant value compared to the previous value. Some devices also manage to retrieve the present dimming value of the actuator to be controlled and start from this one instead 0 or 100%. The benefit of this procedure compared to DPT appears to be that the resolution increases until it reaches steps of 0.4%. This means it is possible to make even finer adjustments in the dimming process. The bus load should however be taken into account since it rises when smaller changes in the value are carried out. The device shown in figure 2 is an example for 8-bit closed loop control Actuators No particular requirements are placed on the dimming actuators initially as only the 4 bit or 8 bit object is required for integral reset. It is however important to be able to select whether this type of actuator should switch off or not when dimming down continually. It is likewise the case with the opposite process. If the closed-loop control is switched on, it should be possible to switch on using 4 bit dimming commands. The timing/dimming curve must be active for both 8 bit value dimming and the 4 bit dimming process as the actuator otherwise dims brighter or darker step by step. The KNX dimmers and dimming actuators that are currently available on the market fulfil almost all these conditions which is not always the case with older devices. To optimise the dimming process, the dimming speed Lighting Control Lighting Control_E0310a 9/34

10 of the actuator and dimming step width and send interval of the controller should match precisely: If e.g. 1/64 dimming telegrams are sent every 2 seconds, the dimmer must be set so that it makes a full cycle of 0 100% in 128 sec and no faster. If it should also be possible to operate the dimmer manually, a shorter dimming period is of course required. Differences can therefore be found in this regard between the available devices as not all of them offer this possibility (see the note in the next section). 4.5 Parameterisation Notes, Flags, Possible Errors, Bus Load etc. The previously named condition (dimming period of 128 sec) is optimised for the control system but not for manual operation. A compromise must often be made: the actuator dims at a slightly slower rate e.g. in 8 sec and the controller transmits at a slightly faster rate to avoid stepwise brightness processes. This increases the bus load however. Alternatively 1/32 is used as a step width instead of 1/64 to reduce the bus load again. This produces a further problem in the case of very bright luminaires (over-dimensioned or still new). The changes in brightness can already be greater than the set hysteresis after a single step of 1/32. This results in continuous fluctuations as the luminaire continually exceeds or falls below the target value. 500 lx Hysteresis Interior lighting External brightness Figure 3: Mismatch of dimming step width and hysteresis The extension of the hysteresis or reduction of the dimming step width can provide some help: 500 lx Hysteresis Interior lighting External brightness Figure 4: Correct ratio of dimming step width and hysteresis Lighting Control Lighting Control_E0310a 10/34

11 A better option is the use of dimming actuators with two time bases. This option has become more common since dimming actuators based on BCU2 have come on to the market. It is then really possible to implement a manual and automatic function: manual operation = short dimming time base, automatic = long dimming time base. Figure 5: Objects of a switch/dim actuator with a dual time base Lighting Control Lighting Control_E0310a 11/34

12 4.6 Parameterisation Example Functions We use 3 KNX components in this layout for a complete control system: a sensor with an integrated controller (type = integral reset by 8 bit), a dimming actuator with a dual dimming time base and a 3-fold push button with text display that enables the following functions. Function Effect Switch light manually (basic) Switches actuator on/off, interrupts the CLL*) control Dim light manually (basic) Dims the actuator, interrupts the CLL control Switch automatic CLL control on/off (basic) Starts the CLL control with the parameterised set point or stops it Set value manually for lighting (continuously) (optional) Sets the brightness value at the actuator between 0 and 100%, interrupts the CLL control Presence (optional) CLL control triggered by a movement / presence detector; or simpler, just by switch Setpoint shift (optional) Variable LUX value setpoint control Calibration Only for commissioning (or for advanced users to recalibrate later) *) CLL: closed loop lighting The usual range in which setpoint values can fluctuate is between 250 lux (lighting level for less demanding activities) and 1500 lux (level for light-intensive laboratory workstations where optical equipment is used such as lenses, microscopes etc.). The sensor must maintain a system deviation of max. +/-15% throughout the range. Two further functions/group addresses are required to calibrate the arrangement after the installation: measured lux value (to compare with the external lux meter) calibration trigger The brightness sensor/controller already mentioned above also enables calibration to be carried out. The address measured lux value is not really always necessary but strongly recommended to be used in order to have an indication about how far the real measured value and that one of the KNX sensor differ before the calibration is started. The calibration process will calculate just a (for the user not accessible) gain factor between Lighting Control Lighting Control_E0310a 12/34

13 the physically measured light level and the either parameterized or via object adjusted setpoint Example The sensor would after the initial full application download send a value of 200. But a Luxmeter would see 500 Lux. The setpoint of the sensor is also 500 Lux. (It has to be otherwise the calibration would be faulty). So after the calibration trigger telegram has been sent, the new measured value would be returned with 500. Only a connection between the controller and the actuator is now missing: Automatic value control (Master value) Parameters Figure 6: Control parameters of the closed loop controller Explanations: Operating mode: Constant light level control is used for continuous dimming Number of slaves: Only 1 master channel required, so no slaves = 0 Send meas. brightn.: (optional) the sensor value can be displayed and monitored Min. variation : 15 Lux means, with deviations of equal or more than 15 Lux a new value will be sent. Setpoint value: Parameter or Comm. Object ; the latter one allows flexible setting of the setpoint Max. var. from setp.: Half of the double sided hysteresis (varies from 15 to 60 Lux) Max. step size : varies from 0.5 up to 3%; = difference between 2 master value telegrams; Transmit next : 2 sec; i.e., together with max. step 0-100% = 120 sec. Lighting Control Lighting Control_E0310a 13/34

14 Start and finish : The controller will firstly read the value status, then calculate the next telegram to be sent, and also stop with a 0% value telegram Figure 7: Parameter (extract) of the switch/dim actuator This setting enables a manually operated dimming speed of 5 sec per 100%. The factor for the dimming time 2 (plus its base timer seconds ) rules an automatic dimming time of 120 sec. This time equals exactly the setting of the master channel of the brightness controller. Lighting Control Lighting Control_E0310a 14/34

15 4.6.4 Group Addresses To summarise, all the group addresses are listed here again: Figure 8: Group address configuration in a convenient constant lighting control system Linking of Sensor and Actuator Objects, Operation In our example a push button with text display (LCD) is used to provide proper labelling of the control functions and the (optional) display of values. Very often, however, customers don t want to spend so much money, so they only use a local pushbutton for simple switching and dimming control as manual override, and the automatic activation will be done e.g. by a central scheduler, or by the twilight sensor on a weather central. Figure 9: Group address links between the 3 KNX devices Lighting Control Lighting Control_E0310a 15/34

16 4.6.6 Additional Notes In general, the actuator is also addressed via central functions (see above) which switch the lights on/off directly or also activate/deactivate the control for example via a time switch. This must also be taken into account in the controller. A direct central switching operation must also switch off the controller with positive drive. These addresses must therefore also be linked to the disable objects of the controller; otherwise the controller will always act against this external input and try to dim up the lights again. 4.7 Installation Notes Many factors are decisive for the optimum installation of a brightness control system. Some are listed here: Alignment of the Measuring Sensor The surface that is to be measured should be as undisturbed as possible i.e. should never indicate different surface characteristics. External light should not directly penetrate the receiving lens if possible, likewise artificial light. Building ceiling Correct Incorrect Lamp Suspended ceiling Receiver Mounting height m Light cone Correct Incorrect 0 4 w A n A _ Calibration required Measuring sensor +/-15% Daylight Figure 10: Optimum position of the measuring sensor (graphics do not resemble the sensor exactly) Several Light Strips with a Varying Proportion of External Light: In this case, which rarely occurs, a single brightness sensor is only sufficient if it is possible to generate different control values for the individual actuator channels. If you do not have a controller that can do this, a separate sensor must be installed for each light strip. As mutual influences (mostly unwanted) can arise, a partitioning of the sensors must take place and the overlapping of the lighting surfaces underneath the individual strips must be minimised. It can, however, invariably lead to oscillation processes or at least an unexpected distribution of brightness (although the measured values of the sensors are correct). The technically better solution nowadays is to only control one strip (whereby it is not possible to simply select any strip but the strip which is installed at the window side, which reacts the most sensitively to daylight changes). The other lighting strips are simply Lighting Control Lighting Control_E0310a 16/34

17 interfaced via a control function e.g. offset adjustment is a so-called master/slave circuit (see the explanations in section 5). Light strip 1 Light strip 2 Light strip 3 ~ 26 % ~ 48 % ~ 70 % Receiver Slave 2 Slave 1 Master 500 lx required illuminance Necessary artificial light Existing daylight Figure 11: Brightness control of a light strip, combined with offset control for the other light strips Fundamental Mismatch A mismatch always occurs in this system. This is based on the one hand on the different lighting spectrum of natural light and artificial light and on the other hand, on the different angle of illumination. The more external light comes in, the greater the measuring error, because the natural light also is picked up by the sensor rod directly instead of only from the controlled surface by reflection. A curve of the controlled variable is produced dependent on the external brightness which reaches its minimum in a ratio of 50:50 between the proportion of external and internal light. The system must always be balanced under these lighting conditions. Ф internal [lx] Optimum adjustment value Actual value 500 Setpoint 250 Actual internal value Proportion of artificial light Proportion of external light Ф external [lx] Figure 12: Behaviour of the actual value dependent on the level of external light Lighting Control Lighting Control_E0310a 17/34

18 5 Brightness Control 5.1 Areas of Application, Objective In contrast to lighting control in which you wish to achieve individual and optimum levels of light intensity as mentioned above, brightness control is mostly considered with regard to minimising installation costs without fully losing sight of the goal of reducing energy costs. It is however agreed between the planner and user that significant deviations from the setpoint/actual value can occur in the control system. This is particularly the case when only switchable lamps are integrated in the control system. Figure 13: Principle of brightness control 5.2 Types of Open-loop Lighting Control For brightness control, a distinction is made between continuous control and two-step control. A sensor measures an external brightness value which is independent of the internal illuminance that is to be set. Starting from this measured value, the internal control value is determined at first via any calculation function which the room illuminance uses to reach the required setpoint. Technically this is an open control loop. The feedback loop is missing. This has both advantages and disadvantages. It is beneficial that this type of lighting control can never oscillate since the feedback loop has been omitted as mentioned. Starting with the measured value of a single sensor, many different control curves can be differentiated. The disadvantage is that a very extensive adjustment must be carried out for continuous control which takes at least one day Continuous Control Continuous control like the closed-loop control above requires dimmers or dimming actuators which can be infinitely adjusted. As an automatic adjustment of the control value cannot take place (due to the missing feedback loop), this must be carried out by selecting a control function. In the simplest case, this can be a straight line determined by two pairs of values: a) maximum external brightness above which there should be 100% interior Lighting Control Lighting Control_E0310a 18/34

19 lighting and b) minimum brightness level above which the light should be switched off. Moreover, the control module must be in a position to carry out a hysteresis in order to ease control in the extreme range between switched on and switched off. Figure 14: Characteristic curve for brightness control a hysteresis is advisable Two-step Control The characteristic curve described in the previous section is further simplified if only two states are possible for the controlled lamps: ON or OFF. Switching value 1 Switch Off point Hysteresis 0 0 Switch On point [ lux ] Measured value of brightness sensor Figure 15: Principle of two step control Lighting Control Lighting Control_E0310a 19/34

20 5.3 Usable Bus Devices General A separation between the sensor and actuator technology is advisable. The control system takes over the evaluation of the sensors (including push buttons) and triggers the actuators Sensors Almost all the devices that can evaluate external inputs can be considered as sensors for brightness control. This includes the simple two-step control via a binary input that is coupled with a floating contact of a light sensor. The disadvantage in this case is that the switching points and hysteresis cannot be influenced via the KNX by telegram or at least by downloadable device parameters. Analogue inputs with KNX capability which supply a measured value in DPT format in lux units are better in this case. The sensors that offer an almost logarithmic resolution of the measured signal are beneficial and of course completely cover the required area. If this is not the case, the measured-value resolution as mentioned above should be sufficiently precise for light control values approx. >50% so that visible fluctuations in the brightness level do not occur in the area in which the artificial light is predominant. As we saw above with closed-loop control, the maximum step width may not be higher than a 3.2% dimming value differential. This characteristic must of course also apply here. This means that we should have at least 50/3.2 = 16 steps in the range 50%-100% for the dimming setpoint. You can now easily specify whether a sensor is sufficient in practice or is not precise enough. Example: A sensor records 1000 lux of external brightness, the dimming level lies at 50%. The resolution of the sensor dimming level lies at 50%. The resolution of the sensor must be at least 1000 / 16 = 6.25 lux. A small query regarding the theory if this sensor with a resolution of 62.5 lux already had a dimming level of 50% at an external brightness of 500 lux is it suitable or not? Actuators As stated above under 3.4.3, there is no limit applicable here. All the actuators designed for normal dimming can be used. All the binary outputs can be used again for two-step control Controllers The brightness control system covers several different control curves. It is therefore a good idea to implement the functions measure external light level and trigger actuators in a special module which doesn t have to be directly linked with the light sensor via cable. In this case, it is possible to concentrate on the optimum position for placing the measuring sensor, as the measuring signal is already formatted as a DPT telegram in the KNX-coupled sensor and then routed through the KNX network as appropriate. A controller module is then located in a distribution board which derives a range of different control curves from the incoming measured value. It is of course always possible to interface another system via a gateway in which DDC functions are also available. This is Lighting Control Lighting Control_E0310a 20/34

21 not a KNX lighting controller but the conversion is carried out externally in the DDC which then sends new dimming control values in response via the gateway to a new measured value of the lighting sensor. (E.g. gateways to Profibus). Figure 16: Conversion of the measured value of the light sensor in different control curves 5.4 Parameterisation Notes, Flags, Bus Load etc. Having already discussed all the important characteristics of the actuators and sensors involved in the Lighting control section, we can now briefly summarise here: statements regarding flags (readability of status objects) and inclusion of manual operation in the automatic system (time-limited interruption of control) also apply here of course. If the lighting should also be switched/dimmed manually via local push buttons or set directly to values, the control system must also be aware of the addresses, otherwise manual operation leads inevitably to an immediate correction by the automatic system. As we no longer have a control loop, it is also possible under certain conditions to implement minimum and maximum limit values for the dimming control value within which the control system operates. Otherwise it is switched off (manual operation). To prevent frequent switching in the two limit ranges, minimum ON and/or maximum OFF times can be requested as well as an ON/OFF hysteresis. The module that can fulfil these additional requirements is of course preferable to those with pure control curve functions. The bus load also plays a role here: it is not merely a question of value dimming but also whether and how the cyclical and/or event controlled sending of the lighting measured value should be set best. It should first be considered that each new brightness value from the sensor results in the same number of value dimming telegrams as active control curves. Lighting Control Lighting Control_E0310a 21/34

22 5.5 Parameterisation Example Figure 17: Links between switch sensors, actuators and the control unit, consisting of the brightness sensor and control module In the above diagram, it can be seen that it is not only the external brightness and dimming control values ( set value ) from the controller to the dimming actuators that are important, but also the ON/OFF lighting command, the optional 4 bit dimming and the 8 bit value setting of the manual push button. The application shown is as in the closed-loop control described in paragraph 3 able to convert increases and decreases in the dimming value into an adjustment of the control curves. The logic operation of the status value is required however as this determines the parallel displacement of the curve. What is still missing in this diagram would be a true automatic ON/OFF function which is controlled via a time switch. This KNX clock would also use the group addresses Enable/disable control and Control ON/OFF. Figure 18: Parameter of 2 different brightness sensors: linear vs. logarithmic value calculation The setting for Sending on change should not be too precise. The 1 st sensor allows 5% changes, always related to the last sent value. Such a value calculation goes along with Lighting Control Lighting Control_E0310a 22/34

23 the logarithmic impression of brightness by the human eye and is much better than a linear output (equidistant values) of sensor 2. Still an option of limiting the amount of bus telegrams per time unit should be available (not visible in this example here). Regarding sensor 2 (Figure 18 lower image): If a measured value interval of 64 lux is still sufficient in the lower range (see 2 nd example above), then the factor should be 8 instead of 4 as shown. During cyclical repetition of the measured value if parameterised values like those shown above are completely unsuitable: assuming that 10 control curves are implemented, up to 11 telegrams in total can occur every 650 msec. The bus load would then already be over 30%. The aim should however be to remain below 2%. Assuming that a maximum of 45 telegrams can be sent on the line on average, then 2% would correspond to 0.9 telegrams / sec. In the case of the aforementioned 11 telegrams per measured value, this means that a measured value may be sent approx. every 12 seconds. This timing resolution is probably quick enough, primarily, because the controller calculates the new control values in proportion and does not always send constant dimming steps as in integral-action closed-loop control. The correct parameter combination for sending the cyclical measured values is then: Base = 130 ms; Factor = 12 sec / 130 ms = 92 Dimming value Measured value Figure 19: Value table for lighting control: a monotone falling curve is important The table shown in the diagram figure 19 can be specified arbitrarily at first. An approximation of a comparable constant lighting control system can mainly be achieved over 3 points. The two values of complete darkness or the level of daylight that is sufficient to light up a room or part of it without artificial light can be quickly determined using a lux meter. The value pair that starts the proportional range should be verified next: in our example this is 500 lux / control value 250 (98%). If there are still considerable deviations in the intermediate lux values, it is possible to recalibrate the particularly poor values a few days later. Lighting Control Lighting Control_E0310a 23/34

24 Figure 20: Parameter of a controller module It is then possible to check whether the curve-specific parameters of the controller (if available) fulfil the requirements of the customer. In our example, that would be the behaviour after bus voltage recovery; the open-loop control would be switched on here the minimum On time: if the external brightness should vary within the limit range so that the control value for the dimmer can fluctuate around the switching point, then the light remains switched on for at least 5 minutes the hysteresis limit values shown mean in our example that the light is only switched off at approx lux (since there is then an underrange in the control value of 20) and switched on again at approx. 600 lux because the control value of 30 has been achieved again. Lighting Control Lighting Control_E0310a 24/34

25 5.6 Installation Notes The installation instructions for the open-loop lighting control system are reduced to notes about the installation of the sensor head: It must be directed outside or be installed outside the building. Its recording of the lighting level may not be influenced by seasonal variations such as leaves on the trees which stand between it and the sky or snow on the receiving lens. Its measurement may (for interior installation) also not be invalidated by the shutter. An installation behind the shutter or roller blind should be avoided where possible. The presence of shutters require a particular type of control: if proportionally-controlled shutters are present, the louvres of the shutters can be adjusted in parallel to the external brightness instead of the light. For an optimum adaptation of rooms that face different directions, it is advisable to use at least 2 differently positioned sensors: one in a south-east direction and another in a north-west direction. Large buildings may require even more sensors which should then be placed as perpendicular as possible to the respective façade and point upwards. 6 Brightness Control, combined with Master/Slave Control 6.1 Objective With combined open-loop/closed-loop lighting control, you are in general pursuing the aim of saving costs without having to relinquish the benefits of a partially true closed-loop control system. These can be: a simple setting procedure optimum lighting conditions in at least one position in the room always the correct lighting level in the rooms even when combined with light direction and sun protection systems. 6.2 Principle An internal sensor measures the lighting level of a surface that should be regulated as in closed-loop control which was described in detail above. The measured values of the sensor are further processed in a control program resulting in a control value which is used to trigger the actuator that is responsible for the direct light strip. To eliminate the requirement for further sensors (and also their deviation), it transfers a full control curve via offset adjustment to all other curves. The required offset adjustment can be determined by 2-3 simple measurements: at an artificial lighting level of 25%, 50% and 75%, the necessary offset of the controlled light strips is determined in comparison to the regulated strip to arrive at the required setpoint in lux. The largest recorded differential (upwards) per strip is then taken as this guarantees that the minimum lighting level never falls below the setpoint. Lighting Control Lighting Control_E0310a 25/34

26 6.3 Available Devices Since the offset adjustment is derived from the dimming value of a regulated dimming actuator, it would be possible for example to use the active status response (8 bit) of this type of dimming actuator and simply add it to the established offset in a function module or visualisation program. The newly specified control value would then be sent to the next controlled light strip via another group address. This procedure is however only advisable if the function module or visualisation program mentioned are also available or if there is a cost benefit in using them compared to a multi-layered lighting control system. In terms of device implementation, it is much simpler in any case to use multi-channel dimming actuators with an integrated sensor connection and controller application. It is also possible here to configure internal offset connections between the actuator channels so that fewer bus telegrams can be sent. This solution not only saves device addresses but also costs in general. 6.4 Parameterisation Example In the following example, 3 light strips in one room should be regulated or controller with a single dimming actuator and only one light sensor. A time-limited manual operation (switching/dimming) of all 3 channels should be possible using a 4-fold push button. The fourth rocker should switch all 3 dimming channels back to automatic mode. A special cleaning light function should also be implemented: when a further 1-fold push button is pressed, the light should be set to full brightness for 1 hour, the closed-loop/open-loop control should be deactivated and then everything should be switched off. Figure 21: Example of a complete 3-channel room control system with an automatic cleaning-light function: only 3 bus devices are required The following can also be detected in figure 21: emergency operating mode via local push buttons if the KNX should fail. In the case of the device shown, these push buttons have the additional function of triggering an automatic calibration of the respective sensor channel, if it acts as a master sensor in the closed-loop control. Lighting Control Lighting Control_E0310a 26/34

27 6.5 Installation and Solution Notes The most important factor in this option of open-loop/closed-loop lighting control is again the optimum selection of the installation place and the alignment of the sensors. The essential points have already been mentioned above but there is one additional factor: in combined closed-loop/open-loop control systems, it must be at least ensured, that in the situation of complete outdoor darkness all lights must be equally turned on to the same value (which should be ruled by the specification of the lighting system). A pure additive / subtractive offset control however means on the other hand, that the difference between the master and the slave will always be equal or less than the given value. The master dimming value can range between 0 and 100%, but the slave is limited to less than this due to the offset. That means: If e.g. slave 1 = master + 20% (master at the window side), and slave 2 = master + 40%, then both dependant rows can only be controlled in the range resp %. If the master has reached 0%, again we have 2 options: the slaves shut off together with the master, then it is too dark there, or they stay on, then it is too bright. But at least at full darkness all rows are at or above the required lux value setpoint. If you look at the same situation, but now with the master in row 3 (darkest area), with a negative offset to the slaves, this means, at high outdoor light levels the dimming works fine, but the closer you come to full darkness, the more unequal the distribution of light would be. In the end row 1 reaches only 60%, row 2 goes to 80%. That this is not the optimum, is self explanatory. So the only conclusion can be: The sensor must be mounted in the window side row which then also must be controlled via closed loop control! Underneath a couple of illustrations to this problem: Figure 22: optimized situation, but only at one point! Lighting Control Lighting Control_E0310a 27/34

28 Figure 23: same as above, but at more external light worst case situation! Figure 24: again same configuration, but at complete darkness rows 2 and 3 waste energy! What is the conclusion of the notes mentioned above? If the offset of the slave is positive, then it will always be able to reach 100%, but cannot dim down to 0%, it will turn off with the master. If it is negative, it can switch off, but not reach 100% of dimming level. So there is never a 100% positive solution as with individual light sensors per each row of luminaries. However, using the configuration with the master at the window, and the slaves with positive offsets in the inner parts of the room, will provide a good compromise. The only slight disadvantage is, that the master will either have to turn off late (at more than 500 lx, which avoids the gap, but causes a much higher level at darkness, or there will be a situation, when the master turns off at 500 lx, where rows 2 and 3 still would need some light, but will switch of with the master. Lighting Control Lighting Control_E0310a 28/34

29 This is an issue, which can be cured when a light controller with a dynamic offset control is used (a multiplicative offset instead of a constant one). In this case the slave follows the master via a linear function like this: S = M x ( 1 + O ). O : = Offset [%]; S = Dimvalue [%] Slave; M = Dimvalue Master [%]. It can easily be seen that at M = 100% and O > 0 the value of S reaches 100%. At very small values of M, however, the absolute difference between S and M will come close to 0! Figure 25: Light controller with multiplicative offset 7 Appendix Tasks 7.1 Task 1: Lighting Control dependent on External Light A room that is fitted with two light strips should receive a brightness control system. Up until now, the light strips have been switched and dimmed individually. The following are used: 1 x 2-fold switch sensor, switching and dimming objects (4 bit) 2 x switch/dim actuators, objects for switching, dimming, value setting and value status must be present. Group addresses for manual control: L1 Switch L2 Switch L1 Dim L2 Dim First put this simple series circuit into operation. The dimmable lighting in the room should now also be controlled by a brightness control module dependent on the external light. Lighting Control Lighting Control_E0310a 29/34

30 Figure 26: Lighting Control dependent on external light Required devices: Brightness sensor e.g. Siemens 5WG AB 02 to record the brightness level (external light) Brightness control module e.g. Siemens 5WG AB 01 2-fold push button Project design Define the following new group addresses Brightness value of sensor (control module, sensor) Calibration request (control module) Dimming value for calibration (control module) Brightness value for calibration (control module) L1 Value set (--> switch/dim actuator + control module) L2 Value set (--> switch/dim actuator + control module) L1 Value status (--> switch/dim actuator + control module) L2 Value status (--> switch/dim actuator + control module) Control L1 enable / block (2-fold push button, automatic) Control L2 enable / block (2-fold push button, automatic) Link the bus devices (Control 1 and 2 for L1 and L2). Check the read flag in the brightness sensor GE 253. Use the default parameter setting of the bus devices. Commissioning Put the brightness control module and brightness sensor into operation. You can now determine the control characteristics using the calibration objects. Lighting Control Lighting Control_E0310a 30/34

Busch-Watchdog Presence EIB Type: 6131-74-102-500

Busch-Watchdog Presence EIB Type: 6131-74-102-500 Type: 6131-74-102-500 Contents Technical data 2-2 Application programs (List) 2-3 Circuit diagrams 2-3 in combination with Bus coupler FM (6120-102): Switch Value Cyclic Monitoring /3 2-4 Switch Value

More information

ABB i-bus EIB Universal Interfaces US/U 4.2 US/U 2.2

ABB i-bus EIB Universal Interfaces US/U 4.2 US/U 2.2 Product Manual ABB i-bus EIB US/U 4.2 US/U 2.2 Intelligent Installation Systems Intelligent and limitless Contents Page 1 General............................................. 3 1.1 Product and functional

More information

Inwall 4 Input / 4 Output Module

Inwall 4 Input / 4 Output Module Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...

More information

How To Use A Power Supply On A Powerline 2.2 (Ai)

How To Use A Power Supply On A Powerline 2.2 (Ai) KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang

More information

ABB i-bus EIB Logic Module LM/S 1.1

ABB i-bus EIB Logic Module LM/S 1.1 Product Manual ABB i-bus EIB Logic Module LM/S 1.1 Intelligent Installation System Contents page 1 General... 3 1.1 About this manual... 3 1.2 Product and functional overview... 3 2 Device technology...

More information

Time functions. Functions of the relay. instabus EIB Application program description. September 2001. 12 A1 Binary 510D01

Time functions. Functions of the relay. instabus EIB Application program description. September 2001. 12 A1 Binary 510D01 September 2 2 A Binary 5D Product family: Product type: Manufacturer: Output Binary output, -fold Siemens Name: Load switch UP 5 Order no.: 5WG 5-2AB Functional description Using the application program

More information

Light scene push button 8gang comfort flush-mounted 751688xx

Light scene push button 8gang comfort flush-mounted 751688xx 751688xx Documentation Product name: Light scene push button 8gang comfort Design: flush-mounting type (Up) ETS search path: Push button / Push button general / Light scene push button 8gang comfort Functional

More information

Operating instructions II / 2004

Operating instructions II / 2004 Operating instructions II / 2004 Light and presence sensor TOUCH DIM LS/PD LI OSRAM GmbH Costumer-Service-Center (CSC) Steinerne Furt 62 86167 Augsburg, Germany www.osram.com www.osram.de Tel. : (+49)

More information

Movement/monitoring 1307/1.0 (6325xx)

Movement/monitoring 1307/1.0 (6325xx) /monitoring 1307/1.0 (6325xx) General In the following the device will be referred to as the movement detector. The movement block will only switch off when there is no more movement in front of the device

More information

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1

ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Product Manual ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Intelligent Installation Systems Contents Page 1 Introduction.......................................

More information

Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111

Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111 , GH Q631 0030 R0111 SK 0010 B 98 The application unit is a DIN rail mounted device for insertion in the distribution board. The connection to the EIB is established via a bus connecting terminal at the

More information

Unica for KNX system 226

Unica for KNX system 226 Unica for KNX system 6 P117504 Greater flexibility and comfort, better energy efficiency with KNX More and more electronic appliances are needed for modern comfortable homes that contain everything from

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

Inwall Room Temperature Unit

Inwall Room Temperature Unit Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall

More information

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx 756627xx, 756637xx, 756657xx Documentation Product name: Push button 2-, 3-, 5- gang RTR + display Design: UP (flush-mounting type) ETS search path: Push button / Push button xgang / Push button xgang

More information

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x B.IQ push button 3-5gang with room Product name: Design: ETS search path: B.IQ push button 3-, 4-, 5gang with room thermostat and display V2 Flush-mounted Push button / B.IQ / B.IQ push button xgang with

More information

ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1

ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1 Product manual ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1 Intelligent Installation Systems This manual describes the function of the DALI-Gateway DG/S 8.1 with the application program Dim Slave Lightscenes

More information

ABB i-bus KNX DALI-Gateway DG/S 8.1

ABB i-bus KNX DALI-Gateway DG/S 8.1 Product manual ABB i-bus KNX DALI-Gateway DG/S 8.1 Intelligent Installation Systems This manual describes the function of the DALI-Gateway DG/S 8.1 with the application program Dim Slave Lightscenes Dynamic

More information

1 Safety instructions. 2 Device components. 3 Function. Leader in Led solutions. Compact presence detector. Operating instructions

1 Safety instructions. 2 Device components. 3 Function. Leader in Led solutions. Compact presence detector. Operating instructions Compact presence detector Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause

More information

Operating instructions IV / 2007

Operating instructions IV / 2007 General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

Product Manual. ABB i-bus KNX. Universal Dim Actuator, MDRC UD/S 2.300.2. Intelligent Installation Systems ABB

Product Manual. ABB i-bus KNX. Universal Dim Actuator, MDRC UD/S 2.300.2. Intelligent Installation Systems ABB Product Manual ABB i-bus KNX Universal Dim Actuator, MDRC UD/S 2.300.2 Intelligent Installation Systems ABB UD/S 2.300.2 Universal Dim Actuator, MDRC This manual describes the function of the Universal

More information

Highly flexible the right KNX/DALI gateway for every requirement

Highly flexible the right KNX/DALI gateway for every requirement The worldwide standard for home and building control Highly flexible the right / gateway for every requirement Integrating lighting control into building control safely, efficiently and comfortably with

More information

KNX System Principles

KNX System Principles Application Module Bus Transceiver KNX b a T1 C1 T2 Left II Left On Left II Right Off Left X Left Off Left X Right On Left II Left On Left II Right Off Left X Left Off Left X Right On c b a c E2 Bus Cable

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

ABB i-bus EIB / KNX Room Controller

ABB i-bus EIB / KNX Room Controller Product Information ABB i-bus EIB / KNX Room Controller Intelligent Installation Systems The Concept One Room Controller per Room The Room Controller consists of a basis device, into which up to 8 selected

More information

Tebis application software

Tebis application software Tebis application software Input products / ON / OFF output / RF dimmer Electrical / Mechanical characteristics: see product user manual Product reference Product designation TP device RF devices WYC81xQ

More information

KNX Gateway RGK02-5023E-01

KNX Gateway RGK02-5023E-01 KNX Gateway RGK02-5023E-01 Table of contents Page 1 General Information 1.1 Technical data 5 1.2. Intended Use 6 1.3 Specifications 6 1.4 Compatibility 6 1.5 Scope of delivery 6 2 Information about the

More information

The ABB i-bus KNX Room Master Concept Your first step into the KNX world

The ABB i-bus KNX Room Master Concept Your first step into the KNX world The ABB i-bus KNX Room Master Concept Your first step into the KNX world The Room Master Concept 1 New Step 1,000 New Options You specialize in installing electrical systems. With the ABB Room Master,

More information

DALIX PROGRAMMING MANUAL. Gateway KNX-DALI V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com

DALIX PROGRAMMING MANUAL. Gateway KNX-DALI V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com Gateway KNX-DALI DALIX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 ingeniumsl@ingeniumsl.com www.ingeniumsl.com

More information

PRESENCE DETECTOR PD-C360i/24 KNX ECO (EP10425844)

PRESENCE DETECTOR PD-C360i/24 KNX ECO (EP10425844) In the Master function, the remote control entries will be acknowledged as follows: acknowledged 3 x with the red LED In the Slave function, each detection is acknowledged 2 x with the green LED. 6 TEST

More information

basicdim DGC Compact control module

basicdim DGC Compact control module luxctrol lighting control sstem DGC Compact control module Product description Compact dimensions for luminaire installation For up to 0 DSI or LI ballasts ( per output channel) LI IN input LI/DSI output

More information

ABB i-bus EIB / KNX Weather Station WS/S 4.1

ABB i-bus EIB / KNX Weather Station WS/S 4.1 Product Manual ABB i-bus EIB / KNX Weather Station WS/S 4.1 Intelligent Installation Systems This manual describes the function of the Weather station WS/S 4.1. Subject to changes and errors excepted.

More information

KNX Powerline PL 110. KNX Association

KNX Powerline PL 110. KNX Association KNX Powerline PL 110 Table of Contents 1 Introduction...3 2 Standardisation...3 3 Transmission Process...4 3.1 Phase Coupling...5 3.2 Telegram Transmission...6 3.2.1 Training Sequence...6 3.2.2 Preamble

More information

PRODUCT MANUAL IRSC. IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC. Program version: 5.14 Manual edition: 5.14_a

PRODUCT MANUAL IRSC. IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC. Program version: 5.14 Manual edition: 5.14_a PRODUCT MANUAL IRSC IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC Program version: 5.14 Manual edition: 5.14_a INDEX Document updates... 3 1. Introduction... 4 1.1. IRSC controller... 4 1.2. Installation...

More information

ZME_WALLC-S Z-Wave Secure Wall Controller

ZME_WALLC-S Z-Wave Secure Wall Controller ZME_WALLC-S Z-Wave Secure Wall Controller Firmware Version : 1.0 Quick Start S This device operates as Z-Wave sensor in two modes: the normal control mode (daily use) or in management mode for setup. Pushing

More information

PRODUCT MANUAL. InZennio Z38i. KNX Touch Panel ZN1VI-TP38i. Program version: 2.2 Manual edition: a

PRODUCT MANUAL. InZennio Z38i. KNX Touch Panel ZN1VI-TP38i. Program version: 2.2 Manual edition: a PRODUCT MANUAL InZennio Z38i KNX Touch Panel ZN1VI-TP38i Program version: 2.2 Manual edition: a INDEX Document updates... 3 1. Introduction... 4 1.1. InZennio Z38i... 4 1.2. Installation... 5 2. Configuration...

More information

Operating instructions

Operating instructions Operating instructions DALI BASIC lighting control system Type: DALI RC BASIC SO OSRAM GmbH Hellabrunner Str. 1 D 81536 Munich Tel.: +49 89 6213 0 Fax: +49 89 6213 2020 Customer Service Center (KSC) Germany

More information

Basics of Dimming. ISC Learning Centre

Basics of Dimming. ISC Learning Centre ISC Learning Centre July 2009 > Dimmers Contents What is a dimmer? Dimmers & customer benefits Dimmers at home Dimmers at the office Dimmers: technical choices Overview of the Schneider Electric offer

More information

ABB i-bus KNX Application Manual Lighting

ABB i-bus KNX Application Manual Lighting Application Manual Lighting Description of the symbols: Sample Note Tip Disadvantage Advantage Table of content Table of content Page Preface/ General... 3 1. Introduction 1.1. Basic control types...5

More information

ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8

ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8 ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8 Quick Start A This device is a Z-Wave Actuator. Triple click one of the buttons on the device will include the device.

More information

PRODUCT MANUAL LUMENTO X4 LED. LED Controller ZN1DI-RGBX4. Program version: 1.0 Manual edition: a

PRODUCT MANUAL LUMENTO X4 LED. LED Controller ZN1DI-RGBX4. Program version: 1.0 Manual edition: a PRODUCT MANUAL LUMENTO X4 LED LED Controller ZN1DI-RGBX4 Program version: 1.0 Manual edition: a INDEX 1. Introduction...3 1.1. Lumento X4... 3 1.2. Installation... 4 2. Configuration...6 3. ETS Parameterization...7

More information

DALI RC BASIC SO. Control unit Operating instructions

DALI RC BASIC SO. Control unit Operating instructions DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness

More information

ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1

ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1 Product Manual ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1 Intelligent Installation Systems This manual describes the function of the Switch

More information

Transmitter Actuator 230V wave UP 560. Operation

Transmitter Actuator 230V wave UP 560. Operation Transmitter ctuator 230V wave UP 560 5WG3 560-201 Product- and pplication Description Diagram The transmitter actuator 230V wave UP 560 (Diagram ) is a flush-mounted device with radio communication for

More information

DIGITAL-TO-ANALOGUE AND ANALOGUE-TO-DIGITAL CONVERSION

DIGITAL-TO-ANALOGUE AND ANALOGUE-TO-DIGITAL CONVERSION DIGITAL-TO-ANALOGUE AND ANALOGUE-TO-DIGITAL CONVERSION Introduction The outputs from sensors and communications receivers are analogue signals that have continuously varying amplitudes. In many systems

More information

Display Board Pulse Width Modulation (PWM) Power/Speed Controller Module

Display Board Pulse Width Modulation (PWM) Power/Speed Controller Module Display Board Pulse Width Modulation (PWM) Power/Speed Controller Module RS0 Microcontroller LEDs Motor Control Pushbuttons Purpose: To demonstrate an easy way of using a Freescale RS0K2 microcontroller

More information

IDDERO HOME SERVER. Quick start guide. www.iddero.com 150302-02

IDDERO HOME SERVER. Quick start guide. www.iddero.com 150302-02 IDDERO HOME SERVER Quick start guide www.iddero.com 150302-02 TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IDDERO CONFIGURATION SOFTWARE... 3 2.1 Installation and First Steps...3 3 IDDERO HOME SERVER CONFIGURATION...

More information

EBDSPIR-DD, EBDSPIR-DD-IP

EBDSPIR-DD, EBDSPIR-DD-IP Product Guide EBDSPIR-DD, EBDSPIR-DD-IP Ceiling PIR presence detector DALI / DSI dimming Overview The EBDSPIR-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with

More information

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5 T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,

More information

Introduction. In this Self-study Programme we will explain to you the design and function of the CAN data bus. SSP 186/01

Introduction. In this Self-study Programme we will explain to you the design and function of the CAN data bus. SSP 186/01 Introduction The requirements relating to driving safety, driving comfort, exhaust emissions and fuel economy are are becoming ever more stringent. This entails more intensive information exchange between

More information

Technology. Presence Detectors. Presence Detection. Light Measurement. Configurations

Technology. Presence Detectors. Presence Detection. Light Measurement. Configurations Technology Presence Detectors Presence Detection Light Measurement Configurations Theben AG Hohenbergstrasse 32 72401 Haigerloch Phone +49 (0) 74 74 692-0 Fax +49 (0) 74 74 692-150 info@theben.de 1104008602/03.10

More information

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, 18 80 W Compact and T5c fluorescent lamps

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, 18 80 W Compact and T5c fluorescent lamps EXCEL oneall series Product description Noise-free precise control via DSI signal, switchdim, corridorfunction or DALI DALI-MEMORY Extended DALI commands CELMA energy class A1 1) Interfaces DALI DSI switchdim

More information

ETS4 Diagnostics. KNX Association

ETS4 Diagnostics. KNX Association ETS4 Diagnostics Table of Contents 1 Diagnostics and fault location... 3 2 Diagnostics: Individual addresses...... 4 2.1 Devices in Programming Mode... 4 2.2 Checking if an address exists and locating

More information

Shutter Actuator, 8-fold, 230 V AC, MDRC JA/S 8.230.1, GH Q631 0063 R0111. ABB i-bus EIB / KNX

Shutter Actuator, 8-fold, 230 V AC, MDRC JA/S 8.230.1, GH Q631 0063 R0111. ABB i-bus EIB / KNX , GH Q631 0063 R0111 2CDC 071 238 F0003 For controlling a maximum of eight independent 230 V AC shutter or sunblind drives via ABB i-bus including the functions Up/Down, Step/Stop, Move to position, Sun

More information

Technical Manual MDT Rain sensor

Technical Manual MDT Rain sensor 9/2012 Technical Manual MDT Rain sensor SCN-RS1R1.01 Technical Manual Rain sensor SCN RS1R1.01 1.1. Settings at the ETS Software Selection at the product database: Manufacturer: MDT Technologies Product

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

WIRELESS INSTRUMENTATION TECHNOLOGY

WIRELESS INSTRUMENTATION TECHNOLOGY BS&B WIRELESS, L.L.C. BS&B WIRELESS, L.L.C. WIRELESS INSTRUMENTATION TECHNOLOGY Printed February 2004 BS&B WIRELESS, L.L.C. 7422-B East 46th Place, Tulsa, OK74145 Phone: 918-622-5950 Fax: 918-665-3904

More information

EBDSPIR-PRM, EBDSPIR-PRM-IP

EBDSPIR-PRM, EBDSPIR-PRM-IP Product Guide EBDSPIR-PRM, EBDSPIR-PRM-IP Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads with optional

More information

Radio sensor powered by a mini solar cell the EnOcean STM 110 now functions with even less light

Radio sensor powered by a mini solar cell the EnOcean STM 110 now functions with even less light Radio sensor powered by a mini solar cell the EnOcean STM 110 now functions with even less light In this issue, we would like to present the EnOcean radio sensor module STM 110 in more detail. The module

More information

So far we have investigated combinational logic for which the output of the logic devices/circuits depends only on the present state of the inputs.

So far we have investigated combinational logic for which the output of the logic devices/circuits depends only on the present state of the inputs. equential Logic o far we have investigated combinational logic for which the output of the logic devices/circuits depends only on the present state of the inputs. In sequential logic the output of the

More information

MAS.836 HOW TO BIAS AN OP-AMP

MAS.836 HOW TO BIAS AN OP-AMP MAS.836 HOW TO BIAS AN OP-AMP Op-Amp Circuits: Bias, in an electronic circuit, describes the steady state operating characteristics with no signal being applied. In an op-amp circuit, the operating characteristic

More information

ELABOTrainingsSysteme. Aus- und Weiterbildung GmbH. Home and Building Control KNX / EIB. www.elabo-ts.com

ELABOTrainingsSysteme. Aus- und Weiterbildung GmbH. Home and Building Control KNX / EIB. www.elabo-ts.com Aus- und Weiterbildung GmbH Home and Building Control KNX / EIB www.elabo-ts.com Design and commissioning of KNX/EIB systems www.elabo-ts.com Hardware page 2-5 Software page 6-9 Projects page 10-15 LOGO!

More information

G-100/200 Operation & Installation

G-100/200 Operation & Installation G-100/200 Operation & Installation 2 Contents 7 Installation 15 Getting Started 16 GPS Mode Setup 18 Wheel Sensor Mode Setup 20 Fuel Calibration 23 Basic Operation 24 Telemetery Screen 27 Entering a Distance

More information

Product Information. Gateway For Connecting EnDat Encoders to PROFIBUS-DP

Product Information. Gateway For Connecting EnDat Encoders to PROFIBUS-DP Product Information Gateway For Connecting EnDat Encoders to PROFIBUS-DP April 2012 PROFIBUS Gateway For Connecting EnDat Encoders Encoders with EnDat interface for connection via gateway All absolute

More information

ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1

ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1 Product Manual ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1 Intelligent Installation Systems This manual describes the function of the EIB monitoring module EUB/S 1.1 with the Application program

More information

DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions

DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions DAI DIM/COVERTER COTRO (DC V) 1 10V (0-10 V) analog DAI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions Dim-and Switch Functions: The DAI Dim/Converter Control DC V is suitable

More information

ABB i-bus KNX i-bus Tool Product Information

ABB i-bus KNX i-bus Tool Product Information ABB i-bus KNX i-bus Tool Product Information A professional Service Tool for System Integrators ABB presents a fully new and innovative software concept with the i-bus Tool. It supports system integrators

More information

A Design of a PID Self-Tuning Controller Using LabVIEW

A Design of a PID Self-Tuning Controller Using LabVIEW Journal of Software Engineering and Applications, 2011, 4, 161-171 doi:10.4236/jsea.2011.43018 Published Online March 2011 (http://www.scirp.org/journal/jsea) 161 A Design of a PID Self-Tuning Controller

More information

7. Latches and Flip-Flops

7. Latches and Flip-Flops Chapter 7 Latches and Flip-Flops Page 1 of 18 7. Latches and Flip-Flops Latches and flip-flops are the basic elements for storing information. One latch or flip-flop can store one bit of information. The

More information

INTERFERENCE OF SOUND WAVES

INTERFERENCE OF SOUND WAVES 2011 Interference - 1 INTERFERENCE OF SOUND WAVES The objectives of this experiment are: To measure the wavelength, frequency, and propagation speed of ultrasonic sound waves. To observe interference phenomena

More information

Configuration example: Scene function in the actuator channel in the ETS. 1 Introduction

Configuration example: Scene function in the actuator channel in the ETS. 1 Introduction Introduction Introduction: KNX actuators offer an amazing number of configuration options. Anything from simple feedback function using elapsed-hours meters up to complex scenes can be activated in the

More information

Software Manual RS232 Laser Merge Module. Document # SU-256521-09 Rev A

Software Manual RS232 Laser Merge Module. Document # SU-256521-09 Rev A Laser Merge Module Document # SU-256521-09 Rev A The information presented in this document is proprietary to Spectral Applied Research Inc. and cannot be used for any purpose other than that for which

More information

Instruction Manual Service Program ULTRA-PROG-IR

Instruction Manual Service Program ULTRA-PROG-IR Instruction Manual Service Program ULTRA-PROG-IR Parameterizing Software for Ultrasonic Sensors with Infrared Interface Contents 1 Installation of the Software ULTRA-PROG-IR... 4 1.1 System Requirements...

More information

Product Manual. ABB i-bus KNX Data Logging Unit BDB/S 1.1. Intelligent Installation Systems ABB

Product Manual. ABB i-bus KNX Data Logging Unit BDB/S 1.1. Intelligent Installation Systems ABB Product Manual ABB i-bus KNX Data Logging Unit BDB/S 1.1 Intelligent Installation Systems ABB This manual describes the function of the Data Logging Unit BDB/S 1.1. Subject to changes and errors excepted.

More information

Agilent AN 1316 Optimizing Spectrum Analyzer Amplitude Accuracy

Agilent AN 1316 Optimizing Spectrum Analyzer Amplitude Accuracy Agilent AN 1316 Optimizing Spectrum Analyzer Amplitude Accuracy Application Note RF & Microwave Spectrum Analyzers Table of Contents 3 3 4 4 5 7 8 8 13 13 14 16 16 Introduction Absolute versus relative

More information

The Answer to the 14 Most Frequently Asked Modbus Questions

The Answer to the 14 Most Frequently Asked Modbus Questions Modbus Frequently Asked Questions WP-34-REV0-0609-1/7 The Answer to the 14 Most Frequently Asked Modbus Questions Exactly what is Modbus? Modbus is an open serial communications protocol widely used in

More information

Push button 3gang standard flush-mounted 751633xx

Push button 3gang standard flush-mounted 751633xx Documentation Product name: Push button 3gang standard Design: device (up) ETS search path: Push button / Push button 3gang / Push button 3gang standard Functional description: The push button 3gang standard

More information

KNX L. Brightness Sensor. Technical specifications and installation instructions Item number 70119

KNX L. Brightness Sensor. Technical specifications and installation instructions Item number 70119 EN KNX L Brightness Sensor Technical specifications and installation instructions Item number 70119 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49 (0) 70

More information

Glass sensor 2gang with room thermostat Glass sensor 3gang with room thermostat

Glass sensor 2gang with room thermostat Glass sensor 3gang with room thermostat KNX/EIB Product documentation Glass sensor 2gang with room thermostat Glass sensor 3gang with room thermostat Issue: 16.01.2009 65750120 Page 1 of 240 KNX/EIB Product documentation Content 1 Product definition...

More information

contents Leading the way in intelligent automation INELS Wireless? Why Click Accessories Complete control

contents Leading the way in intelligent automation INELS Wireless? Why Click Accessories Complete control Wireless Control Systems Accessories Leading the way in intelligent automation contents Range Overview Typical Installations Transmitters Combined Modules Accessories Programming Switching & Dimmer Functions

More information

T0118 T2118 T3118. Instruction Manual

T0118 T2118 T3118. Instruction Manual Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity

More information

Alignment Laser System.

Alignment Laser System. - O T 6 0 0 0 Alignment Laser System. The OT-6000. Multi -Target,Two Dimensional Alignment. Introducing the most powerful way to measure alignment at distances up to 300 feet. The OT-6000 Alignment Laser

More information

PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, 18 80 W Compact and T5c fluorescent lamps

PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, 18 80 W Compact and T5c fluorescent lamps Product description Noise-free precise control via DSI signal or switchdim CELMA energy class A1 1) Interfaces DSI switchdim Integrated SMART-Interface Functions Optimum filament heating in any dimmer

More information

Green Building Handbook for South Africa Chapter: Lighting Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Lighting Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Lighting Luke Osburn CSIR Built Environment Lighting consumes between about 29-35% of the energy used within commercial office space while lighting only

More information

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184 EN KNX TH65-AP Thermo-Hygrometer Technical specifications and installation instructions Item number 70184 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49

More information

EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS

EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS 1 EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS The oscilloscope is the most versatile and most important tool in this lab and is probably the best tool an electrical engineer uses. This outline guides

More information

KNX L. Brightness Sensor. Installation and Adjustment. Item number 70119

KNX L. Brightness Sensor. Installation and Adjustment. Item number 70119 EN KNX L Brightness Sensor Item number 70119 Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical specifications... 3 2. Installation and commissioning... 4 2.1. Installation notes...

More information

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel

THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING R.M.J. Bokel Department of Architecture, Delft Technical University, Delft, The Netherlands,

More information

MAVO-MONITOR / MAVO-SPOT Instrument Set for Contact or Distant Measurements of Luminances

MAVO-MONITOR / MAVO-SPOT Instrument Set for Contact or Distant Measurements of Luminances Operating Instructions MAVO-MONITOR / MAVO-SPOT Instrument Set for Contact or Distant Measurements of Luminances 15043 1/1.00 10 9 8 1 7 6 1 Display 2 Slider switch cd/m² segment test 3 ON/OFF switch 4

More information

SINGLE-SUPPLY OPERATION OF OPERATIONAL AMPLIFIERS

SINGLE-SUPPLY OPERATION OF OPERATIONAL AMPLIFIERS SINGLE-SUPPLY OPERATION OF OPERATIONAL AMPLIFIERS One of the most common applications questions on operational amplifiers concerns operation from a single supply voltage. Can the model OPAxyz be operated

More information

IDDERO HCx-KNX TOUCH PANELS. Quick start guide. www.iddero.com 130125-02

IDDERO HCx-KNX TOUCH PANELS. Quick start guide. www.iddero.com 130125-02 IDDERO HCx-KNX TOUCH PANELS Quick start guide www.iddero.com 130125-02 TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IDDERO CONFIGURATION SOFTWARE... 3 2.1 Installation and First Steps...3 3 TOUCH PANEL CONFIGURATION...

More information

The software beyond the climatic. Environment simulation

The software beyond the climatic. Environment simulation Spirale 2 The software beyond the climatic Environment simulation Spirale 2... Take it easy! Spirale 2 is a new software, based on a reliable system (Windows NT) and if its performances are surprising,

More information

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com Integrations LGAC-KNX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 ingeniumsl@ingeniumsl.com www.ingeniumsl.com

More information

Absolute and relative humidity Precise and comfort air-conditioning

Absolute and relative humidity Precise and comfort air-conditioning Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No

More information

B/S/H/ Error codes and service programmes PH

B/S/H/ Error codes and service programmes PH 1 ERROR CODES AND APPLIANCE MESSAGES... 3 1.1 Complete overview of all error codes (in order)... 3 Automatic switch-off... 3 Display is dark and any individual LEDs are lit... 3 E 005... 3 E 011... 3 E

More information

PCM Encoding and Decoding:

PCM Encoding and Decoding: PCM Encoding and Decoding: Aim: Introduction to PCM encoding and decoding. Introduction: PCM Encoding: The input to the PCM ENCODER module is an analog message. This must be constrained to a defined bandwidth

More information

APPLICATION NOTES: Dimming InGaN LED

APPLICATION NOTES: Dimming InGaN LED APPLICATION NOTES: Dimming InGaN LED Introduction: Indium gallium nitride (InGaN, In x Ga 1-x N) is a semiconductor material made of a mixture of gallium nitride (GaN) and indium nitride (InN). Indium

More information

DME4 V1.23 (06-1999) V1.30 (06-2000) V1.31 (04-2001) V1.32 (09-2001) V1.33 (03-2002) V1.34 (06-2003) V1.35 (05-2004) V2.00 (12-2005) V2.

DME4 V1.23 (06-1999) V1.30 (06-2000) V1.31 (04-2001) V1.32 (09-2001) V1.33 (03-2002) V1.34 (06-2003) V1.35 (05-2004) V2.00 (12-2005) V2. DME4 V1.23 (06-1999) - Correction of unfounded error message 'No measurements configured' when reading measurements from DME440 (MODBUS) if special measurands hadn't been selected to be calculated. - Correction

More information

(Refer Slide Time: 2:03)

(Refer Slide Time: 2:03) Control Engineering Prof. Madan Gopal Department of Electrical Engineering Indian Institute of Technology, Delhi Lecture - 11 Models of Industrial Control Devices and Systems (Contd.) Last time we were

More information