4/6.1/EN/3. Smoke Detector. Type RM-O-VS. Approved by the German Institut für Bautechnik

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "4/6.1/EN/3. Smoke Detector. Type RM-O-VS. Approved by the German Institut für Bautechnik"

Transcription

1 4/6.1/EN/3 Smoke Detector Type RM-O-VS pproved by the German Institut für Bautechnik

2 Contents Technical Data Contents Technical Data 2 Description pplication 3 Installation Instructions 4 Circuit Diagram Wiring Diagrams 5 Overview of Functions 6 Inspection and Maintenance 7 Order Details 8 Smoke detector with power supply, monitoring electronics, smoke alarm and air velocity monitor Connection (plug socket) for diagnostic instrument Push button Test/Reset Green System Monitoring Red larm Yellow Pollution Monitoring Blue ir Velocity Monitoring Remote control terminal Diagnostic instrument Note: Smoke detectors type RM-O-VS require maintenance only once per year due to the increased safety monitoring function. Smoke Detector Terminal Type RM-0-VS Type T-RM-0-VS Diagnostic Instrument Type D-RM-0-VS Terminal Type T-RM-0-VS/1 Technical Data Supply voltage: 230 V, 50/60 Hz Power consumption: max 25 V Enclosure rating: IP 42 Permitted ambient temperature: + 10 C to + 60 C Permitted air velocity in ventilation duct: 1 m/s to 20 m/s Permitted relative humidity: 0 90% relative humidity (condensation and water vapour can cause false alarms) Warning limit for air flow: 2 m/s Warning limit for high pollution: > 70 ± 10 units System monitoring: electric fault EMC: interference suppression to EN and Weight: 1,5 kg Scope of Supply Visual smoke alarm, power supply, switched relay, signal lights (), pushbutton, remote control and diagnostic instrument connection, electronic monitor, integrated in a plastic housing, wired ready for connection to snap terminals, drilling template and fixing materials. vailable accessories: Diagnostic instrument type D-RM-O-VS to scan pollution level, measurement range 0 to 100 units; hand held unit with 1m long connecting lead and plug, battery supply 9 V. Remote control terminal type T-RM-O-VS surface mounting or type T-RM-O-VS/1 panel mounting (size 48 x 96 x 63) with s for alarm, air flow, pollution and system monitoring; plug socket connection for diagnostic instrument type D-RM-O-VS and pushbutton for test/reset function. 2

3 nschluß Test / Rückstellung Diagnosegerät Diagnostic link Reset Terminal T-RM-O-VS zur Rauchauslöseeinrichtung RM-O-VS Elektronik Rauch / Smoke Schmutz / Pollution Betrieb / Operation larm / Störung / Failure Luft / ir >70% v < 2m/sec nschluß Test Diagnosegerät Rückstellung / Diagnostic link Reset Gebrüder Trox GmbH D Neukirchen-Vluyn Telefon / Telefax / Elektronik Rauch / Schmutz / Smoke Pollution Betrieb / Operation larm / Störung / Failure Luft / ir >70% v <2m/sec Description pplication Description The smoke detector works on the optical light scattering principle and is used to monitor the ventilation duct in air conditioning systems. When used with a fire damper, it prevents cold smoke with a temperature of 72 C from propagating through the C system. In the function mode, the smoke alarm of the smoke detector is permanently flushed by the air flow in the duct being monitored. If the smoke density exceeds a specific concentration, the smoke alarm breaks the power circuit to the control device of the fire damper; and the damper closes. To ensure the specified function, the smoke detector is also fitted with an air velocity sensor which monitors the air flow in the immediate vicinity of the smoke alarm. lack of air flow, eg. caused by a closed damper or fan failure, is signalled by an and opening relay contact. The electrical safety circuits of the smoke detector are constantly checked electronically and signalled on failure by an and closing relay contact. t the same time, the opening of the alarm relay contact interrupts the control circuit and the fire damper closes. To avoid false alarms due to pollution, the smoke alarm sampling chamber is continuously monitored electronically. If a permitted threshold of > 70 ± 10 units is exceeded, a signal is given by an and closing relay contact. The actual pollution value can be scanned directly at the smoke detector or on the remote control terminal using the diagnostic instrument. Installation of a remote control terminal enables the electrical function tests to be carried out from a central point, e.g. fire control room Rauchauslöseeinrichtung Typ RM-O-VS irflow v = 1-20 m/s Smoke detector with power supply, monitoring electronics, smoke alarm and air velocity monitor Remote control terminal Diagnostic instrument Fire damper Spring return actuator Central control point Typ D-RM-0-VS pplication ll fire dampers fitted with electric or electric/pneumatic control devices which operate when voltage is removed may be controlled via the smoke detector. This is recorded in the general building authority permits for Trox fire damper. The smoke detectors are marked with the U symbol in accordance with the pproval Mark regulations in Germany. The external verification prescribed by law is carried out by VdS e.v, Cologne. 3

4 Installation Instructions Installation Instructions The smoke detector must be installed on a vibration-free surface, in an area of the duct to be monitored having a uniform air flow over the smoke alarm during normal operation. ttach the drilling template to the centre of the air duct (H/2) and drill holes. Remove housing cover. ttach housing to air duct. For visual inspection or to replace the smoke alarm, an inspection opening should be provided on the upper or lower side of the air duct. Optional electrical connections (mains connection and connection to control device of fire damper) should be such that the entire smoke detector can be removed to replace the smoke alarm. The smoke alarm can be released from its lock by turning anti-clockwise. When re-inserted it is locked by turning clockwise. Connect control device of fire damper to the smoke detector (terminal strip L 3 ). Connect to mains. Connect remote control terminal (if required); connection lines: twin core telephone cable. Fit housing cover Smoke detector with power supply, monitoring electronics, smoke alarm and air velocity monitor. 1.1 Housing cover ir duct provided by others Drilling template Fixing screw Inspection opening by others Electrical connections ir intake opening (Distance from internal side of the ventilation duct) Ø 90 ir flow direction Luftrichtung 1.1 H/2 H Rauchauslöseeinrichtung Typ RM-O-VS 4

5 Circuit Diagram Wiring Diagrams The entire electrical installation must be in accordance with VDE and the local EVU regulations. Fig 1 Fig 2 Fig 3 Fig 4 Connection diagram for smoke detector (fire damper closed) Installation without separate power supply to DC control device on the fire damper to be controlled, maximum load: 8 W / 24 V- Installation with separate power supply for control device on the fire damper to be controlled, maximum switched power 250 V / 10 or 24 V- / 200 W Special installation (voltage on to operate principle) without separate power supply to C control device on the fire damper to be controlled, maximum switched power 250 V / 10 Fig 1 24 V V 50/60 Hz L L N N PE Smoke detector type type RM-0-VS F 1 b b Velocity monitor Smoke alarm L 1 L 4 L 3 L 9 L 7 L Fig 2 L L N N PE b 4 b 2 Remote control Type: T-RM-0-VS Type: T-RM-0-VS/1 L 1 L 4 L 3 Fig 3 Fig 4 B 2 L L N N PE L 1 L L N N PE L 1 B 1 L 4 L L L 3 L (+) N ( ) PE L 1 Mains connection 230V 50/60 Hz L 3 Control device connection (volt-free) Switched power 250 V / 10 or 24 V- / 200 W L 4 Connection of external control max 8 W / 24 V- Connection for 24 V- external supply: Residual wave max 2 %; Consumption min 520 m; Without 8 W consumption 190 m L 9 L 9 /1-2 air velocity monitoring (volt-free)*, L 9 /3-4 pollution monitoring (volt-free)*, L 9 /5-6 system monitoring (volt-free)* * Switched power 110 V/4, 24 V-/100 W L 7/L 10 Connection for remote control type T-RM-O-VS or T-RM-O-VS/1; for remote control, remove link L 7 /1-2 b 1 b2 Pushbutton test/reset b 3 b4 Connection (plug socket) for diagnostic instrument type D-RM-O-VS F1 Fuse 500 mt B1 Link (by others) for connecting 230 V, 50/60 Hz detector B2 Link (by others) for connecting 24 V- control device max 8 Watts Control device for fire damper (C or DC) For parallel control 5

6 Overview of Functions Fire damper Operating Mode / Event Red larm Blue Velocity Monitoring Yellow Pollution Monitoring Green System Monitoring Open Closed Signal Terminal Strip L Terminal Strip L Terminal Strip L Terminal Strip L Mains connected Function status Mains not connected Mains connected, faulty electronics or link L 7 /1-2 or remote control or smoke alarm not fitted Pollution Level 1) 70 units 100 units relay contact: relay contact: 2) 2) Test / Reset Inspection Smoke / Pollution 1) 100 units 3) larm status With air flow: on Without air flow: off 1) Pollution corresponding to diagnostic instrument display: Up to 70 units Normal range 70 units Warning level 100 units larm status 2) May indicate a transitional state, e.g. caused by a cloud of dust 3) n alarm triggered by smoke (event or maintenance) can only be cancelled by pressing the button after the smoke alarm head has cleared of smoke. : on : flashing : off 6

7 Inspection and Maintenance Function Test Smoke detectors must be inspected every 3 months after commissioning of the air conditioning system and maintenance carried out at yearly intervals. Inspection and maintenance can be carried out at the same time. Inspection Pressing the Test/Reset button on the smoke detector or on the remote control terminal interrupts the circuit to the control device on the fire damper which then closes. On releasing the button, fire dampers with actuators automatically return to the open position. Fire dampers with solenoid or magnet release must be opened locally by hand. The fouling of the smoke alarm can be scanned directly on the smoke detector using the diagnostic instrument and/or via the remote control terminal. For signal indication, see overview of functions, page 6. pprox pprox Test tube for checking response/function (by others) Smoke detector with power supply, monitoring electronics, smoke alarm and air velocity monitor Connection (plug socket) for diagnostic instrument Pushbutton Test/Reset Green System Monitoring Red larm Yellow Pollution Monitoring Blue ir Velocity Monitoring ir duct supplied by others Maintenance Check the following: pplication and installation position (during commissioning and after system changes) Correct electrical connections and no loose wires in terminals Electrical interaction of signal emitter, display and control devices on fire damper Response of smoke alarm to smoke aerosol, e.g. cigarette smoke or smoke from smoke cartridge. When the permitted concentration limit is exceeded, the smoke alarm interrupts the circuit to the control device on the fire damper to be controlled and the damper closes Check response of air velocity monitor, e.g. switch off fan Eliminating Faults If inspection or maintenance has revealed any faults, these must be repaired immediately. Faulty components must be replaced only by original Trox spare parts. Only the manufacturer may make repairs to the smoke detector. If a function test reveals that the smoke detector is working correctly but the fire damper to be controlled is not closing, the control device on the damper and the damper itself must be checked for operation. For signal indication see overview of function, page 6. 7

8 Order Details Order Code RM-O-VS Description Smoke detector (smoke detection using optical light scattering principle) with general building supervision approval from the Institut für Bautechnik Berlin, for fire dampers with electric or electric/ pneumatic control device (voltage off to operate), suitable for protection against smoke transmission in air conditioning systems, even with cold smoke t 72 C; suitable for air velocities of 1 m/s to 20 m/s. With additional functions for monitoring the air flow in the measurement area of the smoke alarm, the pollution level on the smoke alarm sampling chamber and the system electronics (maintenance once/year). Order Example Make: TROX Type: RM-O-VS Quantity: 5 Scope of supply: see page 2. Order Code D-RM-O-VS Design changes reserved ll rights reserved Gebrüder Trox GmbH (10/2000) Description: Diagnostic instrument for smoke detector RM-O-VS to scan pollution level. Measurement range units; hand unit with 1m long connection lead and plug; battery supply 9 V. Order Code Description: Remote control terminal for smoke detector RM-O-VS for surface mounting or panel mounting (size 48 x 96 x 63) with signal s for alarm, air flow, pollution and system monitoring; socket connection for diagnostic instrument D-RM-O-VS and pushbutton for test/reset function. Order example Make: TROX Type: D-RM-O-VS Quantity: 1 T-RM-O-VS or T-RM-O-VS/1 Order Example Make: TROX Type: T-RM-O-VS or T-RM-O-VS/1 Quantity: 5 8

Smoke exhaust systems

Smoke exhaust systems 1 Fire zone, e.g. hall 2 Smoke exhaust zone, separated by smoke curtains Natural and mechanical smoke extraction General information 3 Natural smoke and heat exhaust vent 4 Air inlet opening or wake max.

More information

ABB i-bus KNX Keypad for GM/A 8.1, SM BT/A 1.1, 2CDG280001R0011

ABB i-bus KNX Keypad for GM/A 8.1, SM BT/A 1.1, 2CDG280001R0011 Technical data 2CDC513072D0201 ABB i-bus KNX Product description The BT/A 1.1 Keypad is used to operate and display the GM/A 8.1 KNX Security Panel. The display is used to show information about system

More information

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases

More information

Gasmesscomputer GMC from Version 1.0. Output Extension RK Data Sheet. Gas Detection and Warning Systems

Gasmesscomputer GMC from Version 1.0. Output Extension RK Data Sheet. Gas Detection and Warning Systems Gasmesscomputer GMC 8420 from Version 1.0 Output Extension RK 8420 Gas Detection and Warning Systems Application The controller Gasmesscomputer GMC 8420, in conjunction with detectors that supply 4-20

More information

Product Manual. ABB i-bus EIB / KNX Security Module SCM/S 1.1. Intelligent Installation Systems ABB

Product Manual. ABB i-bus EIB / KNX Security Module SCM/S 1.1. Intelligent Installation Systems ABB Product Manual ABB i-bus EIB / KNX Security Module SCM/S 1.1 Intelligent Installation Systems ABB Security Module, MDRC, type SCM/S 1.1 Contents Page 1 General 4 1.1 System overview...4 1.2 Product and

More information

Wireless Detection System with unique detectors for smaller applications

Wireless Detection System with unique detectors for smaller applications Wireless Detection System with unique detectors for smaller applications RCP6 B wireless fire control panel microprocessor controlled 433 MHz 6 zones up to 100 radio addressable devices linkable 4 potential-free

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

Installation Instructions

Installation Instructions CRSMKKIT002A00 CRSMKSEN002A00 FIELDINSTALLEDSMOKEDETECTORS FOR MEDIUM ROOFTOP UNITS 12.5to25TONS Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 SAFETY CONSIDERATIONS... 1 GENERAL...

More information

Operating instructions IV / 2007

Operating instructions IV / 2007 General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating

More information

Operating instructions I / DALI EASY II Version 1.0. General. Contents. General

Operating instructions I / DALI EASY II Version 1.0. General. Contents. General Operating instructions I / 2007 General Contents General Installation Appendix Safety information 2 Definition of terms 3 Application and function 4 Components 5 Wiring diagrams 6 Wiring diagrams 7 System

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Residual current socket 30mA Order No.: 0477..

Residual current socket 30mA Order No.: 0477.. 30mA Order o.: 0477.. 1. Operating description The operating principle of the residual current socket is identical to that of the residual current device. In a fault-free installation, in which no current

More information

Important: Read Before Commissioning

Important: Read Before Commissioning Safty Instructions Important: Read Before Commissioning The user must ensure that all operators are familiar with this operating manual and follow it at all times. The operating manual must be read carefully

More information

BX444 Gas Detector. BX444 Four Zone Gas Detector

BX444 Gas Detector. BX444 Four Zone Gas Detector BX444 Gas Detector BX444 Four Zone Gas Detector Duomo is recognised within the Gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have

More information

Transmitter Actuator 230V wave UP 560. Operation

Transmitter Actuator 230V wave UP 560. Operation Transmitter ctuator 230V wave UP 560 5WG3 560-201 Product- and pplication Description Diagram The transmitter actuator 230V wave UP 560 (Diagram ) is a flush-mounted device with radio communication for

More information

The supplier and installer of the system shall be approved by the local civil defense authority.

The supplier and installer of the system shall be approved by the local civil defense authority. CONVENTIONAL FIRE ALARM SYSTEM The contractor shall supply, install, test and commission a modern Conventional Fire Detection and Alarm System of an approved manufacture and design, and in accordance with

More information

installation quick guide integrated access control & environmental monitoring

installation quick guide integrated access control & environmental monitoring AX300 installation quick guide integrated access control & environmental monitoring Introduction This Installation Quick Guide is suitable for standard wallmountable AX300 controllers. Illustrative technical

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

DUCT SMOKE DETECTOR D4120

DUCT SMOKE DETECTOR D4120 Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES 4-Wire Air Duct Smoke Detector Models DH-60 F-70.05 FEATURES Approvals/Listing UL 268A Listed File S1064 Factory Mutual Approved CSFM Listed #3240-1076:121 NYC MEA Listed #134-95-E City of Los Angeles

More information

Worldwide Manufacturer of Gas Detection Solutions. O 2 Transmitter ZD 21. Operation Manual

Worldwide Manufacturer of Gas Detection Solutions. O 2 Transmitter ZD 21. Operation Manual Worldwide Manufacturer of Gas Detection Solutions O 2 Transmitter ZD 21 Operation Manual Table of Contents For your safety...4 General description...4 Detection principle...5 Operational notes...5 Design...5

More information

Circuit diagram. Inteded use. Function

Circuit diagram. Inteded use. Function SNA 4043 K SNA 4063 K SNA 4044 K SNA 4064 K Basic unit for emergency stop and guard door applications Basic unit as per EN 62061 and EN ISO 13849-1 For safety category 4 and stop category 0 Single or twin

More information

PSR-MS50 / PSR-MS55. Safety relays for monitoring non-equivalent signal generators, Data sheet. 1 Description

PSR-MS50 / PSR-MS55. Safety relays for monitoring non-equivalent signal generators, Data sheet. 1 Description SILCL IEC 62061 Safety relays for monitoring non-equivalent signal generators Data sheet 106170_en_01 PHOENIX CONTACT 2015-05-19 1 Description Intended Use The PSR-MC50 and PSR-MS55 safety relays can be

More information

TC easy Plus Alarm. Operating Instructions

TC easy Plus Alarm. Operating Instructions TC easy Plus Alarm Operating Instructions Overview Accessory 1 2 3 4 Plug power supply 12 V optional Emergency power supply NV 2 TC GB 700 900 139 1 LED S1 2 pushbutton S1 3 LED automatic call acceptance

More information

DALI RC BASIC SO. Control unit Operating instructions

DALI RC BASIC SO. Control unit Operating instructions DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness

More information

FIRERAY 2000 Installation Guide

FIRERAY 2000 Installation Guide FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description

More information

Solar Charge Controller

Solar Charge Controller Table 3: Charging voltage for 4 types of battery Battery Battery GS-MPPT-320W Type Type Code Bulk Voltage Floating Voltage Vented 01 14.3 V 13.2 V Sealed 02 14.3 V 13.4 V Gel 03 14.3 V 13.7 V NiCd 04 14.3

More information

Deep Sea Electronics Plc

Deep Sea Electronics Plc Deep Sea Electronics Plc MODEL 521 REMOTE START ENGINE MANAGEMENT SYSTEM Author:- Miles Revell Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 OPH England Tel: +44 (0) 1723 890099

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

Radio fire detection system Interactive

Radio fire detection system Interactive Cerberus AlgoRex Radio fire detection system Interactive Complete integration in the interactive fire detection system CS1140 Simultaneous operation of wired and wireless fire detectors New possibilities

More information

FIB_FGWPF-101 Schuko Wall Plug with Metering Function

FIB_FGWPF-101 Schuko Wall Plug with Metering Function FIB_FGWPF-101 Schuko Wall Plug with Metering Function Firmware Version : 22.22 Quick Start A This device is a wireless Z-Wave actuator. The inclusion of the device is confirmed by a tripple click on the

More information

USER MANUAL INSTALLATION MANUAL. Isolation transformers. SDIT Isolation Transformer 3600 W 230/240 V

USER MANUAL INSTALLATION MANUAL. Isolation transformers. SDIT Isolation Transformer 3600 W 230/240 V USER MANUAL INSTALLATION MANUAL Isolation transformers SDIT00362040 Isolation Transformer 3600 W 230/240 V Victron Energy B.V. The Netherlands General phone: +31 (0)36 535 97 00 Customer support desk:

More information

SCC-MPPT Solar Charge Controller

SCC-MPPT Solar Charge Controller Table 3: Charging voltage for 4 types of battery Battery Battery 12V battery system 24V battery system Type Type Code Bulk Floating Bulk Floating Vented 01 14.3 V 13.2 V 28.6 V 26.4 V Sealed 02 14.3 V

More information

FIB_FGWPE-101 Wall Plug with Metering Function Type E Firmware Version : 22.22

FIB_FGWPE-101 Wall Plug with Metering Function Type E Firmware Version : 22.22 FIB_FGWPE-101 Wall Plug with Metering Function Type E Firmware Version : 22.22 Quick Start A This device is a wireless Z-Wave actuator. The inclusion of the device is confirmed by a tripple click on the

More information

WAVE 1H HUMIDITY MODULE INSTRUCTION MANUAL

WAVE 1H HUMIDITY MODULE INSTRUCTION MANUAL WAVE 1H HUMIDITY MODULE INSTRUCTION MANUAL WAVE 1H is a microprocessorcontrolled humidity module for the sauna control unit WAVE 1. page 1 of 10 INSTRUCTION MANUAL 1.0.0 UNIT DESCRIPTION 2 1.1.0 GENERAL

More information

Operating instructions Switching amplifier for fibre optics. OBF5xx 704876 / 00 08 / 2010

Operating instructions Switching amplifier for fibre optics. OBF5xx 704876 / 00 08 / 2010 Operating instructions Switching amplifier for fibre optics OBF5xx 70876 / 00 08 / 00 Contents Preliminary note. Symbols used Functions and features. Applications Installation. Attaching the fibre optics

More information

BX150 Gas Detector. Application. Operation

BX150 Gas Detector. Application. Operation BX50 Gas Detector Application Duomo is recognised in the gas industry for providing a comprehensive range of low cost, high reliability gas detection systems for many applications. We have installed and

More information

Outdoor Sensor - PSSENS01

Outdoor Sensor - PSSENS01 (2) Plastic Anchors Sensor Enclosure Seal Gasket (2) Mounting Screws Fig. 1: Sensor Enclosure and Components Front Cover Mounting the Outdoor Sensor 1. Remove the front cover and mounting screws / anchors

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL N2xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL SPECIFICATIONS Supply voltage N224A / N3424A N223A / N3423A PRODUCT DATA 24 Vac 15%, 5/6 Hz 23 Vac 15%,

More information

ABB i-bus EIB/KNX. Watchdog sensor 180 comfort with multi-lens, FM Type: 6122-xx-500. Contents. Technical data 2-2. Application programs (List) 2-3

ABB i-bus EIB/KNX. Watchdog sensor 180 comfort with multi-lens, FM Type: 6122-xx-500. Contents. Technical data 2-2. Application programs (List) 2-3 Contents Technical data 2-2 Application programs (List) 2-3 Circuit diagrams 2-3 in combination with Bus coupler FM (6120-102-500): Switch Value Cyclic Monitoring Threshold /1 2-4 in combination with Switch

More information

TS93 EMR T/PT/TDE. Surface applied door closer

TS93 EMR T/PT/TDE. Surface applied door closer TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double

More information

ABLOY DA60 SWING DOOR OPERATOR Installation and commissioning manual Abloy Oy An ASSA ABLOY Group company APPROVALS / STANDARDS Low Voltage directive 7//EEC as amended by the directive 9/68/EEC EMC directive

More information

FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts. Halton FDS. Multi-blade-type Fire Damper for Rectangular and Circular Ducts

FDS - Multi-blade-type Fire Damper for Rectangular and Circular Ducts. Halton FDS. Multi-blade-type Fire Damper for Rectangular and Circular Ducts Halton FDS Multi-blade-type Fire Damper for Rectangular and Circular Ducts Type-approved unit compliant with the EN -2 and EN 50- standards. Fire resistance class ES 0. Possibility of use as an EIS 0 damper

More information

Central Communication Unit

Central Communication Unit Central Communication Unit for LPB/BSB plants Series B OCI6 Central communication unit for the remote operation and supervision of LPB plants with a maximum of 6 LPB/BSB units Use Plant Buildings Operators

More information

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

Measuring and monitoring relays CM-MSS (4), CM-MSS (5) Thermistor motor protection relays

Measuring and monitoring relays CM-MSS (4), CM-MSS (5) Thermistor motor protection relays Data sheet Measuring and monitoring relays CM-MSS (4), Thermistor motor protection relays The devices CM-MSS (4) and (5) are used to monitor the overload of motors by the wiring temperature. The motors

More information

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB , GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

better measurement Simply a question of

better measurement Simply a question of Simply a question of better measurement SCHMIDT LED measured value display MD 10.010/10.015 The ideal solution for displaying and calculating measured values at the place of use Compressed air technology

More information

Capacitive Proximity Switch Operating Distance mm Item group 100

Capacitive Proximity Switch Operating Distance mm Item group 100 SENSOREN FÜR AUTOMATION Capacitive Proximity Switch Operating Distance 15-70 mm Item group 100 Monitoring of filling levels, convoyer belts, packages -Liquids -Material to be milled -Glass -Wood -Plastics

More information

Electronic timer CT-TGD.12

Electronic timer CT-TGD.12 2CDC 251 098 F0t06 a Rotary switch for the preselection of the time range of the ON time b Potentiometer with direct reading scale for the fine adjustment of the ON time c Rotary switch for the preselection

More information

46 SERIES. Miniature industrial relays 8 to16 A

46 SERIES. Miniature industrial relays 8 to16 A Miniature industrial relays 8 to16 1 & 2 CO industrial style power relays For socket mount or direct connection via Faston connectors Type.52 -- 2 CO 8 Type.61 -- 1 CO 16 C coils & DC coils vailable with:

More information

Salamander Installer Guide

Salamander Installer Guide S A L A M A N D E R I N S T A L L E R G U I D E Salamander Installer Guide Introduction Salamander is a radio-controlled, battery-powered system for holding open fire doors. It combines ease and speed

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

MOUNTING AND OPERATING INSTRUCTIONS

MOUNTING AND OPERATING INSTRUCTIONS MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall

More information

LED Driver Linear / area fixed output

LED Driver Linear / area fixed output Driver LC W /3/3/7/mA fixc lp SNC ESSENCE series Product description Fixed output built-in LED Driver Constant current LED Driver Output current, 3, 3, 7 or 1, ma Max. output power W For luminaires of

More information

Operating Instructions

Operating Instructions Operating Instructions Control unit Ex p > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Designated Use...4 5 Technical Data...4 6 Transport, Storage

More information

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance

More information

Inverter/Charger. PowerWalker Inverter 700 PSW PowerWalker Inverter 700 PSW/FR PowerWalker Inverter 1200 PSW PowerWalker Inverter 1200 PSW/FR

Inverter/Charger. PowerWalker Inverter 700 PSW PowerWalker Inverter 700 PSW/FR PowerWalker Inverter 1200 PSW PowerWalker Inverter 1200 PSW/FR Inverter/Charger PowerWalker Inverter 700 PSW PowerWalker Inverter 700 PSW/FR PowerWalker Inverter 1200 PSW PowerWalker Inverter 1200 PSW/FR Quick Start Guide 1. Introduction This robust inverter is designed

More information

FIRE ALARM SYSTEM. reliable fire detection and alarm signalling system

FIRE ALARM SYSTEM. reliable fire detection and alarm signalling system FIRE ALARM SYSTEM reliable fire detection and alarm signalling system Satel fire alarm devices allow to implement reliable and modern systems responsible for fire safety. A combination of 20-year experience

More information

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet SMA-MA Parameterisable damper actuator for adjusting air dampers in ventilation and air-conditioning systems in buildings Air damper size up to approx. m orque 0 Nm Nominal voltage

More information

Combi switchbox with integrated 3/2 way pilot valve

Combi switchbox with integrated 3/2 way pilot valve H Combi switchbox with integrated 3/2 way pilot valve Construction The GEMÜ combi switchbox with integrated 3/2 way pilot valve for pneumatically operated quarter turn actuators has a micro-processor controlled

More information

Printed Circuit Board

Printed Circuit Board Printed Circuit Board 236-13857-1 with Fixed Time of Availability and Adjustable Operating Time H Trailers and Semi-Trailers 10121327 Page 1 from 11 Survey Pump Voltage [V] Control unit Setting ranges

More information

INSTRUMENT PANEL. 1995 Volvo 850 DESCRIPTION & OPERATION. 1995-96 ACCESSORIES & EQUIPMENT Volvo Instrument Panels

INSTRUMENT PANEL. 1995 Volvo 850 DESCRIPTION & OPERATION. 1995-96 ACCESSORIES & EQUIPMENT Volvo Instrument Panels INSTRUMENT PANEL 1995 Volvo 850 1995-96 ACCESSORIES & EQUIPMENT Volvo Instrument Panels 850 WARNING: When working around steering column and before performing repairs, disconnect and shield battery ground

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe - Infrared flicker detector 1020 - UV flame sensor UVD 971

More information

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems -A_D00001_01_D_XXE/09.2014 LIETRAXX -A etwork and system protection (S protection) for

More information

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses BCU Power Supplies Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses Installation, Commissioning and O perating Manual BCU RANGE

More information

Operating manual PTC-resistor relay MSF 220 V (VU)

Operating manual PTC-resistor relay MSF 220 V (VU) MINIPAN digital panel meters, temperature- and mains controlling, special purpose instruments for customer requirements www.ziehl.com Operating manual PTC-resistor relay MSF 220 V (VU) Page 1 of 8 Contents

More information

SKF TIH 030m Instructions for use

SKF TIH 030m Instructions for use SKF TIH 030m Instructions for use 2 SKF TIH 030m Table of contents EU-DECLARATION OF CONFORMITY...4 SAFETY RECOMMENDATIONS...5 1. INTRODUCTION...6 1.1 Intended use...6 1.2 Principle of operation...6 1.3

More information

ABB i-bus KNX Security Terminals MT/U 2.12.2, MT/S 4.12.2M and 8.12.2M Product Manual

ABB i-bus KNX Security Terminals MT/U 2.12.2, MT/S 4.12.2M and 8.12.2M Product Manual ABB i-bus KNX Security Terminals MT/U 2.12.2, MT/S 4.12.2M and 8.12.2M Product Manual Contents Contents Page 1 General 3 1.1 Use of the product manual...3 1.1.1 Structure of the product manual...3 1.1.2

More information

QUINT-PS AC/24DC/40

QUINT-PS AC/24DC/40 Extract from the online catalog QUINT-PS-100-240AC/24DC/40 Order No.: 2938879 DIN rail power supply unit 24 V DC/40 A, primary switched-mode, 1- phase. Commercial data EAN 4017918987091 Pack 1 pcs. Customs

More information

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke

More information

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2 QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2 2.1 GENERAL...2 2.1.1 Scope 2 2.1.2 References 2 2.1.3 Contractor s Responsibility 2 2.1.4 System Description

More information

SYSTEM DESCRIPTION Termination Boards

SYSTEM DESCRIPTION Termination Boards PROCESS AUTOMATION SYSTEM DESCRIPTION Termination Boards Non-IS Termination Boards for Yokogawa CENTUM C3 and ProSafe RS ISO9001 With regard to the supply of products, the current issue of the following

More information

Testomat AW101 Water Hardness Monitor. A unique water hardness monitoring system with superior performance

Testomat AW101 Water Hardness Monitor. A unique water hardness monitoring system with superior performance Data sheet DS/AW00 EN Rev. D Testomat AW0 Water Hardness Monitor A unique water hardness monitoring system with superior performance Automatic on-line monitoring of residual/total water hardness ideal

More information

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

GS150K Gas Detector. Application. Technical Specification. Operation

GS150K Gas Detector. Application. Technical Specification. Operation GS150K Single Zone Detector Application Duomo is recognised within the Gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have installed

More information

CENTRAL BATTERY UNIT FOR EMERGENCY LIGHTING. Installation and maintenance instructions TKT65XXB

CENTRAL BATTERY UNIT FOR EMERGENCY LIGHTING. Installation and maintenance instructions TKT65XXB 1 VOT6506E CENTRAL BATTERY UNIT FOR EMERGENCY LIGHTING Installation and maintenance instructions TKT65XXB KEEP IN A SAFE PLACE FOR LATER USE 2 TKT65XXB product description REV.4; 20.07.2009 JAK Table of

More information

OH720, OP720, HI720, HI722 Automatic fire detectors

OH720, OP720, HI720, HI722 Automatic fire detectors OH720, OP720, HI720, HI722 Automatic fire detectors For the automatic addressable detector bus C-NET Cerberus PRO The optimum smoke detector for all applications Signal processing with detection algorithms

More information

TRS 06 TRANSPONDER READER- AND CONTROL UNIT. (Door Access Control System) Mounting Manual and Operating Manual

TRS 06 TRANSPONDER READER- AND CONTROL UNIT. (Door Access Control System) Mounting Manual and Operating Manual TRS 06 TRANSPONDER READER- AND CONTROL UNIT (Door Access Control System) Mounting Manual and Operating Manual Table of Contents 1. Function and Description of the Device 2 2. Installation Instructions

More information

Wireless controls Individual room temperature control for surface heating and cooling systems

Wireless controls Individual room temperature control for surface heating and cooling systems Technical information Application: The range of Oventrop wireless controls includes a room thermostat and a room thermostat-clock with wireless transmitter, wireless receivers with 1, 4 and 6 channels

More information

Installation and application

Installation and application Installation and application Leakage detectors, CLS/FLS/FLS10/FLS30/MiniCAS II 892472/05 INTRODUCTION A number of condition monitoring sensors are available for the ITT FLYGT pump range. Thermal switches

More information

Fire Alarm Control Panel. Family. Operating Manual

Fire Alarm Control Panel. Family. Operating Manual Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

INSULATION MONITORING DEVICES

INSULATION MONITORING DEVICES 1 / 8 INDEX: Technical specifications VA40...2 Technical specifications TI1...3 Technical specifications CR5...4 Installation, configuration and use...5 2 / 8 1- INSULATION MONITORING RELAY VA40 1.1- Functions:

More information

PANEL METER N15Z TYPE

PANEL METER N15Z TYPE PANEL METER N15Z TYPE INSTRUCTION MANUAL CONTENTS 1. APPLICATION... 5 2. METER SET... 5 3. BASIC REQUIREMENTS, OPERATIONAL SAFETY... 6 4. INSTALLATION... 8 5. HANDLING... 10 6. SPECIFICATIONS...11 7.

More information

Monitor for Measurement of Speed and Detection of Direction Series D224.xxS2

Monitor for Measurement of Speed and Detection of Direction Series D224.xxS2 D Monitor for Measurement of Speed and Detection of Series D.xxS KEY FEATURES Speed and Monitor with sensor monitoring and self-test function Frequency range 0 Hz 00 khz Analog Output 0/ 0 ma Bright red

More information

CONTENTS. DI-9204Exd Digital Flame-proof Manual Call Point Installation and Operation Manual

CONTENTS. DI-9204Exd Digital Flame-proof Manual Call Point Installation and Operation Manual DI-9204Exd Digital Flame-proof Manual Call Point CONTENTS 1 General... 1 2 Features... 1 3 Technical Specifications... 1 4 Construction and Operation Principle... 2 4.1 Exterior View... 2 4.2 Operation

More information

I. INTRODUCTION TO SEECO MOTOR OPERATORS II. MOTOR OPERATOR INSTALLATION INSTRUCTIONS

I. INTRODUCTION TO SEECO MOTOR OPERATORS II. MOTOR OPERATOR INSTALLATION INSTRUCTIONS I. INTRODUCTION TO SEECO MOTOR OPERATORS Thank you for purchasing a SEECO motor operator. We are excited to be able to provide this product to you and we are certain that it will fulfill your performance

More information

Charge Controller CC611/CC612 Preliminary datasheet

Charge Controller CC611/CC612 Preliminary datasheet Preliminary datasheet Preliminary datasheet CC61x_D00xxx_00_D_XXE_preliminary/04.2015 Product description The ender charge controller CC611 is the main component of a charging point and is designed for

More information