UTILITIES ENGINEERING - ELECTRIC METER SPECIFICATIONS

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "UTILITIES ENGINEERING - ELECTRIC METER SPECIFICATIONS"

Transcription

1 CITY OF PALO ALTO UTILITIES ENGINEERING - ELECTRIC METER SPECIFICATIONS PREPARED : Gopal Jagannath, Power Engineer CHECKED : Patrick Valath, Senior Power Engineer APPROVED : Tomm Marshall, Electrical Engineering Manager METER SPECIFICATIONS PAGE # 1 MAY 1997

2 1. GENERAL INFORMATION 1.1 Description This engineering specification shall apply to all solid-state single phase and poly phase electric meters used in revenue metering applications. These electric meters are referred to as the Meter in the Specification City of Palo Alto (CPA) reserves the right to modify the Specification and to approve deviations from all or part of the Specification Any product exceptions must be approved in writing by CPA The supplier is responsible and accountable for the detailed design and construction of the meter The supplier must have a minimum of 5 years of field experience with quoted meter. 2. SCOPE 2.1 General The specification provides the minimum functional and performance requirements for the meter. All requirements in the specification are intended to assure the expected life cycles, security, accuracy, reliability and minimum maintenance requirement of the meter. Some requirements are specified to maintain the compatibility and interchangeability of the meter. 2.2 Standards The meter shall comply with American National Standards Institute (ANSI) standards and other standards listed in Appendix - I, Applicable Standards, except those modified by this specification. If conflicts exist, the requirements of this specification will supersede those of ANSI and other standards. 3. PERFORMANCE 3.1 Service Life The meter, excluding replaceable battery, shall have a minimum service life of 16 years from the manufacturer s shipping date, or 15 years from the installation METER SPECIFICATIONS PAGE # 2 MAY 1997

3 date, whichever is longer. During the service life period, the meter shall continue to operate in full compliance with this specification Reliability The annual failure rate, excluding user induced failures, shall not exceed 0.75% throughout the service life of the meter. The failure rate is the ratio of the number of Failed Meters of a specific type to the number of installed meters of the same type. 4. WARRANTIES 4.1 Standard Warranty As a minimum, the supplier shall provide a standard warranty of three years from the delivery date of the meter. As an option, the supplier may provide a longer standard warranty or different coverage options beyond the three year standard warranty period. CPA will consider this when evaluating the bids. 4.2 Workmanship and Material Supplier shall warrant that the meter and all parts thereof furnished by supplier, whether or not manufactured by supplier, shall be of the kind and quality described by this specification will be free of defects in workmanship, material, design, and quality, and shall be fit for its intended purpose. 4.3 Performance Supplier shall warrant that when the meter is placed in operation or used, it will perform in the manner set forth by this specification. 5. METER ACCEPTANCE 5.1 Testing Each meter received by CPA will be tested for various physical and electronic attributes and for metering accuracy at the time of installation on the customer s premises. 5.2 Acceptable Quality Level (AQL) The minimum Acceptable Quality Level (AQL) of each meter shall meet or METER SPECIFICATIONS PAGE # 3 MAY 1997

4 exceed that in Section Acceptance Criteria The meter will be accepted by CPA if all of the following criteria are met: The meter passes a combined inspection for physical and electronic attributes and metering accuracy as defined in Section Physical and Electronic Attributes and Metering Accuracy The meter will be inspected for physical and electronic attributes Installation accuracy tests will be performed on the meter The tests will be performed at full and light loads. The test point loads are shown in Table 1. TABLE 1 Test Point Loads Meter Class Full 100% PF Test Points (amps) Light PF Full PF lag * * Class 20 meters may be tested at either set of test points For acceptance of a meter, the metering accuracy at the test points shall be within: ±0.25% at light load at power factor of 100% ±0.25% at full load at power factor of 100% ±0.25% at full load at power factor of 50% lag ±0.25% at full load at power factor of 50% lead 6. ACCURACY shall 6.1 The meter shall meet or exceed the accuracy specifications contained in ANSI C12.10 over its entire service life without the need for adjustment. The meter be factory calibrated by the supplier to provide the following level of accuracy (Table II). TABLE II- Meter Accuracy Requirements METER SPECIFICATIONS PAGE # 4 MAY 1997

5 TYPE %FL %LL %PF SS Polyphase ± 0.2 ± 0.2 ± 0.3 SS Single Phase ± 0.2 ± 0.2 ± 0.3 Hybrid Single Phase ± 0.5 ± 0.5 ± na Mechanical Single Phase ± 0.5 ± 0.5 ± na 6.2 Test Equipment Meter accuracy and calibration tests, both shop and field, shall require only standard test equipment. No special Laboratory-type test equipment or test procedures shall be required to assure accuracy of the meter. 6.3 Creep The meter shall not creep. No pulse generation or registration shall occur for any consumption or demand quantity which depends on current while current circuit is open. 7. METERING FUNCTIONS 7.1 FORM The following meter forms shall be available S, 2S, 3S & 4S with same upgrade capabilities as polyphase meters S/8S (These two forms shall be interchangeable.) S S S/15S (These two forms shall be interchangeable.) 7.2 MEASUREMENT 1. The meter shall have the capability of registering KVA. 2. A single-function meter shall be capable of being upgraded to multifunction meters, preferably by software or otherwise by a board upgrade. 3. A multifunction meter shall register KWH, KW, KVA, KVARH and KVAR 4. The meter shall have Time of Use (TOU) OPTION. METER SPECIFICATIONS PAGE # 5 MAY 1997

6 5. TOU and reactive meters must support field installation of internal modem interface. 6. Modem sharing unit capable of handling up to 12 meters sharing one external modem/one phone line, shall be available from the supplier. 7. The meter shall have load profile capability (32 kilobytes minimum). 8. The meter must have Volts range. with 9. Reactive meters shall be upgradable to full 4 quadrant bi-directional metering upto 4 channels of load survey. If needed, option cards are acceptable for this feature. 7.3 ADJUSTMENT Solid-state meters shall not have any utility accessible calibration accuracy adjustment. This implies that the meter must not require accuracy adjustment when its register is changed or replaced. 7.4 OPTIC PORT The meter shall have an ANSI-approved optical port. This shall allow the meter reader to electronically retrieve billing data and reset the demand(s). 7.5 DEMAND Demand meter must be upgradable to TOU via software keys without requiring additional hardware (except for a battery). TOU meters must be upgradable to measure Kwh and Kvarh (basic reactive) via software keys without requiring additional hardware (except for a battery). The meter shall have a programmable demand interval with 3-minute subdemand intervals. The meter shall have bidirectional demand reset. This is, the meter shall be capable of being reset from the optic port and also manually. The demand reset must be sealable. A demand meter shall retain its register readings, internal identification (ID) number, and demand interval during and after a power outage. METER SPECIFICATIONS PAGE # 6 MAY 1997

7 When a TOU or load-profile meter is used as a demand meter, the meter should not require a battery to retain its internal meter ID number, register readings, and programmed demand interval if power outages occur. 7.6 COVER 7.7 KYZ The manufacturer shall have one standard meter cover for all of its meters in one family. All meters with demand capability shall have a sealable manual demand reset. Solid-state meters shall have acrylic or polycarbonate covers with optic ports. All mechanical single-phase KWH meters shall have glass covers. The meter test mode shall not be accessible from the cover except through the Optical Port via software. KYZ option boards shall be available and shall be easy to install (field install). Single-function KYZ option boards shall have software scaled KWH output. Multifunction bidirectional meters shall have software scaled KWH and KVARH delivered and received, KYZ outputs. 7.8 CERTIFIED TESTS The manufacturer shall supply certified tests and nameplate data. 7.9 PROBE READ The current meter reading computers with probe capabilities should be able to read the meter optically. An optical coupling device/probe that can be attached for interfacing purposes to either the meter s cover (while the cover is on the meter) or to the meter s face (while the meter does not have a cover on); shall be available from the supplier and the meter shall support said optical coupling device/probe SOFTWARE The manufacturer s software should run on the standard laptop used by the metering personnel. Reprogramming of meter must be software protected via City of Palo Alto unique password. Metering personnel must be able to edit the meter register readings via the METER SPECIFICATIONS PAGE # 7 MAY 1997

8 manufacturer s software which shall be City of Palo Alto password protected. Programmable meters shall have two ID fields not exceeding 18 digits each. The internal ID number shall be factory programmed into the first ID field. The internal ID number shall be the manufacturer s serial number that is stamped on the meter nameplate. Leading zeroes shall be used if the serial number has less digits than the programmable ID number field. Access to reprogram this field must be available at the time of installation. The second ID shall be factory programmed with default zeroes. This ID number field will be site specific and will be reprogrammed at the time of installation. The test mode shall be software accessible via the Optical Port. Program development, programming and reading of the meters must be performed with a DOS based software application DISPLAY MODES Each electronic meter shall have three displays: normal, alternate, and test. All register ID numbers and codes shall be software assigned by City of Palo Alto and shall be displayed next to the contents of its register. The next three subsections outline the required registers. A) Normal Display Mode mode. The following registers, if applicable, shall be available in the normal display 1. On-peak KWH (delivered) 2. Off-peak KWH (delivered) 3. Total KWH (delivered) 4. On-peak KW (delivered) 5. Off-peak KW (delivered) METER SPECIFICATIONS PAGE # 8 MAY 1997

9 6. Total KVARH (lag) 7. Peak KVAR (lag) 8. Total KWH (received) 9. Total KVARH (lead) 10. Total KVAR (lead) 11. On-peak KVAH (delivered) 12. Off-peak KVAH (delivered) 13. Total KVAH (delivered) 14. On-peak KVAR (delivered) 15. Off-peak KVAR (delivered) 16. Total KVAH (received) 17. Date of last reset 18. Current date 19. Current time 20. On-peak KVA 21. Off-peak KVA 22. Total KVA B) Alternate Display Mode mode. The following registers, if applicable, shall be available in the alternate display 1. Software version 2. Date of last reset 3. Program ID number METER SPECIFICATIONS PAGE # 9 MAY 1997

10 4. Meter ID number 1 5. Meter ID number 2 6. Date of maximum on-peak demand 7. Time of maximum on-peak demand 8. Date of maximum off-peak demand 9. Time of maximum off-peak demand 10. Time remaining in demand subinterval 11. Watthour per pulse (KYZ) 12. Test watthour per pulse (Kt) 13. Kh 14. Transformer factor 15. Demand interval length 16. Number of subintervals 17. Length of subinterval 18. Number of power outages 19. Number of demand resets 20. Received KWH 21. Average power factor 22. Maximum power factor 23. Minimum power factor 24. Scale factor 25. Date last programmed METER SPECIFICATIONS PAGE # 10 MAY 1997

11 26. Number of times programmed 27. Total KVA C) Test Display Mode The meter test mode should not be accessible without removing the front cover except through the Optical Port via software, and the meter shall remain in test mode (even if power is cycled) until switch is unlocked. The meter shall have programmable test interval with the following display registers when in the test mode: 1. Time remaining in test interval 2. Number of test pulses accumulated since start of test interval 3. KWH since start of the test mode 4. Maximum KW since start of test mode The demand reset will reset this KW to zero 5. All LCD display While the meter is in its mode, the billing registers shall remain unchanged; that is, they shall not accumulate energy or demand. If software is used to access the test mode, the meter shall revert to its normal billing mode after three test intervals. The meter shall have a test interval of one minute. A hardware switch shall be available to leave the meter indefinitely in its test mode. This switch shall only be accessible by removing the meter cover. All meters with optic ports shall have KWH test pulses accessible from their optic ports. Multifunction meters shall also have KVARH test pulse outputs via the optic ports Diagnostic Warnings Meters shall have the following diagnostics, if applicable, that are software retrievable: 1. Potential circuit failure METER SPECIFICATIONS PAGE # 11 MAY 1997

12 7.13 Display Panel 2. Phase angle relationships (in units of degrees) between the current and voltage of each element. 3. Low battery 4. Received energy (unidirectional only) 5. Demand threshold 6. Warnings and errors resulting from a meter health check of its electronics, such as the microprocessor 7. All other error codes and warnings. A) Error Display In the event of an error, the meter display shall freeze in its normal display mode, displaying its error code if any of the following occurs: 1. Potential circuit failure 2. Any other fatal error deemed necessary by the manufacturer The meter will still continue to accumulate registration where possible. B) Visibility Display should be clearly visible in sunlight. C) Operating Temperature The display shall be capable of operating at temperatures between -30 C and +85 C Battery The battery, if necessary, shall have a minimum operating life of two years. 8. DOCUMENTATION The manufacturer shall supply adequate hardware, software, and maintenance manuals. 9. TEST RESULT RECORD METER SPECIFICATIONS PAGE # 12 MAY 1997

13 Each meter test result record shall have the following results as the meter left the factory: 9.1 Reference standard 9.2 Test date 9.3 Complete barcode 9.4 %FL - The percent registration of the meter when the meter s rated test voltage and test amps are applied to all of its elements simultaneously. 9.5 %LL- The percent registration of the meter when the meter s rated test voltage and ten percent of its test amps are applied to all of its elements simultaneously. 9.6 %PF - The percent registration of the meter when the meter s rated test voltage and test amps are applied to all of its elements simultaneously, and the currents lag the voltages by 60 degrees (0.5 power factor.) 9.7 %AF - The percent registration of the meter when the meter s rated test voltage is applied to all of its elements, and test amps are applied to its A element only. 9.8 %BF - The percent registration of the meter when the meter s rated test voltage is applied to all of its elements, and test amps are applied to its B element only. 9.9 %CF - The percent registration of the meter when the meter s rated test voltage is applied to all of its elements, and test amps are applied to its C element only. All test results shall have two digits to the right of the decimal. 10. PRODUCT AND VENDOR EVALUATION A multiplier resulting from a Product and Vendor Evaluation, performed at the end of the year, will be applied to blanket bids. This evaluation includes categories such as accuracy at the time of receipt and accuracy in the field, software use, vendor support, and timely delivery. 11. BAR CODING Meters shall be supplied with a 3-of-9 bar code label permanently affixed to the front of the meter. The bar code information shall follow the format established by American Electric Power Company (AEP) and the information specified in 8.1, Bar Code Layout METER SPECIFICATIONS PAGE # 13 MAY 1997

14 and Content, and in 8.3, Company Bar Code Extension 12. SHIPPING REQUIREMENTS Meters shall be shipped properly protected from being damaged during handling, storage and shipping. Meters shall be packaged 4 to a box and pelletized with 16 or 24 boxes per pallet. Where appropriate 1 meter per box is acceptable. APPENDIX - I APPLICABLE STANDARDS This specification shall be used in conjunction with the following publications. The revisions in effect when bids are awarded shall apply. ANSI C12.1, American National Standard Code for Electricity Metering ANSI C12.10, American National Standard for Electromechanical Watthour Meters METER SPECIFICATIONS PAGE # 14 MAY 1997

15 ANSI C12, 13, American National Standard for Electronic Time-of=Use Registers for Electricity Meters ANSI C12.16, American National Standard for Solid-State Electricity Meters. ANSI C18.1, American National Standard for Dry Cells and Batteries. ANSI C18.2, American National Standard for Sealed Rechargeable Nickel-Cadmium Cylindrical Bare Cells ANSI C , IEEE Standard Surge Withstand Capability (SWC) Tests For Protective Relays and Relay Systems ANSI C62.41, IEEE Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits ANSI/PC-610A, Acceptability of Electronic Assemblies ASTM D-999, Standard Methods for Vibration Testing of Shipping Containers California Weights and Measures for Electric Metering CELT, Requirements for Residential Time-of-Use Meters DOD-HDBK..-263, Electrostatic Discharge Control Handbook for Protection of Electrical and Electronic Parts, Assemblies and Equipment (Excluding Electrically Initiated Explosive Devices) FCC Regulations, Part 15, Technical Standards for Computing Equipment. METER SPECIFICATIONS PAGE # 15 MAY 1997

16 METER SPECIFICATIONS PAGE # 16 MAY 1997

Capacitor Bank Controls

Capacitor Bank Controls Capacitor Bank Controls CBC-8000 Capacitor Bank Controller Device Functional Specification Guide 1. Capacitor Bank Controllers (CBCs) 1.1. The Capacitor Bank Control (CBC) shall be designed to control

More information

Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications

Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications By Michael Bearden Introduction In 1982 Raymond Ray Stevens published a paper Power Flow Direction Definitions for

More information

www.electroind.com. March 15th 2005 EI Solutions - Submetering 1

www.electroind.com. March 15th 2005 EI Solutions - Submetering 1 . March 15th 2005 EI Solutions - Submetering 1 What is Submetering? Electric Service Master Meter Utility Owned POCC Utility Billing Point Sub Meter Electric Distribution Sub Meter Sub Meter Sub Meter

More information

E3 and E3 Plus Electronic Overload Relays with Integrated DeviceNet Communications

E3 and E3 Plus Electronic Overload Relays with Integrated DeviceNet Communications Specification Guide 1.0 General 1.01 The electronic overload relay shall be available in NEMA and IEC contactor mount configurations. 1.02 The electronic overload relay shall be capable of being applied

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS 1. Description and Phone Number Dialing: The dialer shall be a solid state component capable of dialing up to 16 telephone numbers, each up to 60 digits

More information

I-210+ and I-210+c Meters

I-210+ and I-210+c Meters GE Energy I-210+ and I-210+c Meters February 2007 The I-210 +* is GE s latest singlephase basic energy meter with several key features Optional remote connect/disconnect capability with a fully integrated,

More information

Polyphase kwh Electricity Meter

Polyphase kwh Electricity Meter Polyphase kwh Electricity Meter Model Type: 5192B USER MANUAL Issue 1.0 E & O E AMPY Automation Ltd. July 2003 doc. ref. CSD 093 Contents 1 Introduction 2 1.1 Purpose 2 2 Definitions 2 2.1 References 2

More information

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

GE kv2c TM Encompass Electronic Meter

GE kv2c TM Encompass Electronic Meter . GEH-7285 GE kv2c TM Encompass Electronic Meter Product Description, Operating Instructions, Maintenance Instructions, Upgrading, Site Analysis Guides, Diagrams. Price: $ 30.00 Notice The information

More information

A1800 ALPHA Meter. Technical Manual Rev.02 10-2011. www.izmerenie.ru

A1800 ALPHA Meter. Technical Manual Rev.02 10-2011. www.izmerenie.ru A1800 ALPHA Meter Technical Manual Rev.02 10-2011 www.izmerenie.ru Technical manual i Contents Contents Contents Technical manual 1 Introduction....................................... 1-1 A1800 ALPHA

More information

Digital and Analog I/O

Digital and Analog I/O 70072-0127-07 TECHNICAL NOTE 02/2007 Digital and Analog I/O This document discusses the application and configuration of digital and analog inputs/outputs (I/O). Details are for both onboard I/O and external

More information

E650 S4e. Product Specification and Schedule Sheet. Enhanced metering for Commercial and Industrial Applications

E650 S4e. Product Specification and Schedule Sheet. Enhanced metering for Commercial and Industrial Applications E650 S4e Enhanced metering for Commercial and Industrial Applications Built on the time-tested platform, the S4e extends the build a meter concept into the realm of open-architecture protocol, fully supporting

More information

User Manual HomeGrid 3000 Solar Generator

User Manual HomeGrid 3000 Solar Generator User Manual HomeGrid 3000 Solar Generator For more information and instruction videos visit: www.pointzeroenergy.com/learn/videos/ HomeGrid 3000 Solar Generator Congratulations on purchasing Point Zero

More information

FOCUSAX. E330 FOCUS AX E350 FOCUS AX-SD Single Phase E330 FOCUS AX Polyphase. Product Specification and Schedule Sheet

FOCUSAX. E330 FOCUS AX E350 FOCUS AX-SD Single Phase E330 FOCUS AX Polyphase. Product Specification and Schedule Sheet FOCUSAX E330 FOCUS AX E350 FOCUS AX-SD Single Phase E330 FOCUS AX Polyphase The FOCUS family of meters featuring advanced residential metering and light commercial applications. The FOCUS AX platform features

More information

DIRECT ACCESS STANDARDS FOR METERING AND METER DATA (DASMMD) IN CALIFORNIA

DIRECT ACCESS STANDARDS FOR METERING AND METER DATA (DASMMD) IN CALIFORNIA DIRECT ACCESS STANDARDS FOR METERING AND METER DATA (DASMMD) IN CALIFORNIA MARCH 1999 This Page Intentionally Left Blank Introduction The Direct Access Standards for Metering and Meter Data (DASMMD) are

More information

ALPHA Meter Installation Information

ALPHA Meter Installation Information October 006 IL4-400Q ALPHA Meter Installation Information General This instructional leaflet contains general installation instructions for the following single phase and polyphase watthour meters: socket-connected

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

Back-UPS Pro 400/550 Installation and Operation

Back-UPS Pro 400/550 Installation and Operation Back-UPS Pro 400/550 Installation and Operation Inventory USB cable UPS Connect the battery User manual & CD warranty registration card CAT-5 cable Cable strap hook & cable strap Remove the battery door.

More information

5235 Single Phase Credit Meter

5235 Single Phase Credit Meter Electricity Meters Residential BS / IEC British Standard 5235 Single Phase Credit Meter User Manual & Technical Specification Date: 20/11/08 Filename: 5235 User Manual Q Pulse No:IB047 Landis+Gyr Page

More information

Back-UPS RS 700 Installation & Operation

Back-UPS RS 700 Installation & Operation Back-UPS RS 700 Installation & Operation Inventory Safety Do not install the UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Do not connect a laser printer or hair dryer

More information

Back-UPS Pro 900 Installation and Operation

Back-UPS Pro 900 Installation and Operation Back-UPS Pro 900 Installation and Operation Inventory Safety bu001a (2) Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a

More information

Attachment-VEE STANDARDS FOR VALIDATING, EDITING, AND ESTIMATING MONTHLY AND INTERVAL DATA

Attachment-VEE STANDARDS FOR VALIDATING, EDITING, AND ESTIMATING MONTHLY AND INTERVAL DATA Attachment-VEE STANDARDS FOR VALIDATING, EDITING, AND ESTIMATING MONTHLY AND INTERVAL DATA This Page Intentionally Left Blank Table of Contents SECTION A: CA INTERVAL DATA VEE RULES 1. INTRODUCTION...

More information

SECTION INCLUDES REFERENCES SUBMITTALS QUALIFICATIONS DELIVER, STORAGE, AND HANDLING MAHLUM KING'S SCHOOL KING S JUNIOR HIGH SCHOOL MODERNIZATION

SECTION INCLUDES REFERENCES SUBMITTALS QUALIFICATIONS DELIVER, STORAGE, AND HANDLING MAHLUM KING'S SCHOOL KING S JUNIOR HIGH SCHOOL MODERNIZATION PART 1 1.1 1.2 1.3 1.4 1.5 GENERAL SECTION INCLUDES A. Main Switchboard Furnish and install the Service Entrance switchboard(s) as herein specified and shown on the associated electrical drawings. B. Distribution

More information

Dale Pennington, Managing Director, Utiliworks Consulting LLC, New York, USA

Dale Pennington, Managing Director, Utiliworks Consulting LLC, New York, USA Dale Pennington, Managing Director, Utiliworks Consulting LLC, New York, USA Meter Data from Cradle to Grave, do you know where your Data is? Getting Started Create your project team such that all critical

More information

Transformer / Line Loss Calculations

Transformer / Line Loss Calculations 70072-0153-07 TECHNICAL NOVEMBER 2006 Transformer / Line Loss Calculations This document gives a brief overview of transformer loss and line loss calculations and describes how these calculations are implemented

More information

Software High Level Design Specification

Software High Level Design Specification Single-Phase Energy Meter Reference Platform Software High Level Design Specification Ver1.0 Note: This document may subject to change by Renesas Technology Singapore without prior notice. This is to record

More information

Instruction Manual. Model 1550 DC Power Supply with USB Charger Output 1-30V, 0-3.3A

Instruction Manual. Model 1550 DC Power Supply with USB Charger Output 1-30V, 0-3.3A Instruction Manual Model 1550 DC Power Supply with USB Charger Output 1-30V, 0-3.3A Keep this manual in a safe place for quick reference at all times. This manual contains important safety and operation

More information

FUNCTIONAL SPECIFICATION FOR AN ADVANCED METERING INFRASTRUCTURE VERSION 2

FUNCTIONAL SPECIFICATION FOR AN ADVANCED METERING INFRASTRUCTURE VERSION 2 FUNCTIONAL SPECIFICATION FOR AN ADVANCED METERING INFRASTRUCTURE VERSION 2 July 5, 2007 FUNCTIONAL SPECIFICATION FOR AN ADVANCED METERING INFRASTRUCTURE Table of Contents 1.0 APPLICATION OF SPECIFICATION...3

More information

H.V.A.C. Design Plumbing Design

H.V.A.C. Design Plumbing Design H.V.A.C. Design H.V.A.C. Design Mira Costa College Arts Complex CP Upgrade 1. PART 1 GENERAL 1.1. DESCRIPTION SECTION 23 09 00 HVAC INSTRUMENTATION AND CONTROL 2. PART 2 - PRODUCTS 2.1. Materials

More information

Powerterm L120C-D Dual Voltage PSU/Battery Charger Model C2197B 120W 12/24Volt Power Supply/ Battery Charger

Powerterm L120C-D Dual Voltage PSU/Battery Charger Model C2197B 120W 12/24Volt Power Supply/ Battery Charger DATASHEET Supply both 12Vdc 1Amp and 24Vdc 3 Amps average power to loads in a single product. Ideal for RTU s, dataloggers, remote field instrumentation, alarm systems, etc. where 24Volts is required for

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

SECTION PROCESS INSTRUMENTATION AND CONTROL SYSTEM PROGRAMMABLE LOGIC CONTROLLERS

SECTION PROCESS INSTRUMENTATION AND CONTROL SYSTEM PROGRAMMABLE LOGIC CONTROLLERS SECTION 13311 - PROCESS INSTRUMENTATION AND CONTROL SYSTEM PROGRAMMABLE LOGIC CONTROLLERS PART 1 - GENERAL 1.01 WORK INCLUDED A. This Section covers work related to the Programmable Logic Controllers (PLC)

More information

Commercial & Industrial Electricity Metering

Commercial & Industrial Electricity Metering GE Digital Energy Commercial & Industrial Electricity Metering Versatile metering for demanding applications GE s kv2c meter family is designed for revenue class metering in commercial and industrial applications.

More information

DC Inline Watt Meter. RENOGY 150A High Precision Watt Meter and Power Analyzer. 2775 E. Philadelphia St., Ontario CA 91761 1-800-330-8678

DC Inline Watt Meter. RENOGY 150A High Precision Watt Meter and Power Analyzer. 2775 E. Philadelphia St., Ontario CA 91761 1-800-330-8678 DC Inline Watt Meter RENOGY 150A High Precision Watt Meter and Power Analyzer 0 2775 E. Philadelphia St., Ontario CA 91761 1-800-330-8678 Important Safety Instructions Please save these instructions. This

More information

THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATION. For

THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATION. For THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATION For THREE PHASE WHOLE CURRENT (DIRECT CONNECTED) STATIC METERS FOR ACTIVE ENERGY For Use On SMALL COMMERCIAL AND LIGHT INDUSTRIAL INSTALLATIONS NAME DESIGNATION

More information

A. This Section includes PC-based workstation(s) and software for monitoring and control of electrical power system.

A. This Section includes PC-based workstation(s) and software for monitoring and control of electrical power system. SECTION 260913 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes PC-based workstation(s) and software for monitoring and control of electrical power system. 1.2 SUBMITTALS A. Product Data: For each

More information

Meter, Meter Reading Instrument (MRI) and Base Computer Software for Meter Data Management (MDM) Vivek Pathak Secure Meters

Meter, Meter Reading Instrument (MRI) and Base Computer Software for Meter Data Management (MDM) Vivek Pathak Secure Meters Meter, Meter Reading Instrument (MRI) and Base Computer Software for Meter Data Management (MDM) Vivek Pathak Secure Meters A specifically designed programme for Da Afghanistan Breshna Sherkat (DABS) Afghanistan

More information

SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-33 EXPERIMENTAL PRICE PLAN FOR SUPER PEAK TIME-OF-USE GENERAL SERVICE

SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-33 EXPERIMENTAL PRICE PLAN FOR SUPER PEAK TIME-OF-USE GENERAL SERVICE SALT RIVER PROJECT AGRICULTURAL IMPROVEMENT AND POWER DISTRICT E-33 EXPERIMENTAL PRICE PLAN FOR SUPER PEAK TIME-OF-USE GENERAL SERVICE Effective: April 2015 Billing Cycle Supersedes: November 2012 Billing

More information

DCS-E 1kW Series, DLM-E 3kW & 4kW

DCS-E 1kW Series, DLM-E 3kW & 4kW DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies M51A Option: Isolated Analog Programming Manual M362250-01 Rev C www.programmablepower.com About AMETEK AMETEK Programmable Power, Inc., a Division of

More information

PR-2500 Portable Receiver. Owner s Manual

PR-2500 Portable Receiver. Owner s Manual PR-2500 Portable Receiver Owner s Manual CONTENTS The PR-2500, battery charger, and belt clip. (figure 1) Figure 1 Warning This device complies with Part 15 of the FCC rules, operation of this device is

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

NortechCommander Software Operating Manual MAN-00004 R6

NortechCommander Software Operating Manual MAN-00004 R6 NortechCommander Software Operating Manual MAN-00004 R6 If the equipment described herein bears the symbol, the said equipment complies with the applicable European Union Directive and Standards mentioned

More information

Key Information in relation to Residential Solar Systems 2012

Key Information in relation to Residential Solar Systems 2012 Key Information in relation to Residential Solar Systems 2012 1. Key Information Standard Lead Times Standard lead times for the commencement of solar system installations are generally between 6 8 weeks

More information

FP-100 Fuel Pressure and Ammeter Indicator Page 1 of 16. All specification subject to change Aerospace Logic Inc.

FP-100 Fuel Pressure and Ammeter Indicator Page 1 of 16. All specification subject to change Aerospace Logic Inc. Page 1 of 16 All specification subject to change 2002-2005 FP-100 Operations and Installation Manual This manual is certified for use with instrument serial number ASL000000 Use of this manual with any

More information

Alarm Clock USER GUIDE

Alarm Clock USER GUIDE Alarm Clock USER GUIDE Jazwares, Inc. 2010 1 CONTENTS Please read the instructions along with the alarm clock carefully before you use it, so that you can operate it conveniently. WELCOME, Safety Tips

More information

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM Section TELEPHONE AUTOMATIC DIALER SYSTEM PART 1 GENERAL 1.01 SYSTEM DESCRIPTION A. Design Requirements: 1. Electronic monitoring system shall interface plant alarms to public telephone system or cellular

More information

Dakota Energy Cooperative, Inc. POLICY STATEMENT

Dakota Energy Cooperative, Inc. POLICY STATEMENT Dakota Energy Cooperative, Inc. POLICY STATEMENT Subject: Member Owned Small Renewable Energy Policy No. 57 Rate and Interconnection Requirements Issue Date: May 21, 2008 Revised Date: December 16, 2014

More information

Single Phase Single Element Electronic Meters:

Single Phase Single Element Electronic Meters: Single Phase Single Element Electronic Meters: September 2012 13 SEPTEMBER 2012 ISSUE 5 OPERATIONAL MANUAL Single Phase, Single Element Electronic Meters: PREPARED BY: METROLOGY SPECIALIST & LABORATORY

More information

Digital/Analog Megohmmeter Model 1026 USER MANUAL

Digital/Analog Megohmmeter Model 1026 USER MANUAL Digital/Analog Megohmmeter Model 1026 USER MANUAL MEGOHMMETER MODEL 1026 MΩ V Ω TEST LOCK HOLD 4000Ω MΩ - 250V MΩ - 500V V MΩ - 1000V OFF MΩ V Ω 600V CAT III 1000V CAT II 1000V Statement of Compliance

More information

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems This Agreement is made and entered into this day of, 20, ( Effective Date ) by and between the Orlando Utilities Commission

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER FILE: IM_091-120-12E-20 Rev A., 05-06-08 INSTRUCTION MANUAL AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER R MODEL #091-120-12E-20 for ODYSSEY AGM BATTERIES CAUTION This charger is calibrated to the ODYSSEY

More information

The closed-transition transfer switches and controls shall conform to the requirements of:

The closed-transition transfer switches and controls shall conform to the requirements of: SUGGESTED SPECIFICATION for Automatic Closed Transition Transfer Switches Specification writer please note: This system will momentarily connect the emergency generator to the utility during transfer.

More information

STANDARDS. Wholesale Revenue Metering Standard - Hardware PUBLIC. Issue 11.0 MDP_STD_0004

STANDARDS. Wholesale Revenue Metering Standard - Hardware PUBLIC. Issue 11.0 MDP_STD_0004 PUBLIC MDP_STD_0004 STANDARDS Wholesale Revenue Metering Standard - Hardware Issue 11.0 This standard provides the principles, accountabilities, and requirements for metering installations used for settlement

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

SECTION 263235 STANDBY GENERATOR TESTING AND COMMISSIONING

SECTION 263235 STANDBY GENERATOR TESTING AND COMMISSIONING SECTION 263235 STANDBY GENERATOR TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standby generators. 2. Automatic Transfer Switches (ATS). 3. System start-up services. 4.

More information

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark

More information

Elster Metering Systems. EC Directive 2004/22/EC

Elster Metering Systems. EC Directive 2004/22/EC EC Type Examination Certificate Number: UK/ 0120/ SGS0010 Elster Metering Systems Instrument Identification: A1100, Electricity Meter, LB********* Poly Phase, Credit, Active Import/ Export, Multi-rate,

More information

Grid Interactive Inverters with Export Control up to 200 kw

Grid Interactive Inverters with Export Control up to 200 kw TECHNICAL REQUIREMENTS Grid Interactive Inverters with Export Control up to 200 kw Scope The scope of this document is to outline the technical requirements, Certification and documentation required for

More information

N.J.A.C. 14:8-4 NET METERING FOR CLASS I RENEWABLE ENERGY SYSTEMS

N.J.A.C. 14:8-4 NET METERING FOR CLASS I RENEWABLE ENERGY SYSTEMS N.J.A.C. 14:8-4 NET METERING FOR CLASS I RENEWABLE ENERGY SYSTEMS 14:8-4.1 Scope This subchapter sets forth net metering requirements that apply to electric power suppliers, basic generation service providers

More information

Single Phase Magnetic Card Electricity Meter

Single Phase Magnetic Card Electricity Meter Single Phase Magnetic Card Electricity Meter Model Type: 5188A USER MANUAL issue 1.0 Contents 1 Introduction 2 1.1 Overview 2 2 Technical Data 2 2.1 Meter Element 2 2.2 Main Contactor & Auxiliary Relay

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Rocky Mountain Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system

More information

Meter News. FOCUS Family of Residential KWH Meters I NSIDE THIS I SSUE

Meter News. FOCUS Family of Residential KWH Meters I NSIDE THIS I SSUE Meter News A Carlson Sales Metering Solutions, LLC. Publication discussing new products and ideas We are your source for Landis+Gyr Metering serving Oregon, Washington, Alaska, and Idaho Volume 1, Issue

More information

Designing a Tamper Proof Energy Meter Using Kinetis KM34

Designing a Tamper Proof Energy Meter Using Kinetis KM34 Freescale Semiconductor Document Number: AN4993 Application Note Rev 0, 08/2014 Designing a Tamper Proof Energy Meter Using Kinetis KM34 by: Himanshu Singhal 1 Introduction Energy theft is a worldwide

More information

INFORMATION FOR METER SERVICE PROVIDERS (MSP) FOR ARIZONA CERTIFICATION

INFORMATION FOR METER SERVICE PROVIDERS (MSP) FOR ARIZONA CERTIFICATION - 1 - FOR ARIZONA CERTIFICATION Meter Worker Qualification Requirements For Direct Access Metering in Arizona I. Introduction Three classes of meter worker qualifications are set forth as criteria for

More information

Alarm Clock USER GUIDE

Alarm Clock USER GUIDE Alarm Clock USER GUIDE Jazwares, Inc. 2012 CONTENTS Please read the instructions along with the Alarm Clock carefully before you use it, so that you can operate it conveniently. WELCOME & Warnings Page

More information

User manual * * * * * * * * * * * * * * * * SDM120 series User Manual * * * * * * * * * * * * * * * * * * * * * * * * * *

User manual * * * * * * * * * * * * * * * *  SDM120 series User Manual * * * * * * * * * * * * * * * * * * * * * * * * * * SDM120 series User Manual SDM120 SERIES Single phase two wire DIN rail energy meter (One module) User manual ------------ 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications

More information

We Energies Electric Rates

We Energies Electric Rates We Energies Electric Rates for Michigan customers July 2015 The rates in this brochure reflect the authorized base rates of Wisconsin Electric Power Company, doing business under the name of We Energies,

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual 0RQLWRU Pulse Monitor Software Version 1 0 1 Pulse Monitor Card Software Revision 1 4 0 Pulse Monitor Card Product Revision 0 1 0 0 February, 2007 Copyright 2007,

More information

Table of Contents. Introduction...3 Unpacking...4 Warranty Instructions...4. Installation...7

Table of Contents. Introduction...3 Unpacking...4 Warranty Instructions...4. Installation...7 Table of Contents 1 Introduction...3 Unpacking...4 Warranty Instructions...4 Installation...7 Operation...9 Remote Control Buttons...11 Place a Call...11 End a Call...11 Adjust the Volume in the Room...11

More information

E350 series 2. Electricity Meters IEC/MID Residential. ZxF100Ax/Cx. User Manual

E350 series 2. Electricity Meters IEC/MID Residential. ZxF100Ax/Cx. User Manual Electricity Meters IEC/MID Residential ZxF100Ax/Cx E350 series 2 User Manual Date: 20.12.2011 File name: D000027979 E350 ZxF100Ax Cx series 2 User Manual EN.docx Landis+Gyr D000027979 EN n 2/54 Revision

More information

Titelgrau belassen! Leere Vorlage

Titelgrau belassen! Leere Vorlage Titelgrau belassen! Leere Vorlage MAVOWATT 20 Energy Platform Energy and Power Analyzer MAVOWATT 20 The new Energy and Power Analyzer 2 Klaus-Peter Richter Product Management 10.3.2010 Page 2 Applications

More information

DC to AC Power Inverters

DC to AC Power Inverters Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com 121309B OWNERS

More information

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1 Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to

More information

Generator Meter Model: VAAFH Installation/Operation Manual

Generator Meter Model: VAAFH Installation/Operation Manual Generator Meter Model: VAAFH Installation/Operation Manual I) Introduction The VAAFH is an ideal monitor system for 240/120 generators and grid power sources and provides monitor of load balancing on the

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Global Water Instrumentation, Inc. 11257 Coloma Road Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 Insertion Flow Meter: IF200-1 - Congratulations on your purchase of the

More information

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100 Diesel Engine Fire Pump Controllers Product Description Fire Pump Controllers for Business-Critical Continuity

More information

A. This Section includes SPDs for low-voltage power, control, and communication equipment.

A. This Section includes SPDs for low-voltage power, control, and communication equipment. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 1 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 PROJECT CONDITIONS... 3 1.8 COORDINATION...

More information

Belleville Fire Hall/Headquarters and Emergency Operations Centre Belleville, Ontario Page 1 of 6

Belleville Fire Hall/Headquarters and Emergency Operations Centre Belleville, Ontario Page 1 of 6 Belleville, Ontario Page 1 of 6 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

AS230 Single Phase Meter. End User's Guide

AS230 Single Phase Meter. End User's Guide AS230 Single Phase Meter End User's Guide M200 500 5B 12.2011 AS230 Meter 1 ABOUT THIS DOCUMENT This document is intended as a guide to help suppliers of Elster Metering Systems AS230 Meters produce User

More information

Sola/Hevi-Duty S2K Series UPS

Sola/Hevi-Duty S2K Series UPS Sola/Hevi-Duty S2K Series UPS GUIDE SPECIFICATIONS 350VA to 1000VA Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

INSTALLATION MANUAL SLI 50 DISPLAY UNIT SLI 50 LED UNIT

INSTALLATION MANUAL SLI 50 DISPLAY UNIT SLI 50 LED UNIT INSTALLATION MANUAL SLI 50 DISPLAY UNIT SLI 50 LED UNIT (P/N: 3G10001F100G) www.unipowerco.com (P/N: 3G34001F100G) Manual No. SLI-50-DISPLAY-3 2016 UNIPOWER LLC All Rights Reserved UNIPOWER LLC 3900 Coral

More information

POWERLOGIC Circuit Monitor Series 2000

POWERLOGIC Circuit Monitor Series 2000 Class POWERLOGIC Circuit Monitor Series 2000 Features True rms metering Certified ANSI C2.6 revenue accuracy High accuracy 0.2% current and voltage Power quality readings THD, k-factor, crest factor Over

More information

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 METRIC SPECIFICATIONS FOR RS232 LEASED LINE MODEMS (LOW SPEED MODEL 400)

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 METRIC SPECIFICATIONS FOR RS232 LEASED LINE MODEMS (LOW SPEED MODEL 400) STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 METRIC SPECIFICATIONS FOR RS232 LEASED LINE MODEMS (LOW SPEED MODEL 400) N.J. Specification No. Effective Date: July 1, 2001 New

More information

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications Product Name: Enclosed Adjustable Frequency Drive - Class 8839 E-Flex AC Drive for Variable Torque HVAC and Pumping Applications (1-100 hp, 460 V and 1-50 hp, 208/230 V) SECTION 15 Enclosed Adjustable

More information

INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series

INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series Communication system for the management of electrical installations INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series MID Approval Technology for energy efficiency PLC Communications (Power Line Communication)

More information

User's Manual. Heavy Duty Dissolved Oxygen Meter Model 407510

User's Manual. Heavy Duty Dissolved Oxygen Meter Model 407510 User's Manual Heavy Duty Dissolved Oxygen Meter Model 407510 Introduction Congratulations on your purchase of Extech's Heavy Duty Dissolved Oxygen / Temperature Meter which simultaneously displays Dissolved

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

1.02 Scope of Work A. Provide a complete fire pump system as defined by the latest edition of NFPA 20

1.02 Scope of Work A. Provide a complete fire pump system as defined by the latest edition of NFPA 20 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fire pumps. This document is not intended to serve as a guide specification.

More information

PS3000 Weighing Indicator USER GUIDE

PS3000 Weighing Indicator USER GUIDE PS3000 Weighing Indicator USER GUIDE Edition: 08-06-2012 Safety Instruction WARNING Calibration, inspection, and maintenance of the indicator must be performed by a qualified technician. WARNING The indicator

More information

Sound Detector SD-200 User Manual

Sound Detector SD-200 User Manual 3M Occupational Health & Environmental Safety Division 3M TM Sound Detector SD-200 Sound Detector SD-200 User Manual 3M TM Sound Detector SD-200 SD-200: dangers, warnings, cautions & battery Danger! Failure

More information

MINNESOTA VALLEY ELECTRIC COOPERATIVE DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS FOR INVERTER CONNECTED SYSTEMS RATED 40KW OR LESS,

MINNESOTA VALLEY ELECTRIC COOPERATIVE DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS FOR INVERTER CONNECTED SYSTEMS RATED 40KW OR LESS, MINNESOTA VALLEY ELECTRIC COOPERATIVE DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS FOR INVERTER CONNECTED SYSTEMS RATED 40KW OR LESS, TABLE OF CONTENTS 1. Introduction 3 2. References 6 3. Interconnection

More information

Digital USB Postal Scale User Guide M10 M25

Digital USB Postal Scale User Guide M10 M25 Digital USB Postal Scale User Guide M10 M25 DYMO Digital USB Postal Scale This User Guide provides instructions for using your DYMO Digital USB Postal Scale. Visit www.dymo.com/register to register your

More information

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114. Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine

More information

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS + Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,

More information