City of Palestine Centrifuge Control Upgrade Project March 31, 2016 NOTICE TO BIDDERS
|
|
- Grant Crawford
- 7 years ago
- Views:
Transcription
1 City of Palestine Centrifuge Control Upgrade Project March 31, 2016 NOTICE TO BIDDERS Sealed bids will be received by the city of Palestine, Palestine, Texas at the office of Theresa Herrera, City Secretary, 504 N Queen, Palestine, Texas until the 25 th day of April 2016 at 3:00 PM at which time bids duly delivered and submitted will be considered for the following: RFP # City of Palestine Centrifuge Control Upgrade Project Any bid received after stated closing time will be returned unopened. If bids are sent by mail to the City Secretary, the bidder shall be responsible for actual delivery of the bid to the City Secretary before the advertised date and hour for receiving of bids. If mail is delayed by the postal service or courier service beyond the date and hour set for the bid opening, bids thus delayed will not be considered and will be returned unopened. Information concerning the bid specifications may be obtained by calling Felipe Garcia, Waste Water Treatment Plant Supervisor at or fgarcia@palestine-tx.org; or Tim Perry, Public Works and Interim Utilities Director at or timperry@palestine-tx.org. Information on the bid process/procedures may be obtained from Heather Powell, Purchasing Agent at or hpowell@palestine-tx.org. Until the final award by the City of Palestine, said City reserves the right to reject any and/or all bids, to waive technicalities, to re-advertise, to proceed otherwise when the best interests of said City will be realized hereby. Bids will be submitted sealed and plainly marked with the date and time of opening. Publication Dates: Thursday, March 31, 2016 and Thursday, April 7, 2016 Closing Date: Monday, April 25, 3:00 PM Bid Opening: Monday, April 25, 5:30 PM
2 Centrifuge Control Upgrade City of Palestine Waste Water Treatment Plant- Alfa Laval PM I II General A) The back drive and control system of the existing Alfa Laval PM centrifuge at the Main WWTP are antiquated and in need of upgrading, improvement, and/or replacement. The intent of this specification is to obtain the services of a qualified Centrifuge Supplier regularly engaged in the supply and installation of centrifuge drives, control systems to upgrade the back drive system, replace the existing control panel for this unit, and bring the centrifuge back to a dependable operating state. Description A) The purpose of this project is to replace one (1) Alfa Laval PM-3800 Control Panel, Feed Pump Panel, Eddy Current Brake back drive motor and motor mount system. The successful bidder will be required to provide on-site personnel for modification, removal and installation, function testing, start-up, and operator/maintenance training. This project shall be turnkey including removal of old components, control panels, installation of new Centrifuge Control Panels (CCP s) and back drive components. The work shall be provided by a centrifuge manufacturer that is: 1) Currently supplying and installing new centrifuge machines and control systems 2) Experienced in upgrading existing centrifuge systems 3) Familiar with the sludge dewatering process B) This centrifuge shall be modified and fitted with a new back drive motor, motor mount stand and modified belt guard. The new motor shall be properly sized to provide the required speed and torque range required to meet the centrifuge operating capacity. Each new motor shall be an AC inverter duty rated motor. The existing main drive motor shall be utilized. C) The existing centrifuge control panels shall be disconnected, removed and replaced with new CCP s. The new CCP shall be a UL508A listed assembly and shall contain the following major components: 1) Main power disconnect 2) Main Drive Variable Frequency Drive (VFD) 3) Feed pump VFD 4) Back drive VFD torque control system with power regeneration 5) Programmable Logic Controller (PLC) system 6) Color touchscreen Operator Interface Terminal (OIT) 7) Required switches, power supplies, relays, fuses, and terminals D) The City will provide a Licensed Electrical Contractor of its choosing for the site work to make listed modifications and electrical work required to remove obsolete 1 P a g e
3 components, conduit, and wiring and to install new control panels, motors, conduit, and wiring as required per the developed design drawings and instructions. E) The work required for this project shall be coordinated by a Centrifuge Original Equipment Manufacturer (OEM), who will provide guidance for the on-site mechanical and electrical modifications and installation. The Centrifuge OEM shall provide the engineering design, programming, function testing, and start-up of each upgraded centrifuge control system. F) Warranty of supplied components shall be a minimum of one year from delivery at the City s site. An option for an extended warranty shall be provided as an option to the proposal pricing. III References: The design, manufacture, and installation of this equipment shall meet or exceed the applicable provisions and recommendations of the following codes and standards authorities. A) AGMA, American Gear Manufacturers Association B) ASME, American Society of Mechanical Engineers C) ASTM, American Society of Testing and Materials D) ANSI, American National Standards Institute E) IEEE, Institute of Electrical and Electronics Engineers F) NEC, National Electrical Code G) OSHA, Occupational Safety and Health Act IV Quality Assurance A) Bidder Qualifications: 1) Bidder must be a centrifuge OEM and currently engaged in the design, supply, and installation of centrifuges and centrifuge control systems. Confirm this requirement is met with proposal submittal. 2) Provide references with proposal of at least three (3) similar projects completed during the last five (5) years. Include information on the machine type, project description, customer name, and customer contact information. 3) Bidder must possess Alfa Laval/Sharples Centrifuge Factory Training Certification for centrifuges being upgraded. Include a copy of certificate with proposal. 4) Centrifuge OEM s facility must be within two hundred seventy five (300) miles of the City of Palestine, Tx facility. 5) Bidder must have more than ten (10) years of experience supplying and installing centrifuge controls and control system upgrades. B) Workmanship and Design: 1) All parts of the equipment provided are to be designed and manufactured for long, continuous, and uninterrupted service. All materials used are to be of best quality and entirely suitable for service required. 2 P a g e
4 V 2) Modifications to the existing control panels shall be made for easy adjustment or replacement of all serviceable parts. A minimum clearance is required for proper maintenance. 3) Electrical work shall be completed by a qualified Electrical Contractor following all trade codes and standards previously listed and per local code requirements. C) Sub-contractor Services 1) Electrical sub-contractor will be provided by the City, to furnish qualified, licensed electricians for the removal of obsolete components and installation and wiring of new components, and provide for disconnection of DC back drive motor and installation and wiring of new AC back drive motor including new wire pulled in existing conduit for motor power. All work is to be performed per centrifuge manufacturer s engineering documentation and instructions. The electrical sub-contractor shall supply tools, wire, wire markers, and all miscellaneous hardware for complete installation. 2) Centrifuge manufacturer shall furnish a qualified technician for the modification of the existing back drive motor mount, motor, belt guard, and installation of new components and on-site welding if required. All work to be performed per centrifuge manufacturer s engineering documentation and instructions. The centrifuge technician shall supply all tools, welding equipment and miscellaneous hardware for complete installation. Submissions A) Shop drawings, catalog cut sheets, and other materials required to completely describe and specify system and equipment shall be submitted to the City for review. These shall include: 1) Control panel layout and dimensional drawings 2) Revised electrical schematics 3) Revised Bill of Material (BOM) 4) Written control system description 5) Written sequence of operation 6) Back drive motor mount drawings B) At the completion of the project the manufacturer shall supply the following asbuilt documents and electronic files: 1) Control panel layout and schematic drawings 2) BOM 3) Control System Description 4) Sequences of Operation 5) PLC Program code, annotated 6) OIT Application Program 3 P a g e
5 VI 7) Component Operation and Maintenance Information Delivery, Storage, and Handling: Components shall be shipped to the City s site. The City will off load and store in a clean dry environment until commencement of work at which time parts delivered shall be turned over to Contractors Personnel on site. VII Warranty A) Warranty of supplied components shall be a minimum of one year from delivery at the City s site. B) An option for an extended warranty shall be provided as an option to the proposal pricing. VIII Products General A) The equipment specified herein addresses modification for one (1) Alfa Laval PM Centrifuge to be performed by a centrifuge manufacturer meeting all of the detailed requirements of these specifications, without exception. B) Like items of equipment shall be the product of one (1) manufacturer to achieve standardization of operation, spare parts, maintenance, and manufacturer s service. IX Control System Requirements A) The centrifuge control panel shall be a NEMA 4 freestanding enclosure. B) The panel shall include a flange mount main disconnect that can be locked in the off position. C) Main Drive Power Components shall consist of an Allen Bradley Powerflex 753 VFD for bowl drive motor and shall be rated at 40 HP; a Allen Bradley Powerflex 753 VFD rated for 7.5 HP for the scroll drive motor; a Allen Bradley Powerflex 753 for the feed pump. D) The panel shall operate from a 480V AC, 3 phase, 60 Hz service and shall also include a control power transformer for auxiliary components. E) Main control components shall consist of : 1) Square D 100A main circuit breaker 2) Allen Bradley programmable logic controller 3) Control relays 4) Terminal points for interconnection with ancillary equipment F) Door mounted components shall consist of : 1) Mushroom head maintained emergency stop 2) NEMA 4X Allen Bradley 10 inch color touch screen OIT 3) OIT control functions on front of control panel shall, as a minimum, include: Start/Stop, On/Off controls of: (a) System Control Power (hardwired push button) (b) Auto Sequence (c) Clean in Place (CIP) Sequence (d) Centrifuge Drives (e) Wash water Solenoid Valve (f) Alarm control 4 P a g e
6 X OIT Status Indication for: (a) System Control Power on (b) Auto Start Starting in Auto (c) Auto Stop Stopping in Auto (d) CIP Running in CIP (e) Centrifuge Running (f) Wash water Solenoid Open (g) Ready for Feed Ready Alarms shall consist of a siren and strobe light, and shall notify plant personnel of the following faults. (a) Emergency Stop Fault (b) Bowl Motor Overload Fault (c) Bowl Drive Motor Temperature Fault (d) Back Drive VFD Fault (e) Back Drive Motor Temperature Fault (f) Back Drive High Torque Fault (g) Back Drive High-High Torque Fault (h) High Vibration Fault (i) High-High Vibration Fault (j) Low Relative Speed Fault OIT Digital Speed, Flow Indication of: (a) Bowl Speed RPM (b) Back Drive Speed RPM (c) Back Drive Torque Percent (d) Differential Speed RPM (e) Vibration In/Sec (f) Feed Rate Percent OIT Speed Control for: (a) Back Drive Differential Speed (PI Manual) (b) Back Drive Pinion Speed (PI Manual) (c) Back Drive Torque (PI Auto) Back drive System Requirements A) The existing back drive Eddy current motor shall be disconnected and removed. Existing conduit stub shall be reused and unused stubs capped as required for new power feed. B) The existing motor mount, sheaves, and belt guard shall be modified to accommodate new AC motor. The motor shall be replaced and new wire properly sized and pulled through existing conduit. C) The back drive motor shall be 7.5 HP, 460VAC, 3Ph, inverter rated, severe duty, high efficiency. The motor shall be supplied by the centrifuge manufacturer and the motor manufacturer used shall have supplied motors for this type of centrifuge application. 5 P a g e
7 XI Functional Requirements A) The new centrifuge drive, control, and monitoring system shall provide the following functional capabilities: B) Back drive VFD controlled system capable of variable speed for setting differential speed of scroll conveyor. C) The centrifuge shall be capable of operating in three (3) different control modes: 1) Differential Speed Control (manual) mode shall allow operator to set the conveyor speed and maintain the set point. 2) Pinion Speed Control (manual) mode shall allow operator to set the pinion speed and maintain the set point. 3) Torque Control (auto) mode shall allow operator to set percent torque to maintain and the control system shall automatically adjust differential speed to maintain the set point. D) Operator controls, monitoring, and alarms shall incorporate existing system controls along with additional operator controls as deemed necessary for the proper operation of the complete dewatering system. In addition, automatic controls shall be provided for pausing, flushing, and resuming feed and polymer based on warning alarm indications. E) A written centrifuge control system description and sequence of operation shall be provided by the manufacturer for review and approval by the City before modification of the centrifuge system. XII Execution The centrifuge control system upgrade shall not be considered complete and satisfactory until functional testing and training on new control system is complete. A) Electrical sub-contractor shall perform all on site work per the manufacturer engineering design drawings and instructions. B) Electrical sub- contractor shall provide manpower during functional testing phase to assist with any troubleshooting of wiring and installation. XIII On Site Installation Application Manufacturer s Representation for Installation, Start-up, Testing, and Training A) The Centrifuge manufacturer s technical representative for the equipment specified here in shall be present at the jobsite for five (5) work days for the services listed below. The following services shall be provided with allocation of workdays as established by the City with the following distribution as a guide: 1) Two (2) workdays for onsite coordination with Electrical subcontractor 2) Three (3) workdays per centrifuge for functional testing, start-up, and training B) Workdays shall be eight (8) hour days, Monday through Friday. 6 P a g e
8 XIV Field Tests A) Functional testing shall be performed for each centrifuge control system installed. Prior to system start-up, system components shall be inspected for proper alignment, proper connection, and satisfactory operation. The centrifuge manufacturer s representative shall inspect installation of new components, check for minor adjustments, and provide certification that the control system components have been installed correctly and are ready for operation. 7 P a g e
Invitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
More informationETZGAR CONVEYOR COMPANY Controls Section v12.05
Section 7 Controls Page Description 7-1 Controls Index 7-2 Motor Data, Enclosure Rating and Abbreviations 7-3 Controls Safety Guidelines 7-4 Fixed Speed Controls Packages 7-5 Three Phase AC Variable Speed
More informationSECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
More informationOperational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationOperational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
More informationRecommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationE-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT
SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories
More information98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC.
81471067 Electric Monitor Motor Control Panel For use with Model 8394059 SPIT-FIRE Monitor Installation, Operation, and Maintenance Instructions FOR ATEX APPLICATIONS 1302 WEST BEARDSLEY AVENUE P.O. BOX
More informationTOP RUNNING SINGLE GIRDER BRIDGE CRANE
SECTION 14630 TOP RUNNING SINGLE GIRDER BRIDGE CRANE 1.01 SUMMARY PART 1- GENERAL A. The work required under this section shall include the designing, manufacturing, shipping, installing and field testing
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationBuilding Commissioning 17900-1
SECTION 17900 BUILDING COMMISSIONING PART 1 - GENERAL 1.01 WORK DESCRIPTION: A. General: 1. The Commissioning process is a joint team effort to ensure that all mechanical equipment, controls, and systems
More informationADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.
ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS
More informationSECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
More informationInvitation for Bid Sewer Repair Project
Invitation for Bid Sewer Repair Project Section 1 History, Objective, Required Services, and Specifications Objective Repair/Replace a collapsing sewer line consisting of terra cotta clay and concrete.
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationMechanical Installation
Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s
More informationCONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING
PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA
More informationFIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationRoped Hydraulic Residential Elevator Specifications
January 1, 2004 Roped Hydraulic Residential Elevator Specifications P.O. Box 749, 5191 Stump Rd., Plumsteadville, PA 18949 Toll Free: 888-443-2800, Phone: 215-766-3380, Fax: 215-766-3385 CONTENTS Part
More informationAdditional specific restrictions are laid out in the following bid packet. As a courtesy, we have provided the following summary of this bid.
Vendor Notice Please Read! Vendors, this RFP is being issued with the intent of utilizing Federal FCC E-rate funds. You MUST COMPLY with all rules and regulations associated with the E-rate program. If
More informationSample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES
SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES A. The Owner will contract separately and directly for the majority of the commissioning work
More informationSpecifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
More informationLTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationMTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
More informationDesign & Construction Standards, Revised January 2013 5.21.30-1
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.
More informationCONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13
CONTROL PANEL INSTALLATION INSTRUCTIONS Single Phase Simplex Page 2-7 3-Phase Simplex Page 8-13 Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Manufactured by SJE-Rhombus Installation Instructions
More informationINSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
More informationSCHOOL BUS SECURITY SYSTEMS SERVICES - CHILD OCCUPANCY ALARM SYSTEMS PROVIDERS. DATE: November 6, 2015 BID DUE DATE: NOVEMBER 24, 2015 3:00 p.m.
TO: FROM: SCHOOL BUS SECURITY SYSTEMS SERVICES - CHILD OCCUPANCY ALARM SYSTEMS PROVIDERS PUPIL TRANSPORTATION CO-OP DATE: November 6, 2015 BID DUE DATE: NOVEMBER 24, 2015 3:00 p.m. SUBJECT: SCHOOL BUS
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationSECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS)
SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) PART 1: GENERAL 1.01 SCOPE OF WORK A. Under this section of the specifications, the contractor shall furnish and install a shop-fabricated 4X4 Dispersal
More informationCalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
More informationSECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
More informationD. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationNC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
More informationH.V.A.C. Design Plumbing Design
H.V.A.C. Design H.V.A.C. Design Mira Costa College Arts Complex CP Upgrade 1. PART 1 GENERAL 1.1. DESCRIPTION SECTION 23 09 00 HVAC INSTRUMENTATION AND CONTROL 2. PART 2 - PRODUCTS 2.1. Materials
More informationGlossary of Common Crane Ter ms:
Glossary of Common Crane Ter ms: 26 Adjustable brakes: Electro-mechanical device to control crane deceleration. Bridge beam: Traveling beam connected to end trucks - supports trolley hoist and load. Bumpers:
More informationElectric Motor Operator for: Gate Valves / Butterfly Valves / Plug Valves M&H VALVE
Electric Motor Operator for: Gate Valves / Butterfly Valves / Plug Valves M&H VALVE Almost every business day, M&H is assembling and testing valves with Electric Motor operators. Electric motor operator
More informationSAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
More informationSECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationRain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English. 1-800- RAIN BIRD (800-724-6247) or visit www.rainbird.
Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationBT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
More informationWE-350 Series ¼ Turn Electric Actuator
WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information
More informationV1504 Vertical Platform Lift OWNER S MANUAL
V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 01-m03-2016 2 IMPORTANT Ensure that only an authorized Savaria Dealer
More informationVARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems
SECTION 23 81 07 - VARIABLE FREQUENCY DRIVES PART 1 - GENERAL 1.1 SUMMARY A. This section includes all variable frequency drives. All standard and optional features shall be included within the VFD panel
More informationSECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)
PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components
More informationV1504 Vertical Platform Lift OWNER S MANUAL
V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 03-m12-2013 2 IMPORTANT Ensure that only an authorized Savaria Dealer
More informationBeaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems
Beaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems The Beaver Dam Unified School District (BDUSD) is requesting proposals from qualified companies
More informationELECTRICIAN TRADE REGULATION
Province of Alberta APPRENTICESHIP AND INDUSTRY TRAINING ACT ELECTRICIAN TRADE REGULATION Alberta Regulation 274/2000 With amendments up to and including Alberta Regulation 122/2014 Office Consolidation
More informationInstallation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationSWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationControl of Hazardous Energy LOCKOUT/TAGOUT 29 CFR 1910.147
Control of Hazardous Energy LOCKOUT/TAGOUT 29 CFR 1910.147 Contents I. Introduction II. Scope and Application III. Definitions IV. Lockout/Tagout Manual V. Energy Control Procedures 1. Applying Energy
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationAutomatic Door Openers and ADA Devices Rev. 0 Bid # 48240056. Scope of Work
Scope of Work I. Scope of Solicitation II. Instructions to Offerors III. Scope of Work / Specifications IV. Terms and Conditions - Special I. SCOPE OF SOLICITATION Clemson is seeking to initiate a turnkey
More informationREQUEST FOR PROPOSAL FOR BUILDING MANAGEMENT SYSTEMS SERVICES. San Carlos School District
REQUEST FOR PROPOSAL FOR BUILDING MANAGEMENT SYSTEMS SERVICES San Carlos School District June 12, 2015 The San Carlos School District, hereinafter referred to as the Owner invites proposals for the installation
More informationAMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
More informationElectric Panel Pump Control System. Operation, Maintenance and Installation Manual
Manual No. 5EP-OM1-1 Electric Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 SEQUENCE
More informationOPERATING MANUAL CONTRACTOR STYLE AXIAL FANS
Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN
More informationRequest for Qualifications. for. Design-Build of the Proposed. Calaveras River Pump Variable Frequency Drive Upgrade Project
Request for Qualifications for Design-Build of the Proposed Calaveras River Pump Variable Frequency Drive Upgrade Project Request For Qualification No. 7000138614 Issued: June 27, 2016 Qualification Submission
More informationUFGS-16261 (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 29 23 (April 2006) -------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-16261 (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationREQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring
MCC13-04 REQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring Manchester Community College PURPOSE: The purpose of this REQUEST FOR PROPOSAL is to establish a contract for Manchester
More informationMETER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
More informationSEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor
INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:
More informationAmmonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion
More informationMedical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
More informationIndependent School District No. 1 Strive Achieve Succeed Go Beyond Lewiston, Idaho
Independent School District No. 1 Strive Achieve Succeed Go Beyond Lewiston, Idaho REQUEST FOR QUALIFICATIONS Independent School District No. 1, Lewiston, Idaho ( District ) is seeking responses from individuals
More informationSpeed Control Relays SX2
SX2 File 850 CONENS Description.....................................................Page General Information................................................ 2-3 SX2DV General Information...........................................
More informationTP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator
More informationBuilding an Auto-Start Rotary Three Phase Converter. by: Matt Isserstedt
Building an Auto-Start Rotary Three Phase Converter by: Matt Isserstedt Disclaimer: Electrical wiring is inherently dangerous. No warranties are issued or implied about the safety or success of this system.
More informationVilter motor starter solutions The NEW industry standard in motor starter packages
Vilter motor starter solutions The NEW industry standard in motor starter packages Electrical safety by design Built to Underwriters Laboratory (UL) 508A UL Standard for Safety for Industrial Control Panels.
More informationREQUEST FOR PROPOSAL TO PROVIDE CONSTRUCTION MANAGEMENT AND GENERAL CONTRACTOR SERVICES SPRINGVILLE CITY NEW AQUATICS AND ACTIVITIES CENTER
RFP #2016-02 REQUEST FOR PROPOSAL TO PROVIDE CONSTRUCTION MANAGEMENT AND GENERAL CONTRACTOR SERVICES FOR SPRINGVILLE CITY NEW AQUATICS AND ACTIVITIES CENTER RELEASE DATE: January 29, 2016 DUE DATE: February
More informationOwner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance
Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:
More informationP.A.L. S SPECIFICATIONS
PART 1- GENERAL 1.1 SCOPE To furnish all labor, materials and equipment necessary or required to complete the installation of the lift as indicated on the Drawings and Specifications. This specification
More informationLIGHTING CONTROL PANEL
LIGHTING CONTROL PANEL Installation Guide & User Manual THIS PAGE LEFT INTENTIONALLY BLANK 2 WARRANTY STATEMENT Automated Controls & Systems (ACS) warranties its equipment against defects in workmanship
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationDTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
More informationApplication Technique. Safety Function: Magnetic Door Switch Monitoring
Application Technique Safety Function: Magnetic Door Switch Monitoring Products: MC1 Magnetically-coded Door Switch, Guardmaster Dual-input Safety Relay Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008
More information32VFD Variable Frequency Drives for Centrifugal Chillers
32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to
More informationPUSH BUTTON START INSTALLATION MANUAL
PUSH BUTTON START INSTALLATION MANUAL ALTHOUGH THIS PRODUCT HAS BEEN THOROUGHLY TESTED KPIERSON TECHNOLOGIES ASSUMES NO RESPONSIBILITY FOR ANY DAMAGE THAT MAY RESULT BY THE INSTALLATION OF THIS PRODUCT.
More informationFire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
More informationTECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)
TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless
More informationDUPLEX 120 VOLT FLOAT CONTROL PANEL STANDARD SPECIFICATION
DUPLEX 120 VOLT FLOAT CONTROL PANEL STANDARD SPECIFICATION Prepared by: E G Controls Inc. 11790 Phillips Highway Jacksonville fl. 32256 Date Prepared: 3/1/07 3/14/07 1 Copyright, EG Controls, Inc. TABLE
More informationLockout / Tagout Program
Lockout / Tagout Program Table of Contents Page Scope... 2 Definitions... 2 Authorization... 3 Responsibilities... 4 Compliance and Enforcement... 4 When to Lockout/Tagout (LOTO)... 5 Lockout Procedure...
More informationLED MOTION ACTIVATED FLOOD LIGHT
Utilitech & UT Design are registered trademarks of LF, LLC. All Rights Reserved. ITEM #0611551, #0611550 LED MOTION ACTIVATED FLOOD LIGHT MODEL #SE1036-BP2-02LF0-U, SE1036-WH3-02LF0-U Français p. 10 Español
More informationSection 010103 Summary of Work Contract 11-03 Security System, Network Infrastructure and UPS Power
Section 010103 Security System, Network Infrastructure and UPS Power Part 1 General 1.1 Summary (Non-inclusive) A. Section Includes: Construction operations required by Contract Documents, defines aspects
More informationMechanical Contractor Pre-Qualification Packet. SPSC N180 Computer Data Room Phase II. Project No. CP 159313. Notice No. Notice 13-11.
Mechanical Contractor Pre-Qualification Packet SPSC N180 Computer Data Room Phase II Project No. CP 159313 Notice No. Notice 13-11 Issued by Department of Facilities Management Delivery address: Research
More informationC. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
More informationThis equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Power Max Level 2 Charging Station en Installation and Operating Instructions This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the
More informationContractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
More informationLIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
More informationElectrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3
Section 5.1 Electrical Systems - IQAN Digital Control System IQAN Control System Components........................... 5.1.3 IQAN Operational Description: At Machine Startup.....................................
More informationCrawford-AuSable School District VoIP Telephone System REQUEST FOR PROPOSALS March 21, 2011
Crawford-AuSable School District VoIP Telephone System REQUEST FOR PROPOSALS March 21, 2011 I. INVITATION TO BID Crawford AuSable School District, hereby known as District, will accept sealed responses
More informationOffice of Contracts Administration Purchasing
I. Purpose A. The purpose of this bid is to provide the City and County of San Francisco Public Utilities Commission Water Quality Division (WQD) with one (1) (System). II. Scope of Work A. The Contractor
More information12V Portable Diaphragm Compressor Operating and Maintenance Instructions
12V Portable Diaphragm Compressor Operating and Maintenance Instructions (Part No. DC2) Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Guidelines for Product Use...2 Operation
More information