APPLICATION SCHEME BOOK

Size: px
Start display at page:

Download "APPLICATION SCHEME BOOK"

Transcription

1 PPLIIO SHM OOK Global Headquarters 9048 Meridian ircle, orth anton, OH Phone Fax oll Free

2 PPLIIO SHMS - Introduction In order to lay out complicated interlock schemes, it is necessary to understand the simplest applications. On this page, the bic concepts of interlocking are outlined and discussed. Interlocking a Single Unit in One Interlocking wo Units in wo s If it is desired to secure a device in the open position, an interlock is used in Fig. 1. he possession of the key indicates Fig. 1 Fig. 2 that the device is in the open position and is locked by the extension of the interlock bolt. hen the key is inserted in the lock and turned to withdraw the interlock bolt, the device is free to operate to the closed position and the key is held in the lock. hen a device is to be locked only in the closed position an interlock is used shown in Fig. 2. he possession of the key indicates that the device is locked in the closed position, the interlock bolt h been extended to remove the key. hen the key is inserted in the lock and turned to withdraw the interlock bolt, the device is free to operate to the open position and the key is held in the lock. Interlocking a Single Unit in wo s wo methods are used in interlocking a device in both open and closed position. he first method requires only one interlock shown in Fig. 3. he interlock bolt is extended in both the open and closed positions. his is accomplished with two recesses in the device that is being interlocked - each coinciding with the locking bolt in one position. he other method for locking in both the open and closed positions requires two interlocks show n in Fig. 4. Possession of key -1 indicates that the device is locked open. Possession of key -2 indicates that the device is locked closed. he device is shown normally open; therefore, key -1 is free and the L-O interlock bolt is extended into its recess provided in the movable member while key -2 is held and the L- interlock bolt is withdrawn. o close the device, insert key -1 in the L-O lock and turn to withdraw bolt of L-O interlock, which permits the device to be operated. ow the device can be moved to the closed position. Key -2 can be turned to extend the bolt of the L- interlock into its recess, which locks the device in the closed position. 1-1 Fig. 4. his relees Key -2 from the L- interlock. Meanwhile, key -1 is held in the L-O interlock since its withdrawn locking bolt cannot be extended. his method is used more often than the single two-position interlock shown in Fig. 3, due to its adaptability to sequence operations. lso, the possession of key -1 or -2 indicates that the device is locked open or locked closed, respectively. Sequence Interlocking 2 ith the fundamentals developed above, it is quite simple to extend the application to the interlocking of two or more devices in a desired sequence. 1-1 L-O- Fig. 3 he possession of the key indicates that the interlock bolt is extended and that the device is locked either in the open or closed position. Furthermore, the device cannot be operated until the key is inserted and turned in the lock to withdraw the locking bolt. he key cannot be removed from the lock in an intermediate position, but in the fully open or closed positions only. However, in this application, possession of the key gives no indication to whether the device is locked closed or open Fig. 5 wo devices are shown in Fig. 5. In operation they are not closed at the same time. ith the interlocks arranged shown, only one key is required in the interlocking system. oth devices are shown open; therefore, the key is free. o close any one device, the key is inserted and turned in that particular lock to withdraw the interlock bolt. he key is held in this lock until the device is again locked open. his simple interlocking sequence lends itself to a multitude of applications. he procedure is the same for two devices, neither of which is to be opened at the same time.

3 Legend\Symbols -1, -2, -3 evice normally open. evice normally closed. irection of key transfer. Key interchange number. ccess door interlock (etachable latch) ype, M or Y. ccess door interlock Multi-cylinder (etachable latch) ype or M. Interlock with auxiliary switch, 2 make - 2 break, ype SS Interlock with key held. evice in position shown. Interlock with key removed. evice in position shown. ransfer interlock, ype. Interlock with auxiliary switch, 3 make - 3 break, ype SSS L-O L-O Interlock used to lock device open. (with key removed) Interlock used to lock device open. (with key held) ransfer interlock, ype. 3 cylinder Interlock with auxiliary switch ype K Key releed after time delay. L- Interlock used to lock device closed. (with key removed) ransfer interlock, ype. 5 cylinder M ime-delay key relee unit Initiating lock. L- L-O- Interlock used to lock device closed. (with key held) Interlock used to lock device open and closed. Multi-lock interlock. Interlock with an apartment lock. (ccepts one of two keys) 3 Padlock ype P Key Interchange number (showing key held). Interlock with auxiliary switch, 1 make - 1 break, ype S Solenoid key relee unit. Key releed when solenoid is, energized. wo key Solenoid key relee unit. Key releed when solenoid is, energized. Initiating key Key releed when solenoid is energized Key Removable s he or next to the interlock symbol indicates the position of the interlock bolt when the key is removable, = xtended, = ithdrawn. For more information regarding key removable positions plee reference the technical paper How an Individual Key Interlock Operates on our website (lick on ''ustomer Portal", "ownloads", and "Manuals & echnical Papers" then click on How an Individual Key Interlock Operates ). Refer also to the vailable Options on the interlock data sheets and to columns 8 and 9 on either Interlock Ordering Guide (rs or 316 Stainless).

4 able Of ontents Purpose of Interlocking Scheme# Function Switch and reaker Scheme #1 Prevents opening of switch when breaker is closed. Scheme #2 Prevents operation of switch when breaker is closed. Permits re-closing the breaker for servicing when switch is locked open. Scheme #3 Prevents operation of switch when breaker is closed. ircuit cannot be cleared until proper supervisory key is obtained. Grounding Switch with Main Switch Scheme #4 Prevents closing of grounding switch when main switch is closed, and vice versa. Isolating Switches and reaker Scheme #5 Prevents operation of disconnect when breaker is closed. Prevents opening fuse compartment door when disconnect is closed. Scheme #6 Prevents operation of disconnect when any or all of a group of breakers are closed. Operates through transfer interlock, no sequence is required for breaker closing. Scheme #7 Prevents operation of disconnect when any or all of a group of breakers are closed. reakers operated in prearranged sequence. Scheme #8 Prevents operation of disconnects when breaker is closed. Permits servicing of breaker when disconnects are locked open. Scheme #9 Prevents operation of disconnects when breaker is closed, and prevents access to breaker compartment with disconnects closed. Isolating Switches and reaker or Regulator with y-ps Switch Scheme #10 Prevents operation of breaker disconnects and by-ps disconnect under load. Provides for closing of by-ps disconnect before breaker circuit is opened, or permits circuit breaker to be opened with by-ps disconnect remaining open. Scheme #10 Prevents operation of voltage regulator disconnects and by-ps disconnect under load. Permits by-ps disconnect to operate only when regulator is in neutral position. Permits isolating regulator for servicing. Prevent Paralleling of Lines Scheme #11 Prevents paralleling of two lines - single load, fed from either source. Scheme #12 Prevents paralleling of two lines - single load, fed from either source - breaker on load side. Scheme #13 Prevents paralleling of two lines - two loads, fed from either source (one tie breaker) Scheme #14 Prevents paralleling of two lines - two loads, fed from either source (one tie breaker). Prevents operation of switch when breaker is closed (on either source). Scheme #15 Prevents paralleling of two lines - two loads fed from either source (one tie breaker). Prevents operation (open or closed) of disconnect when breaker is closed (on either source). Prevents access to fuses when disconnects and breakers are closed. Scheme #16 Prevents paralleling of three lines - three loads, fed from any source (two tie breakers). Scheme #17 Prevents paralleling of four lines - four loads fed from any source (three tie breakers) Scheme #17 Prevents paralleling of four lines - four loads fed from any source (three tie breakers). lso prevents opening of rear access doors when breakers are energized. Scheme #18 Prevents paralleling of three lines - three loads fed from any source (three tie breakers). Scheme #19 Prevents paralleling of four lines - four leads fed from any source (four tie breakers). Scheme #20 Prevents paralleling of three power sources through a common tie bus not normally in service. Permits feeding any load bus from a second power source through the tie bus. Permits one power source to supply all three load buses through the tie bus. Scheme #21 Prevents paralleling three power sources through a common tie bus not normally in service. Permits feeding any load bus from a second power source through the tie bus only when authorized by a supervisor. Permits one power source to supply all three load buses through the tie bus only when authorized by a supervisor. Scheme #22 Prevents paralleling two incoming primary sources through primary tie bus disconnect. Prevents operation (open or closed) of the disconnects under load. Permits one power source to supply both loads through tie bus. Scheme #23 Prevents paralleling of two incoming primary sources through the primary tie bus disconnect or secondary tie bus breaker. Prevents operation (open or closed) of disconnects under load. Permits one power source to supply both loads through either the primary or secondary tie bus. Scheme #24 Prevents paralleling of two incoming primary sources. Prevents operation (open or closed) of disconnects under load. Permits the isolating of breakers for servicing. Permits one power source to supply both loads through tie bus. Interrupter Switch Scheme #25 Prevents opening fuse compartment door when the interrupter switch is closed. Prevents closing interrupter switch until fuse compartment door is locked closed. Scheme #26 Prevents operation (open or closed) of interrupter switch when breaker is closed. Permits the breaker to be serviced and operated while the interrupter switch is locked open. able of ontents ontinued ext Page

5 able Of ontents Purpose of Interlocking Scheme# Function Interrupter Switch Scheme #27 Prevents operation (open or closed) of interrupter switch when breaker is closed. Prevents opening fuse compartment door when Scheme #28 Scheme #29 Scheme #30 Scheme #31 Scheme #32 interrupter switch is closed. Prevents closing interrupter switch until fuse compartment door is locked closed. Permits the breaker to be serviced and operated while the interrupter switch is locked open. Prevents dropping load when shifting from one source to the other. Prevents opening both interrupter switches at the same time. Permits both interrupter switches to be closed at the same time. Prevents paralleling two lines - requires dropping load when shifting from one source to the other. Prevents closing both interrupter switches at the same time. Permits both interrupter switches to be opened at the same time. Prevents paralleling two lines - requires dropping load when shifting from one source to the other. Prevents closing both interrupter switches at the same time. Permits both interrupter switches to be open at the same time. Prevents operation (open or closed) of either interrupter switch when breaker is closed. Permits the breaker to be serviced and operated while both interrupter switches are locked open. Prevents operation (closed, open or closed) of a three position interrupter switch when the breaker is closed. Permits the breaker to be serviced and operated while the interrupter switch is locked open. Prevents operation (closed, open or closed) of a three position interrupter switch when the breaker is closed. Prevents opening fuse compartment door when the interrupter switch is closed. Prevents closing interrupter switch until fuse compartment door is locked closed. Permits the breaker to be serviced and operated while the interrupter switch is locked open. Motor or Machinery Guard Scheme #33 Prevents opening of guard when motor circuit is closed. Guard may be a door or fence gate that prevents access to moving parts, belts, cutters, or any dangerous equipment. Motor or Machinery Guard with ime elay Scheme #34 Prevents opening of guard (or door) for a predetermined time after removal of power (from motor, centrifuge, condensers, etc.) reakers and Generators Scheme #35 Prevents paralleling of two lines - two loads, fed from either source (one tie breaker). llows switching loads to a generator. Scheme #35 Prevents closing generator breaker when main breaker is closed. Scheme #36 Prevents paralleling of two lines - two loads, fed from either source (one tie breaker). llows switching loads to two generators. apacitor ank ccess Scheme #37 Prevents access to capacitor bank enclosure until capacitors have been grounded and discharged. Scheme #38 Prevents access to capacitor bank enclosure until capacitors have been grounded and discharged - utilizing a ime elay Key Relee Unit (KRU). Uninterrupted Power Sources Scheme #39 Prevents improper maintenance byps of UPS equipment. Scheme #40 Prevents improper maintenance byps of UPS equipment. Precipitator ccess Scheme #41 Prevents access to an electrostatic precipitator, scrubber, or baghouse until all power supplies have been de-energized and properly grounded. Scheme #42 o allow operation of dual output transformer rectifiers with one field removed from service and to prevent opening any access doors of an electrostatic precipitator until all power supplies are de-energized and properly grounded. Scheme #42 o allow operation of dual output transformer rectifiers with one field removed from service and to prevent opening any access doors of an electrostatic precipitator until all power supplies are de-energized and properly grounded. Scheme #42 o allow operation of dual output transformer rectifiers with one field removed from service and to prevent opening any access doors of an electrostatic precipitator until all power supplies are de-energized and properly grounded. able of ontents ontinued ext Page

6 able Of ontents Purpose of Interlocking Scheme# Function ccess Scheme #43 Prevents opening any rectifier enclosure door while the rectifier is operating. Scheme #43 Prevents opening any rectifier enclosure door while the rectifier is operating. Scheme #44 Prevents opening any rectifier enclosure door while the rectifier is operating. Scheme #45 Prevents opening any rectifier enclosure door while the rectifier is operating and prevents opening the negative disconnect switch under load. Scheme #45 Prevents opening any rectifier enclosure door while the rectifier is operating and prevents opening the negative disconnect switch under load.

7 Scheme 1 o prevent opening of switch when breaker is closed. Switch and breaker are in closed position. Key -1 is held in breaker interlock. 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key - 1 is now free. 3. Insert key -1 in L- interlock on switch and turn to unlock. 4. Open switch. Key -1 is now held. Scheme 2-1 o prevent operation of switch when breaker is closed. Permits reclosing of breaker for servicing when switch is locked open. 1 Scheme 3 o prevent operation of switch when breaker is closed. ircuit cannot be cleared until proper supervisory key is obtained. -1 L-O- reaker and switch shown closed. Key -1 held in breaker interlock. Key -2 retained by supervisor. 1. Obtain key -2 from supervisor. 2. Open breaker. 3. Insert key -2 in L-O interlock on breaker and turn key -1 to lock open. key -2 is now held and key -1 is free. 4. Insert key -1 in L-O- interlock on switch and turn to unlock. 5. Open switch. 6. urn key -1 in L-O- interlock on switch to lock open. Key -1 is now free. 7. Return key -1 to breaker interlock and unlock for operation during servicing period SUPRVISORY KY -1 1 L-O- Scheme 4 o prevent closing of grounding switch when main switch is closed, and vice versa L-O- 1-1 Switch and breaker are in closed position. Key -1 is held in breaker interlock. 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key - 1 is now free. 3. Insert key -1 in L-O- interlock on switch and turn to unlock. 4. Open switch. Key -1 is now held. 5. urn key -1 in L-O- interlock on switch to lock open. Key -1 is now free. 6. Return Key -1 to breaker interlock and unlock for operation during servicing period. Main switch shown closed and grounding switch shown open. Key -1 is held in main switch interlock. 1. Open main switch. 2. urn key -1 in L-O interlock on main switch to lock open. Key -1 is now free. 3. Insert Key -1 in L-O interlock on grounding switch and turn to unlock. Key -1 is now held. 4. lose grounding switch.

8 Scheme 5 o prevent operation of disconnect switch when breaker is closed. o prevent opening fuse compartment door when the disconnect switch is closed L-O- reaker, fuse compartment door and disconnect switch are shown in closed positions. Key -1 is held in breaker interlock and key -2 is held in disconnect interlock. o service breaker: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock breaker open. Key -1 is now free. 3. Insert key -1 in L-O- interlock on disconnecting switch and turn to unlock. Key -1 is now held. 4. Open disconnect. 5. urn key -1 in L-O- interlock on disconnect switch to lock open. Key -1 is now free. 6. Return key -1 to breaker interlock and unlock for operation of breaker during servicing. o open fuse compartment door: 1. Proceed from normal position with operations in 1 through 4 above. 2. urn key -2 in L-O interlock on disconnect switch to lock open. Key -2 is now free. 3. Insert key -2 in L- interlock on fuse compartment door and turn to unlock. Key -2 is now held. 4. Open fuse compartment door. Scheme 6 o prevent operation of disconnect switch when breakers,, and are closed. reakers may be opened in any sequence. O: lectrical circuit is equivalent of Scheme L-O isconnect and breakers,, and are shown in closed position. Key -1 is held in transfer interlock. Keys -2, -3, -4 and -5 are held in interlocks on breaker,, and. 1. Open breakers,, and. 2. urn key in L-O interlock on each breaker,, and to lock breakers open. Keys -2, -3, -4 and -5 are now free. 3. Insert keys -2, -3, -4 and -5 in transfer interlock. 4. urn key -1 in transfer interlock. Key -1 is now free. Keys - 2, -3, -4 and -5 are now held. 5. Insert key -1 in L-O- interlock on disconnect and turn to unlock. Key -1 is now held. 6. Open disconnect. 7. urn key -1 in L-O- interlock on disconnect to lock open. Key -1 is now free. 8. Insert key -1 in transfer interlock and turn. Key -1 is now held, Keys -2, -3, -4 and -5 are now free. 9. Return keys -2, -3, -4 and -5, desired, to breaker interlocks and unlock for operation during servicing.

9 Scheme 7 o prevent operation of disconnect switch when breakers,, and are closed. reakers must be opened in pre-arranged sequence. Scheme 8 o prevent operation of disconnects and when breaker is closed. o permit servicing of breaker when disconnects are locked open. O: lectrical circuit is equivalent of Scheme L-O- 5 SUPRVISORY KY isconnect and breakers,, and are shown in closed position. Key -1 is held in breaker interlock, key -2 is held in breaker interlock, key -3 is held in breaker interlock and key -4 is held in breaker interlock. Key -5 is held free in breaker interlock or is retained by supervisor. 1. Obtain key -5 from supervisor. 2. Open breaker. 3. Insert key -5 in L-O interlock on breaker and turn key -4 to lock open. Key -5 is now held. Key -4 is now free. 4. Open breaker. 5. Insert key -4 in L-O interlock on breaker and turn key -3 to lock open. key -4 is now held. key -3 is now free. 6. Open breaker. 7. Insert key -3 in L-O interlock on breaker and turn key -2 to lock open. Key -3 is now held. Key -2 is now free. 8. Open breaker. 9. Insert key -2 in L-O interlock on breaker and turn key -1 to lock open. Key -2 is now held. Key -1 is now free. 10. Insert key -1 in L-O- interlock on disconnect and turn to unlock. Key -1 is now held. 11. Open disconnect. 12. urn key -1 in L-O- interlock on disconnect to lock open. Key -1 is now free. 13. Insert key -1 in L-O interlock on breaker and turn to unlock. Key -1 is now held and key -2 is now free. 14. reaker may now be operated for servicing. 15. Insert key -2 in L-O interlock on breaker and turn to unlock. Key -2 is now held and Key -3 is now free. 16. reaker may now be operated for servicing. 17. Insert key -3 in L-O interlock on breaker and turn to unlock. Key -3 is now held and key -4 is now free. 18. reaker may now be operated for servicing. 19. Insert key -4 in L-O interlock on breaker and turn to unlock. Key -4 is now held and supervisor Key -5 is now free. 20. reaker may now be operated for servicing. reaker and disconnects and are shown closed. One key -1 is held in breaker L-O interlock and the other key -1 is held in L-O interlock on disconnect. Key -2 is held in L-O interlock on disconnect. 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L- interlock on disconnect and turn to unlock. Key -1 is now held. 4. Open disconnect. 5. urn key -2 in L-O interlock on disconnect to lock open. Key -2 is now free. 6. Insert key -2 in L- interlock on disconnect and turn to unlock. Key -2 is now held. 7. Open disconnect. 8. urn key -1 in L-O interlock on disconnect to lock open. Key -1 is now free. 9. Insert key -1 in breaker L-O interlock and turn to unlock for operation during servicing.

10 Scheme 9 o prevent operation of disconnects and with breaker closed. o prevent access to breaker compartment with disconnects closed isconnects and, breaker, and door are normally closed. Keys -1 are held in L-O interlock on breaker and L-O interlock on disconnect. Key -2 is held in the L-O interlock on disconnect. Key -3 is held in L-O interlock on disconnect. 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L- interlock on disconnect and turn to unlock. Key -1 is now held. 4. Open disconnect. 5. urn key -2 in L-O interlock on disconnect to lock open. Key -2 is now free. 6. Insert key -2 in L- interlock on disconnect and turn to unlock. Key -2 is now held. 7. Open disconnect. 8. urn keys -1 and -3 in L-O interlock on disconnect to lock open. Keys -1 and -3 are now free. 9. Insert key -1 in breaker L-O interlock and turn to unlock for operation during servicing. 10. Insert key -3 in L- interlock (type ) on compartment door and turn to unlock. Key -3 is now held. 11. Open compartment door to service breaker. Scheme 10 o prevent operation of disconnects and and by-ps disconnect under load. Provides for closing of by-ps disconnect before breaker circuit is opened, or permits breaker circuit to be opened with by-ps disconnect remaining open. isconnects and and breaker normally closed. y-ps disconnect normally open. Keys -1, -2, and -4 normally held in locks indicated. Key -3 normally free. -4 L-O o transfer load from breaker and disconnects to by-ps switch: 1. Obtain key -3 which is free and insures that both disconnects and are locked closed. 2. Insert key -3 in L- interlock on breaker and turn to lock closed. Key -3 is held and key -4 is now free. 3. Insert key -4 in L-O- interlock on by-ps disconnect and turn to unlock. Key -4 is now held. 4. lose by-ps disconnect. 5. urn key -4 in L-O- interlock on by-ps disconnect to lock closed. Key -4 is now free. 6. Insert key -4 in L- interlock on breaker and turn to unlock. Key -4 is held and key -3 is now free. 7. Open breaker. 8. urn key -1 in L-O interlock on breaker to lock open. Key - 1 is now free. 9. Insert keys -1 and -3 in L- interlock on disconnect and turn to unlock. Keys -1 and -3 are now held. 10. Open disconnect. 11. urn key -2 in L-O interlock on disconnect to lock open. Key -2 is now free. 12. Insert key -2 in L- interlock on disconnect and turn to unlock. Key -2 is now held. 13. Open disconnect. 14. urn key -1 in L-O interlock on disconnect to lock open. Key -1 is now free. 15. Insert key -1 in L-O interlock on breaker and turn to unlock to permit operation during servicing. o open disconnects and and breaker, leaving by-ps disconnect open: 1. Proceed from normal position with operations in 7 to 15 above.

11 Scheme 10 o prevent operation of disconnect and and by-ps disconnect under load. Permits by-ps disconnect to operate only when regulator is in neutral position. Permits isolating regulator for servicing. Scheme 11 o prevent paralleling of lines and. Single load, fed from either source RGULOR isconnect shown closed and disconnect shown open. Key -1 is held in disconnect interlock L Open switch. 2. urn key -1 in L-O interlock on switch to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on switch and turn to unlock. Key -1 is now held. 4. lose switch. Reverse sequence to restore service through switch. isconnects and are normally closed. Regulator is normally in operation. y-ps disconnect is normally open. One key -1 is held in regulator L- (locked neutral) interlock and the second key -1 is held in L-O interlock on disconnect. Key -2 is held in L- interlock on disconnect. Key -3 is held in L-O interlock on disconnect. 1. Operate regulator to neutral position. 2. urn key -1 in L- interlock on regulator to lock in neutral position. Key -1 is now free. 3. Insert key -1 in L-O interlock on by-ps disconnect and turn to unlock. Key -1 is now held. 4. lose by-ps disconnect. 5. urn key -2 in L- interlock on by-ps disconnect to lock closed. Key -2 is now free. 6. Insert key -2 in L- interlock on disconnect and turn to unlock. Key -2 is now held. 7. Open disconnect. 8. urn key -3 in L-O interlock on disconnect to lock open. Key -3 is now free. 9. Insert key -3 in L- interlock on disconnect and turn to unlock. Key -3 is now held. 10. Open disconnect. 11. urn key -1 in L-O interlock on disconnect to lock open. Key -1 is now free. 12. Insert key -1 in regulator L- interlock and turn to unlock. his permits regulator to be operated during inspection and servicing.

12 Scheme 12 o prevent paralleling of lines and. Single load, fed from either source. o prevent operation of disconnect switches and when breaker is closed. 3. Insert key -1 in L-O- interlock on disconnect and turn to unlock. Key -1 is now held. 4. Open disconnect. 5. urn key -1 in L-O- interlock on disconnect to lock open. Key -1 is now free. 6. Return key -1 to breaker interlock and unlock for operation of breaker during servicing. o transfer load from line to line : 2 reaker and disconnect are shown in closed position. isconnect is shown in open position. Key -1 is held in breaker interlock. Key - 2 is held in L-O interlock on disconnect. o service breaker: -1-1 L-O- 1 L-O Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O- interlock on disconnect and turn to unlock. Key -1 is now held. 4. Open disconnect. 5. urn key -1 in L-O- interlock and key -2 in L-O interlock on disconnect to lock open. Keys -1 and -2 are now free. 6. Insert key -1 in L-O- interlock on disconnect and turn to unlock. Key -1 is now held. 7. Insert key -2 in L-O interlock on disconnect and turn to unlock. Key -2 is now held. 8. lose disconnect. 9. urn key -1 in L-O- interlock on disconnect to lock closed. Key -1 is now free. 10. Insert key -1 in breaker interlock and turn to unlock. Key -1 is now held. 11. lose breaker. Reverse sequence to restore service through line. Scheme 13 o prevent paralleling of lines and. wo loads, fed from either source. reaker is closed to supply load M. reaker is closed to supply load. ie-breaker is open. Keys -1 are held in interlocks on both breakers and. ie-breaker cannot be closed unless either or is locked open. o transfer load to breaker : 1. Open breaker 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. M Load M can be supplied through breaker in a similar manner.

13 Scheme 14 Scheme 15 - (ontinued) o prevent paralleling of lines and. wo loads, fed from either source (one tie-breaker). o prevent operation of disconnect switch when breaker is closed. o prevent operation of disconnect switch when breaker is closed L-O L-O- L-O- L-O M Scheme 15 o prevent paralleling of lines and. wo loads, fed from either source (one tie-breaker). o prevent operation of disconnect when breaker is closed. o prevent operation of disconnect switch when breaker is closed. o prevent opening fuse compartment door when the sociated disconnects or and breakers and are closed. isconnect switches and and breakers and are closed. reaker closed to supply load M. reaker closed to supply load. iebreaker is open. Keys -1 and -2 are held in interlock on breaker. Keys -1 and -3 are held in interlock on breaker. ie-breaker cannot be closed until either breaker or is locked open. o transfer load to breaker : 3 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Keys - 1 and -3 are now free. 3. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. Reverse sequence to restore service through breaker. Load M can be supplied through breaker in a similar manner. o service breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Keys - 1 and -3 are now free. 3. Insert key -3 in L-O- interlock on disconnect and turn to unlock. Key -3 is now held. 4. Open disconnect. 5. urn key -3 in L-O- interlock on disconnect to lock open. Key -3 is now free. 6. Return key -3 to L-O interlock on breaker and unlock for operation of breaker during servicing. reaker can be serviced in a similar manner. 2 M isconnect switch and breaker are closed to supply load M. isconnect switch and breaker are closed to supply load. ie-breaker is open. Keys -1 and -2 are held in interlock on breaker. Key -3 is held in L-O interlock on disconnect. Keys -1 and -4 are held in interlock on breaker. Key -5 is held in L-O interlock on disconnect. ie-breaker cannot be closed until either breaker or is locked open. o transfer load to breaker, proceed follows: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Keys -1 and -4 are now free. 3. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. Reverse sequence to restore service through breaker. Load M can be supplied through breaker in a similar manner. o service breaker, proceed follows: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Keys -1 and -4 are now free. 3. Insert key -4 in L-O- interlock on disconnect and turn to unlock. Key -4 is now held. 4. Open disconnect. 5. urn key -4 in L-O- interlock on disconnect to lock open. Key -4 is now free. 6. Return key -4 to L-O interlock on breaker and unlock for operation of breaker during servicing. reaker can be serviced in a similar manner. o enter fuse compartment on line, proceed follows: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Keys -1 and -4 are now free. 3. Insert key -4 in L-O- interlock on disconnect and turn to unlock. Key -4 is now held. 4. Open disconnect. 5. urn key -4 in L-O- interlock on disconnect to lock open. Key -4 is now free. 6. urn key -5 in L-O interlock on disconnect to lock open. Key -5 is now free. 7. Insert keys -4 and -5 in L- interlock on fuse compartment door and turn to unlock. Keys -4 and -5 are now held. 8. Open fuse compartment door. Fuse compartment on line can be entered in a similar manner.

14 Scheme 16 o prevent paralleling of lines,, and. hree loads, fed from any source (two tie-breakers). ie-breaker interlock h a mter or apartment lock and can be unlocked for operation with either keys -1 or -1. ie-breaker h a mter or apartment lock and can be unlocked for operation with either keys -1 or o transfer load M from reaker to breaker : 1. Open breaker 2. urn key -1 in L-O interlock on breaker to lock open. Key - 1 is now free. 3. Insert Key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. Reverse sequence to restore service through breaker. M reaker is closed to supply load M. reaker is closed to supply load. reaker is closed to supply load P. Keys -1, -1, and -1 are held in L-O interlocks of breakers,, and. ie-breakers and are locked open. P o transfer load M and from breakers and to breaker : 1. lose tie-breaker above. 2. urn key -1 in L-O interlock on breaker to lock open. Key - 1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. Reverse sequence to restore service (M and through breakers and ). ny of the loads M,, or P can be transferred from its own supply to any adjacent supply ote: his symbol represents an interlock with an apartment lock. n apartment lock is a single cylinder that will accept two different keys - but only one key at a time. Scheme 17 o prevent paralleling lines,,, and. Four loads, fed from any source (three tie-breakers) o transfer load M from breaker to breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. Reverse sequence to restore service through breaker. o transfer load M and from breaker and to breaker : M reaker is closed to supply load M. reaker is closed to supply load. reaker is closed to supply load P. reaker is closed to supply load R. Keys -1, -1, -1, and -1 are held in L-O interlocks of breakers,,, and. reakers, F and G are locked open. reaker interlock h a mter or apartment lock and can be unlocked for operation with either key -1 or -1. reaker F interlock h a mter or apartment lock and can be unlocked for operation with either key -1 or -1. reaker G interlock h a mter or apartment lock and can be unlocked for operation with either key -1 or -1. F P G R 1. lose tie-breaker above. 2. Open breaker. 3. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 4. Insert key -1 in L-O interlock on tie-breaker F and turn to unlock. Key -1 is now held. 5. lose tie-breaker F. Reverse sequence to restore service (M and ) through breakers and. o transfer load R from breaker to breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker G and turn to unlock. Key -1 is now held. 4. lose tie-breaker G. Reverse sequence to restore service through breaker. ny of the loads M,, P, or R can be transferred from its own supply to any adjacent supply ote: his symbol represents an interlock with an apartment lock. n apartment lock is a single cylinder that will accept two different keys - but only one key at a time.

15 Scheme 17 o prevent paralleling lines,,, and. o prevent opening rear access doors when breakers are energized. SS OOR #1 SS OOR #2 SS OOR #3 SS OOR #4 SS OOR #7 K-1 K-2 K-3 K-4 K-5 K-6 K-7 K-8 K-9 K 3 SS OOR #5 SS OOR #6 K 6 K 9 SS OOR #8 SS OOR #9 ll loads can be transferred described in scheme 17. o open rear access doors K-1, K-2, and K-3: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Open breaker. 4. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 5. Insert key -1 and -1 in transfer interlock. 6. urn key -1 in transfer interlock. Keys K-1, K-2, and K- 3 are now free. Keys -1 and -1 are now held. 7. Insert keys K-1, K-2, and K-3 in their respective rear access door interlocks and turn to unlock. Keys K-1, K-2, and K-3 are now held. 8. Open the rear access doors. K 2 K 1 K 5 K 8 K 4 K F G o open rear access doors K-4, K-5 and K-6 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Open breaker. 4. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 5. Insert key -1 and -1 in transfer interlock. 6. urn key -1 in transfer interlock. Keys K-4, K-5, and K- 6 are now free. Keys -1 and -1 are now held. 7. Insert keys K-4, K-5, and K-6 in their respective rear access door interlocks and turn to unlock. Keys K-4, K-5, and K-6 are now held. 8. Open the rear access doors M reakers,,, and are closed to supply their respective loads. Keys -1, -1, -1, and -1 are held in L-O interlocks of breakers,,, and. ie-reakers, F, and G are locked open. reaker interlock h an apartment lock and can be unlocked for operation with either key -1 or -1. reaker F interlock h an apartment lock and can be unlocked for operation with either key -1 or -1. reaker G interlock h an apartment lock and can be unlocked for operation with either key -1 or -1. ll rear access doors are locked closed. ll keys for rear access doors (K-1 through K-9) are held in transfer interlocks. P R o open rear access doors K-7, K-8 and K-9 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Open breaker. 4. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 5. Insert key -1 and -1 in transfer interlock. 6. urn key -1 in transfer interlock. Keys K-7, K-8, and K- 9 are now free. Keys -1 and -1 are now held. 7. Insert keys K-7, K-8, and K-9 in their respective rear access door interlocks and turn to unlock. Keys K-7, K-8, and K-9 are now held. 8. Open the rear access doors ote: his symbol represents an interlock with an apartment lock. n apartment lock is a single cylinder that will accept two different keys - but only one key at a time.

16 Scheme 18 o prevent paralleling of lines,, and. hree loads, fed from any source (three tie-breakers). Scheme 19 o prevent paralleling lines,,, and. Four loads fed from any source (four tie-breakers) F G M reaker is closed to supply load M. reaker is closed to supply load. reaker is closed to supply load P. Keys -1, -1, and -1 are held in L-O interlocks on breakers, and. ie-breakers,, and F are locked open. Mter or apartment lock interlocks are mounted on tiebreakers,, and F, and can be unlocked for operation with either keys -1 or -1, -1 or -1, and -1 or -1, respectively. F o transfer load M from breaker to breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key - 1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. Reverse sequence to restore service through breaker. o transfer load M and from breakers and to breaker : 1. lose tie-breaker above. 2. Open breaker. 3. urn key -1 in L-O interlock on breaker to lock open. Key - 1 is now free. 4. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 5. lose tie-breaker. Reverse sequence to restore service (loads M and ) through breakers and. o transfer load P from breaker to breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on tie breaker F and turn to unlock. Key -1 is now held. 4. lose tie-breaker F. Reverse sequence to restore service through breaker. F P M -1-1 reaker is closed to supply load M. reaker is closed to supply load. reaker is closed to supply load P. reaker is closed to supply load R Keys -1, -1, -1, and -1 are held in L-O interlocks of breakers,,, and. ie breakers, F, G, and H are locked open. reaker interlock h a mter or apartment lock and can be unlocked with either key -1 or -1. reaker F interlock h a mter or apartment lock and can be unlocked with either key -1 or -1. reaker G interlock h a mter or apartment lock and can be unlocked with either key -1 or -1. reaker H interlock h a mter or apartment lock and can be unlocked with either key -1 or -1. o transfer load M from breaker to breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker and turn to unlock. Key -1 is now held. 4. lose tie-breaker. Reverse sequence to restore service through breaker. o transfer load M and from breaker and to breaker : 1. lose tie-breaker above. 2. Open breaker. 3. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 4. Insert key -1 in L-O interlock on tie-breaker F and turn to unlock. Key -1 is now held. 5. lose tie-breaker F. Reverse sequence to restore service (M and ) through breakers and. o transfer load R from breaker to breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker G and turn to unlock. Key -1 is now held. 4. lose tie-breaker G. Reverse sequence to restore service through breaker. o transfer load M from breaker to breaker : 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O interlock on tie-breaker H and turn to unlock. Key -1 is now held. 4. lose tie-breaker H. Reverse sequence to restore service through breaker. H P H -1-1 G F R -1-1 ote: his symbol represents an interlock with an apartment lock. n apartment lock is a single cylinder that will accept two different keys - but only one key at a time. ny of the loads M,, P, or R can be transferred from its own supply to any adjacent supply ote: his symbol represents an interlock with an apartment lock. n apartment lock is a single cylinder that will accept two different keys - but only one key at a time.

17 Scheme 20 o prevent paralleling three power sources through a common tie bus not normally in service. o permit feeding any load bus from a second power source through the tie bus. o permit one power source to supply all three load busses through the tie bus. Line 1 Line 2 Line 3 reakers,, and are normally closed. reakers,, and F are normally open. Under normal conditions keys -1 and -5 are held in breaker interlock, keys -2 and -5 are held in breaker interlock, and keys -3 and -5 are held in breaker interlock. o transfer load from line o. 1 to line o. 2 or line o. 3 through the tie bus, proceed follows: Load us 5 1 Load us Load us ie us F Open breaker. 2. urn key -1 in L-O interlock on breaker to lock breaker open. Keys -1 and -5 are now free. 3. Insert key -1 in L-O interlock on breaker and turn to unlock. Key -1 is now held. 4. lose breaker. 5. Insert key -5 in L-O interlock on either breaker or F and turn to unlock. Key -5 is now held. 6. lose breaker or F (whichever is selected). Reverse sequence to restore load to line o. 1. o transfer load from lines o. 1 and o. 2 to line o. 3 through tie bus, proceed follows: 1. lose breaker per steps 1 to 4 above. 2. Open breaker. 3. urn key -2 in L-O interlock on breaker to lock breaker open. Keys -2 and -5 are now free. 4. Insert key -2 in L-O interlock on breaker and turn to unlock. Key -2 is now held. 5. lose breaker. 6. Insert one of the -5 keys from either breaker or in L-O interlock on breaker F and turn to unlock. Key -5 is now held. 7. lose breaker F. Reverse sequence to restore load to lines o. 1 and o ote: his symbol represents an interlock with an apartment lock. n apartment lock is a single cylinder that will accept two different keys - but only one key at a time. Scheme 21 o prevent paralleling three power sources through a common tie bus not normally in service. o permit feeding any load bus from a second power source through the tie bus only when authorized by supervisor. o permit one power source to supply all three load busses through the tie bus only when authorized by supervisor. Line 1 Line 2 Line Load us Load us Load us reakers,, and are normally closed. reakers,, and F are normally open. Under normal conditions key -1 is held in breaker interlock, key -2 is held in breaker interlock, and key -3 is held in breaker interlock. Key -5 is retained by supervisor. o transfer load from line o. 1 to line o. 2 or line o. 3 through tie bus, proceed follows: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock breaker open. Key -1 is now free. 3. Insert key -1 in L-O interlock on breaker and turn to unlock. Key -1 is now held. 4. lose breaker. 5. Insert supervisor's key -5 (only one -5 is available) in L-O interlock on either breaker or F and turn to unlock. Key -5 is now held. 6. lose breaker or F (whichever is selected). Reverse sequence to restore load to line o ie us F 5 SUPRVISORY KY o transfer load from lines o. 1 and o. 2 to line o. 3 through tie bus, proceed follows: 1. lose breaker per steps 1 to 4 above. 2. Open breaker. 3. urn key -2 in L-O interlock on breaker to lock breaker open. Key -2 is now free. 4. Insert key -2 in L-O interlock on breaker and turn to unlock. Key -2 is now held. 5. lose breaker. 6. Insert supervisor's key -5 in L-O interlock on breaker F and turn to unlock. Key -5 is now held. 7. lose breaker F. Reverse sequence to restore load to lines o. 1 and o ote: his symbol represents an interlock with an apartment lock. n apartment lock is a single cylinder that will accept two different keys - but only one key at a time.

18 Scheme 22 o prevent paralleling incoming primary sources, lines 1 and 2, through primary tie bus disconnect. o prevent operation (open or closed) of the disconnects under load. Permits one power source to supply both loads through tie bus. Scheme 23 (ontinued) Line 1 Line 2 Line 1 Line Load 1 Load 2 Load 1 Load 2 Under normal conditions breakers and are closed, disconnects and are locked closed, and tie bus disconnect is locked open. Keys -1 are held in L-O interlock on breaker and L- interlock on tie bus disconnect. Keys -2 are held in L-O interlock on disconnects and. Keys -3 are held in L-O interlock on breaker and L- interlock on tie bus disconnect. Keys -4 (free keys) are shown removably held in the L- interlocks on disconnects and. o transfer load o. 1 from line 1 to line 2 through bus tie disconnect, proceed follows: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L- interlock on disconnect and turn to unlock. Keys -1 and -4 are now held. 4. Open disconnect. 5. urn key -2 in L-O interlock on disconnect to lock open. Key - 2 is now free. 6. Insert keys -2 and free key -4 (from L- interlock on disconnect ) in L-O interlock on bus tie disconnect and turn to unlock. Keys -2 and -4 are now held. 7. lose tie bus disconnect. 8. urn key -3 in L- interlock on disconnect to lock closed. Keys -1 and -3 are now free. 9. Insert key -1 in L-O interlock on breaker and turn to unlock. Key -1 is now held. 10. lose breaker. Reverse sequence to restore load o. 1 to line 1. o transfer load o. 2 from line 2 to line 1 through bus tie disconnect, proceed in a similar manner. Scheme 23 o prevent paralleling incoming primary sources, lines 1 and 2, through the primary tie bus disconnect or the secondary tie bus breaker. o prevent operation (open or closed) of the disconnects under load. Permits one power source to supply both loads through either the primary or secondary tie bus. Under normal conditions breakers and are closed, breaker is locked open, disconnects and are locked closed, and tie disconnect is locked open. Keys -1 are held in L-O interlock on breaker and L- interlock on primary tie bus disconnect. Keys -2 are held in L-O interlocks on disconnects and. Keys -3 are held in L-O interlock on breaker and L- interlock on primary tie bus disconnect. Keys -4 (free keys) are shown removably held in the L- interlocks on disconnects and. Keys -5 are held in L-O interlocks on breakers and. o transfer load o. 1 from line 1 to line 2 through primary bus tie disconnect, proceed follows: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Keys -1 and -5 are now free. 3. Insert key -1 and free key -4 in L- interlock on disconnect and turn to unlock. Keys -1 and -4 are now held. 4. Open disconnect. 5. urn key -2 in L-O interlock on disconnect to lock open. Key - 2 is now free. 6. Insert key -2 and free key -4 (from L- interlock on disconnect ) in L-O interlock on primary bus tie disconnect and turn to unlock. Keys -2 and -4 are now held. 7. lose bus tie disconnect. 8. urn key -3 in L- interlock on bus tie disconnect to lock closed. Keys -1 and -3 are now removable. 9. Insert key -1 in L-O interlock on breaker and turn to unlock. Key -1 is now held. 10. lose breaker. Reverse procedure to restore service to line 1. Load o. 2 can be supplied from o. 1 through the primary bus tie in a similar manner. o transfer load o. 1 from line 1 to line 2 through the secondary tie breaker, proceed follows: 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Keys -1 and -5 are now removable. 3. Insert key -5 in L-O interlock on tie breaker and turn to unlock. Key -5 is now held. 4. lose tie breaker. Reverse procedure to restore service on line 1. Load o. 2 can be supplied from line o. 1 through the secondary tie breaker in a similar manner.

19 Scheme 24 o prevent paralleling incoming primary sources, lines 1 and 2. o prevent operation (open or closed) of the disconnects under load. (Permits transformer primary disconnects K & L to open and close the transformer magnetizing current.*) Permits isolating breakers for servicing. Permits one power source to supply both loads through tie bus. Line 1 Line F 1 G H -1 1 o transfer load o. 1 from line 1 to line 2 through bus tie disconnect, proceed follows: 1. Open breaker. 2. urn key -2 in L-O interlock on breaker to lock open. Key -2 is now free. 3. Open breaker. 4. urn key -4 in L-O interlock breaker to lock open. Keys -1 and -4 are now free. 5. Insert key -2 from L-O interlock on breaker and key -1 from L-O interlock on breaker in L- interlock on disconnect F and turn to unlock. Keys -1 and -2 are now held. 6. Open disconnect F. 7. urn key -3 in L-O interlock on disconnect F to lock open. Keys -3 and -1 are now free. 8. Insert key -1 in L-O interlock on bus tie disconnect and turn to unlock. Key -1 is now held. 9. lose bus tie disconnect. 10. urn key -1 in L- interlock on bus tie disconnect to lock closed. Keys -1 and -1 are now free. 11. Insert key -1 in L-O interlock on breaker and turn to unlock. Keys -1 and -4 are now held. 12. lose breaker. Reverse sequence to restore load o. 1 to line 1. o transfer load o. 2 from line 2 to line 1, proceed in a similar manner o isolate breaker for servicing, proceed follows: K L -4-4 L-O- L-O Proceed from normal position with operations in 1 through 7 above. 2. Insert key -3 in L- interlock on disconnect and turn to unlock. Key -3 is now held. 3. Open disconnect. 4. urn key -2 in L-O interlock on disconnect to lock open. Key -2 is now free. 5. Return key -2 to breaker and unlock for operation during servicing. o isolate breaker for servicing, proceed in a similar manner. o isolate breaker for servicing, proceed follows: 4 4 Load 1 Load 2 Under normal conditions breakers,,, and are closed, disconnects, F, G, H, K, and L are locked closed, and bus tie disconnect is locked open. Keys -1 are held in L-O interlock on breaker and L- interlock on bus tie disconnect. Keys -2 are held in L-O interlocks on breaker and disconnect. Key -3 is held in L-O interlock on disconnect F. Key -4 is held in L-O interlock on breaker. Keys -1 are held in L-O interlock on breaker and L- interlock on bus tie disconnect. Keys -2 are held in L-O interlocks on breaker and disconnect G. Key -3 is held in L-O interlock on disconnect H. Key -4 is held in L-O interlock on breaker. Keys -1 are held in L-O interlock on disconnects F and H. 1. Open breaker. 2. urn key -4 in L-O interlock on breaker to lock breaker open. Keys -1 and -4 are now free. 3. Insert key -4 in L-O- interlock on disconnect K and turn to unlock. Key -4 is now held. 4. Open disconnect K. 5. urn key -4 in L-O- interlock on disconnect K to lock open. Key -4 is now free. 6. Return key -4 to breaker and unlock for operation during servicing. o isolate breaker for servicing, proceed in a similar manner. * o prevent primary disconnects K and L from opening magnetizing current only, additional interlocks should be provided for disconnect K and L.

20 Scheme 25 o prevent opening fuse compartment door when the interrupter switch is closed. o prevent closing interrupter switch until fuse compartment door is locked closed. Scheme 27 o prevent operation (open or closed) of interrupter switch when breaker is closed. o prevent opening fuse compartment door when the interrupter switch is closed. o prevent closing interrupter switch until fuse compartment door is locked closed. Permits the breaker to be serviced and operated while the interrupter is locked open Fuse compartment door and interrupter are shown in closed position. Key -1 is held in interrupter interlock. L-O- 1. Open interrupter. 2. urn key -1 in L-O interlock on interrupter switch to lock open. Key -1 is now free. 3. Insert key -1 in L- interlock on fuse compartment door and turn to unlock. Key -1 is now held. 4. Open fuse compartment door. Scheme 26 o prevent operation (open or closed) of interrupter switch when breaker is closed. Permits the breaker to be serviced and operated while the interrupter switch is locked open L-O- reaker, fuse compartment door and interrupter are shown in closed position. Key -1 is held in breaker interlock and key -2 is held in interrupter interlock. o service breaker, proceed follows: 1 Interrupter and breaker are shown in closed position. Key -1 is held in breaker interlock. 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O- interlock on interrupter and turn to unlock. Key -1 is now held. 4. Open interrupter. 5. urn key -1 in L-O- interlock on interrupter to lock open. Key -1 is now free. 6. Return key -1 to breaker interlock and unlock for operation of breaker during servicing. -1 L-O- 1. Open breaker. 2. urn key -1 in L-O interlock on breaker to lock open. Key -1 is now free. 3. Insert key -1 in L-O- interlock on interrupter and turn to unlock. Key -1 is now held. 4. Open interrupter. 5. urn key -1 in L-O- interlock on interrupter to lock open. Key -1 is now free. 6. Return key -1 to breaker interlock and unlock for operation of breaker during servicing. o open fuse compartment door, proceed follows: 1. Proceed from normal position with operations in 1 through 4 above. 2. urn key -2 in L-O interlock on interrupter switch to lock open. Key -2 is now free. 3. Insert key -2 in L- interlock on fuse compartment door and turn to unlock. Key -2 is now held. 4. Open fuse compartment door.

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Trapped Key Interlocks for. Switchgear. Applications Guide. www.castell.com

Trapped Key Interlocks for. Switchgear. Applications Guide. www.castell.com Trapped Key Interlocks for Switchgear pplications Guide www.castell.com London Chicago Cologne Shanghai Castell Offices Castell Installations We Keep You Safe at Work Worldwide Switchgear pplications Guide

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5

Cam switches. Page. Overview 4-2. ON-OFF switches, main switches, maintenance switches 4-3. Changeover switches, reversing switches 4-5 Eaton Wiring Manual / Page Overview - ON-OFF switches, main switches, maintenance switches - Changeover switches, reversing switches - (Reversing) star-delta switches - Multi-Speed Switches - Interlock

More information

Low Voltage Disconnect Switches. NFPA79 and UL508A Industrial Machinery Operating Handle Requirements White Paper

Low Voltage Disconnect Switches. NFPA79 and UL508A Industrial Machinery Operating Handle Requirements White Paper Low Voltage Disconnect Switches NFPA79 and UL508A Industrial Machinery Operating Handle Requirements White Paper Scope This document is intended to discuss the functional requirements for the disconnecting

More information

PowerFlex 700H and 700S AC Drives Frame 11 Main Fan Capacitor Replacement Kit

PowerFlex 700H and 700S AC Drives Frame 11 Main Fan Capacitor Replacement Kit Installation Instructions PowerFlex 700H and 700S AC Drives Frame 11 Main Fan Capacitor Replacement Kit ATTENTION: The sheet metal cover and mounting screws on the ASIC Board located on the power structure

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Local Back-up Protection for an Electric Power System

Local Back-up Protection for an Electric Power System MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................

More information

Medium voltage VCP-W MR2 (integral racking)

Medium voltage VCP-W MR2 (integral racking) Supersedes March 2013 Contents Description Page Notices and warnings...................... 2 Introduction.............................. 3 Breaker pan configurations.................. 3 Inspection/maintenance.....................

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

Reverse-feed applications for circuit breakers

Reverse-feed applications for circuit breakers Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

Energy Control Lockout/Tagout

Energy Control Lockout/Tagout Energy Control Lockout/Tagout Page Introduction Purpose. 2 Background. 2 Who s Covered... 3 Responsibilities. 3 Explanation of Key Terms. 4 How It Works General Lockout/Tagout Procedure. 5 General Lock/Tag

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

LOCKOUT GUIDELINE. To ensure that a piece of equipment cannot be turned on, pressurized or switched on accidently while an employee is working on it.

LOCKOUT GUIDELINE. To ensure that a piece of equipment cannot be turned on, pressurized or switched on accidently while an employee is working on it. Background LOCKOUT GUIDELINE Both Aspasa in its ISHE (Initiating Safety Health & Education) program and Sarma in its SHREQ (Safety, Health, Road Transport, Environment & Quality) program have seen that

More information

Lockout/Tagout Training Program

Lockout/Tagout Training Program Lockout/Tagout Training Program (Student Handouts) Name Date This page intentionally left blank. Notes page: 2 Notes page: 3 Sample Written Program for Control of Hazardous Energy (Lockout/Tagout) 4 1910.147

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

Electrical Symbols and Line Diagrams

Electrical Symbols and Line Diagrams Electrical Symbols and Line Diagrams Chapter 3 Material taken from Chapter 3 of One-Line Diagrams One-line diagram a diagram that uses single lines and graphic symbols to indicate the path and components

More information

WEEKLY SAFETY MEETING All Euramax Subsidiaries LOCKOUT / TAGOUT. Safety Meeting Contents. Meeting Notice. Leaders Guide.

WEEKLY SAFETY MEETING All Euramax Subsidiaries LOCKOUT / TAGOUT. Safety Meeting Contents. Meeting Notice. Leaders Guide. Safety Meeting Contents Meeting Notice Leaders Guide Employee Handout Employee Quiz Meeting Sign-In Sheet Employee Puzzle PRIOR TO THE WEEKLY MEETING: - Post the meeting notice by the timeclock - Read

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun DC disconnects for solar photovoltaic installations Connecting the power of the sun Solar energy is heating up Interest in renewable energy sources has never been greater, and the fastest growing of these

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Lockout/Tagout. Training: 29 CFR-1910.148 Lockout Tagout Standard States employer must provide training on lockout tagout.

Lockout/Tagout. Training: 29 CFR-1910.148 Lockout Tagout Standard States employer must provide training on lockout tagout. Lockout/Tagout Training: 29 CFR-1910.148 Lockout Tagout Standard States employer must provide training on lockout tagout. Lockout/Tagout System Helps safeguard employees from the unexpected startup of

More information

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations Connecting the Power of the Sun DC Disconnects for Solar Photovoltaic Installations DC disconnects for solar photovoltaic installations Solar energy is heating up Interest in renewable energy sources has

More information

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12 Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator

More information

Power/Vac Metal-Clad Switchgear and Vacuum Circuit Breakers Maintenance and Troubleshooting Suggestions

Power/Vac Metal-Clad Switchgear and Vacuum Circuit Breakers Maintenance and Troubleshooting Suggestions 1 GE Consumer & Industrial Electrical Distribution Applications / Specifications DET-456 Power/Vac Metal-Clad Switchgear and Vacuum Circuit Breakers Maintenance and Troubleshooting Suggestions 2 POWER/VAC

More information

BODY ELECTRICAL TOYOTA ELECTRICAL WIRING DIAGRAM WORKBOOK. ASSIGNMENT Version 1.8 WORKSHEETS. http://www.autoshop101.com

BODY ELECTRICAL TOYOTA ELECTRICAL WIRING DIAGRAM WORKBOOK. ASSIGNMENT Version 1.8 WORKSHEETS. http://www.autoshop101.com BODY ELECTRICAL ASSIGNMENT Version 1.8 WORKSHEETS TOYOTA ELECTRICAL WIRING DIAGRAM WORKBOOK http://www.autoshop101.com Developed by Kevin R. Sullivan All Rights Reserved TOYOTA Table of Contents Wiring

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Eaton Automatic Transfer Switches

Eaton Automatic Transfer Switches This is a photographic template your photograph should fit precisely within this rectangle. Eaton Automatic Transfer Switches Jody Grabowski Eaton ATS Product Line Sales Engineer February 1st, 2011 2008

More information

Comparison of NEMA and IEC schematic diagrams

Comparison of NEMA and IEC schematic diagrams Cross-Reference MZ081001EN Comparison of NEMA and IEC schematic diagrams General With the increasing emphasis on globalization, many industries are now looking to all parts of the world to produce, market,

More information

Page85. Lock-out Tag-out Plan

Page85. Lock-out Tag-out Plan Page85 Lock-out Tag-out Plan Page86 Lock-out / Tag-Out Plan Table of Contents 1. Policy 2. Purpose 3. Scope 4. General Procedures 5. Application of Control Procedure 6. Release from Control Procedure 7.

More information

LOCK-OUT/TAG-OUT PROGRAM I. Purpose

LOCK-OUT/TAG-OUT PROGRAM I. Purpose LOCK-OUT/TAG-OUT PROGRAM I. Purpose This procedure establishes requirements for the lockout of energy isolating devices. It should be used to ensure that the machine or piece of equipment is isolated from

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Industrial Automation Commonly-Used Terms

Industrial Automation Commonly-Used Terms Engineering Smarter Systems Industrial Automation Commonly-Used Terms A Glossary of Industrial Automation and Control Terms LECINC.COM 1 A Accelerating Time: Across the Line Starter: Action Device: Actuator:

More information

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM

LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM 1 UNIVERSITY OF WEST FLORIDA LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM (EQUIPMENT HAZARD DE-ENERGIZING AND ISOLATION) DEPARTMENT OF ENVIRONMENTAL HEALTH AND SAFETY 11000University Parkway Pensacola, FL 32514

More information

Procedures for daily inspection and testing of mechanical power presses and press brakes

Procedures for daily inspection and testing of mechanical power presses and press brakes Procedures for daily inspection and testing of mechanical power presses and press brakes INTRODUCTION This leaflet gives guidance on the minimum safety checks that should be carried out on mechanical power

More information

LOCK-OUT / TAG-OUT SAFETY TRAINING

LOCK-OUT / TAG-OUT SAFETY TRAINING LOCK-OUT / TAG-OUT SAFETY TRAINING Introduction Welcome to Lock-out Tag-out Training "So I m on the job one day, doing some repair on a cutting machine.replacing a guide on the table. Pretty routine everything

More information

Lockout / Tagout Program

Lockout / Tagout Program Lockout / Tagout Program Table of Contents Page Scope... 2 Definitions... 2 Authorization... 3 Responsibilities... 4 Compliance and Enforcement... 4 When to Lockout/Tagout (LOTO)... 5 Lockout Procedure...

More information

Department of Environmental Health & Safety. Lock Out/Tag Out Program. Date Effective: November 2010

Department of Environmental Health & Safety. Lock Out/Tag Out Program. Date Effective: November 2010 Department of Environmental Health & Safety Lock Out/Tag Out Program Issued by: Jeff Campbell Date Effective: November 2010 Date Revised: April 2014 General Policy Ohio University Lockout/Tagout Policy

More information

Limited Service Pump Controllers (Produced after July 18, 2006) Installation- Start Up - Service

Limited Service Pump Controllers (Produced after July 18, 2006) Installation- Start Up - Service Instruction Bulletin Limited Service Pump Controllers (Produced after July 18, 2006) Installation- Start Up - Service This instruction is a guide for personnel involved with Maintenance, Engineering and

More information

Trapped Key Interlocks

Trapped Key Interlocks Trapped Key s Product Catalogue Isolation Key Exchange Access Control Keys & Accessories London Chicago Cologne Shanghai Chennai Castell Offices Castell Installations We Keep You Safe at Work Worldwide

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

Control of Hazardous Energy (Lockout / Tagout)

Control of Hazardous Energy (Lockout / Tagout) WAUKESHA COUNTY TECHNICAL COLLEGE Control of Hazardous Energy (Lockout / Tagout) Release Date: March 26, 2012 Revision Date: March 26, 2012 Revision Level: 1 TABLE OF CONTENTS Purpose... 1 Scope... 1 Responsibilities...

More information

VEHICLE THEFT/SECURITY SYSTEMS

VEHICLE THEFT/SECURITY SYSTEMS DN VEHICLE THEFT/SECURITY SYSTEMS 8Q - 1 VEHICLE THEFT/SECURITY SYSTEMS TABLE OF CONTENTS page GENERAL INFORMATION INTRODUCTION...1 VEHICLE THEFT SECURITY SYSTEM....1 ENABLING...1 ARMING...1 DISARMING...2

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

Electrical System From The Top Down By Rick Denney, GMC Eastern States April 2006

Electrical System From The Top Down By Rick Denney, GMC Eastern States April 2006 GMC Motorhome Electrical System From The Top Down By Rick Denney, GMC Eastern States April 2006 The electrical system of the GMC is fairly simple when considered as a system, but it s easy to get lost

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

Programming Logic controllers

Programming Logic controllers Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,

More information

Utility Distribution Systems

Utility Distribution Systems Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date

More information

Lock-out/Tag-out. http://www.utdallas.edu/ehs

Lock-out/Tag-out. http://www.utdallas.edu/ehs Lock-out/Tag-out Environmental Health and Safety Department 800 West Campbell Rd., SG10 Richardson, Tx 75080-3021 Phone 972-883-2381/4111 Fax 972-883-6115 http://www.utdallas.edu/ehs Modified: March 2012

More information

Logical Consideration on Lockout and Trapped Key Interlock for Machine

Logical Consideration on Lockout and Trapped Key Interlock for Machine Industrial 460 Health 2010, 48, 460 469 Original M KIMURA Article et al. Logical Consideration on Lockout and Trapped Key Interlock for Machine Makoto KIMURA 1 * and Noboru SUGIMOTO 2 1 Environment & Safety

More information

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives

More information

Lockout/Tagout (LOTO) Compliance Guide

Lockout/Tagout (LOTO) Compliance Guide Lockout/Tagout (LOTO) Compliance Guide Prepared for By Date Scope The OSHA Control of Hazardous Energy (Lockout/Tagout) standard (29 CFR 1910.147) covers the servicing and maintenance of machines and equipment

More information

Reversing starter circuit for single phase induction motors Updated 1 st September 2008

Reversing starter circuit for single phase induction motors Updated 1 st September 2008 Reversing starter circuit for single phase induction motors Updated st September 008 Most single phase electric motors fitted to machine tools, compressors etc. are squirrel cage induction type which can

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured. SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

HealthStream Regulatory Script

HealthStream Regulatory Script HealthStream Regulatory Script Control of Hazardous Energy: Lockout/Tagout Release Date: August 2009 HLC Version: 602 Lesson 1: Introduction Lesson 2: Energy Control Basics Lesson 2: Lockout and Tagout

More information

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES. Leader s Guide. 2005, CLMI Training

C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES. Leader s Guide. 2005, CLMI Training C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES Leader s Guide 2005, CLMI Training LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES This easy-to-use Leader s Guide is provided to assist in conducting a successful

More information

Understanding HUD s UPCS Protocol for Inspecting Electrical Devices Revised Oct. 2010

Understanding HUD s UPCS Protocol for Inspecting Electrical Devices Revised Oct. 2010 PIH REAC is providing the following information to assist in properly identifying and mitigating electrical hazards that may exist on the property. This information presents common electrical hazards but

More information

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION It is the intention of this presentation to provide an explanation of the automatic synchronizing process,

More information

Quickie Rhapsody Service Manual

Quickie Rhapsody Service Manual Quickie Rhapsody Service Manual 2006 Sunrise Medical Inc. 101976 Rev A Quickie Rhapsody Service Manual Contents Introduction... 0.1 VR2 Controller... 0.2 Plugs/Connectors... 0.3 Basic Tool List & Main

More information

How To Build A Germany Power Plant

How To Build A Germany Power Plant Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

The Starting System. Section 4. Starting System Overview. Starter. The starting system:

The Starting System. Section 4. Starting System Overview. Starter. The starting system: The Starting System Starter The starter motor drives the engine through a pinion gear that engages the ring gear on the flywheel. Fig. 4-01 TL623f401c Starting System Overview The starting system: Uses

More information

3BASIC RELAY INSTRUCTIONS

3BASIC RELAY INSTRUCTIONS M O D U L E T H R E E 3BASIC RELAY INSTRUCTIONS Key Points So far, you have learned about the components of the MicroLogix 1000 PLC, including the CPU, the memory system, the power supply, and the input/output

More information

BWC Division of Safety and Hygiene

BWC Division of Safety and Hygiene BWC Division of Safety and Hygiene A SAMPLE LOCKOUT/TAGOUT PROCEDURE A good Lockout/Tagout Procedure, at a minimum, should contain the following elements: 1. All maintenance personnel shall be provided

More information

Control of Hazardous Energy LOCKOUT/TAGOUT 29 CFR 1910.147

Control of Hazardous Energy LOCKOUT/TAGOUT 29 CFR 1910.147 Control of Hazardous Energy LOCKOUT/TAGOUT 29 CFR 1910.147 Contents I. Introduction II. Scope and Application III. Definitions IV. Lockout/Tagout Manual V. Energy Control Procedures 1. Applying Energy

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

Data Sheet. Electro-mechanical counters Hengstler 800 series

Data Sheet. Electro-mechanical counters Hengstler 800 series Data Pack D Issued March 00 504897 Data Sheet Electro-mechanical counters Hengstler 800 series The 800 series totalising and predetermining batch counters, manufactured by Hengstler, is available from

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

FUEL-16, Troubleshooting Fuel Supply Problems

FUEL-16, Troubleshooting Fuel Supply Problems FUEL-16, Troubleshooting Fuel Supply Problems Introduction This procedure is used to troubleshooting fuel supply problems including failure of the fuel pump to start during engine cranking. Fuel Pump Not

More information