1 Inspection Report Mr. Leon Bayer Property Address: 4525 San Taela Court Woodland Hills CA Leon Bayer Home 20/20 Vision Home Inspections, LLC David Trent Glendale Blvd., Unit 163 Los Angeles, CA (323)

2 Table of Contents Cover Page...1 Table of Contents...2 Intro Page Roofing Exterior Garage Interiors Structural Components Plumbing System Electrical System Heating / Central Air Conditioning Insulation and Ventilation Built-In Kitchen Appliances...37 General Summary...40 Back Page San Taela Court Page 2 of 43

3 Date: 5/28/2013 Time: 09:00 PM Report ID: Property: 4525 San Taela Court Woodland Hills CA Customer: Mr. Leon Bayer Comment Key or Definitions Real Estate Professional: The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property. Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear. Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting. Not Present (NP) = This item, component or unit is not in this home or building. Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement. Standards of Practice: ASHI American Society of Home Inspectors In Attendance: Customer Type of building: Single Family (2 story) Approximate age of building: Over 25 Years Home Faces: North Temperature: Over 65 (F) = 18 (C) Weather: Clear Ground/Soil surface condition: Dry Rain in last 3 days: No 4525 San Taela Court Page 3 of 43

4 1. Roofing The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors. IN NI NP RR 1.0 Roof Coverings 1.1 Flashings 1.2 Skylights, Chimneys and Roof Penetrations 1.3 Roof Drainage Systems IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Styles & Materials Roof Covering: 3-Tab fiberglass Viewed roof covering from: Ground Sky Light(s): None Chimney (exterior): Masonry Stucco Comments: 1.0 The report is an opinion of the general quality of the roof. The inspector cannot, and does not, offer an opinion or warranty as to whether the roof has leaked in the past, or may be subject to future leakage. The roof was too high to inspect. It was viewed from across the street with binoculars however, it was impossible to make a professional assessment of the roof condition. However, I was able to view from a distance a small section on the south side of the home. This is an educated guess assessment as the roof was viewed from a distance of approximately feet. It appeared that the asphalt roof covering was nearing the end of its functional life and should be further evaluated and repaired by a licensed roofing contractor within the next 1-5 years. 1.0 Item 1(Picture) Roof From Across the stret 1.0 Item 2(Picture) South section of roof 1.1 Due to the height of the roof the flashings were not inspected. 1.2 (1) Roofs, skylights and flashings are not water tested for leaks. (2) Due to the height of the roof, the skylights,chimneys and roof penetrations were not inspected. (2) Due to the height of the roof the roof drainage systems were not inspected. Gutters and roof drains are not water tested San Taela Court Page 4 of 43

5 (3) The downspouts could not be inspected at the rear of the home as the system is installed on the interior of the exterior walls. The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 5 of 43

6 2. Exterior The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility. 2.0 Wall Cladding Flashing and Trim 2.1 Doors (Exterior) 2.2 Windows Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings Vegetation, Grading, Drainage, Driveways, Patio Floor, Walkways and Retaining Walls (With respect to their effect on the condition of the building) 2.5 Eaves, Soffits and Fascias IN NI NP RR Styles & Materials Siding Style: Cement stucco Siding Material: Cement-Fiber Exterior Entry Doors: Wood Single pane Appurtenance: Deck with steps Balcony Driveway: Concrete IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace Comments: IN NI NP RR 2.0 (1) The stucco siding appeared functional at the time of the inspection. 2.0 Item 1(Picture) Stucco wall covering 4525 San Taela Court Page 6 of 43

7 (2) Siding in contact with ground at (East side of home) and (West side of home). Because the siding is in contact with ground it is possible for framing to be deteriorated. We did not inspect behind this siding. Recommend a ground clearance of six to eight inches where possible. 2.0 Item 2(Picture) Stucco contact with ground 2.1 The entry doors at front and rear of home were functional at the time of the inspection. 2.1 Item 1(Picture) Front Door 2.1 Item 2(Picture) Rear Sliding doors 4525 San Taela Court Page 7 of 43

8 2.2 Windows were functional at the time of inspection. 2.2 Item 1(Picture) Functional windows 2.3 (1) The Retractable canopy appeared functional at the time of inspection. 2.3 Item 1(Picture) Rear exterior stairs 2.3 Item 2(Picture) Retractable canopy 4525 San Taela Court Page 8 of 43

9 (2) The exterior stairs appeared functional at the time of inspection. 2.3 Item 3(Picture) Handrails faulty (3) The metal guardrails on on upper level deck and exterior stairs at the rear of home are missing balusters does not have a guard rail with proper picket spacing. Spacing more than 4 inches apart could allow an adult, child or pet to fall through. A qualified contractor should repair or replace as needed. 2.3 Item 4(Picture) Slight peeling (4) There is slight peeling of paint on the treads of the exterior stairs. It is recommended to re-seal stairs to avoid further damage San Taela Court Page 9 of 43

10 2.4 (1) The sprinkler system is not in the scope of this inspection. The system needs to be adjusted so it does not spray structures, sidewalks and fences. This inspection does not include geological conditions or site stability information. For information concerning these conditions, a geologist or soils engineer should be consulted. In order to prevent critters from entering crawl space I recommend closing off the opening where the AC refrigerant enters home. 2.4 Item 1(Picture) Yard Walls 2.4 Item 2(Picture) Close opening (2) The wood timber wall at the front, rear and sides of home though functional, have no structural value as retaining walls. They need to be monitored for movement and deterioration. A qualified contractor should repair or replace as needed. (3) There is a negative slope towards the front of home. This area does not appear to drain water away from home. However, a drain system has been put in place to reduce the possibility of water infiltration at foundation. 2.4 Item 3(Picture) Trouth and drains front of home 4525 San Taela Court Page 10 of 43

11 2.5 Generally the soffits/fascia and exterior trim appear in general to be in good condition at the time of inspection. 2.5 Item 1(Picture) Fascia, soffits and eaves good The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 11 of 43

12 3. Garage IN NI NP RR 3.0 Garage Ceilings 3.1 Garage Walls (including Firewall Separation) 3.2 Garage Floor 3.3 Garage Door (s) 3.4 Occupant Door (from garage to inside of home) Styles & Materials Garage Door Type: One automatic Garage Door Material: Fiberglass Metal Auto-opener Manufacturer: CHAMBERLAIN 3.5 Garage Door Operators (Report whether or not doors will reverse when met with resistance) IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace Comments: IN NI NP RR 3.0 Garage ceilings appear to be functional at the time of inspection. 3.0 Item 1(Picture) Covered Garage Ceiling 3.0 Item 2(Picture) Fire seperation wall. 3.1 (1) Of what sections of wall that could be seen, they appeared in good condition at the time of the inspection. (2) The firewall / ceiling was not fully visible at the time of inspection. 3.2 At the time of inspection the garage floor seemed functional. However, the inspection was limited as vehicles and owner belongings covered much of the area. 3.3 The Garage door was functional at the time of inspection. 3.4 The occupant door from inside garage to inside the home is not a fire rated door. This means that should a fire occur in garage, the occupant door does not afford protection until fireman arrive. This door should be replaced with a fire rated door. 3.5 The sensors are in place for garage door(s) and will reverse the door San Taela Court Page 12 of 43

13 4. Interiors The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installed cabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments. 4.0 Ceilings 4.1 Walls 4.2 Floors 4.3 Steps, Stairways, Balconies and Railings 4.4 Counters and Cabinets (representative number) 4.5 Doors (representative number) 4.6 Windows (representative number) IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace Comments: IN NI NP RR IN NI NP RR Styles & Materials Ceiling Materials: Gypsum Board Wall Material: Gypsum Board Floor Covering(s): Laminated T&G Tile Interior Doors: Hollow core Window Types: Thermal/Insulated Sliders Window Manufacturer: UNKNOWN Cabinetry: Wood Laminate Countertop: Tile Marble New: 4.0 Determining whether acoustic sprayed ceilings contain asbestos is beyond the scope of this inspection. For more information contact the American Lung Association or an asbestos specialists. Ceilings were functional at the time of the inspection. 4.0 Item 1(Picture) Functional Ceilings 4525 San Taela Court Page 13 of 43

14 4.1 The condition of walls behind wallpaper, paneling and furnishings cannot be judged. The walls of the home were in good general condition at the time of the inspection. 4.1 Item 1(Picture) Functional walls 4.2 Determining odors or stains is not included. Floor covering / damage may be hidden by furniture of other owner possessions. The condition of the flooring below carpet or vinyl is not inspected. General the flooring surfaces appeared to be in functional and good condition at the time of then installation. 4.2 Item 1(Picture) Bathroom Floor Tile 4.2 Item 2(Picture) Wood Flooring 4525 San Taela Court Page 14 of 43

15 4.3 The stairs, handrails and balconies appear functional at the time of the inspection. 4.3 Item 1(Picture) 4.3 Item 2(Picture) Exterior Balcony 4.5 (1) The represented number of doors tested appear to be functional at the time of the inspection. 4.5 Item 1(Picture) Functional sliding door 4525 San Taela Court Page 15 of 43

16 4.6 (1) Determining condition of all insulated windows is not possible due to temperature, weather and lighting conditions. Check with owner for further information. 4.6 Item 1(Picture) Functional windows (2) The represented number of windows tested appear to be functional at the time of the inspection. The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 16 of 43

17 5. Structural Components The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home inspector or other persons. 5.0 Foundations, Basement and Crawlspace (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) 5.1 Walls (Structural) 5.2 Columns or Piers 5.3 Floors (Structural) 5.4 Ceilings (Structural) 5.5 Roof Structure and Attic IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR IN NI NP RR Styles & Materials Foundation: Poured concrete Method used to observe Crawlspace: Crawled No access Floor Structure: Wood joists Wall Structure: Wood Ceiling Structure: 6'" or better Roof Structure: 2 X 6 Rafters Roof-Type: Gable Method used to observe attic: Walked Attic info: Attic access Attic hatch New: Comments: 4525 San Taela Court Page 17 of 43

18 5.0 White efflorescence (powder substance) on block wall indicates moisture is in contact with the masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, a water proofing paint could be applied to the interior side of the block if necessary. Efflorescence is found on many homes without water intrusion occurring inside the home. But, it should alert you to the possibility that future steps may be needed. 5.0 Item 1(Picture) Efflorescence 5.1 The rear and middle sections of the crawlspace were accessible and the structural walls appeared functional at the time of the inspection. The front section was too small for me to enter and therefor the inspection was limited. Unable to inspect walls for functionality. Refer to termite report. 5.1 Item 1(Picture) Hold owns 5.1 Item 2(Picture) Structural brawl space walls 4525 San Taela Court Page 18 of 43

19 5.3 (1) All slabs experience some degree of cracking due to shrinkage during the drying process. In most instances floor coverings prevent recognition of cracks or settlement in all but the most severe cases. The inspector will, at additional cost, reinspect, provided the client removes floor covering and releases the inspector from damage caused by this process. Floor coverings are not removed during this inspection. The inspector does not determine the effectiveness of any system installed to control or remove hazardous substances. No engineering is performed during this inspection. (2) The section was too small for me to enter and therefore the inspection was limited. Unable to inspect structural flooring for functionality. Refer to termite report. Middle and rear sections of the structural floor had a limited inspection as insulation covered most of the substructure. 5.3 Item 1(Picture) Inaccessible structural flooring 5.3 Item 2(Picture) Insulation 5.4 Insulation prevented inspector from inspecting ceiling structure. 5.4 Item 1(Picture) Ceiling covered 4525 San Taela Court Page 19 of 43

20 5.5 (1) No engineering is performed during this inspection. 5.5 Item 1(Picture) 5.5 Item 2(Picture) Roof structure (2) Roof structure appeared functional at the time of inspection. The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 20 of 43

21 6. Plumbing System The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials. 6.0 Plumbing Drain, Waste and Vent Systems 6.1 Plumbing Water Supply, Distribution System and Fixtures 6.2 Hot Water Systems, Controls, Chimneys, Flues and Vents 6.3 Main Water Shut-off Device (Describe location) 6.4 Fuel Storage and Distribution Systems (Interior fuel storage, piping, venting, supports, leaks) 6.5 Main Fuel Shut-off (Describe Location) 6.6 Sump Pump 6.7 Jacuzzi/tub/shower 6.8 Gas Fuel Source IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR IN NI NP RR Styles & Materials Water Source: Public Water Filters: (We do not inspect filtration systems) Plumbing Water Supply (into home): Copper Plumbing Water Distribution (inside home): Copper Washer Drain Size: 1 1/2" Diameter (undersized) Plumbing Waste: PVC ABS Water Heater Power Source: Electric Gas (quick recovery) Water Heater Capacity: Tankless Manufacturer: Rinnai Water Heater Location: Attic Comments: 4525 San Taela Court Page 21 of 43

22 6.0 Washing machines and dryers are not moved during this inspection - condition of walls or flooring under these machines cannot be judged. The inspector does not test washing machine, drains or supply valves. Water supply valves if turned may be subject to leaking. All drain, waste and venting appeared functional at the time of inspection. No deficiencies were noted. 6.0 Item 1(Picture) Plumbing vent 6.0 Item 2(Picture) Drain system 4525 San Taela Court Page 22 of 43

23 6.1 (1) Underground pipes or pipes inside walls cannot be judged for size, leaks or corrosion. Water quality testing or testing for hazards such as lead is not a part of this inspection. City sewer service, septic systems and all underground pipes are not a part of this inspection. Future drainage performance is also not determined. All plumbing fixtures throughout home were functional at the time of the inspection. Left master bathroom sink faucet has restricted flow. 6.1 Item 1(Picture) Water supply 6.1 Item 2(Picture) 6.1 Item 3(Picture) Low water pressure 6.1 Item 4(Picture) Disfunctional (2) The water pressure was reduced when bath sink faucet and shower was on and toilet was flushed, but it still passed functional flow. (3) The toilet flush know has slow to respond and water filling tank would not stop running when being refilled. Recommend that the flush kit be replaced San Taela Court Page 23 of 43

24 6.2 (1) Estimate of remaining life is not a part of this inspection. Solar systems are not a part of this inspection. Hot water recirculating pumps/systems are not a part of this inspection. 6.2 Item 2(Picture) Tank less vent 6.2 Item 1(Picture) Tankless H2O heater (2) Tankless water heater vent should have additional clearance Recommend further evaluation and repair by qualified plumbing contractor. (3) Unable to access roof and inspect the chimney flue or vent penetrations. From attic all appeared functional. 6.3 (1) The main shut off is the *IDENTIFY(plumbing/shut-off)* located *LOCATION(rooms-plumbing/shut-off)*. This is for your information. 6.3 Item 1(Picture) Main water shut off (2) The main shut off is the knob located outside near west exterior wall. This is for your information San Taela Court Page 24 of 43

25 6.4 (1) Underground piping and fuel tanks cannot be judged. Pipes inside walls or pipes concealed from view cannot be judged and the inspector does not perform tests for gas leaks or pipe size. Verification of the location or condition of the underground fuel storage tanks is not part of this inspection. Environmental risks, if any, are not a part of this inspection and are not included. 6.4 Item 1(Picture) Gas Line to HVAC and 6.4 Item 2(Picture) Questionable area reducing valve (2) The gas piping changes metals at the reducing coupler. Recommend licensed plumber evaluate and repair as needed. Check plumbing code prior to calling plumber. 6.5 (1) The main shut off is at the electric panel. The main fuel shut off is at gas meter outside 6.5 Item 1(Picture) Main Gas Line (2) Main shut of for gas is located outside at west wall. near front of house San Taela Court Page 25 of 43

26 6.7 Shower pan noted at bathrooms, not inspected for leaks, seller to disclose/check termite report. All tub/showers appear functional at the time of inspection. 6.7 Item 1(Picture) Drain Pan 6.8 Main Gas shutoff valve is located??? Fuel Type is Gas Meter The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 26 of 43

27 7. Electrical System The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment. 7.0 Service Entrance Conductors Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) Polarity and Grounding of Receptacles within 6 feet of interior plumbing fixtures, all receptacles in garage, carport and exterior walls of inspected structure 7.5 Operation of GFCI (Ground Fault Circuit Interrupters) 7.6 Location of Main and Distribution Panels 7.7 Smoke Detectors IN NI NP RR 7.8 Carbon Monoxide Detectors Styles & Materials Electrical Service Conductors: Overhead service Aluminum Copper 220 volts Panel capacity: 100 AMP Panel Type: Circuit breakers Electric Panel Manufacturer: Unknown Branch wire 15 and 20 AMP: Copper Wiring Methods: Romex IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace Comments: IN NI NP RR 4525 San Taela Court Page 27 of 43

28 7.0 Six or fewer breakers usually do not require a main breaker, however this may indicate minimal electrical capacity. If the service amperage is less than 100, upgrade may be necessary to operate larger electrical appliances. 7.0 Item 1(Picture) 7.1 (1) The main panel is not properly labeled. Recommend accurate label. 7.1 Item 1(Picture) Main Panel (2) The main panel box is located at the outside on east wall. The panel is missing screws and has undersized wiring for the breakers. This is a safety issue that needs to be corrected Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor should perform repairs that involve wiring San Taela Court Page 28 of 43

29 7.2 (1) The sub-panel box is located at the garage. The panel has undersized wiring for the breakers. This is a safety issue that needs to be corrected Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor should perform repairs that involve wiring. Additionally, is is being used improperly as a junction box. This needs to be corrected. 7.2 Item 2(Picture) undersized wiring 7.2 Item 1(Picture) Panel as junction box (2) Problem(s) discovered with Branch Circuits such as improper size/gauge wiring, and any other problems that an electrical contractor may discover while performing repairs need correcting. I recommend a licensed electrical contractor inspect further and correct as needed. (3) A white conductor,usually used as a neutral has been inserted into a breaker. If this is a neutral wire then this issue needs to be corrected by a licensed electrical contractor. If however it is being used as a hot wire, then it needs to be marked as so San Taela Court Page 29 of 43

30 7.3 two outlets are not working in the master bedroom and office. Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor should perform repairs that involve wiring. 7.3 Item 1(Picture) outlet not working 7.6 (1) The main panel box is located at the outside on east wall. (2) The sub panel box is located at the garage. 7.7 The smoke detector should be tested at common hallway to bedrooms upon moving in to home. 7.8 Recommend CO detector at upper and lower hallway for safety. The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 30 of 43

31 8. Heating / Central Air Conditioning The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to home; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms. 8.0 Heating Equipment 8.1 Normal Operating Controls 8.2 Automatic Safety Controls 8.3 Distribution Systems (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) 8.4 Presence of Installed Heat Source in Each Room 8.5 Chimneys, Flues and Vents (for fireplaces, gas water heaters or heat systems) 8.6 Solid Fuel Heating Devices (Fireplaces, Woodstove) IN NI NP RR 8.7 Gas/LP Firelogs and Fireplaces 8.8 Cooling and Air Handler Equipment 8.9 Normal Operating Controls 8.10 Presence of Installed Cooling Source in Each Room IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Styles & Materials Heat Type: Forced Air Energy Source: Gas Number of Heat Systems (excluding wood): One Heat System Brand: LENNOX Ductwork: Insulated Filter Type: Disposable Filter Size: N/A Types of Fireplaces: Conventional Operable Fireplaces: One Number of Woodstoves: None Cooling Equipment Type: Air conditioner unit Cooling Equipment Energy Source: Electricity Central Air Manufacturer: UNKNOWN Number of AC Only Units: One Comments: 4525 San Taela Court Page 31 of 43

32 8.0 If a fuel burning heater / furnace is located in a bedroom, we recommend evaluation by a qualified heating contractor for safety and air volume requirements Inspector does not light pilots. If pilots are "OFF", a full inspection is not possible. It is suggested that heating systems be activated and fully inspected PRIOR TO CLOSE OF TRANSACTION. The inspector is not equiped to thoroughly inspect heat exchangers for evidence of cracks or holes, as this can only be done by dismantling the unit or use of other technical procedures. Some furnaces are designed in such a way that inspection is almost impossible. Safety devices are not tested by this company. 8.0 Item 1(Picture) Forced air unit 8.1 Thermostats are not checked for calibration or timed functions. Adequacy, efficiency or even heat distribution of the system through the house is not a part of this inspection. Unit responded to controls and was functional at the time of inspection. 8.1 Item 1(Picture) Functional Heat 8.2 The safety switch shut off the unit when the service door was removed San Taela Court Page 32 of 43

33 8.3 (1) Asbestos materials have been commonly used in heating systems. Determining the presence of asbestos can Only be performed by laboratory testing and is beyond the scope of this inspection. Electronic air cleaners, humidifiers and dehumidifiers are beyond the scope of this inspection. Have these systems evaluated by a qualified individual. Combustion chamber was functional at the time of inspection. (2) The distribution ducts were insulated. 8.3 Item 1(Picture) Insulated ductwork 8.6 Firebox and flue appeared functional at the time of inspection. 8.7 Inspector does not light pilots. If pilots are "OFF", a full inspection is not possible. It is suggested that heating systems be activated and fully inspected PRIOR TO CLOSE OF TRANSACTION. 8.8 The cooling equipment was tested and was functional at the time of the inspection. 8.8 Item 1(Picture) AC unit 8.8 Item 2(Picture) Functional 8.9 AC unit responded to normal controls at the time of the inspection. Functional San Taela Court Page 33 of 43

34 The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 34 of 43

35 9. Insulation and Ventilation The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances. IN NI NP RR 9.0 Insulation in Attic 9.1 Insulation Under Floor System 9.2 Vapor Retarders (in Crawlspace or basement) 9.3 Ventilation of Attic and Foundation Areas 9.4 Venting Systems (Kitchens, Baths and Laundry) 9.5 Ventilation Fans and Thermostatic Controls in Attic IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR Comments: Styles & Materials Attic Insulation: Batt Approximate R-19 Ventilation: Gable vents Thermostatically controlled fan Exhaust Fans: Fan only Dryer Power Source: 220 Electric Dryer Vent: Flexible Metal Floor System Insulation: Unfaced Below R is about seven inches thick or 25.6 R-Value. 9.0 Item 1(Picture) Attic insulation 4525 San Taela Court Page 35 of 43

36 9.1 The floor is currently insulated with what appears to be R-13 in value. 9.1 Item 1(Picture) floor insulation 9.2 The vapor barrier (plastic) on the crawlspace ground is missing. A vapor barrier provides added protection to the floor system from moisture or dampness that can enter from ground. A qualified person should repair or replace as needed. 9.2 Item 1(Picture) No vapor barrier 9.3 Foundation vents appeared functional as temperature was normal and the ground under the structure of the home was free of moisture. Gable end vents were insufficient to adequately regulate the attic temperature. A electric powered thermostat controlled attic vent was installed and it assisted in controlling attic temperature. Recommend owner to monitor and add another unit if needed. 9.4 (1) Bathroom vents were functional at the time of inspection. (2) The kitchen hood was functional at the time of the inspection. The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 36 of 43

37 10. Built-In Kitchen Appliances The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable. IN NI NP RR 10.0 Dishwasher 10.1 Ranges/Ovens/Cooktops 10.2 Range Hood (s) 10.3 Trash Compactor 10.4 Food Waste Disposer 10.5 Microwave Cooking Equipment 10.6 Refrigerators/freezers/ice makers Styles & Materials Dishwasher Brand: VIKING Disposer Brand: UNKNOWN Exhaust/Range hood: VENTED Range/Oven: VIKING Built in Microwave: NONE Trash Compactors: NONE IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace Comments: IN NI NP RR 10.0 Dishwasher responded to controls and appeared to be working properly at time of inspection. The inspector cannot determine the remaining working life of unit and therefore cannot, and does not, offer an opinion or warranty regarding such Item 1(Picture) dishwasher 4525 San Taela Court Page 37 of 43

38 10.1 (1) Inspector does not light pilots. If pilots are "OFF", a full inspection is not possible. It is suggested that heating systems be activated and fully inspected PRIOR TO CLOSE OF TRANSACTION. Self and/or continuous cleaning operations, clocks, timing devices, lights and thermostat accuracy are not tested during inspection. Appliances are not moves Item 1(Picture) Range (2) The range and oven were functional at the time of the inspection Range hood responded to controls and appeared to be working properly at time of inspection. The inspector cannot determine the remaining working life of unit and therefore cannot, and does not, offer an opinion or warranty regarding such Item 1(Picture) Hood 4525 San Taela Court Page 38 of 43

39 10.4 Food waster disposer responded to controls and appeared to be working properly at time of inspection. The inspector cannot determine the remaining working life of unit and therefore cannot, and does not, offer an opinion or warranty regarding such Refrigerators, freezers and built-in ice maker are not a part of this inspection. The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report San Taela Court Page 39 of 43

40 General Summary 20/20 Vision Home Inspections, LLC 3371 Glendale Blvd., Unit 163 Los Angeles, CA (323) Customer Mr. Leon Bayer Address 4525 San Taela Court Woodland Hills CA The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report. 1. Roofing 1.0 Roof Coverings Inspected, Repair or Replace The report is an opinion of the general quality of the roof. The inspector cannot, and does not, offer an opinion or warranty as to whether the roof has leaked in the past, or may be subject to future leakage. The roof was too high to inspect. It was viewed from across the street with binoculars however, it was impossible to make a professional assessment of the roof condition. However, I was able to view from a distance a small section on the south side of the home. This is an educated guess assessment as the roof was viewed from a distance of approximately feet. It appeared that the asphalt roof covering was nearing the end of its functional life and should be further evaluated and repaired by a licensed roofing contractor within the next 1-5 years. 2. Exterior 2.3 Decks, Balconies, Stoops, Steps, Areaways, Porches, Patio/Cover and Applicable Railings 4525 San Taela Court Page 40 of 43

41 2. Exterior Inspected, Repair or Replace (1) The Retractable canopy appeared functional at the time of inspection. (2) The exterior stairs appeared functional at the time of inspection. (3) The metal guardrails on on upper level deck and exterior stairs at the rear of home are missing balusters does not have a guard rail with proper picket spacing. Spacing more than 4 inches apart could allow an adult, child or pet to fall through. A qualified contractor should repair or replace as needed. (4) There is slight peeling of paint on the treads of the exterior stairs. It is recommended to re-seal stairs to avoid further damage. 3. Garage 3.4 Occupant Door (from garage to inside of home) Inspected, Repair or Replace The occupant door from inside garage to inside the home is not a fire rated door. This means that should a fire occur in garage, the occupant door does not afford protection until fireman arrive. This door should be replaced with a fire rated door. 6. Plumbing System 6.4 Fuel Storage and Distribution Systems (Interior fuel storage, piping, venting, supports, leaks) Inspected, Repair or Replace (1) Underground piping and fuel tanks cannot be judged. Pipes inside walls or pipes concealed from view cannot be judged and the inspector does not perform tests for gas leaks or pipe size. Verification of the location or condition of the underground fuel storage tanks is not part of this inspection. Environmental risks, if any, are not a part of this inspection and are not included. (2) The gas piping changes metals at the reducing coupler. Recommend licensed plumber evaluate and repair as needed. Check plumbing code prior to calling plumber. 7. Electrical System 7.1 Service and Grounding Equipment, Main Overcurrent Device, Main and Distribution Panels Inspected, Repair or Replace (1) The main panel is not properly labeled. Recommend accurate label. (2) The main panel box is located at the outside on east wall. The panel is missing screws and has undersized wiring for the breakers. This is a safety issue that needs to be corrected Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor should perform repairs that involve wiring. (3) 7.2 Branch Circuit Conductors, Overcurrent Devices and Compatability of their Amperage and Voltage Inspected, Repair or Replace (1) The sub-panel box is located at the garage. The panel has undersized wiring for the breakers. This is a safety issue that needs to be corrected Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor should perform repairs that involve wiring. Additionally, is is being used improperly as a junction box. This needs to be corrected San Taela Court Page 41 of 43

42 7. Electrical System (2) Problem(s) discovered with Branch Circuits such as improper size/gauge wiring, and any other problems that an electrical contractor may discover while performing repairs need correcting. I recommend a licensed electrical contractor inspect further and correct as needed. (3) A white conductor,usually used as a neutral has been inserted into a breaker. If this is a neutral wire then this issue needs to be corrected by a licensed electrical contractor. If however it is being used as a hot wire, then it needs to be marked as so. 7.3 Connected Devices and Fixtures (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) Inspected, Repair or Replace two outlets are not working in the master bedroom and office. Electrical issues are considered a hazard until repaired. A qualified licensed electrical contractor should perform repairs that involve wiring. 7.8 Carbon Monoxide Detectors Inspected, Repair or Replace Recommend CO detector at upper and lower hallway for safety. 9. Insulation and Ventilation 9.2 Vapor Retarders (in Crawlspace or basement) Inspected, Repair or Replace The vapor barrier (plastic) on the crawlspace ground is missing. A vapor barrier provides added protection to the floor system from moisture or dampness that can enter from ground. A qualified person should repair or replace as needed. Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property. Prepared Using HomeGauge : Licensed To David Trent 4525 San Taela Court Page 42 of 43

Inspection Report Atlanta Strip Mall Commercial Building Property Address:

Inspection Report Atlanta Strip Mall Commercial Building Property Address: Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of

More information

SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS

SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS SECTION.1100 - NC HOME INSPECTOR STANDARDS OF PRACTICE AND CODE OF ETHICS.1101 DEFINITIONS The following definitions apply to this Section: (1) Automatic safety controls means devices designed and installed

More information

Page 1 of 24 Inspection Report Ms. Laurie Property Address: Spencer Oklahoma 73084 AAOK Home Inspections LLC Donald I. McCreary 70001429 3413 Terry Way Del City, OK 73115 405-778-4488 Page 2 of 24 Table

More information

STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE:

STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: 61-30.801 Standards of Practice, General. (1) Home inspections performed to these Standards of Practice are intended to provide the client with information

More information

Inspection Report. Mr. Happy 2 flat owner. Property Address: Focal Point Home Inspection Ltd.

Inspection Report. Mr. Happy 2 flat owner. Property Address: Focal Point Home Inspection Ltd. Page 1 of 35 Inspection Report Mr. Happy Property Address: Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 35 Table of Contents Cover Page Table of Contents

More information

Inspecton Report. Property Address:

Inspecton Report. Property Address: Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 bob@nationalhomeinspections.com www.nationalhomeservices.com Property Address: 873

More information

Inspection Report. Justin Anderson. JP's Home Inspection Services. Property Address: 987 Bluffs Drive Thistown Ia 65765. Jeff Peiffer 925 46th St.

Inspection Report. Justin Anderson. JP's Home Inspection Services. Property Address: 987 Bluffs Drive Thistown Ia 65765. Jeff Peiffer 925 46th St. Inspection Report Justin Property Address: 987 Bluffs Drive Thistown Ia 65765 JP's Home Inspection Services Jeff Peiffer 925 46th St. Sioux City, Ia 51104 (712) 301-8220 987 Bluffs Drive Page 2 of 23 Table

More information

Inspection Report TPCC. Property Address: 22 Touisset Road Warren RI 02885. Lane's Perfection Inspections

Inspection Report TPCC. Property Address: 22 Touisset Road Warren RI 02885. Lane's Perfection Inspections Inspection Report TPCC Property Address: 22 Touisset Road Warren RI 02885 Lane's Perfection Inspections Lane Ukura Ma.# 578 7 St.Louis Avenue Bristol, R.I. 02809 401-255-0726 Table of Contents Cover Page...1

More information

ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS

ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS 1. INTRODUCTION 1.1 This ASHI Standard of Professional Practice for Home Inspections (Standard) defines the scope of home inspections performed

More information

Inspection Report. Mr. JOHN SMITH. Property Address: 12345 S. Main St Denver Co 12349. A Happy House Home Inspection, LLC

Inspection Report. Mr. JOHN SMITH. Property Address: 12345 S. Main St Denver Co 12349. A Happy House Home Inspection, LLC Inspection Report Mr. JOHN SMITH Property Address: 12345 S. Main St Denver Co 12349 A Happy House Home Inspection, LLC Hans Coleman Centennial, Co 80015 720-988-4830 Table of Contents Cover Page...1 Table

More information

Home Inspection Report

Home Inspection Report 4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:

More information

Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections

Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections Summary of Oregon Home Inspector Certification Law and Standards of Practice for Home Inspections This is a summary of your rights and responsibilities when having a home inspection done by an Oregon certified

More information

Inspection Report. Mr. Sample Sample. Property Address: 1234 USA Drive Indianapolis IN 12345. 1234 USA Drive. Morris Home Inspection Group, LLC

Inspection Report. Mr. Sample Sample. Property Address: 1234 USA Drive Indianapolis IN 12345. 1234 USA Drive. Morris Home Inspection Group, LLC Inspection Report Mr. Sample Sample Property Address: 1234 USA Drive Indianapolis IN 12345 1234 USA Drive Morris Home Inspection Group, LLC Cedric Morris HI01200039 Fishers, IN 46037 317-550-6281 Table

More information

Inspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections

Inspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections Page 1 of 37 Inspection Report Prepared For: Sampath Sample Property Address: Alpharetta, GA 30004 Atlanta Home Inspections Matthew A Thoroman 6625 Hwy. 53 E. Ste. 410-151 Dawsonville Ga 30534 (678)-410-8062

More information

South Carolina Home Inspector Standards of Practice

South Carolina Home Inspector Standards of Practice South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,

More information

Inspection Report Mr. Sample Customer Property Address:

Inspection Report Mr. Sample Customer Property Address: Inspection Report Mr. Sample Customer Property Address: 1234 Sample Street Castle Rock Co 80000 1234 Sample Street, Castle Rock, CO 80000 Seven Stars Home Advisors Chad Chadwick 6839 W. Jackson Cr Rd Sedalia,

More information

Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668

Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668 Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

Inspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066

Inspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066 Page 1 of 58 Inspection Report Prepared For: Atlanta Commercial Customer Property Address: Building 5 Marietta, GA 30066 Superior Home Inspections Ray Thoroman 8070 Ivy Shaw Dr. Gainesville,GA 30506 678-410-3005

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

License Requirements for Persons Engaging in the Business of Inspection Practice:

License Requirements for Persons Engaging in the Business of Inspection Practice: SC Standards of Practice SOUTH CAROLINA RESIDENTIAL BUILDERS COMMISSION HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998 PURPOSE: The purpose of a residential

More information

Inspection Report. Mr. Simon Praveet. Property Address: 6643 Report Road Cincinnati OH 45233. Gerard Home Inspection

Inspection Report. Mr. Simon Praveet. Property Address: 6643 Report Road Cincinnati OH 45233. Gerard Home Inspection Inspection Report Mr. Simon Property Address: 6643 Report Road Cincinnati OH 45233 Gerard Home Inspection Garrett Gerard PO Box 33164 Cincinnati, OH 45233 KY: (859) 878-7768 OH: (513) 387-9173 Table of

More information

Total Home Inspection Checklist

Total Home Inspection Checklist Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are

More information

BUILDING ANALYSIS REPORT. John Doe 1234 Smith Road Atlanta, Georgia 30396

BUILDING ANALYSIS REPORT. John Doe 1234 Smith Road Atlanta, Georgia 30396 BUILDING ANALYSIS REPORT July 25, 2014 John Doe 1234 Smith Road Atlanta, Georgia 30396 Agent: Ausker and Barbara Morris AT Morris Realty Group, Inc. 3162 Johnson Ferry Road, Suite 260-25 Marietta, Georgia

More information

Inspection Report. sample sample. Property Address: 333 Wild Rasberry Lane. Etowah NC. Hubert Lowe Home Inspections

Inspection Report. sample sample. Property Address: 333 Wild Rasberry Lane. Etowah NC. Hubert Lowe Home Inspections Page 1 of 44 Inspection Report Property Address: Etowah NC Hubert Lowe Home Inspections Hubert Lowe North Carolina # 1602 4 Deerwood Cir Oak Island NC 28465 Cell 910-279-4728 Office 910-278-1542 Page 2

More information

PROPERTY INSPECTION REPORT

PROPERTY INSPECTION REPORT (850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304

More information

Inspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants

Inspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants Page 1 of 53 Inspection Report Jacksonville Property Address: Jacksonville FL 32204 South East Building Consultants Ray Thoroman Inspecting Jacksonville FL and entire South East Page 2 of 53 Table of Contents

More information

I NI NP R Inspected Items

I NI NP R Inspected Items 6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and

More information

HOME INSPECTION REPORT

HOME INSPECTION REPORT Edgewood Home Inspections, Inc. 407 W. Smith Valley Rd. #1032 Greenwood, IN 46142 (317) 833-6048 HOME INSPECTION REPORT Indianapolis IN 46000 Inspector's Name: License Number: Scott Kissel HI00800073 TABLE

More information

Standards of Professional Practice

Standards of Professional Practice Standards of Professional Practice Adapted with permission from Standards of Practice, Effective June 1, 1992, Copyright 1993 American Society of Home Inspectors, Inc. Adopted by AZ ASHI Effective January

More information

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000 Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

Inspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg

Inspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property

More information

Inspection Report. Property Address: St. Marks Ave. Brooklyn NY 11213. Five Borough Home Inspection, LLC. Derek Lomer

Inspection Report. Property Address: St. Marks Ave. Brooklyn NY 11213. Five Borough Home Inspection, LLC. Derek Lomer Inspection Report Property Address: St. Marks Ave. Brooklyn NY 11213 Five Borough Home Inspection, LLC Derek Lomer NYS Licence Lic # 16000051234 790 Washington Ave., Unit 112 Brooklyn, NY, 11238 917-494-8474

More information

A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111

A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 Inspector Name: Tim Knight, ASHI Member 202490 Inspection No: 12121212 Inspection Date: 1/1/2012 Client: Address: John

More information

South Carolina Home Inspector Standards of Practice

South Carolina Home Inspector Standards of Practice South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,

More information

Inspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748

Inspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748 Inspection Report provided by: Delaware Property Inspection Inspector: Richard Hiddemen (302)355-1748 ASHI # 243377 DPR #H4-0000018 DDA #06-444 Delaware 1992105842 Wilmington #03857 New Castle #2010-845

More information

Vari Inspection Services

Vari Inspection Services Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54

More information

Home Inspection Report

Home Inspection Report Report# 21009 Page 1 of 24 Home Inspection Report Property Address: 123 Maple Lane, St. Augustine, FL 32092 Prepared For: Mr. Smith Prepared By: EDGE Inspections www.edgeinspections.com PO Box 601055 Jacksonville,

More information

Inspection Report. Sample Client. Property Address: XXXX N. Atolia Drive Tucson AZ 85743. House and Home

Inspection Report. Sample Client. Property Address: XXXX N. Atolia Drive Tucson AZ 85743. House and Home Inspection Report Sample Property Address: XXXX N. Atolia Drive Tucson AZ 85743 House and Home Brian Pemble #45238 6909 E. Kingston Drive Tucson, AZ. 85710. 520-245-7897 Table of Contents Cover Page...1

More information

WILL INSPECT: (A) INSTALLED AND ACCESSIBLE SYSTEMS AND COMPONENTS OF HOMES LISTED IN THESE INSPECTOR STANDARDS. INSPECTORS WILL REPORT

WILL INSPECT: (A) INSTALLED AND ACCESSIBLE SYSTEMS AND COMPONENTS OF HOMES LISTED IN THESE INSPECTOR STANDARDS. INSPECTORS WILL REPORT Page 1 of 14 Article I. SECTION 1.01 INTRODUCTION PREFACE THE INTERNATIONAL SOCIETY OF HOME INSPECTORS, INC. (ISHI) IS A NOT-FOR-PROFIT PROFESSIONAL SOCIETY ESTABLISHED IN 1995. MEMBERSHIP IN ISHI IS VOLUNTARY

More information

COMPREHENSIVE PROPERTY INSPECTIONS

COMPREHENSIVE PROPERTY INSPECTIONS COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited

More information

HOME INSPECTOR STANDARDS OF PRACTICE

HOME INSPECTOR STANDARDS OF PRACTICE HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998, South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the

More information

Self-Home Inspection Checklist

Self-Home Inspection Checklist To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional

More information

Inspection Report. Bob and Betty Buyer. Property Address: 4567 Home street Anchorage AK 99507. Inspection Connection LLC

Inspection Report. Bob and Betty Buyer. Property Address: 4567 Home street Anchorage AK 99507. Inspection Connection LLC Inspection Report Bob and Betty Property Address: 4567 Home street Anchorage AK 99507 Inspection Connection LLC Richard A. Long Alaska Registered #183 8621 Barney Circle Anchorage, AK 99507 (907) 868-8096

More information

Georgia Home Inspection Services

Georgia Home Inspection Services Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in

More information

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector

More information

Inspection Report. Mr. John Doe. Property Address: 123 Somewhere Jacksonville FL 32224. Tabor Hill & Associates LLC

Inspection Report. Mr. John Doe. Property Address: 123 Somewhere Jacksonville FL 32224. Tabor Hill & Associates LLC Inspection Report Mr. John Property Address: 123 Somewhere Jacksonville FL 32224 Tabor Hill & Associates LLC James Cox HI4634 P.O. Box 65699 Orange Park FL 32065 Table of Contents Cover Page...1 Table

More information

Inspection Report. Inspection Date: 12/1/2010. Commercial Property Sample Report. Property Address: Street. City State Zip

Inspection Report. Inspection Date: 12/1/2010. Commercial Property Sample Report. Property Address: Street. City State Zip Page 1 of 41 Inspection Report Inspection Date: 12/1/2010 Commercial Property Sample Report Property Address: City State Zip All In One Home Inspection LLC Joseph W Fleming III - Home Inspector License

More information

HOME INSPECTION CHECKLIST

HOME INSPECTION CHECKLIST CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways

More information

PROPERTY INSPECTION REPORT Property Address:

PROPERTY INSPECTION REPORT Property Address: Scott Certified Member P. O. Box 9007 Indianapolis, IN 690-007 (7)-750-60 Fax: 7-876-8 PROPERTY INSPECTION REPORT Property Address: Prepared for: Inspection Inspector: Lou Buehler Inspection #: BUYERS

More information

Inspection Report. Joe Smith Report. Property Address: 111 Main Street St Augustine FL 32080. Eagle Eye Home Inspections

Inspection Report. Joe Smith Report. Property Address: 111 Main Street St Augustine FL 32080. Eagle Eye Home Inspections Inspection Report Joe Report Property Address: 111 Main Street St Augustine FL 32080 Eagle Eye Home Inspections Rick Glodowski HI 4677 5255 Atlantic View St Augustine, FL 32080 904-461-2550 111 Main Street

More information

Inspection Report. Joe and Sue Smith. Property Address: 1234 Your St. Bothell WA 98011. Transparent Inspections

Inspection Report. Joe and Sue Smith. Property Address: 1234 Your St. Bothell WA 98011. Transparent Inspections Page 1 of 33 Inspection Report Joe and Sue Property Address: Bothell WA 98011 Transparent Inspections Austin McFeeley 13221 Meridian Ave S Unit A Everett WA 98208 425-773-6637 Page 2 of 33 Table of Contents

More information

159 Morningside Avenue, Toronto

159 Morningside Avenue, Toronto 159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in

More information

Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10

Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792

More information

Propery Inspection Report

Propery Inspection Report Propery Inspection Report Cover Page,, Ok Inspection prepared for: Date of Inspection: 9/28/2014 Time: 8:30 AM Age of Home: 2011 MOL Weather: Clear 62 degrees Inspector: License #130 5400 Hwy 177, Marland,

More information

Inspection Report. Prepared Exclusively For:Joe Sample. Property Address: 552 Brindway. Raleigh NC

Inspection Report. Prepared Exclusively For:Joe Sample. Property Address: 552 Brindway. Raleigh NC Page 1 of 22 Inspection Report Prepared Exclusively For:Joe Property Address: Raleigh NC By: Steve Smallman, N.C. Home Inspector License #3 2611 Sherborne Place Raleigh N.C. 27612 919-669-3639 Page 2 of

More information

HOMEOWNER S PERMIT GUIDE

HOMEOWNER S PERMIT GUIDE HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448

More information

Inspection Report. Happy Chicago Bungalow Owner. Property Address: Focal Point Home Inspection Ltd.

Inspection Report. Happy Chicago Bungalow Owner. Property Address: Focal Point Home Inspection Ltd. Page 1 of 31 Inspection Report Happy Property Address: Focal Point Home Inspection Ltd. Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 31 Table of Contents

More information

Inspection Report. Mr. John Homebuyer. Property Address: 123 Main Street Houston TX 77007. Front View. EDP Consulting Engineers, PLLC

Inspection Report. Mr. John Homebuyer. Property Address: 123 Main Street Houston TX 77007. Front View. EDP Consulting Engineers, PLLC Page 1 of 14 Inspection Report Mr. John Homebuyer Property Address: 123 Main Street Houston TX 77007 Front View EDP Consulting Engineers, PLLC Gerald C. Reece, PE TREC #7825 14119 Willowsong Ct Missouri

More information

Inspection Report. Sample Report. Property Address: 1234 Anywhere street Phoenix AZ. Veteran Inspection Professionals

Inspection Report. Sample Report. Property Address: 1234 Anywhere street Phoenix AZ. Veteran Inspection Professionals Inspection Report Property Address: 1234 Anywhere street Phoenix AZ Veteran Inspection Professionals Mark Mandery 040901 4725 W. Aire Libre Ave Glendale AZ, 85306 480-694-2111 Table of Contents Cover Page...1

More information

FAIRA TRANSPARENCY REPORTS. 1116 Whitman Ct NE, Renton, WA 98059 March 11, 2016

FAIRA TRANSPARENCY REPORTS. 1116 Whitman Ct NE, Renton, WA 98059 March 11, 2016 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS, Renton, WA 98059 March 11, 2016 Thank you for your interest in this Faira Certified home.

More information

Inspection Report. Mr. Doug Smith. Property Address: 123 House Street SAINT LOUIS MO 63116. Street View CANDID HOME INSPECTION SERVICE, LLC.

Inspection Report. Mr. Doug Smith. Property Address: 123 House Street SAINT LOUIS MO 63116. Street View CANDID HOME INSPECTION SERVICE, LLC. Inspection Report Mr. Doug Smith Property Address: 123 House Street SAINT LOUIS MO 63116 Street View CANDID HOME INSPECTION SERVICE, LLC. STEVE SHORETTE 3 ELK TRAIL COURT ARNOLD, MO. 63010 636.282.2747

More information

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA

More information

Inspection Report. Ms. Onah Holmes 123 Maple Street Springfield, Ontario

Inspection Report. Ms. Onah Holmes 123 Maple Street Springfield, Ontario Inspection Report Ms. Onah Holmes 123 Maple Street Springfield, Ontario 123 Maple Street Page 2 of 30 Cover Page Table of Contents Table of Contents Intro Page 1 Roof 2 Exterior 3 Basement, Foundation,

More information

Property Inspection Report

Property Inspection Report Property Inspection Report 1441 Euclid St NW #B2 Washington DC 20009 PREPARED FOR: Eli Valentin Prepared by: Glenford Blanc MDHIL #29749 PRO-SPEX Inc. 15503 Misty Pine Rd Laurel, MD 20707 301-675-8411/8851

More information

Code Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division

Code Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division Code Enforcement Inspection Manual City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division LIVING ROOM 304.15 EXTERIOR DOOR(S) Check door(s) and trim for condition,

More information

Does Wall Township require an inspection by the building department on resale of a home?

Does Wall Township require an inspection by the building department on resale of a home? Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,

More information

Terry Jenkins, Owner Member, American Society of Home Inspectors Virginia Certified Home Inspector Certificate # 3380 000373, expires 1/2010

Terry Jenkins, Owner Member, American Society of Home Inspectors Virginia Certified Home Inspector Certificate # 3380 000373, expires 1/2010 Terry Jenkins, Owner Member, American Society of Home Inspectors Virginia Certified Home Inspector Certificate # 3380 000373, expires 1/2010 Tel: (804) 378-0861 terry@prospectpropertiesva.com Inspection

More information

dsfsdfs STLhomeinspector.com

dsfsdfs STLhomeinspector.com Cover Page 555 Sample Road, St. Louis MO, 63110 Inspection prepared for: Sample Report Inspection Date: 2/15/2012 Inspector: Bill Boerner Phone: (314) 805-2137 Email: office@stlhomeinspector.com Residential

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check

#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check #1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check Zoning laws Deed restrictions on home size, foundation style, roof pitch, etc. Suitability (slope, wetland issues, etc.) Accessibility

More information

CHRIS CURLES and ASSOCIATES INSPECTION SERVICES

CHRIS CURLES and ASSOCIATES INSPECTION SERVICES CHRIS CURLES and ASSOCIATES INSPECTION SERVICES Inc. Chris Curles, President www.homeinspectionsatlanta.com chriscurl@comcast.net Office: 770-493-0227 Professional Member Of: GAHI # 93006 ASHI # 211725

More information

Inspection Report. John Doe Property Address: 6555 Any Street, Atlanta Metro. Any Town Ga. 30097. Sample Report. Georgia State Inspections

Inspection Report. John Doe Property Address: 6555 Any Street, Atlanta Metro. Any Town Ga. 30097. Sample Report. Georgia State Inspections Inspection Report John Doe Property Address: Any Town Ga. 30097 Sample Report Georgia State Inspections Jake Accardi ICC 8034454- B2 www.gastateinspections.com 404.514.7457 jaccardi@gastateinspections.com

More information

SWF Home Inspections

SWF Home Inspections Cover Page SWF Home Inspections Property Inspection Report Inspection prepared for: Mr & Mrs Home Buyer Real Estate Agent: My Favorite Agent - Date of Inspection: 7/4/2013 Age of Home: 2004 Size: 1568

More information

2. What building projects are exempted? (permit not required)

2. What building projects are exempted? (permit not required) BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

Structure Survey Findings:

Structure Survey Findings: Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,

More information

Inspection Report 95 Old Stage Road East Brunswick NJ Scott Frederick

Inspection Report 95 Old Stage Road East Brunswick NJ Scott Frederick Inspection Report 95 Old Stage Road East Brunswick NJ Scott Frederick Prepared by: The Inspection Guys www.inspectionguys.com 16 Mt. Bethel Road, Suite 171 Warren, NJ 07059 800-903-0670 Fax: 732-238-7092

More information

BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER

BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE

More information

Orlando Home Inspection Services

Orlando Home Inspection Services PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com

More information

Inspection Report. John Doe. Property Address: 125 Main Street Mesa AZ 85207. Sunrise Inspection Services PLC

Inspection Report. John Doe. Property Address: 125 Main Street Mesa AZ 85207. Sunrise Inspection Services PLC Inspection Report John Property Address: 125 Main Street Mesa AZ 85207 Sunrise Inspection Services PLC Paul Stokle 54338 PO Box 6618 Goodyear, AZ. 85338 (480) 432-7066 Table of Contents Cover Page...1

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

THE STANDARD OF PRACTICE FOR HOME INSPECTIONS AND THE CODE OF ETHICS FOR THE HOME INSPECTION PROFESSION

THE STANDARD OF PRACTICE FOR HOME INSPECTIONS AND THE CODE OF ETHICS FOR THE HOME INSPECTION PROFESSION THE STANDARD OF PRACTICE FOR HOME INSPECTIONS AND THE CODE OF ETHICS FOR THE HOME INSPECTION PROFESSION www.ashi.org Distribution of this material is not an indication of ASHI Membership. To find an ASHI

More information

Professional standards of practice for residential building inspection

Professional standards of practice for residential building inspection Professional standards of practice for residential building inspection A PUBLICATION OF THE ORDRE DES ARCHITECTES DU QUÉBEC ORDRE DES ÉVALUATEURS AGRÉÉS DU QUÉBEC ORDRE DES TECHNOLOGUES PROFESSIONNELS

More information

Aztec Property Inspections 2719 Mission Blvd San Diego, CA 92109 (858) 245-9329. 6352 Some Road San Diego, CA 92114

Aztec Property Inspections 2719 Mission Blvd San Diego, CA 92109 (858) 245-9329. 6352 Some Road San Diego, CA 92114 2719 Mission Blvd San Diego, CA 92109 (858) 245-9329 Client: Could Be You 6352 Some Road San Diego, CA 92114 Page 1 of 14 Defective Summary This summary is not the entire report. The complete report may

More information

RULES OF TENNESSEE DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF REGULATORY BOARDS CHAPTER 0780-5-12 HOME INSPECTORS TABLE OF CONTENTS

RULES OF TENNESSEE DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF REGULATORY BOARDS CHAPTER 0780-5-12 HOME INSPECTORS TABLE OF CONTENTS RULES OF TENNESSEE DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF REGULATORY BOARDS CHAPTER 0780-5-12 HOME INSPECTORS TABLE OF CONTENTS 0780-5-12-.01 Purpose 0780-5-12-.07 Qualifying and Continuing Education

More information

GENERAL WIRING RULES FOR HOUSES

GENERAL WIRING RULES FOR HOUSES GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Cincinnati, Ohio 45000 Prepared for: Dean Murphy Prepared by: BEDROCK ENTERPRISES, INC. 4060 Simca Lane Cincinnati, OH 45211 20:13 July 07, 2008 Page 1 of 18 Definitions NOTE: All

More information

First Flight Home Inspections, Inc.

First Flight Home Inspections, Inc. First Flight Home Inspections, Inc. HOME INSPECTION REPORT Exclusively For Clients Name Property Address: 1234 Sample Report Drive Anytown, NC 27000 Field Inspection Performed on January 1, 2015 Time:

More information

Villa Home Inspections

Villa Home Inspections PROPERTY INSPECTION REPORT SITE INFORMATION Property Address: City, State, Zip: Date of Inspection: Time of Inspection: Parties Present during Inspection: Inspector: Address Omitted. Inglewood, CA 90305.

More information

GeorgiaHomePros.com. 6858 Yellow Creek Road Ball Ground, GA 30107 770-893-2271 www.georgiahomepros.com inspections@tds.net Inspected By: Scott Webb

GeorgiaHomePros.com. 6858 Yellow Creek Road Ball Ground, GA 30107 770-893-2271 www.georgiahomepros.com inspections@tds.net Inspected By: Scott Webb GeorgiaHomePros.com 6858 Yellow Creek Road Ball Ground, GA 30107 770-893-2271 www.georgiahomepros.com inspections@tds.net Inspected By: Scott Webb Home Inspection Report Prepared For: Jack & Diane Samples

More information

VIRGINIA HOME INSPECTIONS P.O.BOX 586 CHINCOTEAGUE ISLAND, VA 23336 PHONE 757 336-3450 Inspector1@verizon.net

VIRGINIA HOME INSPECTIONS P.O.BOX 586 CHINCOTEAGUE ISLAND, VA 23336 PHONE 757 336-3450 Inspector1@verizon.net CLIENT: DATE: LOCATION: TEMPERATURE: WEATHER CONDITIONS: PERSONS PRESENT: VIRGINIA HOME INSPECTIONS P.O.BOX 586 CHINCOTEAGUE ISLAND, VA 23336 PHONE 757 336-3450 Inspector1@verizon.net 1 Virginia Home Inspections

More information

Home Inspection Report

Home Inspection Report Home Inspection Report 555 Wind Way, Fake City, OR 54645 Inspection Date: Monday May 12, 2014 Prepared For: John Doe Prepared By: House to Home 3468 N. Bartlett Ave Milwaukee, WI 53211 262-754-5973 christopher@ahit.com

More information