1 21 May 2014 PART 1 - GENERAL WORK INCLUDED QUALITY ASSURANCE APPROVALS... 1 PART 2 - PRODUCTS HEATING BOILERS BOILER SEQUENCE CONTROL... Error! Bookmark not defined BOILER SCHEDULE... Error! Bookmark not defined. PART 3 - EXECUTION INSTALLATION STARTUP... 4 INDEX

2 21 May 2014 Page 1 PART 1 - GENERAL 1.1. WORK INCLUDED.1 Comply with Division 1, General Requirements and all documents referred to therein..2 Provide all labour, materials, products, equipment and services to supply and install the heated water boilers and controls indicated on the Drawings and specified in this Section of the Specifications QUALITY ASSURANCE.1 Manufacture and install in accordance with governing codes and regulations and the following reference standards:.1 Provincial Boiler and Pressure Vessels Act.2 CSA Standard B.51 (latest edition): Code for the construction and Inspection of Boilers and Pressure Vessels.3 ASME: Boiler and Pressure Vessel Code, Section IV.4 Canadian Electrical Code.5 Piping to ANSI Standards.6 Provincial Environmental and Energy Acts.7 CSA/CGA B149 Natural Gas Installation Code.2 Provide factory tests to confirm specified construction, and proper operation of unit APPROVALS.1 Obtain and pay for Environmental Protection Act Permit..2 Submit to the Owner Canadian registration number of the unit attesting to units meeting the requirements of the Authorized Inspection Agency. PART 2 - PRODUCTS 2.1. HEATING BOILERS.1 Provide natural gas fired hydronic hot water heating boilers of proven and certifiable low NOx design with ASHRAE 90.1 approval. Boilers shall be, constructed in accordance with ASME standards complete with approval stamp for 160 psi working pressure..2 Boilers shall be certified and listed by CSA International under the latest edition of the harmonized ANSI Z21.13 test standard for the U.S. and Canada and shall bear a CGA Seal as a hydronic boiler..3 Meet performance requirements shown on schedules. Minimum efficiency 85%..4 Provide boilers constructed as follows:

3 21 May 2014 Page 2.1 The boiler shall bear the ASME "H" stamp for 160 psi working pressure and shall be National Board listed. There shall be no banding material, bolts, gaskets or "O" rings in the header configuration. The 316L stainless steel combustion chamber shall be designed to drain condensation to the bottom of the heat exchanger assembly. A built-in trap shall allow condensation to drain from the heat exchanger assembly. The complete heat exchanger assembly shall carry a ten (10) year limited warranty..2 The boiler shall be certified and listed by C.S.A. International under the latest edition of the harmonized ANSI Z21.13 test standard for the U.S. and Canada. The boiler shall comply with the energy efficiency requirements of the latest edition of the ASHRAE 90.1 Standard and the minimum efficiency requirements of the latest edition of the BTS2000 Standard. The boiler shall operate at a minimum of 94% thermal efficiency at full fire. The boiler shall operate up to 98% thermal efficiency with return water temperatures at 100 F or below. The boiler shall be certified for indoor installation. The boiler s Thermal Efficiency shall be verified through third party testing by the Hydronics Institute Division of AHRI and listed in the AHRI Certification Directory..3 The boiler shall be constructed with a heavy gauge steel jacket assembly, primed and pre-painted on both sides. The combustion chamber shall be sealed and completely enclosed, independent of the outer jacket assembly, so that integrity of the outer jacket does not affect a proper seal. A burner/flame observation port shall be provided. The burner shall be a premix design and constructed of high temperature stainless steel with a woven metal fiber outer covering to provide modulating firing rates. The boiler shall be supplied with a gas valve designed with negative pressure regulation and be equipped with a variable speed blower system, to precisely control the fuel/air mixture to provide modulating boiler firing rates for maximum efficiency. The boiler shall operate in a safe condition at a derated output with gas supply pressures as low as 4 inches of water column. The boiler shall be equipped with leveling legs..4 The boiler shall utilize a 24 VAC control circuit and components. The control system shall have an electronic display for boiler set-up, boiler status, and boiler diagnostics. All components shall be easily accessed and serviceable from the front and top of the jacket. The boiler shall be equipped with; a temperature/pressure gauge, high limit temperature control certified to UL353, ASME certified pressure relief valve, outlet water temperature sensor, return water temperature sensor, a UL 353 certified flue temperature sensor, outdoor air sensor, low water flow protection and built-in adjustable freeze protection..5 The boiler shall feature the Smart System control with a Multi-Colored Graphic LCD display with Navigation Dial and Soft Keys for, password security, three loop temperature setpoints with individual outdoor air reset curves, pump delay with adjustable freeze protection, pump exercise, and USB PC port connection. The boiler shall be capable of controlling a variable speed boiler pump to keep a constant Delta T at all modulation rates. The boiler shall have the capability to accept a 0-10 VDC input connection for BMS control of modulation or setpoint, enable disable of the boiler, variable system pump signal and a 0-10VDC output of boiler modulation rate. The Boiler shall have a built-in Cascade with sequencing options for lead lag or efficiency optimized modulation logic, with both capable of rotation while maintaining modulation of up to eight boilers

4 21 May 2014 Page 3 without utilization of an external controller. Supply voltage shall be 120 volt / 60 hertz / single phase..6 The boiler shall be equipped with two terminal strips for electrical connection. A low voltage connection board with 42 data points for safety and operating controls, i.e., Auxiliary Relay, Auxiliary Proving Switch, Alarm Contacts, Runtime Contacts, Manual Reset Low Water Cutoff, Flow Switch, High and Low Gas Pressure Switches, Tank Thermostat, Three Wall Thermostat/Zone Controls, System Supply Sensor, Outdoor Sensor, Building Management System Signal, Modbus Control Contacts and Cascade Control Circuit. A high voltage terminal strip shall be provided for supply voltage. The high voltage terminal strip plus integral relays are provided for independent pump control of the System pump, the Boiler pump and the Domestic Hot Water pump..7 The boiler shall be installed and vented with a:.1 Direct Vent Sidewall system with a horizontal sidewall termination of both the vent and combustion air. The flue shall be PVC, CPVC or Stainless Steel sealed vent material terminating at the sidewall with the manufacturers specified vent termination. A separate pipe shall supply combustion air directly to the BOILER from the outside. The air inlet pipe may be PVC, CPVC, ABS, Galvanized, Dryer Vent, or Stainless Steel sealed pipe. The air inlet must terminate on the same sidewall with the manufacturer s specified air inlet cap. The BOILER s total combined air intake length shall not exceed 100 equivalent feet. The BOILER s total combined exhaust venting length shall not exceed 100 equivalent feet..8 Additional standard equipment shall include a flow switch, high temperature limit control, an air pressure switch to monitor low air and blocked flue conditions, low voltage transformer with a five amp circuit breaker for the 24 volt control circuit, a 50 PSI ASME pressure relief valve and a temperature / pressure gauge. All units must be factory tested and complete with a quality test report shipped with the unit. Supply Voltage to boiler at 120 volts..9 All components shall be easily accessed and serviceable and have multi-pin plug in type connectors to ease service, troubleshooting and lower removal and replacement costs. Indicating lights shall be provided for power on, pre purge, trial for ignition, flame failure, low air and individual stage operation. The ignition module shall provide status indication visible from the unit control panel. PART 3 - EXECUTION 3.1. INSTALLATION.1 Follow manufacturer's erection, operation and maintenance instructions..2 Provide wiring between boiler control panels and sequence controller. Iinstall and wire controls for boilers and any loose control components.3 Provide, to the appropriate trade, steel angle inserts to be placed in the housekeeping pads for the support of the boilers.

5 21 May 2014 Page 4.4 Pipe relief valves and drains from each unit to funnel floor drain or hub drain. Make required piping, electrical, venting, and control connections STARTUP.1 Manufacturers representative to provide start-up assistance service for contractor under the direction of the consultant complete with flue gas analysis showing NOx emissions for submission with start up report..2 System commissioning shall be the responsibility of the contractor and payment for any equipment commissioning shall be the responsibility of the contractor..3 Manufacturers representative to also provide for one half day (4 hours) of maintenance and operating instructions for the owners representative and include for training on troubleshooting potential problems. Provide engineering consultant adequate notice prior to start-up assistance and instruction sessions and provide a written start up report of installation results. END OF SECTION

Up To 99% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY

Up To 99% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY 7 INPUTS FROM 1.5 TO 5.0 MILLION BTU/HR FIRING RATE MODULATION UP TO 25:1 DIRECT-VENT FLEXIBILITY

More information

Versatility ::::::::::::::::::::::::::::::::::::::: the best. mod/con Performance. and UP TO. www.knightheatingboiler.com

Versatility ::::::::::::::::::::::::::::::::::::::: the best. mod/con Performance. and UP TO. www.knightheatingboiler.com the best mod/con Performance UP TO 96 % DOE AFUE Efficiency and Versatility Now with Floor and Wall Mount Models www.knightheatingboiler.com ::::::::::::::::::::::::::::::::::::::: a Legendary Performer

More information

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger

More information

ACCESSORIES Pipe Cover Neutralizer Kit Isolation Valve Kits Concentric Termination PRODUCT PRESERVERS ANTI-SCALE SYSTEM

ACCESSORIES Pipe Cover Neutralizer Kit Isolation Valve Kits Concentric Termination PRODUCT PRESERVERS ANTI-SCALE SYSTEM TANKLESS HIGH EFFICIENCY CONDENSING MODELS Ultra-Low NOx Gas with Condensing Technology featuring an unprecedented.95 Energy Factor which lowers operating costs and is environmentally friendly ATI and

More information

DESIGNER S HIGH EFFICIENCY GUIDE SYNC COMMERCIAL BOILERS. Up to 98% Thermal Efficiency. www.lochinvar.com

DESIGNER S HIGH EFFICIENCY GUIDE SYNC COMMERCIAL BOILERS. Up to 98% Thermal Efficiency. www.lochinvar.com DESIGNER S HIGH EFFICIENCY GUIDE SYNC COMMERCIAL BOILERS Up to 98% Thermal Efficiency www.lochinvar.com Table of Contents 1 Combustion & Ventilation Air Page 2 2 Venting... Page 5 3 Gas.... Page 13 4 Water......

More information

Evergreen. Easy heat, Effortless comfort COMMERCIAL HIGH-EFFICIENCY BOILER. DURABLE Stainless steel fire tube heat exchanger

Evergreen. Easy heat, Effortless comfort COMMERCIAL HIGH-EFFICIENCY BOILER. DURABLE Stainless steel fire tube heat exchanger Evergreen www.weil-mclain.com COMMERCIAL HIGH-EFFICIENCY BOILER Water Natural/Propane Gas 220-399 MBH 3 Sizes Direct Vent 95% AFUE* Easy heat, Effortless comfort DURABLE Stainless steel fire tube heat

More information

TANKLESS HIGH EFFICIENCY CONDENSING WATER HEATERS

TANKLESS HIGH EFFICIENCY CONDENSING WATER HEATERS TANKLESS HIGH EFFICIENCY CONDENSING WATER HEATERS FEATURES INDOOR MODELS GTS-240, GTS-340, GTS-540 OUTDOOR MODELS GTS-240, GTS-340, GTS-540 ANSI Z21.10.3 CSA 4.3 GTS 540 model only Ultra-Low NOx Condensing

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

Commercial Gas Water Heater

Commercial Gas Water Heater Commercial Gas Water Heater 3-Year Limited Tank/1-Year Limited Parts Warranty* The Polaris has a high grade 444 stainless steel tank with brass connections for years of dependable, trouble-free service

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600

More information

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH Centauri Condensing Fire Tube Water Boiler 399 to 1000 MBH Pre-mix surface burner with up to a 7-to-1 turndown NOx levels as low a 5 ppm at full rate Operates on 4" gas pressure shown with optional gauges

More information

High Efficiency Commercial Gas Boilers. Up to 97% Thermal Efficiency 1.5, 1.7 & 2.0 Million Btu/hr Less than 20ppm NOx

High Efficiency Commercial Gas Boilers. Up to 97% Thermal Efficiency 1.5, 1.7 & 2.0 Million Btu/hr Less than 20ppm NOx High Efficiency Commercial Gas Boilers Up to 97% Thermal Efficiency 1.5, 1.7 & 2.0 Million Btu/hr Less than 20ppm NOx Variable Frequency Drive Lets You Change Output to Match Demand Intelli-Fin is the

More information

PART 5 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL

PART 5 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL 28 2. Connect DHW (domestic hot water) piping to indirect storage water heater. L. ZONING WITH CIRCULATORS 1. Connect the boiler to the system when using circulator zoning as shown in Boiler Piping Details.

More information

XLP POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: XPN

XLP POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: XPN XLP POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: XPN 399 800 XLP Pool Package The XLP pool package system is a high efficiency commercial condensing boiler, pre-piped package system from the factory

More information

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER A steam boiler has been built and installed at a factory for the provision of process steam. The following lists the requirements used in the commissioning

More information

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459 SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR The heat transfer innovators. THE RELIANCE COPPER FINNED TUBE HYDRONIC BOILER FEATURES Copper Fin-Tube Heat Exchanger Up to 88% Thermal

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

Originators of the Flexible Water Tube design

Originators of the Flexible Water Tube design BRYAN FLEXIBLE WATER TUBE AB SERIES STEAM AND WATER BOILER 900,000 TO 3,000,000 BTUH FORCED DRAFT GAS, OIL OR DUAL FUEL FIRED Water Boiler AB120-W-FDGO Steam Boiler AB250-S-150-FDG Originators of the Flexible

More information

JACKET/FRAME ASSEMBLY See page 4

JACKET/FRAME ASSEMBLY See page 4 PSD-3-148 WIRING/HARNESS & PROBES See page 8 PROPANE GAS TRAIN ASSEMBLY See page 6 COMMERCIAL POWER BURNER BOILER REPLACEMENT PARTS LIST COPPER BOILERS FOR HYDRONIC HEATING & HOT WATER SUPPLY LEGEND MODELS

More information

BRAVA small size, big performance

BRAVA small size, big performance BRAVA small size, big performance www.sime.it BRAVA: small size, big performance Brava Slim and Brava One are part of a new generation wall hung boilers, particularly compact and functional. They represent

More information

Replacement parts. SlimFit COMMERCIAL CONDENSING GAS-FIRED WATER BOILER Boiler Manual. Vent/air piping components

Replacement parts. SlimFit COMMERCIAL CONDENSING GAS-FIRED WATER BOILER Boiler Manual. Vent/air piping components Replacement parts Replacement parts must be purchased through a local Weil-McLain distributor. When ordering, specify boiler model and size and include description and part number of replacement part.

More information

Advanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler

Advanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler Advanced Heating & Hot Water Systems A Trailblazing Energy Star Listed Boiler that Installs like a Mid-Efficiency Boiler with the Performance of a High-Efficiency Product Ultra High Efficiency Energy Star

More information

Williams & Davis Boilers

Williams & Davis Boilers Williams & Davis Boilers Established 1921 2-Pass Dry-Back Scotch Marine Boiler SIZES 15HP THROUGH 1500HP GAS, OIL OR COMBINATION BURNER FIRETUBE HOT WATER & PRESSURE STEAM BOILERS 2000D Standard Features

More information

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially

More information

F9MXE. Product Specifications

F9MXE. Product Specifications 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports

More information

COMMERCIAL GAS SERVICE PARTS LIST

COMMERCIAL GAS SERVICE PARTS LIST 125 Southeast Parkway Franklin, TN 37068 www.hotwater.com 1-800-433-2545 JACKET/FRAME ASSEMBLY SEE PAGE 2 COMMERCIAL POWER BURNER BOILER COMMERCIAL GAS SERVICE PARTS LIST COPPER BOILERS FOR HYDRONIC HEATING

More information

PART 11: START-UP PROCEDURES FOR THE INSTALLER

PART 11: START-UP PROCEDURES FOR THE INSTALLER PART 11: START-UP PROCEDURES FOR THE INSTALLER NOTICE It is important to note that the user can adjust the heat curve down by adjusting the central heating temperature to a lower setting. 212 CENTRAL HEATING

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters UP TO 96% THERMAL EFFICIENCY, DIRECT-VENT FEATURES TM BTH-120 through BTH-500 The A. O. Smith Cyclone Xi family of products represents the industry s most technologically advanced commercial water heaters.

More information

Commercial Semi-Instantaneous Water Heaters

Commercial Semi-Instantaneous Water Heaters FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

Light Duty Commercial Electric Water Heater

Light Duty Commercial Electric Water Heater Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

G9MXE. Product Specifications

G9MXE. Product Specifications Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)

More information

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers Peerless Boilers Series GM Residential/Commercial Gas Boilers The Series GM cast iron, hot water boiler is ideal for use in large residences or commercial applications. This gas-fired, atmospheric boiler

More information

Side Wall Venting Means

Side Wall Venting Means Compare These Side Wall Venting Means No Chimney/Chase More Living Space Increased Safety & Efficiency Lower Installation Costs Venting for heating appliances doesn t have to go through the roof, either

More information

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

Y-200 Multi-Stage Sequencer

Y-200 Multi-Stage Sequencer Y-200 Multi-Stage Sequencer Designed for use with single or multiple space heating or hot water supply systems, the Y-200 is offered in 4- and 8-stage configurations and is available loose or factory-mounted

More information

WAYNE COUNTY AIRPORT AUTHORITY GAS FIRED INFRARED RADIANT HEATER HANGAR 1 IR HEATING 23 55 23 / 1

WAYNE COUNTY AIRPORT AUTHORITY GAS FIRED INFRARED RADIANT HEATER HANGAR 1 IR HEATING 23 55 23 / 1 HANGAR 1 IR HEATING 23 55 23 / 1 SECTION 23 55 23 GAS FIRED INFRARED RADIANT HEATER PART 1 GENERAL 1.1 SECTION INCLUDES: A. Summary B. Related Codes and Standards C. Submittals D. Warranty 1.2 SUMMARY

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Commercial Boiler Systems and Controls

Commercial Boiler Systems and Controls Commercial Boiler Systems and Controls Condensing Non-condensing Hybrid Systems Steel Medium Mass Copper Instantaneous Electric Riverside R HYDRONICS An introduction to hybrid boiler systems What is a

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

NPE-A and NPE-S Condensing Tankless Water Heaters

NPE-A and NPE-S Condensing Tankless Water Heaters NPE-A and NPE-S Condensing Tankless Water Heaters Navien makes it easy to go tankless in residential and commercial applications. New NaviLink Wi-Fi remote control system...now available as an add-on accessory.

More information

PRESSURE AND TEMPERATURE SENSORS FOR THE E340 BOILER ROOM CONTROL

PRESSURE AND TEMPERATURE SENSORS FOR THE E340 BOILER ROOM CONTROL ES-3481 JUNE 27, 2005 PRESSURE AND TEMPERATURE SENSORS FOR THE E340 BOILER ROOM CONTROL DESCRIPTION The PS348 and TS348 Series of pressure and temperature sensors are designed for use with the E340 Boiler

More information

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION 1 2 3 4 5 Inadequate or no earth ground sensed by the Intelli-Vent control. Power supply to Intelli-Vent control has reversed polarity. Pressure switch circuit remaining closed for more than 5 seconds

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

G234X-55 Conventional Gas Boiler

G234X-55 Conventional Gas Boiler Engineering Submittal Sheet Boiler Overview C US Engineering Specifications There shall be provided and installed a quantity of Buderus G234X-55 fl oor standing hot water boiler(s), suitable with natural

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

A flat plate heat exchanger is used when the system requires isolating:

A flat plate heat exchanger is used when the system requires isolating: Technical Bulletin #4 PLUMBING CONFIGURATIONS The Frontier Series provides a steady flow of high-temperature heat transfer fluid to various devices in your hydronic heating system, including hot water

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

Service Manual Models: 80-285

Service Manual Models: 80-285 KB-SER-08 Service Manual Models: 80-285 Starting Serial #H07H10040039 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this

More information

OWNER MANUAL INSTALLATION INSTRUCTIONS

OWNER MANUAL INSTALLATION INSTRUCTIONS RIELLO BURNER SYSTEM mectron 3M TYPE 215 OWNER MANUAL INSTALLATION INSTRUCTIONS We are delighted that you have chosen the Riello burner. It is modern. clean, efficient and like any quality product. must

More information

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance

More information

Water Heaters. Solar Applications

Water Heaters. Solar Applications Water Heaters Applications Over (Optional) CEM-TROL Controller 3-way diverting valve Pump Over Bypass for Cooling Water Bypass Return STONESTEEL is a registered trademark of Cemline Corporation CEMLINE

More information

RECON WATER HEATER INSTALLATION FORM

RECON WATER HEATER INSTALLATION FORM RECON WATER HEATER INSTALLATION FORM Please complete ONE (1) form for each SITE and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM.

More information

ASME Packaged Indirect Fired Water Heater

ASME Packaged Indirect Fired Water Heater Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

Model 222S (Galvanized receiver optional) AURORA. 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS

Model 222S (Galvanized receiver optional) AURORA. 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS Model 222S (Galvanized receiver optional) AURORA 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS WWW.AURORAPUMP.COM AURORA 220 Series Single Stage Condensate and Boiler Feed Pumps 2 Introduction

More information

Chapter 2 Boiler 101: typical NYC residential heating system

Chapter 2 Boiler 101: typical NYC residential heating system Chapter 2 Boiler 101: typical NYC residential heating system One and two family homes often use forced-hot-air heating systems, which include a burner, heat exchanger and blower(s). In these types of systems,

More information

PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL

PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL 41 PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL The heater must be vented as detailed in this Venting Section. Ensure exhaust and intake piping complies with these instructions regarding vent

More information

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00 RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

FOAM SYSTEM SPECIFICATION

FOAM SYSTEM SPECIFICATION FOAM SYSTEM SPECIFICATION WET PIPE AFFF SPRINKLER SYSTEM The sprinkler system shall be a closed-head wet pipe AFFF foam water sprinkler system designed to provide adequately proportioned foam water solution

More information

Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED

Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED High Efficiency Condensing Boilers Proven Reliability, American-Made Home Heating Comfort. Look for this logo throughout this literature to see the unique features that set U.S. Boiler Company apart from

More information

Service Manual Models: 150-500

Service Manual Models: 150-500 Models: 150-500 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Armor Water Heater Installation and Operation

More information

Why Choose Navien? Navien Condensing Tankless Gas Water Heater. Ultra Condensing Efficiency. Extended Lifecycle

Why Choose Navien? Navien Condensing Tankless Gas Water Heater. Ultra Condensing Efficiency. Extended Lifecycle NRNP-082312-1.0 Navien Condensing Tankless Gas Water Heater Why Choose Navien? Navien s Technology Condensation is created inside Navien s condensing heat exchanger from incoming cold water cooling the

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for

More information

Commercial Electric Water Heater

Commercial Electric Water Heater MODEL SE Commercial Electric Water Heater 6-120 Gallon Capacity, up to 58 KW in all Three Phase Voltages, Over 6 KW in all Single Phase Voltages Features Heavy Duty Construction Hydrastone cement lining

More information

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating

More information

DESIGNER S GUIDE EFFICIENCY+ BOILER

DESIGNER S GUIDE EFFICIENCY+ BOILER DESIGNER S GUIDE EFFICIENCY+ BOILER 150,000 300,000 BTU/HR Dear Specifier/Project Manager, At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter

More information

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details

More information

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause

More information

Boiler Preparation, Start-Up and Shutdown

Boiler Preparation, Start-Up and Shutdown Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717 Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717 The first truly integrated mixed control system that communicates directly to the Munchkin Boiler. USING THIS MANUAL USING THIS MANUAL

More information

INSTALLATION OPERATION AND SERVICE MANUAL

INSTALLATION OPERATION AND SERVICE MANUAL INSTALLATION OPERATION AND SERVICE MANUAL GAS FIRED WALL HUNG & FLOOR MOUNT RESIDENTIAL COMMERCIAL STAINLESS STEEL BOILERS DynaMax SERIES HYDRONIC HEATING Models; DMH081, 101, 151, 201, 251, 211, 261,

More information

Safety & Installation Instructions

Safety & Installation Instructions 8400 Series Thermostats Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61000652D 8400 Tstat Install.indd 1 Table of contents Installation Installation location recommendations... 3

More information

AC Electrical System Tests Sign-Off Sheet. STEP Initials Date

AC Electrical System Tests Sign-Off Sheet. STEP Initials Date AC Electrical System Tests Hot Skin Test Prepare Documentation? Make sure shore line is plugged into 120VAC source? Set VOM to AC voltage scale? Place one probe on a bare metal surface of the RV (i.e.,

More information

OTF Oil Fired Pool Heater

OTF Oil Fired Pool Heater OTF Oil Fired Pool Heater Installation Operation Maintenance Manual Service Policy 722010 Congratulations on the purchase of your new pool heater. In order to maintain peak performance of your pool heater

More information

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.

More information

Vitodens 200, B2HA / B2HB - Product Introduction

Vitodens 200, B2HA / B2HB - Product Introduction - Product Introduction Foil 2, 10/2015 Viessmann Manufacturing Wall Mounted, Gas-Fired Condensing Boiler Foil 3, 10/2015 Viessmann Manufacturing A member of the Viessmann family of heating products Condensing

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty

One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable

More information

High efficiency, cast-iron gas boiler

High efficiency, cast-iron gas boiler SENTRY High efficiency, cast-iron gas boiler LOWER PROFILE MAKES PROBLEM INSTALLATIONS EASY SENTRY High efficiency, cast-iron gas boiler A smarter choice for informed The boiler you choose for your home

More information

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions

More information

CL - STANDARD SPEC 1: COOLING WATER FILTER

CL - STANDARD SPEC 1: COOLING WATER FILTER CL - STANDARD SPEC 1: COOLING WATER FILTER CLOSED LOOP HOT AND CHILLED WATER SYSTEM, PROCESS WATER SYSTEM A. GENERAL Contractor shall furnish and install a high efficiency media filtration system rated

More information

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change

More information

Parker Indirect Fired Hot Water Boiler

Parker Indirect Fired Hot Water Boiler Parker Indirect Fired Hot Water Boiler Mfg: Parker Model: WH-970 Stock No. CGCB074.1 Serial No. Parker Indirect Fired Hot Water Boiler. Model: WH-970. MAWP: 125 psi., heating surface: 103.5 sq. ft. Horse

More information

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications

SECTION 15 Enclosed Adjustable Frequency Drive Variable Torque HVAC and Pumping Applications Product Name: Enclosed Adjustable Frequency Drive - Class 8839 E-Flex AC Drive for Variable Torque HVAC and Pumping Applications (1-100 hp, 460 V and 1-50 hp, 208/230 V) SECTION 15 Enclosed Adjustable

More information

MODEL AC-SCC-1 INSTALLATION, OPERATION & MAINTENANCE MANUAL

MODEL AC-SCC-1 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIM2-0413 W30-AC0056 MODEL AC-SCC-1 INSTALLATION, OPERATION & MAINTENANCE MANUAL Single-zone Hydronic Chiller Interface Module SECTION 1: INTRODUCTION Unit description... 5 Location... 5 Handling... 5

More information