Transcription
1 Suite 03.04, 55 Miller Street Pyrmont NSW 2009 Phone: Fax: BUILDING CODE COMPLIANCE ASSESSMENT REPORT REPORT NO 3081-REV02 DATE 8 APRIL 2011 PREPARED FOR ELEPHANTS FOOT GARBAGE COMPACTORS PTY LTD PREPARED BY AE&D
2 C O N T E N T S Executive Summary Introduction BCA Assessment Data BCA Assessment & Recommendations Conclusion Appendix A CSIRO Report FSP Appendix B CSIRO materials test FNE Appendix C Ventilation Requirements from AS REVISION STATUS REPORT NO & REVISION DATE STATUS WRITTEN CHECKED REV ISSUED CH TJ COMMERCIAL IN CONFIDENCE This document contains confidential material that is intended solely for the client commissioning AE&D to prepare this report. The client, project team and all regulatory authorities shall exercise precautionary measures to ensure that the information contained herein is not to be accessed by any third party. AE&D will take no responsibility for the use of any information contained within this report by any third party, unless AE&D s permission is requested and provided in writing. 2
3 E X E C U T I V E S U M M A R Y This report has assessed the Elephants Foot Compactors garbage linen chutes under the provisions of the Building Code of Australia 2010 (BCA) 1, where it has been determined that the proposed design of the Elephants Foot Garbage chute constructed from Alkatuff LL711UV linear low density polyethylene plastic complies to the deemed-to-satisfy (DTS) provisions of the BCA. A summary is detailed in the following table. BCA PROVISIONS FOR # BCA Requirements Outcome 1. SPRINKLER PROVISIONS The chute design must have provisions for sprinkler protection at every second hopper door on a level by level basis in addition to a sprinkler at the head of the chute in accordance with AS Automatic fire sprinkler systems provide a building with a high level of protection for both the occupants and environment against a major structural fire. Sprinklers also protect against major structural damage to a building and make a return to normal operations following a fire possible. Pass Pending provisions have been made for sprinklers at every 2 nd level on a floor by floor basis, in addition to a sprinkler provision at the head of the chute. 2. FIRE RATING OF SELF CLOSING HOPPER DOORSETS The hopper doorsets to be installed within a building of Type A construction requires that the chute system must be of non-combustible construction if the shaft is a garbage shaft and have a FRL of not less than -/60/30 if providing access to a ventilating, pipe or other service shaft as detailed in C3.13(d) and C3.13(b) of the BCA. Pass Hopper Doorsets have FRL of -/120/30 The hopper doorsets are non-combustible. 3. FIRE HAZARD PROPERTIES From the BCA C1.10 and Specification C1.10, materials used in construction of the chute must have: a spread of flame index not more than 9 and a smoke-developed index not more than 8 if the spread of flame index is more than 5. Pass Spread of flame = 7 Smoke-Developed Index = 5 4. FIRE RATING OF SURROUNDING BUILDING ELEMENTS The shaft around the chute must have a fire resistance level of at least that detailed in C1.1 and Specification C1.1 of the BCA. Chute to be installed into shaft with FRL as set out in C1.1 and Specification C1.1 of the BCA. 1 Australian Building Codes Board. Building Code of Australia AS Australian Standard. Automatic fire sprinkler systems Part 1: General requirements 3
4 BCA PROVISIONS FOR # BCA Requirements Outcome 5. VENTILATION The requirements F4.5 of the BCA state that the Garbage/linen room where the chute dispenses must be adequately ventilated in accordance with AS Ventilation to be provided to garbage/laundry rooms as follows: Garbage rooms 5.0 L/s per m 2 of floor area (requirement) L/s for each floor level in the building (recommendation) Laundry Rooms Commercial or Hospital L/s per m 2 of floor area Residential 20L/s per laundry room Exhaust Fan at head of chute fitted with damper with FRL of at least -/60/- Make-up air paths to be provided to garbage/laundry rooms 3 AS Australian Standard. The use of mechanical ventilation and air-conditioning in buildings, Part 2: Mechanical ventilation for acceptable indoor-air quality 4
5 1. 0 I N T R O D U C T I O N AE&D has been commissioned by Elephants Foot Waste Compactors to determine if a proposed plastic garbage/linen chute complies with the provisions of the BCA. Additionally, the ventilation requirements of the garbage/linen room will be assessed and outlined in accordance with the BCA and relevant Australian Standards. It is the intention of Elephants Foot Garbage Compactors Pty Ltd to install these chute systems in sprinkler protected high rise buildings in compliance with the guidelines set out in the BCA B a s i s o f R e p o r t The key basis of this report is to address compliance with the significant requirements of the Building Code of Australia (BCA) 2010 as relevant to the new garbage/linen chute system. The scope of services is limited to, Section C - Fire Resistance, Section E- Services and Equipment and Section F - Health and Amenity of the BCA. This report is based on a desktop assessment of the following: CSIRO Report FSP1443 Fire Resistance on a Self-Closing Hopper Doorset. Elephants Foot Garbage chute. Appendix A CSIRO materials test FNE9701 Simultaneous Determination of Ignitability, Flame Propagation, Heat Release and Smoke Release on the Elephants Foot garbage chute material. Appendix B The Building Code of Australia 2010 (BCA), prepared by the Australian Building Codes Board. The Guide to the BCA 2010, prepared by the Australian Building Codes Board R e g u l a t o r y B a s i s o f t h e R e p o r t The assessment of BCA compliance is subject to the following basis, where this application of compliance is consistent with the requirement of sprinkler provisions, fire rating of hopper doorsets, fire rating of the chute and building elements surrounding the chute and ventilation requirements. These requirements are detailed in the following table. BCA PROVISIONS FOR # Recommendation Type & Action Required BCA Requirements 1. Regulatory SPRINKLER PROVISIONS The chute design must have provisions for sprinkler protection at every second hopper door on a level by level basis in addition to a sprinkler at the head of the chute in accordance with AS Regulatory FIRE RATING OF SELF CLOSING HOPPER DOORSETS The hopper doorsets to be installed in the chute system must have a FRL of not less than -/60/30 (for linen chutes) or be of non-combustible construction (for garbage chutes) to comply with C3.13(b) and C3.13(d) in the BCA. 5
6 BCA PROVISIONS FOR # Recommendation Type & Action Required BCA Requirements 3. Regulatory FIRE HAZARD PROPERTIES From the BCA C1.10 and Specification C1.10, materials used in construction of the chute must have: a spread of flame index not more than 9 and a smoke-developed index not more than 8 if the spread of flame index is more than Regulatory FIRE RATING OF SURROUNDING BUILDING ELEMENTS The shaft around the chute must be have a FRL as detailed in C1.1 and Specification C1.1 of the BCA. 5. Regulatory VENTILATION The requirements of clause F4.5 of the BCA state that the garbage/linen rooms where the chute system dispenses must be adequately ventilated in accordance with AS For garbage rooms the ventilation required is 5L/s per m 2 of floor area. For laundry s in commercial or hospital buildings the ventilation required is 15L/s per m 2 of floor area while in residential buildings the ventilation required for a laundry room is 20L/s P u r p o s e o f t h e R e p o r t The purpose of this report is to assess the following: Assessment of the new garbage/linen chute under the current Building Code of Australia 2010 and detail any significant departures from the BCA2010; Provide recommendations to best address any significant departures from the requirements of BCA 2010 that are contained in, or caused by the proposed design L i m i t a t i o n s o f t h e R e p o r t The report is limited to a desktop assessment of the specified Elephants Foot Chute system only and does not constitute assessment of any existing buildings or site limitations in any way. Assessment is strictly limited to those works that have specifically been nominated within assessed documentation detailed in Section 1.1 of this report. Access and facilities for people with disabilities is addressed however compliance with Disability Discrimination Act 1992 (DDA) is outside the scope of this report. It should be noted that BCA compliance does not necessarily meet the requirements of the Disability Discrimination Act (DDA). Reporting on hazardous materials, OH&S matters or site contamination Assessment of any structural elements or geotechnical matters relating to the building, including any structural or other assessment of the existing fire resistant levels of the building Consideration of any fire services operations (including hydraulic, electrical or other systems) Assessment of plumbing and drainage installations, including stormwater Assessment of mechanical plant operations, electrical systems or security systems Heritage significance Consideration of energy or water authority requirements 6
7 Consideration of Council s local planning policies Environmental or planning issues Requirements of statutory authorities Pest inspection or assessment building damage caused by pests (general/visual pest invasion or damage will be reported, however invasive or intrusive inspections have not be carried out) Provision of any construction approvals or certification under Part 4A or Part 5 of the Environmental Planning & Assessment Act Determining compliance of any as installed systems. 7
8 2. 0 B C A A S S E S S M E N T D A T A This section details the relevant BCA assessment data to the proposal under the current Building Code of Australia. CSIRO have been commissioned by Elephants Foot Garbage Compactors to perform the fire hazard property tests on the chute material and the fire resistance tests on the hopper doorsets. The chute design assessment is based on these test results. The CSIRO reports are reproduced in Appendix A- Fire Hazard Properties of Chute Material and Appendix B- Fire Resistance of Hopper Doorsets of this report C h u t e D e s i g n A s s e s s m e n t Elephants Foot Garbage Compactors have developed a garbage/linen chute constructed of Alkatuff LL711UV linear low density black polyethylene plastic having a nominal thickness of 5mm and a nominal total mass of 938 kg/m 3. The specific BCA requirements of the chute design are detailed in section 1.2 of this report. The schematics of the chute system are represented below. According to the BCA clause E1.5, a high rise building with an effective height of more than 25m requires sprinkler protection and would need to be Type A construction. The provision of sprinklers is based on AS , where in high rise buildings sprinklers must be protected internally at every second hopper door on a floor by floor basis in addition to a sprinkler at the head of the chute. The proposed chute design complies with these requirements. The fire resistance of the self closing hopper doors in the proposed design were tested by the CSIRO resulting in a FRL of at least -/120/30 (see Appendix A), which complies with BCA Clause C3.13(b). The hopper doors are constructed from 30mm thick MAXI-LITE panel faced on both sides by 1.6mm thick panels of 250 grade mild steel sheet. Therefore the hopper door complies with BCA Clause C3.13(d) for openings in shafts. The chute system has been subjected to the fire hazard property tests in accordance with BCA clause C1.10 and Specification C1.10, which requires tests to be carried out in accordance with AS (see Appendix B). It was determined from this assessment that the chute material had a spread of flame index of 7 and a smoke developed index of 5, in compliance with BCA C1.10 and Specification C1.10. The chute must be located within a shaft that complies with the BCA requirements for fire resistance as defined in Clause C1.1 and Specification C AS , Australian Standard. Methods for fire tests on building materials, components and structures. Simultaneous determination of ignitability, flame propagation, heat release and smoke release. 8
9 Schematics of the Elephants foot chute system 9
10 2. 2 G a r b a g e r o o m V e n t i l a t i o n The proposed chute is to dispense into an associated garbage room and according to the BCA Clause F4.5, any room occupied by any person must have either natural ventilation or a mechanical ventilation system complying with AS (see table in Appendix C). While the garbage room is not frequently occupied, ventilation must be provided in accordance with the requirements of the BCA and will also act to remove odours from the garbage area. The requirements for ventilation in a garbage room is a flow rate of 5 L/s per m 2 of floor area. If the chute is to be used as a linen chute that dispenses into a laundry then the ventilation required would be 15 L/s per m 2 of floor area in a commercial or hospital laundry or 20 L/s for a residential building. For this particular chute system the following recommendations are proposed to ensure adequate ventilation: Garbage rooms must be ventilated to produce a minimum of 5 L/s per m 2, where it is also recommended that additional 5L/s per level in the building be provided to ensure adequate ventilation. i.e. Recommended ventilation = 5 L/s per m 2 of garbage room floor area + (5L/s x Number of levels in building). Laundry rooms in commercial or hospital buildings must be ventilated to produce a minimum of 15L/s per m 2 of laundry floor area. Laundry rooms in a residential building must be ventilated to produce a minimum of 20L/s per laundry room. Suitable provisions for make-up air paths would need to be provided into the garbage/laundry rooms. 10
11 3. 0 B C A C O M P L I A N C E A S S E S S M E N T & R E C O M M E N D A T I O N S The following table identifies the requirements of the Building Code of Australia for the proposed garbage/linen chute design. BCA PROVISIONS FOR # BCA Requirements Outcome 1. SPRINKLER PROVISIONS The chute design must have provisions for sprinkler protection at every second hopper door on a level by level basis in addition to a sprinkler at the head of the chute in accordance with AS Automatic fire sprinkler systems provide a building with a high level of protection for both the occupants and environment against a major structural fire. Sprinklers also protect against major structural damage to a building and make a return to normal operations following a fire possible. Pass Pending provisions have been made for sprinklers at every 2 nd level on a floor by floor basis, in addition to a sprinkler provision at the head of the chute. 2. FIRE RATING OF SELF CLOSING HOPPER DOORSETS The hopper doorsets to be installed within a building of Type A construction requires that the chute system must be of non-combustible construction if the shaft is a garbage shaft and have a FRL of not less than -/60/30 if providing access to a ventilating, pipe or other service shaft as detailed in C3.13(d) and C3.13(b) of the BCA. Pass Hopper Doorsets have FRL of -/120/30 The hopper doorsets are non-combustible. 3. FIRE HAZARD PROPERTIES From the BCA C1.10 and Specification C1.10, materials used in construction of the chute must have: a spread of flame index not more than 9 and a smoke-developed index not more than 8 if the spread of flame index is more than 5. Pass Spread of flame = 7 Smoke-Developed Index = 5 4. FIRE RATING OF SURROUNDING BUILDING ELEMENTS The shaft around the chute must be have a fire resistance level of at least that detailed in C1.1 and Specification C1.1 of the BCA. Chute to be installed into shaft with FRL as set out in C1.1 and Specification C1.1 of the BCA. 5 AS Australian Standard. Automatic fire sprinkler systems Part 1: General requirements 11
12 BCA PROVISIONS FOR # BCA Requirements Outcome 5. VENTILATION The requirements F4.5 of the BCA state that the Garbage/linen room where the chute dispenses must be adequately ventilated in accordance with AS Ventilation to be provided to garbage/laundry rooms as follows: Garbage rooms 5.0 L/s per m 2 of floor area (requirement) L/s for each floor level in the building (recommendation) Laundry Rooms Commercial or Hospital L/s per m 2 of floor area Residential 20L/s per laundry room Exhaust Fan at head of chute fitted with damper with FRL of at least -/60/- Make-up air paths to be provided to garbage/laundry rooms 12
13 4. 0 C O N C L U S I O N This report has assessed the compliance of the Elephants Foot Garbage/linen chute design with the BCA s regulatory requirements and it has been determined that the design is considered to be at a sufficient level to demonstrate compliance with the BCA Deemed-To-Satisfy provisions, and thus certification confirming that the design documentation complies will be issued by AE&D. Provided that the Alkatuff LL711UV linear low density polyethylene chute being contained in a suitably fire rated shaft, is fitted with hopper doors that have a minimum FRL of -/120/30 and sprinkler protection is provided in accordance with Clause E1.5 in the BCA and AS when necessary. Provisions must be made for adequate ventilation of the garbage/linen rooms where the chute dispenses as is detailed in section 2.2 of this report. Report By: Reviewed By: Clynton Halstead for AE&D Nathan Halstead for AE&D B Medicinal Chemistry (Hons- First Class) PhD - Phytochemistry and Analytical Chemistry MAIBS, Grad Dip Fire Eng (VU), M Build Surv (UWS) Accredited Certifier / Principal Certifying Authority (Building) - Grade A1 AIBS National - Accredited Building Surveyor 13
14 A P P E N D I X A CSIRO Report FSP1443 Fire Resistance on a Self-Closing Hopper Doorset. Elephants Foot Garbage Chute 14
15 A P P E N D I X B CSIRO materials test FNE9701 Simultaneous Determination of Ignitability, Flame Propagation, Heat Release and Smoke Release on the Elephants Foot garbage chute material 15
16 A P P E N D I X C Ventilation Requirements from AS
Australian/New Zealand Standard
Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The
More informationOverview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationFLOODS FACT SHEET ADVICE FOR RESIDENTS Approvals for repairing, renovating or rebuilding flood-affected houses
2 February 2011 Updated 16 March 2011 FLOODS FACT SHEET ADVICE FOR RESIDENTS Approvals for repairing, renovating or rebuilding flood-affected houses This fact sheet provides advice for residents about
More informationDecree of the Ministry of the Environment on fire safety of ventilation systems
THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18
More informationInformation Bulletin. Sprinkler System Component Fault Monitoring. Version 1.1 Approved for release September 2013
Version 1.1 Approved for release September 2013 Table of contents 1.0 Purpose Statement... 3 2.0 Audience... 3 3.0 Why is sprinkler system component fault monitoring important?... 3 4.0 Communication of
More informationLPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market
LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market Ian Stewart Passive installer scheme manager September 2011 Introduction to BRE Global Research,
More informationPractice Note 2014-62
Practice Note 2014-62 Documentation Required for Applications for Building Permits Reference to the Building Code of Australia (BCA) in this Practice Note means Volume One and Volume Two of the National
More informationFire-resistance test on fire collars protecting a concrete slab penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1614 Date: 14 February 2014 Client:
More informationBUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
More informationNew Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
More informationRHODE ISLAND. Downloaded 01.15.11
Housekeeping/Laundry/Maintenance Section 35.0 Housekeeping RHODE ISLAND Downloaded 01.15.11 35.1 A full time employee of the facility shall be designated responsible for housekeeping services, supervision
More informationGuidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
More informationWe hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
More informationThe risk assessment of fire damper installations
The risk assessment of fire damper installations June 2010 Paul White OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationGuidance on loft conversions in two-storey houses
Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for
More informationHealth Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More informationNational Archives and Records Administration (NARA) Facility Standards for Federal Records Storage Facilities
National Archives and Records Administration (NARA) Facility Standards for Federal Records Storage Facilities A quick overview of what Federal Records Officers need to know about: What the Records Storage
More informationPractice Note for Authorized Persons, Buildings Department Registered Structural Engineers and APP-13 Registered Geotechnical Engineers
Practice Note for Authorized Persons, Buildings Department Registered Structural Engineers and APP-13 Registered Geotechnical Engineers Submission of Certificate of Completion of Building Works Application
More informationServices Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationCapital Development Guideline. 7. 6 Fire risk management for hospitals
Capital Development Guideline 7. 6 Fire risk management for hospitals Department of Human Services Capital Management Branch 2008 Acknowledgments Copyright State of Victoria 2008. Published by the Capital
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationProject Building Permit No. One complete set of Record or as-built drawings (electronic) One complete set of Record or as-built drawings (hard copy)
University at Albany, State University of New York Office of Facilities Management Code Administration Certificate of Occupancy/Compliance Records Checklist On-site Inspection Items Not Included Project
More informationWASTE STORAGE AND COLLECTION GUIDANCE FOR NEW DEVELOPMENTS
WASTE STORAGE AND COLLECTION GUIDANCE FOR NEW DEVELOPMENTS CONTENTS Page 1 Introduction 2 2 Planning Applications 3 3 Internal Segregation of Waste 3 4 Housing Developments 4 5 Apartment Developments 5-6
More informationWHS LEGISLATIVE COMPLIANCE GUIDELINES
WHS LEGISLATIVE COMPLIANCE GUIDELINES CONTENTS 1 Introduction... 2 2 Scope... 2 3 Responsibilities... 2 3.1 Manager WHS Unit... 2 3.2 Management of Faculties, Divisions and Research Institutes... 2 4 Maintaining
More informationGENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)
GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft
More informationLIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
More informationAn inventory of hazardous materials used in your workplace will prove useful.
Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the
More informationpresents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
More informationBuilding Permit Information House Relocation
Building Permit Information House Relocation About private Building Surveyors Until about 1992 all building permits were issued by Councils. This function was then privatised, and while many Councils still
More informationCIS Asset Identification and Labelling Standard
CIS Asset Identification and Labelling Standard The University of Sydney Engineering & Sustainability Team Document Control Document Name: CIS Asset Identification and Labelling Standard Document ID: CIS-PLA-STD-Asset
More informationFire Prevention Plan for Commons 1655 Musketeer Drive
Commons for Commons 1655 Musketeer Drive Xavier University November 7, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace Fire Hazards... 3 Methods
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More informationInstallation Instructions
Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email info@pecan-eng.com.au Phone:
More informationDenver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12
Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.
More information- 5 - Table1. Maximum Compartment Volumes
- 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,
More informationBuilding Control Guidance Note
Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you
More informationExhibit B. Property Acquisition and Disposition Division Residential Design & Performance Standards
Exhibit B Property Acquisition and Disposition Division Residential Design & Performance Standards I. Introduction The Property Acquisition and Disposition Division ( PADD ) has developed design standards
More informationADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
More informationSample Written Program. For. Flammable Liquids
Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and
More informationDUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
More informationSPECIFICATIONS FOR APPROVED OFFSITE RECORDS STORAGE FACILITIES
1. Bonding and Insurance 2. Facilities (including equipment and materiel e.g., shelving, pallets, containers and other internal fixtures and contents) The storage facility company must be bonded and insured.
More informationPMS Reflex Blue C Mining PMS 8401C
PMS Reflex Blue C ing PMS 8401C About Poly Pipe Pty Ltd Located in the Hunter Valley, NSW, Australia, Poly Pipe Pty Ltd (Poly Pipe) has an ultra modern extrusion, high tech manufacturing facility. It supplies
More informationSTARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS
STARTING A NEW FOOD BUSINESS? GUIDELINES FOR OPENING A CLASS 3 FOOD BUSINESS Updated: July 2010 Contents Procedure for opening a new Food Business... 2 Basic Records... 3 Summary - Construction and Fitout
More informationProposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
More informationRelease: 1. CPCCBS6010 Conduct and report on building surveying audits of residential buildings up to three storeys
Release: 1 CPCCBS6010 Conduct and report on building surveying audits of residential buildings up to three storeys CPCCBS6010 Conduct and report on building surveying audits of residential buildings up
More informationCHAPTER 6 DUCT SYSTEMS
CHAPTER 6 DUCT SYSTEMS SECTION MC 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this
More informationINFORMATION HANDBOOK. Applying energy efficiency provisions to new building work associated with existing Class 2 to 9 buildings
INFORMATION HANDBOOK Applying energy efficiency provisions to new building work associated with existing Class 2 to 9 buildings 2010 Applying energy efficiency provisions to new buildings work associated
More informationfire separating walls #2
210108 fire separating walls #2 ISSUE BSA has identified a number of instances of defective fire separating walls in duplexes, town houses and multi-residential complexes. The system of fire separating
More informationPROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings Version 2006.1 AUSTRALIAN BUILDING CODES BOARD JANUARY 2006 TABLE OF CONTENTS Foreword 1. Scope 2. Purpose and context
More informationEnclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: sales@durasystems.com. The Passive Fire Protection Specialists
Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals
More informationAdditional Services Agreement. Part 3: Schedule of our requirements
Additional Services Agreement Part 3: Schedule of our requirements Schedule of our requirements Part A Water Services 1 All water services All connections to our water mains, including those used for construction
More informationPollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2
Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,
More informationTechnical Specification Fire Blanket Firemaster Fire Protection-Cables Tray Fire Protection Department
INABENSA INABENSA Technical Specification Fire Blanket Firemaster Fire Protection-Cables Tray Fire Protection Department Blanket is a non-combustible flexible blanket made by alkaline earth silicate fibers,
More informationUCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
More informationPlumbing Code of Australia
Plumbing Code of Australia Comments on the draft PCA should be sent to: National Plumbing Regulators Forum C/O Plumbing Industry Commission PO Box 360 Caulfield East VIC 3145 Australia or Fax to: (03)
More informationSUPPLEMENTAL TERMS AND CONDITIONS TO STATE FORM SC-5.1TC ARCHITECT/ENGINEER AGREEMENT TERMS AND CONDITIONS DESIGN/BID/BUILD
ATTACHMENT 2 UNIVERSITY OF COLORADO BOULDER SUPPLEMENTAL TERMS AND CONDITIONS TO STATE FORM SC-5.1TC ARCHITECT/ENGINEER AGREEMENT TERMS AND CONDITIONS DESIGN/BID/BUILD Table of Contents, Exhibits Delete
More informationTG 105 ALLOWABLE PIPE SIZE, CLASS AND MATERIALS FOR WATER MAINS TECHNICAL GUIDELINE. Manager Asset Management SOUTH AUSTRALIAN WATER CORPORATION
TG 105 SOUTH AUSTRALIAN WATER CORPORATION TECHNICAL GUIDELINE ALLOWABLE PIPE SIZE, CLASS AND MATERIALS FOR WATER MAINS Issued by: Manager Asset Management Issue Date: SA WATER 2007 This document is copyright
More informationSTATE OF SOUTH CAROLINA RESIDENTIAL PROPERTY CONDITION DISCLOSURE STATEMENT
STATE OF SOUTH CAROLINA RESIDENTIAL PROPERTY CONDITION DISCLOSURE STATEMENT The South Carolina Code of Laws (Title 27, Chapter 50, Article 1) requires that an owner of residential real property (single
More informationCHILD CARE CENTER INFORMATION SHEET
CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It
More informationCommercial Building Permit Application & Submittal Guidelines
Building Inspection Department 1625 13 th Street, Suite 106 Lubbock, Texas 79457 (806) 775-2087 (806) 775-2088 http://buildinsp.ci.lubbock.tx.us/ Commercial Building Permit Application & Submittal Guidelines
More information2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More informationA Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
More informationMINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
More informationComposite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
More informationFire Prevention Plan for Flynn Hall 1648 Musketeer Drive
Audit and Risk Management and Xavier Police Fire Prevention Plan for Flynn Hall 1648 Musketeer Drive Xavier University October 12, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Fire Prevention
More informationStatic Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
More informationTYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
More informationFIRE SAFETY INFORMATION FACT SHEET
Disclaimers: This information was believed to be correct at the date of its publication. This information is for general information purposes only and should not be relied upon for legal advice. FIRE SAFETY
More informationSPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
More informationUnderwriting Guidelines for Condominium Pac and Condominium Pac Plus
UNDERWRITING GUIDELINES FOR CONDOMINIUMS SEGMENT Local exceptions to these underwriting guidelines may apply. Please consult with your underwriter or sales executive for details and to discuss risks which
More informationAi Group Submission. in response to the. ACCC Consultation on Evaporative Air Conditioners in Bushfire Prone Zones
Ai Group Submission in response to the ACCC Consultation on Evaporative Air Conditioners in Bushfire Prone Zones May 2012 EXECUTIVE SUMMARY The Australian Industry Group (Ai Group) welcomes the opportunity
More information07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
More informationBUILDING OR RENOVATING
A GUIDE TO BUILDING OR RENOVATING YOUR IDEAL HOME building work? What records should I keep? Is insurance required? W I need approval for? What do I need approval for? How do I obtain building work? How
More informationFire safety ONLINE VERSION APPROVED DOCUMENT VOLUME 2 BUILDINGS OTHER THAN DWELLINGHOUSES ONLINE VERSION. The Building Regulations 2010
Building Regulations 2010 Published by NBS, part of RIBA Enterprises Ltd, and available to purchase from: RIBA Bookshops Mail Order The Old Post Office, St Nicholas Street, Newcastle Upon Tyne, NE1 1RH
More informationThe New Life Safety Chapter What It Applies to and How Organizations Can Comply with It
The New Life Safety Chapter What It Applies to and How Organizations Can Comply with It The Joint Commission requires health care organizations to comply with the Life Safety Code * to help ensure fire
More informationCommercial Applications
Commercial Applications Introduction This guide is designed to provide information for owners applying for Building Consent to carry out building work on an industrial or commercial site. General information
More informationInsulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW
Insulated Roof & Wall Panels Trapezoidal Insulated Roof Panels KS1000 RW Overview Kingspan roof panel systems present a superior system compared to conventional multi-part site assembled systems. They
More informationHow To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
More informationDisaster Prevention and Protection Checklist
Preservation Services Leaflet 1438 West Peachtree Street, Suite 200/Atlanta, GA 30309 Phone: 404-892-0943/Fax: 404-892-7879 Website: Disaster Prevention and Protection Checklist The inspection
More informationRC44. for fire risk assessment of catering extract ventilation
Catering extract 17/10/06 15:45 Page 1 RC44 for fire risk assessment of catering extract ventilation IMPORTANT NOTICE This document has been developed through the Insurers Fire Research Strategy scheme
More informationBuilding Services Engineering Technician
Building Services Engineering Technician A competent Building Services Engineering Technician is expected to be able to demonstrate the following skills and competences: Systems design in the building
More informationFebruary 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities
FIRE CODE VARIANCE February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5 ISSUE: Fire Safety and Hand Hygiene in Healthcare Facilities This Variance covers alcohol based hand hygiene products used in healthcare
More informationNew Zealand Fire Service. Design Review Unit. Audit
New Zealand Fire Service Design Review Unit Audit by Ian Thomas Director, CESARE Victoria University, Melbourne, Australia New Zealand Fire Service Design Review Unit Audit Executive Summary This audit
More informationMansion on Bourke. 2 Mansion on Bourke Case Study S E R V I C E D A P A R T M E N T S
C A S E S T U D Y Mansion on Bourke S E R V I C E D A P A R T M E N T S Mansion on Bourke Mansion on Bourke is a 63 unit apartment complex in Melbourne s central business district at 151-163 Bourke Street.
More informationSpray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
More informationHigh Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications
International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications
More informationHomeland Insurance Company of New York York Insurance Company of Maine
Homeland Insurance Company of New York York Insurance Company of Maine LONG TERM CARE ORGANIZATION PROFESSIONAL AND GENERAL LIABILITY RENEWAL APPLICATION NOTICE: CERTAIN COVERAGE PARTS OF THE POLICY WHICH
More informationDRY CLEANING PLANTS REQUIREMENTS FOR INSTALLATION AND OPERATION
DEPARTMENT OF TRADE MERCHANT SHIPPING NOTICE NO.M.847 DRY CLEANING PLANTS REQUIREMENTS FOR INSTALLATION AND OPERATION Notice to Shipowners, Masters, Shipbuilders and Repairers 1. It has come to the notice
More informationStatic Spark Ignites Flammable Liquid during Portable Tank Filling Operation
Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation No. 2008-02-I-IA (September 2008) Key Lessons for Safe Handling and Storage of Flammables Ensure that equipment, such as fill
More informationCity of Peterborough
City of Peterborough Building Division Basement Finishing Guide Residential Information Guides This information is intended to be used as an guide that outlines minimum requirements when finishing a basement,
More informationConcealed Door Closers
Concealed Door Closers We take the worry out of protecting what s valuable to you. Lockwood: no worries www.lockweb.com.au We take the worry out of protecting what s valuable to you. Lockwood: no worries
More informationPractice Note 2006-27
Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two
More informationFIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
More informationHEAVY DUTY STORAGE GAS
Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many
More information