SECTION TRANSIENT VOLTAGE SURGE SUPPRESSORS

Size: px
Start display at page:

Download "SECTION 16709 - TRANSIENT VOLTAGE SURGE SUPPRESSORS"

Transcription

1 SECTION TRANSIENT VOLTAGE SURGE SUPPRESSORS PART 1 - GENERAL 1.01 DESCRIPTION A. Surge Suppressors for AC Power Systems B. Surge Suppressors Communication Circuits 1.02 RELATED WORK A. Section 16110: Raceways and Conduits 1.03 APPLICABLE PUBLICATIONS A. General: The latest edition of the following standards and publications shall apply to the work of this section; 1. ANSI/IEEE C62.33 IEEE Standard Test Specifications for Varistor Surge Protective Devices. 2. ANSI/IEEE C62.35 IEEE Standard Test Specification for Avalanche Junction Semiconductor Surge Protective Devices. 3. ANSI/IEEE C62.36 IEEE Standard Test Methods for Surge Protectors Used in Low-Voltage AC Power Circuits. 4. ANSI/IEEE C62.41 IEEE Guide on Surge Testing for Equipment Connected to Low-Voltage AC Power Circuits. 5. ANSI/IEEE C62.45 Guide on Surge Testing for Equipment Connected to Low Voltage AC Power Circuits. 6. IEEE Standard Recommended Practice for Grounding 7. IEEE Standard 518 Recommended Guide on Electrical Noise 8. UL-1283 Standard for Safety - Electromagnetic Interference Filters 9. UL-1449, 2nd Edition Standard for Safety - Transient Voltage Surge Suppressors 10. NFPA 70 National Electrical Code 11. NFPA 75 Standard for Protection of Electronic Computer Systems TRANSIENT VOLTAGE SURGE SUPPRESSORS

2 1.04 SYSTEM DESCRIPTION 12. NFPA 780 Standard for the Installation of Lightning Protection Systems 13. Military Standard (MIL Std.) 220A 14. Federal Information Processing Standards (FIPS) Publication 94 a. CCITT Rec. K-17 Waveform specification for electronic systems 15. NEMA LS-1 Low Voltage Surge Protective Devices A. General: Transient voltage surge suppressor (TVSS) or Surge Protective Device (SPD) is the equipment required for the protection, within specified and tested limits, of AC electrical circuits and electronic equipment from the effects of lightning induced voltages, external switching transients and internally generated switching transients. Individual suppressors shall be provided where shown on the drawings. B. Definitions (Clauses) 1.05 SUBMITTALS A. Submit in accordance with Section 16010, Basic Electrical Requirements. B. Submit installation details for all suppressors demonstrating mechanical and electrical connections to equipment being protected. C. Submit specific test data for the actual method of installation proposed. Submittals will not be reviewed unless they include proper project related data. Interpretation of standard manufacturers published data will not be acceptable unless the data coincides with the actual installation procedure. D. Submittals shall include, but shall not be limited to, the following data; 1. Complete data for each suppressor type indicating conductor sizes, conductor types, connection configuration, lead lengths and all appropriate dimensions. 2. Dimensions for each suppressor type indicating mounting dimensions and required accessory hardware. 3. Certified test data from a nationally recognized independent testing laboratory indicating the ability of the product to meet or exceed all requirements of this specification. Tested units shall survive all testing and be fully functional without damage. TRANSIENT VOLTAGE SURGE SUPPRESSORS

3 4. If requested, a sample, which will be returned, of each suppressor type to be used shall be submitted. 5. Drawings shall be provided indicating suppressor mounting arrangement and lead length configuration, and mounting arrangement of remote diagnostic equipment and assemblies. 6. List and detail all protection systems such as fuses, disconnecting means and protective materials. 7. Documentation of type of suppression Components utilized within the TVSS to perform the rated and tested purpose. Documentation provided to UL for listing purposes is acceptable. Confidentiality agreements will be signed as required for access to this documentation. 8. Listing to UL 1449, 2nd Edition and include UL nd Edition listing/classification page verifying UL clamping voltage stated on catalog data. 9. Conformance to appropriate referenced standards and publications listed in paragraph 1.03A. 10. The submittal shall include a listed comparison and proof of compliance with each paragraph of these specifications. E. Submitted components shall comply through verified testing to the minimum and maximum values listed and shall be equal to or better than the characteristics specified herein. F. Electrical performance data shall be provided on form A included at the end of this section SUBMITTALS FOR INFORMATION A. Submit in accordance with Section 16010, Basic Electrical Requirements PROJECT CLOSEOUT SUBMITTALS A. Record actual locations of suppressors, grounding terminations, bonding connections, and routing of system conductors in project record documents. B. Installation Certification: After installation, the manufacturer shall furnish a letter indicating that the installation was inspected by a factory authorized representative, the date of inspection, date equipment was put into service, and that it meets all of the manufacturer's wiring and installation requirements. Submit three copies to the Engineer for review. TRANSIENT VOLTAGE SURGE SUPPRESSORS

4 1.08 QUALITY ASSURANCE A. Surge suppression, grounding and bonding shall effectively protect within tested limits, the systems to which applied against lightning transients, internal and external switching transients, and other surge transients throughout the useful life of the system. Surge Protective devices (SPD) and related grounding and bonding systems shall be designed and installed in such a manner that normal operation, performance ratings, and listing of the system is not impaired by the installation of such devices, wiring or connections. B. Any SPD which shows evidence of failure or incorrect operation during the ten year warranty period shall be repaired or replaced at no expense to Owner including labor and materials. Since "Acts of Nature" or similar statements include the lightning threat to which these suppression devices shall be exposed, any such general clause limiting warranty responsibility in the general conditions of this specification shall not apply to this section. The warranty shall cover the entire device not just the modules. C. Installation of SPD in or on electrical or electronic distribution systems and equipment shall in no way compromise or violate equipment listing, function, labeling, or warranty of the distribution equipment. D. All surge protective devices (SPD) and supporting components shall be guaranteed by the installing contractor to be free of defects in materials and workmanship for a period of ten years from the date of substantial completion for the system to which the SPD is attached. Suppressors or components damaged prior to substantial completion shall be replaced at no cost to the Owner QUALIFICATIONS A. Manufacturer: Company specializing in surge suppression equipment of the type herein specified with minimum ten years documented experience. B. Installer: Installation shall be by the manufacturer or a duly licensed electrical contractor FIELD MEASUREMENTS A. Verify that field measurements are as indicated on shop drawings COORDINATION A. Coordinate work with electrical installations. TRANSIENT VOLTAGE SURGE SUPPRESSORS

5 PART 2 - PRODUCTS 2.01 MANUFACTURERS A. The intent of this specification is to allow manufacturers with similar equipment utilizing silicon avalanche diode or metal oxide varistor (MOV) technology to provide transient voltage surge suppression which will adequately protect equipment within the guidelines set forth herein. B. The surge protective devices manufacturer shall offer factory repair service and replacement for all units. The manufacturer shall provide this service within four working days, and provide replacement components shipped to the Owner for installation within the allocated response time. C. Single Sources of Supply: All AC power suppressors (SPD) shall be manufactured by a single manufacturer - Transtector, PowerLogics, Advanced Protection Technology (APT), Raychem Rayvoss, Leviton, Cutler Hammer, Northern Technologies, Inc. All electronic system suppressors shall be manufactured by a single manufacturer, Transtector, Northern Technologies, EDCO, Phoenix, Polyphaser or Atlantic Scientific. Manufacturers listed herein have demonstrated that they can provide equipment that meets or exceeds all specification requirements, however other manufacturers will also be considered. Specific demonstration of meeting all specification requirements is required for any submitted equipment whether listed herein or not. TRANSIENT VOLTAGE SURGE SUPPRESSORS

6 2.02 COMPONENTS A. Main Service and Distribution Equipment Suppressors (SPD): The A.C. Voltage Surge Protective Devices shall be a high speed, high current solidstate device designed to protect electronic equipment and electrical systems from transient over voltages. It shall limit the magnitude of a transient overvoltage present on the A.C. service or distribution power lines. The suppressor shall provide continuous bi-polar, bi-directional, non-interrupting protection and be capable of instant automatic reset with no degradation in protection capabilities. Gas tubes are not acceptable. The suppressor shall be solid state, utilizing silicon junction avalanche diodes or MOV's. It shall start to suppress the transient at a minimum of 115% of the peak voltage of the sine wave. This is the Minimum Voltage Protection Level (MVPL). At maximum surge current dissipation, the device shall not exceed the maximum voltage protection level (MXVPL). The suppressor assembly shall be installed in parallel with the service main disconnect, distribution or branch panel main lugs as shown. Connect suppressor to over current protection sized as shown with an AIC rating equal to panel rating. The suppressor shall be contained in an enclosure appropriate for the environmental application in accordance with paragraph 2.02C. In addition, it shall have status indicator lights, dry contacts with remote alarm capabilities and an audible alarm. Suppressors shall be assembled as modular units to permit quick, easy replacement of failed components. Provide one spare module of each type suppressor for Owner s use. If entire suppressor is one module, provide one complete spare. 1. Electrical Service a. Voltage 480/277 VAC 120/208 VAC b. Frequency 50/60 Hz 50/60 Hz c. Phases 3 phase 3 phase d. Wiring configuration 4 wire, Wye 4 wire, Wye e. IEEE (Table 4) catagories unless otherwise indicated on the drawings: Service Entrance Sizes < 600A B3/C1 B3/C1 > 600 A to 1.2 ka C2 C2 > 1.2 ka C3 C3 Distribution or Sub panels B2 B2 f. IEEE (Table 8) 10/1000 waveform requirements. Use High Exposure level for all suppressor TRANSIENT VOLTAGE SURGE SUPPRESSORS

7 locations. 1 kv & 4 ka 0.5 kv & 2 ka 2. Electrical Performance a. Min. Voltage Protection Level 470 volts 200 volts (MVPL)(L-N) (10x1000 µsec peak peak waveform) b. Max. Voltage Protection Level 700 volts 300 volts (MXVPL)(L-N)(10x1000 µsec peak peak waveform) c. Max. Voltage Protection Level per IEEE volts 400 volts (6 & 10kV 1.2/50µs, peak peak 3 & 5 Ka 8/20µs) (20KV 1.2/50µs; 10KA 8/20µs) 900 volts peak 500 volts peak UL nd Edition SVR s 700 volts 330 volts (6 kv, 1.2/50µs;0.5 ka 8/20µs) peak peak d. Max. Continuous Operating 115% 115% Voltage (MCOV) of nominal minimum minimum line TRANSIENT VOLTAGE SURGE SUPPRESSORS

8 e. Max. Surge Current Dissipation See 2.02.A.1.e & f See 2.02.A.1.e & f per Phase per Polarity (the voltage protection levels per paragraphs 2.02.A.2.b & c shall not be exceeded during this performance test.) f. Response Time 5 ns 5 ns g. Min. Service Life The suppressor shall be provided with a 10 year unconditional warranty or shall meet the following surge tests without being damaged or changing the voltage protection level (clamping voltage) by 10% of initial value provided. Maximum seconds between pulses. (1) Shortwave Test surge current 1000 surges 1000 surges (6kV, 1.2/50µs; 3kA, 8/20µs) (2) Longwave - surge current 5000 surges 5000 surges (10 x 1000 µs) (1kv & 4 277V 0.5 kv & 2 120V) h. Temperatures (1) Operating 0 o C to +50 o C. 0 o C to +50 o C. (2) Storage -20 o C to +65 o C. -20 o C to +65 o C. i. Electrical Safety UL 1449 UL nd Edition Lst. 2nd Edition Lst. j. Suppression system shall be normal mode (L-N) only (for 480/277VAC & 208/120 VAC services). k. Power On Indicators and Failure Detection (for 480/277VAC & 208/120 VAC): A lighted panel on the cover shall provide indication that the suppressor is properly activated and shall also indicate mode failure. If the suppressor fails, an isolated 2 amp 120 VAC contact shall close. In addition, an audible alarm shall be provided with manual reset. TRANSIENT VOLTAGE SURGE SUPPRESSORS

9 l. Failure mode SPD s shall be designed to fail shorted. Any fuses in series with the SPD s shall not open during a surge event. B. Disconnect: Main service suppressors shall be provided with an integral fused disconnect switch or external branch circuit breaker as shown or required by UL. Breakers and suppressors shall have an AIC fault withstand rating equal or greater than the AIC rating of the equipment to which it is connected. The length of wiring from the tap at the service conductors to the suppressor being protected, however, shall not exceed the maximum length permitted by manufacturer, to maintain the maximum voltage protection level. Suppressors may be installed within switchgear or panelboards where UL label or listing is not affected, suppressors are completely and easily accessible, indicator lights are visible and audible alarm can be easily heard. C. Enclosures: Enclosures for main service suppressors shall be as follows; 1. Minimum 14 gauge painted steel or suitable enclosure to meet the NEMA selected requirements as listed with fully hinged door and lockable latch. a. NEMA 1 (General Purpose). b. NEMA 4 Watertight, and dust-tight. c. NEMA 4X Watertight, dust-tight and corrosion resistant. d. NEMA 12 Dust-tight and drip-tight (where specified on drawings). D. Operation Status Indicator Audible remote signaling and Visual Systems: Service entrance equipment 1. Install in front enclosure of equipment a. Visual System Equipment with LED indicator lights per phase. 1. Protection: Suppressor Working - Green LED's. 2. Warning/Fault: Suppressor Burnout - Red LED's. 3. LED's shall be field replaceable. (4) Other visual indicators where approved. b. Remote Signaling (1) Relay with Auxiliary Form C contacts: Two 2 ampere, 120 volts each. 1 Set N.O. and 1 set N.C. to operate upon failure of suppression module, blown fuse or tripped circuit breaker in suppressor module or in disconnect switch for alarm connection to remote location. TRANSIENT VOLTAGE SURGE SUPPRESSORS

10 c. Audible The audible alarm shall activate upon a fault condition within the suppressor. An alarm silence/reset switch and push-totest switch shall be provided. E. Plug-in Receptacle SPD Devices: (Receptacles Suppressor) - Unit shall include the following features: 1. Instant automatic reset after safely eliminating transient surges from switching transients, induced lightning, inductive motor switching and other forms of transient over voltages in normal mode (L-N) only. 2. Designed for 120 VAC, 1 phase (3 wire service), plug-in applications arranged to plug into any 15 or 20 amp, duplex, grounded receptacle. 3. A minimum of two single or one duplex, grounded 20 amp receptacles. 4. To be connected in parallel. 5. Employ only solid-state, silicon avalanche junction diode suppressors or metal oxide varistors. 6. Response time: less than 5 nanoseconds. 7. Suppression power: Minimum 12,000 watts or 12 joules. (10 x1000 µs pulse), at a max.vdl of 300Vpeak. 8. Operating temperature: -0/C to 50/C. 9. Voltage (V peak) protection level: 220 Minimum, 300 Maximum (10x1000 µs pulse). 330 maximum per UL nd Edition. 10. Service Frequency: 50/60 Hertz. warranty. 11. Life expectancy: 10 years plus. Minimum 10 year unconditional 12. Indicator light to turn on when unit is non-operational. (Usually Off) 13. Internally fused to take unit off-line if it self-sacrifices to protect against catastrophic power failure. Equipment plugged into suppressor shall continue to operate. 14. Warranty: 3 year guarantee to be repaired or replaced at no cost if damaged by normal operating use during the warranty period. 15. U.L. 1449, 2nd Edition listed (6kV 1.2/50 µs; 500 A 8/20 µs). 16. IEEE C62.41 Cat. A3 and B3 tests. (B3 = 6kV and 3kA) TRANSIENT VOLTAGE SURGE SUPPRESSORS

11 F. Receptacle suppressor with one input and one output RJ-11 jacks: Unit shall be same as in paragraph `A' above with the addition of 1-telephone protector and 2-RJ-11 (input and output) jacks with common grounds with the AC power. Telephone protector shall have the following characteristics and shall provide common and normal mode protection. 1. D-C Protective Level voltage (maximum) T-R V T-G V R-G V 2. Leakage Current 60HZ)...<10µa 3. Holding current (min.) ma 4. Peak On-State Voltage I T = 1A...3V 5. Response time...<1ns 6. Peak Pulse Current (10x1000µs) a. Applied between T-R, T-G, R-G.100A b. Applied simultaneously T-G and R-G...200A 7. Capacitance...<100pf G. 120V direct connected Hard Wired suppressors shall be provided with mounting provisions and wire leads for hardwire connection. Suppressors shall have the same characteristics as the above specified receptacle suppressors (E). H. Bonding and Grounding Conductors and Materials for Main Service Suppressors: 1. Size: Conductors utilized for surge suppressor connections to service conductors shall be a minimum of #6 AWG stranded insulated copper unless otherwise specified. 2. Bus: Ground bus or strip material where used shall be copper, a minimum of 1/4 inch thickness and two inches wide unless otherwise specified. Bus materials shall be secured to surfaces with a appropriate insulators and mechanical fasteners. Bus connections shall be bolted and reinforced as necessary to provide a permanent and secure connection. 3. Connections Compliance: Connectors, splices, and other fittings used to interconnect grounding conductors, bonding to equipment or ground TRANSIENT VOLTAGE SURGE SUPPRESSORS

12 bars, shall comply with requirements of the National Electric Code and be accepted by Underwriters' Laboratories for the purpose. 4. Connectors: Connectors and fittings for grounding and bonding conductors shall be of the compression type in above grade locations. Connections below grade shall be exothermically welded. 5. Dissimilar Materials: Bonding connections between electrically dissimilar metals shall be made using exothermic welds or using bimetal connectors designed to prevent galvanic corrosion. I. Communication Lines: The following standard for separately mounted telephone and signal line suppressors shall apply. All protectors shall be securely mounted at protected equipment location. All suppressors shall provide common (L-G) and normal (L-L) protection. Suppressors shall be tested in accordance with IEEE C as a minimum. Protective interfacing with the telephone wire pairs shall be listed to UL 497A. J. Data Line Protection: Solid state, silicon avalanche diode circuitry for protection from over voltages on long cable runs employing standard RS-232, 9, 15, or 25-pin "D" connectors utilized to interface a remote station with a host CPU. Unit shall have 2 built-in or ribbon cable attached connectors (in and out) and an external ground lug or cable. Connect ground lug or cable to CPU or terminal grounding system with a No. 12 copper green insulated stranded ground wire as short as possible. Select pins requiring protection based on protected equipment wiring requirements. Protectors shall be designed to be easily installed on multiplex panels with connector spacing at a minimum of 1.0 inch centers. 1. Signal line voltage (max)...15v peak 2. Leakage at signal voltage...<5m amp 3. Voltage protection level....16v peak 4. Response time...5 nanoseconds or less 5. Impedance per line...40 OHM max. 6. Peak power dissipation...15,000 watts (10/1000 Test Wave form) 7. Temperature range o C to +65 o C TRANSIENT VOLTAGE SURGE SUPPRESSORS

13 8. Capacitance: a. data rates <20,000 baud - <2,000 pf b. data rates 20,000 baud to 2Mhz - <100 pf c. data rates >2MHz to 100 Mhz - <40 pf 9. UL 497B listed. K. Signal line protection (telephone) - solid state, silicon avalanche diode circuitry for protection from over voltages on 2 or 4 wire signal lines such as balanced pair telephone, metallic pair telephone, buried and overhead field cable, remote radio equipment, and control systems. Unit shall have an external ground lug or wire. Connect ground lug or wire to protected equipment grounding system with a No. 12 green insulated stranded ground wire as short as possible. 1. L-L & L-G voltage (peak) L-L & L-G Voltage Protection Level Wave 2. L-L and L-G max L-L and L-G voltage...<5µa 3. Response time...,.<5 nanoseconds 4. Series impedance(each line)...33 Ohm max. 5. Peak power dissipation (L-L) or (L-G)...15,000 watts (10 x 1000 Test Form) 6. Temperature Range o C to +65 o C 7. U.L. 497B listed L. Modem protector for leased lines - solid state silicon avalanche diode circuitry for non-faulting/non-interrupting protection from over voltages on leased phone lines. Full duplex protection shall be provided for both send and receive channels. Terminals shall be provided for 4-wire leased line input and output to equipment plus ground. Connect ground terminal to equipment ground. 1. Signal line voltage (max)...160v peak 2. signal voltage...5µa 3. Clamp point...200v peak 4. Response time...<5 nanoseconds. 5. Series impedance...33 Ohm max. 6. Peak power dissipation...15,000 watts 7. Operating Temperature o C to +65 o C M. Modular, twisted pair protection - solid state, silicon avalanche diode circuitry for protection from over voltages on twisted pair data or audio lines. Protectors shall clip mount on 66 punch down blocks furnished with grounding bar or studs and shall be totally enclosed. Units shall be securely mounted at TRANSIENT VOLTAGE SURGE SUPPRESSORS

14 terminal locations where shown and shall be grounded to the main building ground with a minimum No. 8 stranded copper green insulated ground conductor as short as possible. Terminals shall be screw insertion lug type. No crimp fork or ring type permitted. 1. Response time...<5 nanoseconds 2. Peak power dissipation (1ms)...15,000 watts 3. Temperature range o C to +50 o C 4. Maximum voltage protection levels (peak) utilizing a 10 x 1000µs waveform for normal and common mode protection shall be V or 45V as indicated on the drawings. 5. Peak repetitive pulse current. a. 1. x 2. µsec amp b. 8 x 20µsec amp c. 10 x 1000µsec amp N. 75 ohm coaxial cable protectors - Solid state, silicon avalanche diode circuitry for non-interrupting overvoltage protection of RG- 59/U coaxial cable. Unit shall be provided with one female input connector for "F" series male connector, one output RG-59/U coax cable terminated with an "F" series male cable end connector and A #16 stranded, 18 inch long grounding wire on output end of unit or similar arrangement. Securely mount adjacent to protection equipment and ground to equipment or local building ground if an equipment ground is not available. PART 3 - EXECUTION 1. Normal Operating Characteristics a. Voltage...5.8V max b. Current...500ma max c. Frequency...DC to 10 Mhz d. Insertion 4Mhz 2. Protection Requirements a. Transient suppression level...7.5v Voltage Protection Level b. Transient response...<5 nanoseconds c. Operating temp o C to +50 o C d. Energy dissipation...15,000 watts (10X1000 Test Wave) 3.01 INSTALLATION OF MAIN SERVICE AND DISTRIBUTION EQUIPMENT SURGE SUPPRESSORS A. Suppressors shall be installed at Service Entrance switchboards and distribution equipment where shown as close as practical to equipment to be protected consistent with the available space. Where installation space permits and where no code restrictions apply, suppressors may be installed TRANSIENT VOLTAGE SURGE SUPPRESSORS

15 within protected equipment. Suppressors installed in this manner shall utilize the equipment ground bus or enclosure as a medium for bonding of their ground terminals. Bonding jumpers not exceeding two inches in length shall be installed between the ground bus or enclosure and suppressor ground terminals. Bolted connections with star washers shall be used to insure electrical and mechanical integrity of connections to the ground bus or enclosure. Remove paint where connections are made to the enclosure. Conductors from suppressors shall attach to main service bus in the service entrance equipment on the load side of any electrical metering equipment. B. Suppressors shall be installed in a neat, workmanlike manner. Lead dress shall be consistent with recommended industry practices for the system on which these devices are installed. C. All system wiring shall be classified into protected and non-protected categories. Wiring on the exposed side of suppression devices shall be considered unprotected. Surge suppressor grounding and bonding conductors shall also fall into this category. D. All wiring between surge suppressors and protected equipment shall be considered protected and connected in accordance with the latest edition of the NEC. E. A minimum of three inches of separation shall be provided between parallel runs of protected and unprotected wiring in control panels, terminal cabinets, terminal boards and other locations. In no case shall protected and unprotected wiring be bundled together or routed through the same conduit. Where bundles of protected and unprotected wiring cross, such crossings shall be made at right angles FIELD QUALITY CONTROL A. Disconnect suppressor prior to megger testing of service entrance distribution equipment and panelboards. B. Supply certified test reports for all tested parts, elements and/or systems or where required by the Owner to substantiate published ratings of claims. END OF SECTION TRANSIENT VOLTAGE SURGE SUPPRESSORS

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1 Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

Power surges can also be generated by equipment in your facility such as:

Power surges can also be generated by equipment in your facility such as: Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

Applications. Remote Display Mounting Kits

Applications. Remote Display Mounting Kits June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge

More information

CPS 100 480Y S K CPS 100 480Y S C

CPS 100 480Y S K CPS 100 480Y S C Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch

More information

Surgelogic Surge Protective Device (SPD)

Surgelogic Surge Protective Device (SPD) Surgelogic Surge Protective Device () EB, EM, and HW Series atalog 1310T0202R05/09 2009 lass 1310 OTETS Description............................................. Page Product Description...........................................2

More information

Intersection Preassembled 19-inch Rack

Intersection Preassembled 19-inch Rack Intersection Preassembled 19-inch Rack The intersection preassembled 19-inch rack comes fully assembled, wired and ready to be installed in a server rack. The rack provides communications, power conversion

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

CalMod Design-Build Electrification Services

CalMod Design-Build Electrification Services SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

************* OWNER'S MANUAL BAMF800/2 BAMF1250/2 BAMF1800/2 BAMF2200/2 BAMF2600/2 BAMF1200/4 BAMF1600/4 BAMF2000/1D BAMF4000/1D BAMF5500/1D

************* OWNER'S MANUAL BAMF800/2 BAMF1250/2 BAMF1800/2 BAMF2200/2 BAMF2600/2 BAMF1200/4 BAMF1600/4 BAMF2000/1D BAMF4000/1D BAMF5500/1D ************* OWNER'S MANUAL BAMF800/2 BAMF1250/2 BAMF1800/2 BAMF2200/2 BAMF2600/2 BAMF1200/4 BAMF1600/4 BAMF2000/1D BAMF4000/1D BAMF5500/1D INTRODUCTION Power Acoustik amplifiers provide high-performance

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

Surgelogic Surge Protection Device EMA, EBA, and HWA Series

Surgelogic Surge Protection Device EMA, EBA, and HWA Series Surgelogic Surge Protection Device EM, EB, and HW Series atalog 1310T0202R5/07 2007 lass 1310 OTETS Description..............................................Page Product Descriptions..........................................

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

Protect your home and family with Advanced Technology from Cutler-Hammer

Protect your home and family with Advanced Technology from Cutler-Hammer Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

INTRUSION DETECTION SYSTEM Section 281600

INTRUSION DETECTION SYSTEM Section 281600 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

AC and DC Drive System Installation Information

AC and DC Drive System Installation Information Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS

More information

Power Management Module 2. Installation

Power Management Module 2. Installation Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Amplifier for Small Magnetic and Electric Wideband Receiving Antennas (model AAA-1B)

Amplifier for Small Magnetic and Electric Wideband Receiving Antennas (model AAA-1B) Amplifier for Small Magnetic and Electric Wideband Receiving Antennas (model AAA-1B) 1. Description and Specifications Contents 1.1 Description 1.2 1.2 Specifications 1.3 1.3 Tested parameters in production

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Uninterruptible Power Supply

Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features

More information

Operation and Installation Manual

Operation and Installation Manual Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0 FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION

More information

Single Station Remote Alarm

Single Station Remote Alarm ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation

More information

Telecommunication Line Protectors

Telecommunication Line Protectors TN CR 0025 Telecommunication Line s 1.1 The nature of telecom surges The telecom services considered in this report are transported on twisted pair. Each service has two wires, or lines, sometimes called

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information

Report On Surge Protection & Voltage Fluctuation

Report On Surge Protection & Voltage Fluctuation Report On Surge Protection & Voltage Fluctuation 1. Introduction Power is the greatest challenge for most installations in the developing world. Where there are electrical networks, they are often poorly

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

TSn SERIES Surge Protective Device

TSn SERIES Surge Protective Device Page: 1 of 8 TSn SERIES Surge Protective Installation & Operation Manual 3621 Saunders Avenue www.systems.us Ph 804.355.1100 Richmond, VA 23227 4354 Sales@Systems.us Fax 804.355.8900 Page: 2 of 8 Quick

More information

A series of technology briefs spanning Tyco Electronics product portfolio

A series of technology briefs spanning Tyco Electronics product portfolio A series of technology briefs spanning Tyco Electronics product portfolio Coordinated Circuit Protection Schemes Help Prevent Overvoltage and Overcurrent Damage Through advances in materials science and

More information

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

LOXONE 12 Channel Amplifier

LOXONE 12 Channel Amplifier LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room

More information

1. Franklin Rod Performance 2. LEC/DAS Performance

1. Franklin Rod Performance 2. LEC/DAS Performance THREE ESSENTIALS OF LIGHTNING PROTECTION: BONDING, GROUNDING AND SURGE PROTECTION by Richard Kithil, President and Orlando Alzamora, Vice-President National Lightning Safety Institute (NLSI) 1.0 Summary.

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors APPENDIX APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS RJ12 connectors Pin # 1 Signal Name Not Used 2 +TR Description + Data Line 3 +R Remote OFF Required or Remote OFF control 4 -TR 5 Not Used 6 RTN -

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1. USER GUIDE Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator Version 1.3 DM Engineering 2174 Chandler St. Camarillo, CA 91345-4611 805-987-7881 800-249-0487

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting Series - Relay interface modules 8-10 - 16 A Features.01.02 1 & 2 pole relay interface modules, screw terminal socket, mm wide. Ideal interface for PL and electronic systems.01-1 Pole 16 A.02-2 Pole 8

More information

Power Quality for Information Technology System

Power Quality for Information Technology System Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS

More information

RC NETWORKS SALES GUIDE

RC NETWORKS SALES GUIDE SALES GUIDE INTRODUCTION TO Recent developments in electronic equipment have shown the following trends: Increasing demands for numerical control machines, robotics and technically advanced appliances

More information

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS 1. Description and Phone Number Dialing: The dialer shall be a solid state component capable of dialing up to 16 telephone numbers, each up to 60 digits

More information

ASCO SERIES 185 Power Transfer Switches

ASCO SERIES 185 Power Transfer Switches ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

Special Specification 6111 LED Neighborhood Friendly High Mast (NFHM) Illumination Assemblies

Special Specification 6111 LED Neighborhood Friendly High Mast (NFHM) Illumination Assemblies Special Specification LED Neighborhood Friendly High Mast (NFHM) Illumination Assemblies 1. DESCRIPTION 2. MATERIALS Furnish and install light emitting diode (LED) neighborhood friendly high mast illumination

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

Chapter 9. Bonding and Grounding

Chapter 9. Bonding and Grounding Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

More information

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM Section TELEPHONE AUTOMATIC DIALER SYSTEM PART 1 GENERAL 1.01 SYSTEM DESCRIPTION A. Design Requirements: 1. Electronic monitoring system shall interface plant alarms to public telephone system or cellular

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Solid State Timers Type F

Solid State Timers Type F Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application

More information

For Models #6-5001, #6-7501, #10-7501 & #10-12K1

For Models #6-5001, #6-7501, #10-7501 & #10-12K1 EmerGen Switch Manual Transfer Switch Manufactured by CONNECTICUT ELECTRIC SWITCH MFG. CO. 1-800-730-2557 OWNER S MANUAL & INSTALLATION INSTRUCTIONS For Models #6-5001, #6-7501, #10-7501 & #10-12K1 PLEASE

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information