EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.
|
|
- Christina Alexander
- 7 years ago
- Views:
Transcription
1 ENGLISH EATS6 EATS6N Installation and user manual Copyright 05 EATON All rights reserved. Service and suppt: Call your local service representative
2 SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains imptant instructions that should be followed during installation and maintenance of the ATS. The EATON ATS models that are covered in this manual are intended f installation in an environment within 0 C to 40 C ( F to 04 F) and free of conductive contaminant. Certification standards Safety: IEC 60- EMC: IEC 60- Perfmance: IEC 60- CE Mark Additional confmances : - IEC CISPR Class B Imptant safety notes Only qualified personnel can service this equipment. Follow the following precautions when wking on this unit. - Remove watches, rings, other metal objects. - Use tools with insulated handles. Examine the packing container. Notify the carrier immediately if any damage is present. Do not disassemble the unit. Do not operate the unit near water in an area with excessive humidity. Keep liquid and feign objects from getting inside the unit. Do not operate the unit close to gas fire. Verify whether the branch circuit breaker fuse on service feed is crect. Verify line voltage requirements and the supplied line voltage pri to installation. This unit is supplied from multiple sources, disconnect all sources befe servicing. Electrical warnings Warning Check that power cds, plugs, and outlets are in good condition. RAL equipment: "Equipment intended f installation in Restricted Access Location". Intended to be connected to computer load. Not to be connected to inductive load with >: crest fact load. Page
3 Contents. Introduction... 4 ENGLISH. Presentation Weights and dimensions Rear panel layout - EATS6 - EATS6N...4. Control panel LCD description Power flow Measures ATS settings Warning...8. Installation f ATS Checking the accessy kit - EATS6 - EATS6N...9. Stage Installation f rack mounting (nmal installation) Installation f rack mounting ( post installation) Wall installation Instructions Power cables connection Installation diagram Input/Output connection EATS6 - EATS6N Communication Communication pts: EATS6N Eaton Intelligent Power Software suite Maintenance Troubleshooting Specifications... 6 Page
4 . Introduction The EATON Automatic Transfer Switch (ATS) is a high availability switch designed f providing redundant power f sensitive equipment. It is powered by two independent power sources and automatically makes a rapid switch from one source to the other when the power supply used to power its connected load fails. This ATS is designed to be efficient and reliable. Users can know EATON ATS s power flow, status, parameters from the LCD interface. Besides, the EATS6N unit has a netwk interface f users to read and write parameters. The netwk interface can be implemented via the Ethernet protocol through an RJ45 connect.. Presentation. Weights and dimensions Rack installation W D H Description Weights (kg / lb) Dimensions H x W x D (mm / inch) EATS6. / 7. 4 x 48 x 50 /.7 x 7.4 x 9.84 EATS6N.54 / x 48 x 50 /.7 x 7.4 x Rear panel layout - EATS6 - EATS6N 4 Input Source : IEC C0 inlet Input Source : IEC C0 inlet Output: 8 x C 0 A 4 Output: x C9 6 A. Control panel The ATS has three buttons on the control panel and a LCD display. It provides useful infmation about the ATS itself, load status, events, measurements and settings. LCD panel Navigation: Scroll down button 5 Navigation: Enter button 4 Navigation: Escape button 4 5 Transfer Test: Scroll down and Enter buttons pressed f 5s Page 4
5 .4 LCD description. Presentation ENGLISH 4 Power flow ATS Settings Measures/Infos 4 Events.4. Power flow S is defined as the priity source (true by default) S is defined as the priity source (can be set) S not powered S not powered S powering the load S powering the load S powered but not powering the load S powered but not powering the load Transfer from S to S Transfer from S to S Transfer from S to S f Test Transfer from S to S f Test Page 5
6 . Presentation.4. Measures Output current (default display) Output voltage Input voltage : S (default display only when S voltage is out of tolerance) Input frequency: S (default display only when S frequency is out of tolerance) Input voltage : S (default display only when S voltage is out of tolerance) Input frequency: S (default display only when S frequency is out of tolerance) S and S phase shift (available only when S and S are not synchronized).5 ATS settings OUTPUT: Sets voltage thresholds - ALARM: Silents alarm - SENSITIVITY (mainly f LIA UPS): Sets Sensitivity mode f input mains detection. - P SOURCE: Sets the priity source TRANSFER: 00 V - 08 V - 0 V - 0 V (default) - 40 V ON: nmal beep in warning fault mode, by default OFF: silent. Std: Nmal Sensitivity, by default Lo: Low Sensitivity, f compatibility with distted wavefm. Sc.: Priity on Source, by default Sc.: Priity on Source Std: no additional break even if S and S are not synchronized, by default Gap: additional break during transfer if S and S are not synchronized. Page 6
7 Press Enter to reach settings menu. Presentation ENGLISH OUTPUT ALARM To cancel the changes To select value SENSITIVITY PRIORITY SOURCE TRANSFER Page 7
8 . Presentation.6 Warning F Fault, refer to troubleshooting section 6.. Event Example of displays Rootcause Overload Unsynchronized sources Load is over nominal rating Remove some of the equipment from the ATS. The ATS continues to operate, but may shutdown if the load increases. The alarm resets when the condition becomes inactive. One source N and L are reversed S ansd S are fed by different phase (L/L/L) S and S frequency are different Source Source power loss One of the source is missing, The ATS power on the load with the source that is present. Source Source voltage out of tolerance One of the source voltage is out of tolerance. The display shows the voltage measure of the faulty source. Source Source frequency out of tolerance One of the source frequency is out of tolerance. The display shows the frequency measure of the faulty source. Source and Source quality The sources are outside ranges so that it generates too many transfers within a sht period of time. The alarm resets when the condition becomes inactive. Page 8
9 . Checking the accessy kit - EATS6 - EATS6N. Installation f ATS ENGLISH Verify that the following additional items are included with the ATS: EATS6 User manual Quick start guide Safety manual printed 4 x Input cables: C9-C0 5 x Input cable lockers 6 Plastic strips f output locking 7 RS cable 8 Accessies f rack installation EATS6N 4 User manual Quick start guide Safety manual printed 4 x Input cables: C9-C0 5 x Input cable lockers 6 Plastic strips f output locking 7 RS cable 8 DB9/RJ45 serial cable f NMC card 9 Accessies f rack installation Page 9
10 . Installation f ATS. Stage Please ste the ATS in its iginal package and in a dry place. Keep the stage temperature between - to F (-5 C and +55 C).. Installation f rack mounting (nmal installation) Follow steps to f module mounting on the rails. Accessies f rack installation x Ear (Left) x Ear (Right) 4 x M4 x 6 flat screw f ear 4 x M6 x 0 cage nut clip f rack4 4 x M6 x flat screw f rack 4 x M6 washer conical plate f rack.4 Installation f rack mounting ( post installation) Follow steps to f module mounting on the rails. Accessies f rack installation x Ear (Left) x Ear (Right) 4 x M4 x 6 flat screw f ear 4 x M6 x 0 cage nut clip f rack4 4 x M6 x flat screw f rack 4 x M6 washer conical plate f rack Page 0
11 .5 Wall installation. Installation f ATS ENGLISH Follow steps to f module mounting on the wall..6 Instructions. Elevated Operating Ambient - If installed in a closed multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefe, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tmax) specified by the manufacturer.. Reduced Air Flow - Installation of the equipment in a rack should be such that the amount of air flow required f safe operation of the equipment is not compromised.. Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading. 4. Circuit Overloading - Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern. 5. Reliable Earthing - Reliable grounding of rack-mounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips). Page
12 4. Power cables connection 4. Installation diagram UPS Input UPS UPS Output ATS Input S ATS ATS Output to the sensitive equiment UPS Input UPS UPS Output ATS Input S 4. Input/Output connection EATS6 - EATS6N Inputs connections from UPSs outputs Ouput connection to equipment. Connect input power cables to UPSs output and to ATS inputs (S is the default priity source).. Connect ATS output to the equipment. Page
13 5. Communication pts: EATS6N 5. Communication ENGLISH RS communication pt. Connect the RS communication cable to the serial on the computer.. Connect the other end of the communication cable to the RS communication pt on the ATS. The ATS can now communicate with EATON power management software. Characteristics of the optocouplers communication pt When a signal is activated, the contact is closed between the common (Pin 4) and the pin of the cresponding signal f n.o contact, and vice versa f n.c contact. common Contact characteristics (optocoupler) Voltage: 48 V DC max Current: 5 ma max Power:. W Pin assignment Description Contact type Open State Close State Pin Summary alarm signal n.o Nmal Alarm occurred Pin RX Pin TX Pin 4 Common Pin 5 GND Pin 6 Source OK n.c Source is failure Source is ok Pin 7 Source OK n.c Source is failure Source is ok Pin 8 Load on source n.c Source not take load Source takes load Pin 9 Load on source n.c Source not take load Source takes load n.o: nmally opened n.c: nmally closed Page
14 5. Communication Connectivity Cards: EATS6N Connectivity cards allow the ATS to communicate in a variety of netwking environments and with different types of devices. The Netwk-MS card has SNMP and HTTP capabilities as well as moniting through a Web browser interface; connects to Ethernet netwk. In addition, an Environmental Moniting Probe can be attached to obtain humidity, temperature, smoke alarm, and security infmation. ETHERNET Setting/Sens 00M 0M UPS data Reset Netwk-MS card 5. Eaton Intelligent Power Software suite Eaton Software suite provides up-to-date graphics of ATS power and system data and power flow. It also gives you a complete recd of critical power events, and it notifies you of imptant ATS power infmation. Page 4
15 6. Troubleshooting 6. Maintenance ENGLISH Operation status Possible cause Action Overload Power requirement exceeds the ATS capacity (greater than 05 % of nominal). Remove some of the equipment from the ATS.The ATS continues to operate, but may shutdown if the load increases.the alarm resets when the condition becomes inactive. Sht-circuit fault A sht-circuit occurred. Check device connection integrity. If err persists, note the alarm message and the ATS serial number, and then contact your service representative. Internal relay fault Internal relay fault, note that the load is no powered. Note the alarm message and the ATS serial number, and then contact your service representative. Source Source power supply fault Internal power supply of one of the source is faulty; the other source is powering the load. Note the alarm message and the ATS serial number, and then contact your service representative. EEPROM fault EEPROM fault, note that the load is still powered. Note the alarm message and the ATS serial number, and then contact your service representative. Page 5
16 7. Specifications Table. Model list Model Operating voltage Current rating Operating frequency EATS6 EATS6N Table. Weights and dimensions 00/08/0/0/40 Vac ɸ 6A 50/60 Hz Model Dimensions H x W x D (mm/inch) Weight (kg/lb) EATS6 4 x 48 x 50 /.7 x 7.4 x / 7. EATS6N 4 x 48 x 50 /.7 x 7.4 x / 7.8 Table. Electrical input connections Model EATS6 - EATS6N Input connection Table 4. Electrical output connections Model EATS6 - EATS6N IEC C0 inlet ( x Input cables: C9-C0 provided) Output connection x C9 8 x C Table 5. Environmental and safety Operating temperature 0 C to 40 C ( F to 04 F) Stage temperature -5 C to 55 C / - F to F Relative humidity Stage: 0-90% Operating: 0-85% Operating altitude 000m meters (65 ft) Audible noise 5 dba max (without buzzer) Page 6
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
More informationTable of Contents. 1. Introduction...1. 2. PDU Package...2. 3. Function...3. 4. Installation...5. 5. Web Interface...7
PDU User Manual Table of Contents 1. Introduction...1 2. PDU Package...2 3. Function...3 4. Installation...5 5. Web Interface...7 1. Introduction The PDU is an Internet ready device designed and is equipped
More informationHP R12000 and R18000 DirectFlow UPS User Guide
HP R12000 and R18000 DirectFlow UPS User Guide Abstract This document includes installation, configuration, and operation information for the HP R12000 and R18000 DirectFlow UPS. This document is for the
More informationDaker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
More informationBack-UPS Pro 1300/1500 Installation and Operation
Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationIndustrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P
Technical Data Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Topic Page 1609-P Specifications 2 1609-P Approximate Dimensions and Shipping Weights 3 Additional Resources
More informationUninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
More informationNC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
More informationInstallation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
More informationAPC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
More information100 - SERIES NETWORK SWITCHES QUICK START GUIDE
100 - SERIES NETWORK SWITCHES QUICK START GUIDE Unmanaged IT Rack Network Switches FCC Warning This device has been tested and found to comply with limits for a Class A digital device, pursuant to Part
More informationUser Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
More informationRack Installation. Unpacking the System. Choosing a Setup Location. General Server Precautions. Barracuda Appliances
This set of instructions applies to racking and rail kit installation for 6XX and above. The Rack Mounting Instructions section below provides information on installing the SC825 chassis into a rack unit
More informationMAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
More informationHotSwap MBP Maintenance Bypass
ENGLISH HotSwap MBP Maintenance Bypass MBP6Ki MBP11Ki MBP11Ki1 Installation and user manual Copyright 201 EATON All rights reserved. Service and support: Call your local service representative SAFETY INSTRUCTIONS
More informationOnline UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
More informationFive9NS R2100RS Rack Mount Server. Installation Manual
Five9NS R2100RS Rack Mount Server Installation Manual Version July 24, 2014: This version supersedes all previous versions. 2014 Five9 Network Systems LLC, 300 Main Street, Suite 12A, East Rochester, NY
More informationMatch. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
More information10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
More informationInstallation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
More informationUser s Manual. Professional Rack Mount LCD Series PR1000ELCDRT2U/PR1500ELCDRT2U/ PR2200ELCDRT2U K01-0000070-01
EN User s Manual Professional Rack Mount LCD Series PR1000ELCDRT2U/PR1500ELCDRT2U/ PR2200ELCDRT2U K01-0000070-01 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS This manual contains important
More information33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
More informationHow To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
More information5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
More informationDLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
More informationGB USER S MANUAL GB 41
GB USER S MANUAL GB 41 INTRODUCTION Thanks you for choosing this product of the DIALOG DUAL range. Riello UPS are renowned specialists in the development and production of uninterruptible power supplies
More informationWD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
More informationBARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
More informationTMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
More informationGalleon 6-10K Online UPS. Voltronic Power Technology Corporation
Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection
More information8-Port PoE Network Switch
Page 1 of 12 8-Port PoE Network Switch User s Guide Document Number 91I00-1 Rev A August, 2009 FCC Warning: Page 2 of 12 This devices has been tested and found to comply with the regulations for Class
More informationUSER MANUAL Online UPS 1K/2K/3K Rack
USER MANUAL EN Online UPS 1K/2K/3K Rack Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3. Installation 2 1-4. Operation 2
More informationQuick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)
Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Table of Contents Introduction.. Power Over Ethernet (PoE) & Features.... Unpacking and
More informationOutdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
More informationLevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
More informationCharge Controller CC611/CC612 Preliminary datasheet
Preliminary datasheet Preliminary datasheet CC61x_D00xxx_00_D_XXE_preliminary/04.2015 Product description The ender charge controller CC611 is the main component of a charging point and is designed for
More informationJNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
More informationInstallation manual. Generator Paralleling Controller GPC multi-line 2 4189340225C
Installation manual Generator Paralleling Controller GPC multi-line 2 Software ver. 1.3X Compact system in one unit - dynamic synchronisation - load sharing - generator protection DEIF A/S 3-phase AC RMS
More informationSmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
More informationDrayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
More informationHow To Test A Power Distribution Unit
PDUAC3U SERIES AC POWER DISTRIBUTIO UITS www.unipowerco.com Manual o. PDUAC3U-1 pduac3u-man-rev1-1015.indd 2015 UIPOWER LLC All Rights Reserved ORTH AMERICA 3900 Coral Ridge Drive, Coral Springs, Florida
More informationNEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL info@tuncmatik.com / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
More information1. SAFETY INFORMATION
RS-232 Sound Level Meter 72-860A INSTRUCTION MANUAL www.tenma.com 1. SAFETY INFORMATION Read the following safety information carefully before attempting to operate or service the meter. Use the meter
More informationSNQ-60x0-320 Series Data Center Switch. Quick Installation Guide
Introduction This guide is to assist the reader with the most basic form of installation and connection to switches in this series. As there is more than one switch in this series, the diagrams might slightly
More informationInstallation and User Guide
Installation and User Guide 458-UNI8 8-Channel Universal Dimmer Module Introduction The 458/UNI8 is an 8-channel universal, digital transistor, dimmer module. Each channel s mode can be selected for either
More informationUser s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
More informationSNMP Web Management. User s Manual For SNMP Web Card/Box
SNMP Web Management User s Manual For SNMP Web Card/Box Management Software for Off-Grid Inverter Version: 1.2 Table of Contents 1. Overview... 1 1.1 Introduction... 1 1.2 Features... 1 1.3 Overlook...
More informationAU-110 racking guide NBXPN: 023
AU-110 racking guide NBXPN: 023 1. Overview NIMBOXX AU-110 Rack Installation This guide provides setup instructions for installing your NIMBOXX AU-110 in a rack. Following these steps in the order given
More informationCAUTION. CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury.
Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts,
More informationProduct and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
More informationGSM Autodialer Professional GJD700 Speech & Text Autodialer
Text Edit message GSM Autodialer Professional GJD700 Speech & Text Autodialer Introduction The GSM Autodialer Professional works in conjunction with standard alarm systems and makes use of your preferred
More informationUser Manual for CH-PFC76810
AA Portable Power Corp www.batteryspace.com, Email: Sales@batteryspace.com User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those
More informationBPM Series. Metered Rack Mount PDUs. Quick Start Guide. Models Covered:
WTI Part No.: 13963 Rev.: PM Series Metered Rack Mount PDUs Models Covered: PM-8HS20-1 PM-16VS30-1 PM-24VS30-1 PM-24VS30-D PM-8HS20-2 PM-16VS30-2 PM-24VS30-2 PM-24VS30-Y PM-16VS20-1 PM-24VS20-1 PM-24VS20-D
More informationAIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,
More information3500/93 System Display
3500/93 System Display Bently Nevada* Asset Condition Monitoring Description The 3500/93 System Display is designed to meet the requirements of American Petroleum Institute (API) Standard 670 and provide
More informationDRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationBlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC900300000
Manual EN BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC900300000 Contents EN 1.Important safety instructions... 2 2. Installation... 2 3.Product
More informationSmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX1000RT2U Highlights 1kVA / 1000VA / 900W line-interactive 2U rack/tower UPS, Sine
More informationUSER MANUAL Online UPS 6K/10K RACK
USER MANUAL EN Online UPS 6K/10K RACK Uninterruptible Power Supply System Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully
More informationManual Ranging MultiMeter
Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!
More informationUnpacking the Product. Rack Installation. Then, use the screws provided with the equipment rack to mount the firewall in the rack.
About This Guide This guide contains step-by-step instructions for setting up the D-Link DFL-260E/860E Firewall. Please note that the model you have purchased may appear slightly different from those shown
More informationUSER MANUAL Online UPS 1K/2K/3K
USER MANUAL EN Online UPS 1K/2K/3K Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1.1. Transportation 2 1.2. Preparation 2 1.3. Installation 2 1.4. Operation 2 1.5.
More informationLine Interactive UPS. PowerWalker VI 500T/HID PowerWalker VI 750T/HID PowerWalker VI 1000T/HID PowerWalker VI 1500T/HID.
Line Interactive UPS PowerWalker VI 500T/HID PowerWalker VI 750T/HID PowerWalker VI 1000T/HID PowerWalker VI 1500T/HID Quick Start Guide CONTT IMPORTANT SAFETY INSTRUCTIONS... 1 1. Introduction... 4 2.
More informationSEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use
s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum
More informationHow to Set Up Your NSM4000 Appliance
How to Set Up Your NSM4000 Appliance Juniper Networks NSM4000 is an appliance version of Network and Security Manager (NSM), a software application that centralizes control and management of your Juniper
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
More informationSmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
More informationTraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to
More informationCo-location Interconnect Power Panel (CIPP) Installation Guide
Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...
More informationINSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
More informationProgrammable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains
Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation
More informationTECHNICAL. Add Peripherals without Changing Your Phone System C-1000A. Door Entry Controller
TECHNICAL Practice TELECOM SOLUTIS FOR THE 21ST CENTURY C-1000A Do Entry Controller June 21, 2002 Features Allows two Viking doboxes paging amplifiers to share a single telephone line with a residential
More informationDigital I/O: OUTPUT: Basic, Count, Count+, Smart+
Digital I/O: OUTPUT: Basic, Count, Count+, Smart+ The digital I/O option port in the 4-Series provides us with 4 optically isolated inputs and 4 optically isolated outputs. All power is supplied externally.
More informationPowerware 5110 UPS User s manual
Powerware 5110 UPS 2005 Eaton Corporation All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care
More informationSmart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
More informationPower Commander Power Distribution Units from Wiremold/Legrand offer
Power Commander Power Distribution Units Rack Power Distribution Solutions for IT/Network Environments Power Commander Power Distribution Units from Wiremold/Legrand offer comprehensive power distribution
More informationHP ProDisplay P19A LED Backlit Monitor. User Guide
HP ProDisplay P19A LED Backlit Monitor User Guide 2013 Hewlett-Packard Development Company, L.P. The only warranties for HP products and services are set forth in the express warranty statements accompanying
More informationInstruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011
Instruction Manual 2in1 LAN Tester & Multimeter Model: LA-1011 1 Contents Introduction... Features... Safety Precautions.. Meter Description... Electrical Specification... Operation.. AutoRanging Multimeter.
More information16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide
16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide 1. Introduction Thank you for purchasing this 16-Port RS232 to USB2.0 High Speed Multi Serial Adapter. It is an
More informationApplied Electronics. Commercial Dimming System UPDATE NOTICE
REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with
More informationPower Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
More informationUser Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1
User Manual Hybrid 1KW-5KW INVERTER / CHARGER Version: 1.1 Table of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Product Overview... 3 INSTALLATION...
More informationEnergy Communication Unit (ECU)
Altenergy Power System Energy Communication Unit (ECU) Installation and User Manual (For ECU-3 V3.7) Version:3.0 ALTENERGY POWER SYSTEM INC. All rights reserved TABLE OF CONTENTS 1.0 Introduction... 2
More informationUser s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
More informationModel #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: saleshelp@tripplite.com Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
More information30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
More information40.3. Control Relays and Timers
.3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories
More informationBack-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
More informationInstallation and Operating Instructions for ROBA -takt Control Unit Type 014.000.2
Manufacturer s Declaration This product is intended f installation in a machine system, based on the machine directive 006/4/EC. It is fbidden to start use of the product until the machine system into
More informationOptions for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface
Options for ABB drives, converters and inverters User s manual FDPI-02 diagnostics and panel interface Table of contents Table of contents 3 1. FDPI-02 diagnostics and panel interface Safety..............................................
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationDC UPS. RTB.e 50-1000 A. IMB.e/ITB.e 5-200 kva. E2001.e/E3001.e 5-200 kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.
Oil & Gas Energy Catalogue DC UPS RTB.e 50-1000 A 3 phase rectifier battery chargers voltage: 400 Vac, 3-phase, 50/60 Hz voltage: 24/48/110/220 Vdc RMB.e/RCB.e 50-100-150 A 1 and 3 phase compact rectifier
More informationQuickSpecs. HP Fixed Cord PDUs & Extension Bars (Zero-U/1U Modular PDUs) Overview
Overview Fixed Cord PDUs and Extension Bars have a unique architecture designed specifically for 1U fixed rail servers (HP ProLiant DL360, HP ProLiant DL320, HP ProLiant DL140). This new design consists
More informationADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
More informationNEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.
NEW APC Smart-UPS Advanced line interactive power protection for servers and network equipment. > The world s most popular network and server UPS. Award-winning Smart-UPS protects critical data by supplying
More informationDVI DA2 and DVI DA 4 User Guide
DVI DA2 and DVI DA 4 User Guide This guide describes the installation and operation of the Extron DVI DA2 and DVI DA4 Distribution Amplifiers. Unless stated otherwise, distribution amplifier or the unit
More informationAPC Step-Down Transformer. User s Manual
APC Step-Down Transformer Models: AP9621, SURT005, SURT006, SUTF3, SYTF2, SYTF2J, SYTF3 and SYTF3J User s Manual English 990-7820D, July 2003 TABLE OF CONTENTS APC Contact Numbers and Support Visit the
More informationVX 2400 Dimmer User's Manual
TM VX 2400 Dimmer User's Manual 21-2119C Manual Revision 1.01 Software Version 1.0 10 March 1994 Table of Contents 1. General Description...3 1.1. Standard Features:...3 2. Installing Options...4 2.1.
More information