Engineering & Facilities Policy GENERATOR OPERATION AND TESTING
|
|
- Allan Douglas
- 7 years ago
- Views:
Transcription
1 Page 1 of 6 The University inspects, tests, and maintains emergency power systems in accordance with the Joint Commission Environment of Care Standard EC for the following facilities and equipment: Bldg. 925, Hollings Cancer Center, Generator #1 ( ), Generator #3 ( ) Bldg. 148, 135 Cannon St., Generator #1 ( ) Bldg. 750, Psych Inst., Generator #1 ( ), Generator #2 ( ) Bldg. 180, Family Med., Generator #1 ( ) The following is quoted from the Joint Commission standards for reference: EC : The Hospital inspects, tests, and maintains emergency power systems. EC : Twelve times a year, at intervals of not less than 20 days and not more than 40 days, the hospital tests each emergency generator for at least 30 continuous minutes. The completion dates of the tests are documented in the generator and ATS testing logs by the technicians performing the tests. EC : The Hospital s emergency generator tests are conducted with a dynamic load that is at least 30% of the nameplate rating of the generator or meets the manufacturer s recommended prime movers exhaust gas temperature. If MUHA does not meet either the 30% of nameplate rating or the recommended exhaust gas temperature during any test in EC EP 4, the Facilities Maintenance Department will test each emergency generator once every 12 months using supplemental (dynamic or static) loads of: 25% of nameplate rating for 30 minutes, followed by 50% of nameplate rating for 30 minutes, followed by 75% of nameplate rating for 60 minutes, for a total of 2 continuous hours. If required, the completion date of the tests is documented in the generator and ATS testing logs by the technicians performing the test. EC : Twelve times a year, at intervals of not less than 20 days and not more than 40 days, the hospital tests all automatic transfer switches. The completion date of the tests is documented in the generator and ATS testing logs by the technicians performing the tests. EC : At least once every 36 months, hospitals with a generator providing emergency power for the services listed in Standard EC EP s 5 and 6 must test each emergency generator for a minimum of 4 continuous hours. The completion date of the tests is documented in the generator and ATS testing logs by the technicians performing the tests. EC : The 36-month emergency generator test uses a dynamic or static load that is at least 30% of the nameplate rating of the generator or meets the manufacturer s recommended prime movers' exhaust gas temperature. EC : If a required emergency power system test fails, the hospital implements measures to protect patients, visitors, and staff until necessary repairs or corrections are completed. EC : If a required emergency power system test fails, the hospital performs a re-test after making the necessary repairs or corrections.
2 Page 2 of 6 Definitions: Generator: A machine that generates electrical power and is configured to automatically start when a power failure occurs from the Electric Utility. Emergency Power Standby System (EPSS): One or more generators that are connected to a building s emergency distribution system by the means of Automatic Transfer Switches. Automatic Transfer Switch (ATS): An electrical switching device that, on a loss of normal incoming power, will automatically request an Emergency Power Standby System (EPSS) to start and, once emergency power is produced, transfer the load from the normal source to the generated emergency source. Generator System Log Book: A binder containing individual generator and ATS testing log sheets. Computerized Maintenance Management System (CMMS): The Computerized Maintenance Management System is a computer software system that maintains a computerized record of equipment and systems, calculates preventive maintenance due dates and provide reminders to perform tasks as programmed in a given facility. The system also provides a means to generate work order or work request tickets to track requests received by customers requiring service. Purpose: This procedure is intended to establish the process whereby the Emergency Power Standby Systems serving Joint Commission related University facilities that contain clinical operations are tested and maintained. General: Power disruptions, small or large, can have a serious impact on the ability to perform critical care for our patients. The Emergency Power Standby System in each of our facilities is designed to provide emergency power in case of an electrical utility failure. These systems provide the critical power for fire and life safety, patient critical care systems, and critical equipment. Maintenance and testing of this equipment within the requirements of the Joint Commission mandates is considered to be one of the Facilities Maintenance group s highest priorities. The detection and reaction to power failures is covered under Policy System Failure Protocol. This procedure will specifically address testing and maintenance to ensure the EPSS functions properly in the event of these failures. Generator Inventory and Generator System Log Books 1. Each Generator is identified in the Computerized Management System Inventory. 2. Each building shall have a Generator System Log book. 3. Each Generator System Log Book shall contain: A. A generator summary log that summarizes the individual generator test log sheets
3 Page 3 of 6 B. A log sheet for each Generator in the system for each test performed C. An ATS summary log that summarized the individual ATS test log sheets D. A log sheet for each ATS in the system for each test performed E. Any annual load test log sheets F. Any tri-annual load test log sheets 4. Each calendar year, a new Generator System Log Book is created for each generator system. 5. Prior year Generator System Log Books will be kept for no longer than 3 years in archives. Automatic Transfer Switch Inventory and Testing Logs 1. Each Automatic Transfer Switch (ATS) is identified in the Computerized Maintenance Management System Inventory. 2. Each Automatic Transfer Switch will have identification showing the Emergency Power Standby System Generator(s) that it is connected to. 3. A listing of the ATS equipment will be kept in the Generator System Log Book as well as the ATS testing log sheets. 4. An ATS log sheet will be added to the Generator System Log Book for each ATS test. 5. An ATS summary log sheet will summarize all the ATS tests in the Generator System Log Book. Generator Testing Intervals 1. To meet The Joint Commission requirements, at intervals of not less than 20 days and not more than 40 days, the hospital tests each emergency generator for at least 30 continuous minutes. The completion dates of the tests are documented in generator testing logs by the technicians performing the tests. 2. During loaded runs, it will be the electrical shop s intention to add the static or dynamic load necessary to reach at least 30% of the nameplate value for each Generator. 3. If testing does not meet either the 30% of nameplate rating or the recommended exhaust gas temperature during any test noted above, test each emergency generator once every 12 months using supplemental (dynamic or static) loads of: 25% of nameplate rating for 30 minutes, followed by 50% of nameplate rating for 30 minutes, followed by 75% of nameplate rating for 60 minutes, for a total of 2 continuous hours. The completion date of the tests is documented in the generator testing logs by the technicians performing the tests.
4 Page 4 of 6 4. At least once every 36 months, a generator providing emergency power for the services listed in Standard EC EP s 5 and 6 will be tested for a minimum of 4 continuous hours. The completion date of the tests is documented in the generator testing logs by the technicians performing the tests. ATS Testing Intervals 1. Twelve times a year, at intervals of not less than 20 days and not more than 40 days, test all automatic transfer switches. 2. The completion date of the tests is documented in the ATS testing logs by the technicians performing the test and kept in their appropriate Generator System Log Book. 3. During each generator system test, the technician will document which Automatic Transfer Switch was used to initiate the test and each ATS that was transferred on the ATS log sheet. 4. At least one time per year, each ATS will be tested to start the generator system as part of the Generator testing. Failed Tests 1. If a required emergency power system test fails, the testing technician shall report it immediately to the Electrical Shop Supervisor or designee. 2. The Electrical Shop Supervisor will notify the University Maintenance Manager and the MUHA Infrastructure Systems Manager of the nature of the failure. If the problem is readily found and is resolved immediately, a repeated test will be scheduled as soon as possible. If there is any concern for the generator s functionality, then proceed to step three. 3. If the problem is not readily known and repairable, the Electrical Shop Supervisor, the University Maintenance Manager and MUHA Infrastructure Manager will take steps to implement measures to protect patients, visitors, and staff until necessary repairs or corrections are completed. 4. The same process shall be used in case of any related ATS switch s failure to transfer or provide a start signal to the generator. 5. If needed, Facilities Maintenance will have a temporary generator delivered and the load connected to the temporary generator until the building system is repaired and tested to function properly. 6. During times a temporary generator is used, the temporary generator will be tested within the same intervals and tested and logged as if it was part of the building system.
5 Page 5 of 6 Reporting Generator System Failures to the EOC and Clinical Staff 1. If, during testing or scheduled maintenance, emergency power is known to be unavailable for any length of time, it will be reported to the MUHA Infrastructure Manager or MUHA Electrical Shop Supervisor who will notify the EOC Chairman and the Clinical Communication Coordinator so appropriate clinical work-around activities can be put in place. 2. If the system cannot be restored immediately, a temporary generator to provide emergency power will be put in place and connected to the inoperable emergency system s load. 3. The temporary generator will be tested once it is connected and clinical operations will permitted to be performed. 4. The temporary generator will remain in place until a successful test of the building system is completed. 5. During times a temporary generator is used, the temporary generator will be tested within the same intervals and tested and logged as if it was part of the building system. Review of Testing and Maintenance of Each Generator 1. Each week, an Electrical Shop Supervisor shall review the documents for accuracy and any anomalies in data that was recorded by the technician on the testing logs. 2. If any data is missing or illegible or errors are found, the Supervisor shall contact the original testing technician and review the test information with them. If the testing log needs to be changed or corrected, the original testing technician shall indicate their agreement with the change on the document by signing their initials. 3. Every three (3) weeks or twenty-one (21) days, the Electrical Shop Supervisor shall review the Generator logs for accuracy. If any data is missing or illegible or errors are found, the Electrical Shop Supervisor shall contact the original testing technician and review the test information with them. If the testing log needs to be changed or corrected, the original testing technician shall indicate their agreement with the change on the document by signing their initials. 4. If any of the tests are deemed to be invalid, the Electrical Shop Supervisor will consult with the University Maintenance Manager and may require additional testing to be done in order to remain compliant within the intervals outlined above. Auditing of Generator Log Books 1. Every month or thirty (30) days, the University Maintenance Manager shall review the Generator logs for accuracy. If any data is missing or illegible or errors are found, the Electrical Shop Supervisor, and the original testing technician shall review the test information. 2. If the testing log needs to be changed or corrected, the original testing technician shall indicate their agreement with the change on the document by signing their initials. If any of the tests are
6 Page 6 of 6 deemed to be invalid, the University Maintenance Manager may request additional testing to be performed to maintain compliance. 3. Discrepancies found during the auditing process shall be documented for the Director of Facilities Operations. 4. Due to the critical nature of maintaining full compliance of these systems with testing, maintenance, and documentation, personnel who fail to comply with this procedure are subject to disciplinary action under the appropriate Human Resource disciplinary policy. Appendix 1: Generator Testing Templates Generator Testing Log Template Automatic Transfer Switch Log Template Please Note: these forms can be found in our in-house forms page: Note: This Policy, like all other policies within Engineering and Facilities is not a contract and should not be relied upon as such. Questions concerning Interpretation of this document or suggestions for improvement should be directed to MUSC Facilities and Engineering. Approved By: Effective Date: Greg Weigle Mark Brown September 12, 2012 Chief Facilities Officer Director of Facilities Operations Engineering & Facilities Engineering & Facilities
To describe the responsibilities, procedures and methods for the operation of the facilities work order system.
Facilities Work Order System I. Purpose To describe the responsibilities, procedures and methods for the operation of the facilities work order system. II. Scope This regulation is applicable to all personnel
More informationQUALITY ASSURANCE MANUAL JPM OF MISSISSIPPI, INC.
QUALITY ASSURANCE MANUAL JPM OF MISSISSIPPI, INC. Hattiesburg, MS Revision E 01/19/11 Revised to ISO 9001:2008 on July 9, 2009 JPM OF MISSISSIPPI, INC. MANAGEMENT QUALITY POLICY It is the goal of JPM of
More informationINSPECTION AND TESTING OF EMERGENCY GENERATORS
INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,
More informationThe State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities
Generator Testing in Nursing Facilities Introduction Recent emergencies and natural disasters have emphasized the need to ensure that nursing facilities have an adequate EPSS in place should the loss of
More informationEnvironment of Care Utility Systems Management Plan 2014 Updated 4.18.2014
Environment of Care Utility Systems Management Plan 2014 Updated 4.18.2014 PURPOSE The objectives of the Utility Systems Management plan is to establish, maintain, and continually provide a reliable utility
More informationPrime Power Services, Inc. Georgia, Carolinas 800 741 0128. NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010
Prime Power Services, Inc. Georgia, Carolinas 800 741 0128 NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010 NFPA Disclaimer The views and opinions expressed in this seminar are purely
More informationImplementation Date: November 9, 2012. Table of Contents. Section Description Page
Recommended by ITM Steering Committee: June 27, 2012 Recommended by President s Council: November 9, 2012 Approved by Executive Committee: January 24, 2013 NAIT Guideline ITM.1.6 ITS Help Desk Implementation
More informationSAFETY COMMITTEE ANNUAL PLAN TEMPLATE
SAFETY COMMITTEE ANNUAL PLAN TEMPLATE The safety committee and the unit administration work together in promoting the unit s safety and health efforts. The Safety Committee Annual Plan provides a blueprint
More informationOFFICE OF THE CITY AUDITOR
OFFICE OF THE CITY AUDITOR PERFORMANCE AUDIT OF FUEL SERVICE CARDS Paul T. Garner Assistant City Auditor Prepared by: Theresa Hampden, CPA Audit Manager Regina Cannon Auditor October 29, 2004 Memorandum
More informationCity facilities that are currently part of the System are listed below. Other City facilities may be added in the future.
Equipment and Building Services Department, Security Division Introduction The City of Dallas (City) Equipment and Building Service (EBS) Security Division is requesting Bids to provide Security System
More informationFixed Asset Inventory (FAI) Policies and Procedures
College of Education and Allied Professions Western Carolina University Purpose: Fixed Asset Inventory (FAI) Policies and Procedures This will serve as the governing document that regulates the accountability
More informationPOLICY SUBJECT: EFFECTIVE DATE: 5/31/2013. To be reviewed at least annually by the Ethics & Compliance Committee COMPLIANCE PLAN OVERVIEW
Compliance Policy Number 1 POLICY SUBJECT: EFFECTIVE DATE: 5/31/2013 Compliance Plan To be reviewed at least annually by the Ethics & Compliance Committee COMPLIANCE PLAN OVERVIEW Sound Inpatient Physicians,
More informationCOMMERCIAL CONNECTIVITY SERVICES -AT&T VPN ACCESS ATTACHMENT
COMMERCIAL CONNECTIVITY SERVICES -AT&T VPN ACCESS ATTACHMENT Last Revised: 4/8/16 1. Commercial Connectivity Services AT&T VPN Access. Pursuant to the terms and conditions of the Agreement and this Attachment,
More informationDISASTER RECOVERY. Omniture Disaster Plan. June 2, 2008 Version 2.0
DISASTER RECOVERY Omniture Disaster Plan June 2, 2008 Version 2.0 CHAPTER 1 1 Disaster Recovery Plan Overview In the event that one of our data collection environments are unavailable due to an event,
More informationClovis Municipal School District Information Technology (IT) Disaster Recovery Plan
Clovis Municipal School District Information Technology (IT) Disaster Recovery Plan Revision History REVISION DATE NAME DESCRIPTION Draft 1.0 Eric Wimbish IT Backup Disaster Table of Contents Information
More informationSEATTLE UNIVERSITY POLICY ON INVOLUNTARY LEAVE OF ABSENCE FOR MEDICAL REASONS JANUARY 2015
POLICY STATEMENT SEATTLE UNIVERSITY POLICY ON INVOLUNTARY LEAVE OF ABSENCE FOR MEDICAL REASONS JANUARY 2015 The University strives to ensure that all students can fully participate as members of the University
More informationPART 10 COMPUTER SYSTEMS
PART 10 COMPUTER SYSTEMS 10-1 PART 10 COMPUTER SYSTEMS The following is a general outline of steps to follow when contemplating the purchase of data processing hardware and/or software. The State Board
More informationSafety Resources from
Safety Resources from Sample Safety Program TABLE OF CONTENTS I. DECLARATION OF POLICY II. DUTIES AND RESPONSIBILITIES III. SAFETY COMMITTEE IV. PROGRAM REINFORCEMENT V. CORPORATE DRUG POLICY VI. HAZARD
More informationChapter 4 Emergency Management Page 1 of 5
Chapter 4 Emergency Management Page 1 of 5 CHAPTER 4 EMERGENCY MANAGEMENT 4.01 POLICY AND PURPOSE. To prepare Taylor County to promptly and adequately respond to and cope with various emergencies resulting
More informationHow To Monitor A Municipality
UMHLABUYALINGANA MUNICIPALITY ACTIVITY MONITORING POLICY AND PROCEDURE Activity Monitoring Policy and Procedure Approval and Version Control Approval Process: Position or Meeting Number: Date: Originator
More informationCHAPTER 11 COMPUTER SYSTEMS INFORMATION TECHNOLOGY SERVICES CONTROLS
11-1 CHAPTER 11 COMPUTER SYSTEMS INFORMATION TECHNOLOGY SERVICES CONTROLS INTRODUCTION The State Board of Accounts, in accordance with State statutes and the Statements on Auditing Standards Numbers 78
More informationQuality Assurance Policy And Project Organisation Plan
Quality Assurance Policy Quality Assurance Policy And Project Organisation Plan This document defines the general policy for Quality Assurance to be used for the whole project. It gives the project organisation,
More informationNMSU Procedural Guidelines (Policy 2.64 - Security Cameras on University Premises)
NMSU Procedural Guidelines (Policy 2.64 - Security Cameras on University Premises) A. NMSU Entities requesting security cameras will be required to follow the procedures outlined below. 1. Justification
More informationCMS/Accreditation Surveys The Physical Environment
CMS/Accreditation Surveys The Physical Environment Critical Aspects for 2013 Presenter Robert H. Bartels, CHFM CHSP CHEP SASHE President Safety Management Services, Inc. A program presented by: SAFETY
More informationM E D I C AL D I AG N O S T I C S P E C I AL I S T Schematic Code 14251 (31000081)
I. DESCRIPTION OF WORK M E D I C AL D I AG N O S T I C S P E C I AL I S T Schematic Code 14251 (31000081) Positions in this banded class perform skilled technical work in the administration of specialized
More informationmeans the charges applied by Ancar B Technologies Limited which recur annually;
This Service Schedule is supplemental to the Master Service Agreement Net-L1-3. CONTENTS Schedule 1 - DEFINITIONS... 1 Schedule 2 - MANAGED INTERNET ACCESS SERVICE PRODUCT INFORMATION... 3 1 MANAGED INTERNET
More informationCommunity Unit School District No. 308 5:110. General Personnel. A safety-sensitive function includes, but is not limited to:
General Personnel Bus Driver Controlled Substance and Alcohol Testing I. Introduction Page 1 of 11 Unless specifically stated otherwise, the terms of this policy are to implement the Department of Transportation
More informationFacilities Planning & Management Maintenance Repair Parts Policies & Procedures
Facilities Planning & Management Policies & Procedures Revised 10/2013 Facilities Planning & Management Policies & Procedures PURCHASE REQUESTS cspolicy1.wpd 1-4 ISSUES FROM STOCK cspolicy2.wpd 5-7 MONTHLY
More informationSupplier/ Vendor Evaluation Form
. Dated 1. General: Supplier/ Vendor Evaluation Form i. Name of Supplier/ Vendor: i Address of Supplier/ Vendor: Contact Person: Phone. v. Fax. v vi ix. Email: Web Address: Year of Establishment: Facility
More informationProtocol for the use of Mobile Phones. For Schools Managed staff and Centrally Employed Teachers
Protocol for the use of Mobile Phones For Schools Managed staff and Centrally Employed Teachers May 2015 Contents 1.0 Introduction 2.0 Principles 3.0 Use of mobile phones during the working day 4.0 Business
More informationBROWARD AMATEUR RADIO CLUB, INC. BY-LAWS (As Adopted, November, 2011) 1.1 The name of the organization is: Broward Amateur Radio Club, Inc.
BROWARD AMATEUR RADIO CLUB, INC. BY-LAWS (As Adopted, November, 2011) 1.0 NAME 1.1 The name of the organization is: Broward Amateur Radio Club, Inc. 2.0 PURPOSE 2.1 To promote the association of amateur
More informationNC SBI QUALITY ASSURANCE PROGRAM
NC SBI QUALITY ASSURANCE PROGRAM for the SBI Reviewed by: Deputy Assistant Director Bill Weis Date: Approved by: Assistant Director Jerry Richardson Date: Originating Unit: SBI Effective Date: July 25,
More informationCCG: IG06: Records Management Policy and Strategy
Corporate CCG: IG06: Records Management Policy and Strategy Version Number Date Issued Review Date V3 08/01/2016 01/01/2018 Prepared By: Consultation Process: Senior Governance Manager, NECS CCG Head of
More informationCopies of this document shall be classified either as Controlled or Uncontrolled, and shall be identified as such on the cover sheet.
INTRODUCTION This document describes an inspection system broken down into four separate levels. When Inspection Level IV is invoked, this system meets the requirements of former MIL-I-45208A. The primary
More informationInstallation and Operational Qualification Protocol (Reference: SOP )
Project Name Equipment Process Line/Location Project Number Serial Number Model Number Protocol number WRITTEN BY: REVIEWED BY: Position APPROVAL TO EXECUTE: Position: PROTOCOL COMPLETION APPROVAL: Position:
More informationFIRE ALARM AND PROTECTIONS SYSTEM BYLAW
FIRE ALARM AND PROTECTIONS SYSTEM BYLAW Section 1: Purpose and Intent The proliferation of fire alarm systems monitored by the Boxborough Fire Department has imposed an increasing burden on said Department.
More informationHuman Resources Management Policy. Leave Transfer Program. Policy 48
Human Resources Management Policy Leave Transfer Program Policy 48 NOTE: THIS POLICY, LIKE ALL OTHER MUSC HUMAN RESOURCES POLICIES, IS NOT A CONTRACT OF EMPLOYMENT AND SHOULD NOT BE RELIED UPON AS SUCH.
More informationAustin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
More informationDisaster Recovery and Business Continuity Plan
Disaster Recovery and Business Continuity Plan Table of Contents 1. Introduction... 3 2. Objectives... 3 3. Risks... 3 4. Steps of Disaster Recovery Plan formulation... 3 5. Audit Procedure.... 5 Appendix
More informationInspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationK12 FLORIDA LLC POLICIES AND PROCEDURES RELATED TO PARTICIPATION IN STATE TESTING
K12 FLORIDA LLC POLICIES AND PROCEDURES RELATED TO PARTICIPATION IN STATE TESTING These K12 Florida LLC Policies and Procedures Related to Participation in State Testing are posted on our disclosure website
More informationElectronic copies on the Sharepoint are considered controlled. All other copies are to be considered uncontrolled
Title: Element 12 BMP Documentation and Document Control City of Grand Rapids Environmental Services Department Policies and Procedures Created by: Dave Harris Approved by: William R. Kaiser Policy Number:
More informationInformation Security Risk Assessment Checklist. A High-Level Tool to Assist USG Institutions with Risk Analysis
Information Security Risk Assessment Checklist A High-Level Tool to Assist USG Institutions with Risk Analysis Updated Oct 2008 Introduction Information security is an important issue for the University
More informationQuality Management System Manual
Effective Date: 03/08/2011 Page: 1 of 17 Quality Management System Manual Thomas C. West Eric Weagle Stephen Oliver President ISO Management General Manager Representative Effective Date: 03/08/2011 Page:
More informationSCARC, Inc. 11 US Route 206, Suite 100 Augusta, NJ 07822 973-383-7442
Section: D.6 Page 1 of 5 The purpose of this policy is to define Supported Employment, describe SCARC s Supported Employment, and establish standards and procedures for job development and support for
More informationtips How smallchangescan saveyou big, &
warehousesafety tips How smallchangescan saveyou big preventaccidentsreduceinjuries, & increaseproductivity.. Table of Contents Welcome Statement...4 Safety Policy Statement...5 Guiding Principles...6
More informationHealth and Safety Activity Checklist
Health and Safety Activity Checklist Workplace Health, Safety and Compensation Commission of New Brunswick WHSCC CSSIAT Commission de la santé, de la sécurité et de l indemnisation des accidents au travail
More informationIntroduction. General Use
Introduction Dane County provides a variety of technological resources to its employees to improve public service and maximize efficiency. The purpose of this policy is to advise users regarding the use
More informationProduct Support and Maintenance Terms & Conditions
Product Support and Maintenance Terms & Conditions 1. Customer Information Customer site address: As per invoice (unless otherwise agreed) Equipment or Software to be covered: Refer to invoice Contract
More informationSection 2. A new Chapter 8.38 is hereby added to Title 8 of the Brea City Code to read as follows: CHAPTER 8.38: REGULATION OF ALARM SYSTEMS
ORDINANCE NO. [DRAFT 04-07-04] AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF BREA ESTABLISHING REGULATIONS FOR THE OPERATION OF ALARM SYSTEMS The City Council hereby ordains as follows: Section 1. Chapter
More informationA Comparison. Safety and Health Management Systems and Joint Commission Standards. Sources for Comparison
and Standards A Comparison The organizational culture, principles, methods, and tools for creating safety are the same, regardless of the population whose safety is the focus. The. 2012. Improving Patient
More informationSAMPLE IT CONTINGENCY PLAN FORMAT
SAMPLE IT CONTINGENCY PLAN FORMAT This sample format provides a template for preparing an information technology (IT) contingency plan. The template is intended to be used as a guide, and the Contingency
More informationControl of Hazardous Energy (Lockout / Tagout)
WAUKESHA COUNTY TECHNICAL COLLEGE Control of Hazardous Energy (Lockout / Tagout) Release Date: March 26, 2012 Revision Date: March 26, 2012 Revision Level: 1 TABLE OF CONTENTS Purpose... 1 Scope... 1 Responsibilities...
More informationWORKSTATION MANAGEMENT STANDARD PROCEDURES
OFFICE OF THE VICE PRESIDENT FOR INFORMATION TECHNOLOGY POST OFFICE BOX 8122 STATESBORO, GEORGIA 30460-8122 TELEPHONE (912) 478-1294 FAX (912) 478-7720 WORKSTATION MANAGEMENT STANDARD PROCEDURES I. Authorization
More informationPHILADELPHIA POLICE DEPARTMENT DIRECTIVE 7.18
PHILADELPHIA POLICE DEPARTMENT DIRECTIVE 7.18 Issued Date: 12-23-14 Effective Date: 12-23-14 Updated Date: SUBJECT: GRANT APPLICATIONS, PROCESSING AND ADMINISTRATION PLEAC 1.6.1 1. PURPOSE A. The purpose
More informationStaff Mobile Phone Policy
Staff Mobile Phone Policy Thistley Hough January 2013 Date policy initially accepted by Governors: Date of Review 1: Date Review 1 Completed: 11 th January 2013 The purpose of this protocol is to inform
More informationLASER SAFETY MANUAL UNIVERSITY OF KENTUCKY POLICIES AND PROCEDURES FOR LASER USERS REVISED EDITION 2012 ISSUED BY
LASER SAFETY MANUAL UNIVERSITY OF KENTUCKY POLICIES AND PROCEDURES FOR LASER USERS REVISED EDITION 2012 ISSUED BY UNIVERSITY OF KENTUCKY RADIATION SAFETY OFFICE TABLE OF CONTENTS POLICY AND PURPOSE 2 LASER
More informationSOFTWARE UPDATE SERVICES (SUS)
SOFTWARE UPDATE SERVICES (SUS) These Software Update Services terms and conditions ( Terms and Conditions ) apply to any quote, order, order acknowledgment, and invoice, and any sale or provision of Software
More informationThis interpretation of the revised Annex
Reprinted from PHARMACEUTICAL ENGINEERING The Official Magazine of ISPE July/August 2011, Vol. 31 No. 4 www.ispe.org Copyright ISPE 2011 The ISPE GAMP Community of Practice (COP) provides its interpretation
More information543.7 What are the minimum internal control standards for bingo?
Bingo Purpose This section provides guidance on the development of internal controls, policies, and procedures for the operation of bingo. It has been compiled by tribal regulators, Class II gaming operators,
More informationGENERAL APPLICATION FOR ELECTRONIC COMMUNICATION SYSTEM ( ECS ) INSURANCE
GENERAL APPLICATION FOR ELECTRONIC COMMUNICATION SYSTEM ( ECS ) INSURANCE (CLAIMS MADE BASIS) APPLICANT S INSTRUCTIONS: 1. Answer all questions. If the answer requires detail, please attach a separate
More informationNORTH AMERICA OPERATIONS. (Fairmont and Montreal Facilities) QUALITY MANUAL. Prepared to comply with the requirements of ISO 9001:2008
WEIGH-TRONIX CANADA ULC NORTH AMERICA OPERATIONS (Fairmont and Montreal Facilities) QUALITY MANUAL Prepared to comply with the requirements of ISO 9001:2008 Meets or exceeds the requirements for design,
More informationCity of Grand Rapids Environmental Services Department Policies and Procedures
Title: Element 12 EMS Documentation and Document Control City of Grand Rapids Environmental Services Department Policies and Procedures Approved by: Policy Number: 1103-12 Effective: 2/16/2006 General
More informationOHIO VALLEY EDUCATIONAL COOPERATIVE TECHNOLOGY ACCEPTABLE USE POLICY
OHIO VALLEY EDUCATIONAL COOPERATIVE TECHNOLOGY ACCEPTABLE USE POLICY 03.13211 Referenced by OVEC Policy Manual and OVEC Employee Handbook Version 2.0.0 2/12/2014 Section headings: 1. Introductory paragraph
More informationSTATE OF MISSOURI, DEPARTMENT OF NATURAL RESOURCES MISSOURI AIR CONSERVATION COMMISSION PERMIT TO CONSTRUCT
--.--~.-------------------------------- STATE OF MISSOURI, DEPARTMENT OF NATURAL RESOURCES MISSOURI AIR CONSERVATION COMMISSION PERMIT TO CONSTRUCT Under the authority of RSMo 643 and the Federal Clean
More informationNOTE: In the event that the seal is accidentally broken, the narcotic may be wasted via narcotic wastage procedures.
HOSPITAL NAME INSTITUTIONAL POLICY AND PROCEDURE (IPP) Department: Manual: Section: TITLE/DESCRIPTION POLICY NUMBER NARCOTICS AND CONTROLLED DRUGS EFFECTIVE DATE REVIEW DUE REPLACES NUMBER NO. OF PAGES
More informationCHAPTER 5 - SAFETY ASSESSMENTS, LOG OF DEFICIENCIES AND CORRECTIVE ACTION PLANS
CHAPTER 5 - SAFETY ASSESSMENTS, LOG OF DEFICIENCIES AND CORRECTIVE ACTION PLANS A. INTRODUCTION... 1 B. CHAPTER-SPECIFIC ROLES AND RESPONSIBILITIES... 1 C. SAFETY PROGRAM ASSESSMENT PROCESS... 3 D. FACILITY-MAINTAINED
More informationDAIDS Appendix 2 No.: DWD-POL-DM-01.00A2. Data Management Requirements for Central Data Management Facilities
DAIDS Appendix 2 No.: DWD-POL-DM-01.00A2 Data Management Requirements for Central Data Management Facilities The following clinical trial data management requirements must be met in order to ensure the
More informationM.I.E.M.S.S. REGION V ALERT STATUS SYSTEM
M.I.E.M.S.S. REGION V ALERT STATUS SYSTEM Approved by the Maryland Region V EMS Advisory Council January 28, 1999 Amended November 16, 2000 Reprinted with Corrections January 16, 2001 Note: Patients destined
More informationEMNAMBITHI/LADYSMITH MUNICIPALITY CHANGE MANAGEMENT POLICY
EMNAMBITHI/LADYSMITH MUNICIPALITY CHANGE MANAGEMENT POLICY Emnambithi/Ladysmith Municipality Change Management Policy 2015/2016 Page 1 of 7 Document Configuration Management Document Identification File
More informationWORKPLACE HEALTH AND SAFETY AUDITING GUIDELINES
WHS UNIT WORKPLACE HEALTH AND SAFETY AUDITING GUIDELINES Contents 1 Purpose... 1 2 Scope... 1 3 Definitions... 1 4 Responsibilities... 1 4.1 WHS Unit... 1 4.2 Auditor(s)... 1 4.3 Managers of Faculties
More informationQuality Certificate for Kaspersky DDoS Prevention Software
Quality Certificate for Kaspersky DDoS Prevention Software Quality Certificate for Kaspersky DDoS Prevention Software Table of Contents Definitions 3 1. Conditions of software operability 4 2. General
More informationQuality Management System Manual Revision L
This Page 1 of 35 of the Quality Management System Manual If issued as a controlled copy, the serial number of this copy is Quality Management System Manual Certified to AS9100 Revision C Printed copies
More informationUNCONTROLLED COPY FOR REFERENCE ONLY
CLOVER MACHINE AND MFG. 800 MATHEW ST. #101 SANTA CLARA, CA 95050 727-3380 727-7015 fax REVISION: DATE: PAGE 1 OF 45 QUALITY POLICY MANUAL DISTRIBUTION LIST: President Purchasing Manager Vice President
More informationISO 9001: 2008 Construction Quality Management System Sample - Selected pages (not a complete plan)
ISO 9001: 2008 Construction Quality Management System Sample - Selected pages (not a complete plan) Part 1: Project-Specific Quality Plan Part 2: Company Quality Manual Part 3: Submittal Forms Part 4:
More informationNew Jersey Administrative Code. Encumbrance Accounting and Certifications of Availability of Funds
New Jersey Administrative Code N.J.A.C. 5:30-5.1 to 5.5. 5:30-5.1 5:30-5.2 5:30-5.3 5:30-5.4 5:30-5.5 Encumbrance Accounting and Certifications of Availability of Funds General authority Encumbrance systems
More informationDocument Title: Trust Approval and Research Governance
Document Title: Trust Approval and Research Governance Document Number: SOP034 Staff involved in development: Job titles only Document author/owner: Directorate: Department: For use by: RM&G Manager, R&D
More informationContra Costa Community College District Business Procedure 10.57 SECURITY CAMERA OPERATING PROCEDURE
Contra Costa Community College District Business Procedure 10.57 SECURITY CAMERA OPERATING PROCEDURE The District and its colleges are committed to enhancing the quality of life of the community by integrating
More informationUniversity of San Francisco
University of San Francisco Acceptable Use Policy (AUP) & Agreement for POS Devices and PCI Network 1. Purpose University of San Francisco (USF) provides access to the PCI network for processing CASHNet
More informationD. Student and Academic. Academic Scheduling and Timetabling
OLDS COLLEGE POLICY Olds College recognizes the need for Policies and Procedures, and the need for staff and students to be familiar with and follow such policies and procedures. It is the intent of Olds
More informationDedicated Servers (Fixed and Custom Configurations) Service Level Agreement
Dedicated Servers (Fixed and Custom Configurations) Service Level Agreement Terms and Abbreviations Customer's Control Panel the web page intended for managing the Services rendered by the Executor, retaining
More informationAVNET Logistics & EM Americas. Quality Manual
AVNET Logistics & EM Americas Quality Manual Avnet is committed to ensuring customer satisfaction while meeting all customer and applicable legal, statutory and regulatory requirements. This is accomplished
More informationGFRS Quality Assurance (Fire Safety) Policy Statement
GFRS Quality Assurance (Fire Safety) Policy Statement This document details the internal auditing procedures (Quality assurance of fire safety standards) that the GFRS will use to ensure that the professional
More informationExtremeWorks Remote Monitoring Service
SERVICE DESCRIPTION DOCUMENT (SDD) ExtremeWorks Remote Monitoring Service Service: ExtremeWorks Managed Service Remote Monitoring Service Version: 1.0 Date: November 2015 Availability: Global Order Code:
More informationIntrado Call Handling CPE. Standard Maintenance and Support Services ( MSS Terms )
Intrado Call Handling CPE Standard Maintenance and Support Services ( MSS Terms ) These Maintenance and Support Services terms ( MSS Terms ) describe the current offerings for maintenance and support services
More informationPOUGHKEEPSIE CITY SCHOOL DISTRICT PUPIL PERSONNEL DEPARTMENT S MEDICAID BILLING COMPLIANCE PROGRAM AND PROCEDURES
POUGHKEEPSIE CITY SCHOOL DISTRICT PUPIL PERSONNEL DEPARTMENT S MEDICAID BILLING COMPLIANCE PROGRAM AND PROCEDURES INTRODUCTION This Poughkeepsie City School District Medicaid Billing Compliance Program
More informationGENERAL WELDING & FABRICATING, INC. 991 Maple Road Elma, New York 14059
QUALITY MANUAL GENERAL WELDING & FABRICATING, INC. 991 Maple Road Elma, New York 14059 Distribution: Position Location Copy # President / CEO Office 1 Operations Manager Office 2 Quality Assurance Office
More informationService Level Agreement for Database Hosting Services
Service Level Agreement for Database Hosting Services Objective Global Service Levels include the general areas of support that are applicable to every ITS service. The purpose of the Service Level Agreement
More informationGLOSSARY. Glossary of Terms for Capacity Based Demand Response PUBLIC. Issue 3.0 GOT-1
PUBLIC GOT-1 GLOSSARY Glossary of Terms for Capacity Based Demand Response Issue 3.0 This document provides a glossary of terms with definitions used in the Capacity Based Demand Response program. Public
More informationArchiving of Research Documentation
Suspension, Termination & Completion Standard Operating Procedure VERSION / REVISION: 2.0 EFFECTIVE DATE: 28 05 12 REVIEW DATE: 28 05 14 AUTHOR(S): CONTROLLER: APPROVED BY: Clinical Trials Manager; Recruitment
More informationCHAPTER 99-01.3-04 BINGO
Section 99-01.3-04-01 Bingo 99-01.3-04-02 Equipment 99-01.3-04-03 Conduct and Play 99-01.3-04-04 Cash Register 99-01.3-04-05 Tickets 99-01.3-04-06 Paper Card Count 99-01.3-04-07 Floorworker Sales Report
More informationMDOT ITS Document Control and Management Plan
MDOT ITS Document Control and Management Plan Document No.: MDOT-ITS 001-01-002 Version: 1.0 Prepared by: Gresham Smith and Partners & URS August 19, 2009 Revision History Date Version Description 5/9/2008
More information1 OF 7. there will be few "surprises" as the work progresses.
1 OF 7 FP-G1.94 GUIDELINES FOR SUCCESSFUL SUPERVISION OF SCHOOL DISTRICT CAPITAL CONSTRUCTION PROJECTS There is no doubt that the successful completion of any capital construction project is the result
More informationHealth and Safety Policy and Procedures
Health and Safety Policy and Procedures Health & Safety Policy & Procedures Contents s REVISION AND AMENDMENT RECORD : Summary of Change Whole Policy 4.0 05 Nov 08 Complete re-issue Whole Policy 4.1 10
More informationSTATE HOSPITAL QUALITY PROCEDURES MANUAL
APPROVED BY: PAGE: Page 1 of 8 1.0 Purpose To define a complaints procedure which is as transparent, fair and impartial as possible to all users and providers of the services undertaken by the State Hospital.
More informationDisciplinary Action Rule
West Virginia Northern Community College Disciplinary Action Rule Rule Number: NC-2031 Effective Date: April 1, 2009 Date Approved by WVNCC Board of Governors: March 26, 2009 Authority Reference: WV Code
More informationEmergency Operations California State University Los Angeles
Business Continuity Plan Emergency Operations California State University Los Angeles 1. Objective & Scope 2. Definition of Disaster 3. Risk and Business Impact Analysis Summary 4. Business Continuity
More informationDefense Security Service (DSS)
Defense Security Service (DSS) Center for Development of Security Excellence (CDSE) ADMINISTRATIVE INQUIRY (AI) PROCESS JOB AID July 2011 TABLE OF CONTENTS 1. INTRODUCTION... 1 1.1 Scope... 1 2. PRELIMINARY
More information