1 Products Solutions Services High Level Alarms Industrial Safety
2 Erwin Post Product Manager Level Tankgauging Praxis mit Gamma. Only a safe plant is economical Endress+Hauser B.V. Nikkelstraat AJ Naarden The Netherlands Phone: Mobile: Fax: Erwin.Post@nl.endress.com
3 Topics Overfill prevention Bunchfield lessons learned PGS29 translation Tank types and level detection State of the art SIL level technology Only a safe plant is economical
4 The Buncefield facility
5 Buncefield overspill incident
6 Even visible from space
7 Buncefield days after.
8 And no casualties (thank God it s was Sunday)
9 The Buncefield incident Fuel depot in Buncefield near London Sunday morning, December 11th, 2005 Failure of level measurement, no change in level indication High level alarm in override. Overspill of 300m 3 of gasoline. Heavy explosion 40 people injured No fatal casualties Depot and surroundings have been heavily damaged Took several days before the fire was under control Environmental emissions and damage.
10 Products Solutions Services High Level Alarms
11 Lessons learned Recommendation 3: Operators of Buncefield-type sites should protect against loss of containment of petrol and other highly flammable liquids by fitting a high integrity, automatic operating overfill prevention system (or a number of such systems, as appropriate) that is physically and electrically separate and independent from the tank gauging system.
12 Lessons learned Recommendation 5: All elements of an overfill prevention system should be proof tested in accordance with the validated arrangements and procedures sufficiently frequent to ensure the specified safety integrity level is maintained in practice in accordance with the requirements of Part 1 of BS EN
13 Post Buncefield effect Oops, can that happen to us too? Are the risk assessments OK? Are the HAZOP studies done? Did we cover all scenarios? Authorities start to interfere Regulations are improved or re-written (PGS 29) Proof testing becomes mandatory! What about SIL?
14 SIL Legal status Legal framework Seveso Directive [ Seveso II - Directive 96/84/EC] Workers protection regulations (social) Environmental regulations Associated permits or license system, local, regional or even national Regulations require state of the art equipment for safety assurance State of the art is defined in standards. i.e. for functional safety EN/IEC [EN August 2002] (generic standard) EN/IEC [EN August 2004] (process industry standard)
15 PGS29:2008, 84 pages.
16 PGS29:2008, 84 pages Hoogniveau-alarmering en overvulbeveiliging 87. Tanks moeten zijn uitgevoerd met: a. een hoogniveau-alarmering die ter plaatse en / of in de controlekamer, alarm geeft, voordat het hoogst toelaatbare vloeistofniveau in de tank wordt bereikt, zodat maatregelen genomen kunnen worden om de pompcapaciteit te verminderen of het verpompen te stoppen, en; b. een fysiek onafhankelijke instrumentele overvulbeveiliging die bij het bereiken van het hoogst toelaatbare vloeistofniveau in de tank de toevoer naar de tank doet stoppen.
17 PGS29:2008, 84 pages. De betrouwbaarheid van de instrumentatie en beveiligingen moet in relatie staan tot het veiligheidsrisico. Er dient een methodiek gehanteerd te worden die de samenhang tussen de risico s, vastgesteld middels veiligheidsstudies, en (de betrouwbaarheid van de) maatregelen (instrumentatie en beveiligingen) aantoont en documenteert. Voorbeelden van methodieken: SIL-systematiek waarin, afhankelijk van de gewenste risicoreductie, eisen worden gesteld aan de keuze en onderhoudsfrequentie/type van de benodigde regelingen en beveiligingen; (NEN-EN 61511/61508) safety-layerssystematiek, bijv. LOPA; bedrijfsbeleid waarmee het risico gekoppeld wordt aan de maatregel; b.v. bij een scenario met risicowaardering X moeten minimaal twee onafhankelijke LOD s (Lines Of Defense) worden ingezet om het risico te beheersen.
18 PGS29:2008, 84 pages. Toelichting: Indien bij scheepslossingen de tweede beveiliging technisch niet mogelijk is, kan in overleg met het bevoegd gezag hiervan afgezien worden of een alternatieve oplossing worden overeengekomen met een aanvaardbaar beschermingsniveau. Onder fysiek onafhankelijk wordt verstaan: Los van niveaumeting Apart stuursignaal Onder overvulbeveiliging wordt verstaan: Elk systeem dat de toevoer tot de tank automatisch doet stoppen zonder tussenkomst van een operator.
19 Simple instrument safety rules still apply A good High Level Alarm typically: is based on a different physical phenomenon (avoid systematic failures) is Fail to Safe classified for SIL services is active (needs power to operate) is proven technology has all appropriate certificates (IEC 61508/61511) is provided with internal diagnostics is preferably provided with a separate failure alarm can be checked easily. Proof testing has a long, predictable lifetime can be repaired immediately without process interference
20 Typical bulk liquid storage tanks Possibilities are determined by tank constructions Fig. a. storage tank with conical roof Fig. b. storage tank with external floating roof
21 Fixed Roof SAFE HHLA Solutions Tuning Fork Measurement of aggregation phase by density, Gas versus Liquid Radar and Guided Wave Radar. Measurement of true level using di-electric impedance jump at phase change
22 Liquid Bulk Storage, Independent High Level Alarms State of the art. Liquiphant is always the first solution. SIL2/3 Compliant - IEC61508/IEC61511 Loop approach! Suitable for all Cone Roof Tanks using existing tank fittings. Very simple and cost effective proof testing by push button only!
23 Liquiphant summary Liquiphant is an active in-situ density measurement rather than a switch! Density change of liquids is huge and the absolute density of liquid phase is irrelevant thus providing a robust physical deviation. Easy test methodology using push button activated test generator Simplicity of the concept offers extremely low failure rates. Availability joined to the highest safety level! Proven as robust. Reliable lifetime is typically long!
24 Function Principle evaluation electronic filter / amplifier phase shift amplifier
25 Self-Monitoring Safe alarm function Immersion depth fa -15% switch point approx. 850 Hz fa oscillation frequency in air approx. 1 khz 25 mm 0 A L A R M A L A R M fa -15% fa fa + 6,5% 1500 f [Hz] sensor alarm 0,4 s delayed normal operation corrosion alarm 60 s delayed sensor Alarm 0,4 s delayed
26 Recurring Proof Test of Overspill Protections switch relay test generator switch switching electronic pulse switch receiver fault relay
27 Push button proof test coverage (1) λ du 40 FIT Drive current Resonance frequency Only the resonance controller is not covered Frequency λ du controller: 10 FIT [FIT = h )
28 Push button proof test coverage (2) Failure rate FTL5* and 7* series connected to FTL325P 2,100E-03 1,750E-03 1,400E-03 PFD 1,050E-03 7,000E-04 PTC 75% 3,500E-04 0,000E yr
29 Overview of measures for SIS according to IEC61511 Component Level Systematic Failures & Random Failures & Certified IEC Prove in application or Proven-in use [supplier] or Prior-use demonstration [user] PFD avg Certified IEC61508 Failure Tolerance Redundancy 1oo1 1oo2 2oo2 2oo3
30 Fixed Roof SAFE HHLA Solutions Tuning Fork Measurement of aggregation phase by density, Gas versus Liquid Radar and Guided Wave Radar Measurement of true level using di-electric impedance jump at phase change
31 Liquid Bulk Storage - Fixed Roof Tanks Guided radar Suitable for all Cone Roof Tanks using existing tank fittings on tank. Continuous level Measurement. Flexible set points via 4-20mA Signal Deviation alarms possible (comparing with ATG) Provided with internal redundancy using End Of Probe algorithm SIL 2/3 Compliant - IEC61508 Safety parameters are state of the art. Proof testing by generating test signals.
32 Developed according IEC61508 Continuous automatic internal check in the device Logic program run control Check Reference pulse HF Quartz synchronization Measuring cycle time Supply voltage Temperature Check sum RAM Cable breakage Continuous self-monitoring to check the correct functionality of the device More than 80 diagnostic measures and techniques permanently running in the background
33 Proof test from control room Proof procedure via manual started self check (proof test) Check Send Developed acc. to IEC61508, also the data communication between Device-DTM and device is secured (send check).
34 HistoROM Example HistoROM functionality Electronic change during night shift The HistoROM is fixed in the housing (can not be lost or forgotten )
35 Floating Roof Safe HHLA Solutions (Tuning fork Stilling well mounted is always preferred) Free Field Radar, Time of Flight Measurement of roof level using dielectric reflection at phase change Capacitance type contact switching Measurement of dielectric impedance change by roof contact
36 Floating Roof Tanks Free Space Radar Free Space Radar Suitable for all tank types (Excluding Spheres). Continuous level Measurement. Flexible set points via 2-wire 4-20mA Signal SIL2/3 Compliant - IEC61508 Proof testing by test generator
37 Floating Roof Tanks Free Space Radar Proof Testing external External Swivel plate for functional proof testing
38 Floating Roof Tanks Radar Proof Testing integral design Complete with checker mechanism to enable safe alarm checks can be performed and ensuring Zone segregation.
39 Developed according IEC61508 Continuous automatic internal check in the device Logic program run control Check Reference pulse HF Quartz synchronization Measuring cycle time Supply voltage Temperature Check sum RAM Cable breakage Continuous self-monitoring to check the correct functionality of the device More than 80 diagnostic measures and techniques permanently running in the background
40 Floating Roof Safe HHLA Solutions (Tuning fork Stilling well mounted is always preferred) Free Field Radar, Time of Flight Measurement of roof level using dielectric reflection at phase change Capacitance type contact switching Measurement of dielectric impedance change by roof contact
41 Floating Roof Tanks (alternatively) Capacitance Capacitance Probe Suitable for all Cone Roof Tanks using existing tank fittings on tank. Suitable for Floating Decks. Flexible set points via 4-20mA Signal, or via switch point. SIL2 Compliant - IEC61508/IEC61511 Snow tolerant solution Hard to test (mechanical contact required)
42 Secure Switch Settings using Contact Plate
43 Floating roof failure scenarios Snow cover Damaged deck Lost deck Free space Radar May lead to lost echo Fails Safe Availability increased using new Advanced May lead to lost and deflected echo depending on deck position Fails Safe May lead to some switch point deviation (up to 100 mm) No failure Dynamics design Capacitance type Top of snow detected as raised level No Failure Switch level may raise depending on deck position May fail when deck gets over flooded May lead to severe switch point deviation Fails dangerous May become safe when weight is modified
44 Summary Overfill prevention Bunchfield lessons learned PGS29 translation Tank types and level detection State of the art SIL level technology Only a safe plant is economical
45 Products Solutions Services Thank you very much for your attention
Liquid Level Limit Switch liquiphant T FTL 20
Technical Information TI 64F/4/ae Liquid Level Limit Switch liquiphant T FTL 0 Level limit switch for liquids Applications The Liquiphant T FTL 0 is a level limit switch for virtually any kind of fluid
More informationGMP-Z Annex 15: Kwalificatie en validatie
-Z Annex 15: Kwalificatie en validatie item Gewijzigd richtsnoer -Z Toelichting Principle 1. This Annex describes the principles of qualification and validation which are applicable to the manufacture
More informationTank Gauging & Inventory Management Solutions
& Inventory Management Solutions Automation solutions for oil & gas, defense and aviation applications FuelsManager, Varec s industry-leading software is available in four editions: Standard, Professional,
More informationSelecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004)
Selecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004) Dale Perry Worldwide Pressure Marketing Manager Emerson Process Management Rosemount Division Chanhassen, MN 55317 USA
More informationCO-BRANDING RICHTLIJNEN
A minimum margin surrounding the logo keeps CO-BRANDING RICHTLIJNEN 22 Last mei revised, 2013 30 April 2013 The preferred version of the co-branding logo is white on a Magenta background. Depending on
More informationSAFETY MANUAL SIL Switch Amplifier
PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SR-(Ex)*(.LB)(.SP), HiC282* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The General
More informationWhy SIL3? Josse Brys TUV Engineer j.brys@hima.com
Why SIL3? Josse Brys TUV Engineer j.brys@hima.com Agenda Functional Safety Good planning if specifications are not right? What is the difference between a normal safety and SIL3 loop? How do systems achieve
More informationIsolating Barriers for our sensors A5S1 in Ex-areas Series D461
D46 Isolating Barriers for our sensors A5S1 in Ex-areas Series KEY FEATURES ATEX / IECEx certified, also approval for UL / CSA and EAC (Russia, Kazakhstan and Belarus Customs Union) Protection grade Ex
More informationTriple Waveband Infra-Red Flame Detection
Minerva S200PLUS Ex ia Intrinsically Safe & Ex d Flameproof Solar Blind Flame Detectors Triple Waveband Infra-Red Flame Detection Key Features Unrivalled black body rejection over a wide range of source
More informationBasic Fundamentals Of Safety Instrumented Systems
September 2005 DVC6000 SIS Training Course 1 Basic Fundamentals Of Safety Instrumented Systems Overview Definitions of basic terms Basics of safety and layers of protection Basics of Safety Instrumented
More informationIEC 61508 Functional Safety Assessment. Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter.
61508 SIL 3 CAPABLE IEC 61508 Functional Safety Assessment Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter Customer: K-TEK Corporation Prairieville, LA USA Contract No.:
More informationInstruction Manual Service Program ULTRA-PROG-IR
Instruction Manual Service Program ULTRA-PROG-IR Parameterizing Software for Ultrasonic Sensors with Infrared Interface Contents 1 Installation of the Software ULTRA-PROG-IR... 4 1.1 System Requirements...
More informationFMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany
FMEDA and Proven-in-use Assessment Project: Inductive NAMUR sensors Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 03/11-10 Report No.: P+F 03/11-10 R015 Version V1, Revision R1.1, July
More informationCONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
More informationThyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
More informationCLASSIFICATION NOTES
CLASSIFICATION NOTES Type Approval, Installation and Testing of Water Level Detectors on Bulk Carriers and Single Hold Cargo Ships other than Bulk Carriers General Information This edition of the classification
More informationVIBROCONTROL 4000. Sensitive Machine Monitoring
VIBROCONTROL 4000 Sensitive Machine Monitoring Reliable Machine Protection with VIBROCONTROL 4000 Brüel & Kjaer Vibro has for many years been one of the leading manufacturers of machine protection systems.
More informationSAFETY MANUAL SIL RELAY MODULE
PROCESS AUTOMATION SAFETY MANUAL SIL RELAY MODULE KFD0-RSH-1.4S.PS2 ISO9001 3 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories BF 18 Mounting flange, 18 mm EXG-18 Quick mounting bracket with dead stop Technical Data specifications
More informationEffective Compliance. Selecting Solenoid Valves for Safety Systems. A White Paper From ASCO Valve, Inc. by David Park and George Wahlers
Effective Compliance with IEC 61508 When Selecting Solenoid Valves for Safety Systems by David Park and George Wahlers A White Paper From ASCO Valve, Inc. Introduction Regulatory modifications in 2010
More informationTHE WORLD'S FIRST WIRELESS GUIDED WAVE RADAR
THE WORLD'S FIRST WIRELESS GUIDED WAVE RADAR Level measurements where you need them, however remote "Research 80% indicates that nearly of production downtime is preventable..." Ian Nimmo, Founder of the
More informationRegulations and Recommended Practices. Introduction. American Petroleum Institute Recommended Practices 2350
Meeting Spill Prevention Regulations using RF Admittance and Ultrasonic Level Measurement Technologies Martin Bahner Marketing Manager Drexelbrook Engineering Co. 205 Keith Valley Rd. Horsham, PA 19044
More informationSafety Requirements Specification Guideline
Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary Safety Requirement
More informationGAM900/GAM900S. Acceleration precisely measured and safely monitored
GAM900/GAM900S Acceleration precisely measured and safely monitored The benefits at a glance: Less sensors more safety Minimum size, maximum performance Extremely reliable and robust IP 67 protection thanks
More informationInductive slot sensor
0102 Model Number Features 3.5 mm slot width Usable up to SIL 3 acc. to IEC 61508 Extended temperature range Application Danger! In safety-related applications the sensor must be operated with a qualified
More informationHardware safety integrity Guideline
Hardware safety integrity Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se Quoting of this report is allowed
More informationSafety Manual BT50(T) Safety relay / Expansion relay
Safety Manual BT50(T) Safety relay / Expansion relay ABB Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this document
More informationMachineontwerp volgens IEC 62061
Machineontwerp volgens IEC 62061 Insert Photo Here Safety solution Architect Safety Local Business Leader Benelux. Stephen Podevyn Safety Solution Seminar Agenda deel 1 1. Richtlijnen en normen 2. Safety
More informationStilling Well Recommendations
White Paper June 24, 2009 Stilling Well Recommendations This document describes general requirements for stilling wells used for radar tank gauging applications. Automation solutions for oil & gas, defense
More informationHealth and Safety Executive Safety and environmental standards for fuel storage sites
Health and Safety Executive Safety and environmental standards for fuel storage sites Process Safety Leadership Group Health and Safety Executive Safety and environmental standards for fuel storage sites
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
More informationLabkotec SET. Labkotec separator alarm system protecting our environment. Measure your success
Labkotec SET Labkotec separator alarm system protecting our environment Designed to comply EN 858-1&2 and PPG3 norms Warns of excessive levels of oil, sludge & liquids Prevents pollution incidents Fail-safe
More informationdin din-s 90Ah/plate 155Ah/plate 115Ah/plate 140Ah/plate
traction BATTERIES din 50Ah/plate [h1 = 282, h2 = 305 mm length = b = 198 mm] 2 EPzS 100 L 2 Pg 190 L 100 45 6,8 5,7 3 EPzS 150 L 3 Pg 190 L 150 63 9,6 7,7 4 EPzS 200 L 4 Pg 190 L 200 81 12,4 9,9 5 EPzS
More informationCELO5. User & Installation Manual. www.audac.eu
CELO5 User & Installation Manual www.audac.eu 2 Introduction 5 High-end Slim Ceiling Speaker The CELO5 is the 5 version of AUDAC s CELO High-end Slim ceiling speaker series with an RMS power of 50 Watt
More informationViewpoint on ISA TR84.0.02 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President
Viewpoint on ISA TR84.0.0 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President Presented at Interkama, Dusseldorf, Germany, October 1999, Published in ISA Transactions,
More informationExpert Report. History of the development of water level control in steam- and hot water boilers
Expert Report Dipl.-Ing. Jochen Loos Dipl.-Wirtschaftsing. (FH), Dipl.-Informationswirt (FH) Markus Tuffner, Bosch Industriekessel GmbH History of the development of water level control in steam- and hot
More informationFailure Modes, Effects and Diagnostic Analysis
Failure Modes, Effects and Diagnostic Analysis Project: Plant-STOP 9475 Company: R. STAHL Schaltgeräte GmbH Waldenburg Germany Contract No.: STAHL 13/04-027 Report No.: STAHL 13/04-027 R024 Version V1,
More informationUnderstanding Safety Integrity Levels (SIL) and its Effects for Field Instruments
Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments Introduction The Industrial process industry is experiencing a dynamic growth in Functional Process Safety applications.
More informationTank Gauging Products for Bulk Liquid Storage Tanks. Simple, Safe and Reliable Inventory Measurement
Products for Bulk Liquid Storage Tanks 2500 Automatic Tank Gauge The industry standard for float and tape tank gauging for over 50 years Provides a level accuracy of 0.2-1 inch (4-25 mm) Continuous level
More informationTechnical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
More informationGMP-Z Hoofdstuk 4 Documentatie. Inleiding
-Z Hoofdstuk 4 Documentatie Inleiding Het hoofdstuk Documentatie uit de -richtsnoeren is in zijn algemeenheid goed toepasbaar in de ziekenhuisapotheek. Verschil met de industriële is dat de bereidingen
More informationSafety controls, alarms, and interlocks as IPLs
Safety controls, alarms, and interlocks as IPLs Angela E. Summers, Ph.D., P.E. SIS-TECH Solutions 12621 Featherwood Dr. Suite 120, Houston, TX 77034 Keywords: safety controls, alarms, interlocks, SIS,
More information100 Series Keyboard Tray Pivot
00 Series Keyboard Tray Pivot INSTALLATION MANUAL USA -800-888-8458 Europe +3 0 3.9.39 A B 3/3" 4x 8-3 x 5/6" Ergonomics Ergonomía Ergonomie Ergonomi 888-99-04 REMOVE PIVOT COVERS IF ALREADY ATTACHED.
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
More informationSAFETY MANUAL SIL SMART Transmitter Power Supply
PROCESS AUTOMATION SAFETY MANUAL SIL SMART Transmitter Power Supply KFD2-STC4-(Ex)*, KFD2-STV4-(Ex)*, KFD2-CR4-(Ex)* ISO9001 2 3 With regard to the supply of products, the current issue of the following
More informationAutomatic Fire Fighting Monitors
Automatic Fire Fighting Monitors Fire Protection Solutions Automatic Fire Fighting Monitors Foreword Automatic monitors are devices used to deliver large amounts of water or water/foam solution to remote
More informationIntegrated Fire and Gas Solution - Improves Plant Safety and Business Performance
Integrated Fire and Gas Solution - Improves Plant Safety and Business Performance Integrated Fire and Gas Solution - Improves Plant Safety and Business Performance 1 Table of Contents Table of Figures...1
More informationInductive sensor NI10-M18-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12
More informationSafety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September 2010. Answers for industry.
SIMATIC Safety Matrix The Management Tool for all Phases of the Safety Lifecycle Brochure September 2010 Safety Integrated Answers for industry. Functional safety and Safety Lifecycle Management Hazard
More informationTLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR
TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.
More informationTechnical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5
Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis
More informationDrayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
More informationSafety Integrity Level (SIL) Assessment as key element within the plant design
Safety Integrity Level (SIL) Assessment as key element within the plant design Tobias WALK ILF Consulting Engineers GmbH Germany Abstract Special attention has to be provide to safety instrumented functions
More informationSAFETY MANUAL SIL SWITCH AMPLIFIER
PROCESS AUTOMATION SAFETY MANUAL SIL SWITCH AMPLIFIER KF**-SR2-(Ex)*(.LB), KFD2-SR2-(Ex)2.2S ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable:
More informationRelationele Databases 2002/2003
1 Relationele Databases 2002/2003 Hoorcollege 5 22 mei 2003 Jaap Kamps & Maarten de Rijke April Juli 2003 Plan voor Vandaag Praktische dingen 3.8, 3.9, 3.10, 4.1, 4.4 en 4.5 SQL Aantekeningen 3 Meer Queries.
More informationVersion: 1.0 Latest Edition: 2006-08-24. Guideline
Management of Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se Quoting of this report is allowed but please
More informationTMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
More informationwww.kem-kueppers.com info@kem-kueppers.com Certified according to DIN EN ISO 9001 Technical Datasheet KVO Series Vortex Flow Meter
www.kem-kueppers.com Certified according to DIN EN ISO 9001 Technical Datasheet KVO Series Vortex Flow Meter Description The KVO Vortex flow meters utilize two primary sensing elements a vortex shedding
More informationFerrostat Speed Sensor Series DSF Explosion Proof Versions EEx
Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment
More informationNorthern Region. Underground Storage Tank
California CUPA Northern Region Presents Underground Storage Tank Designated Operators Workshop Workshop Agenda Definitions Tank Construction Corrosion Protection Spill Prevention Overfill Prevention Piping
More informationPlena Two-zone Call Station. Installation and User Instructions PLE-2CS
Plena Two-zone Call Station en Installation and User Instructions PLE-2CS Plena Two-zone Call Station Installation and User Instructions Important safeguards en 2 Important safeguards Before installing
More informationPower Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
More informationSentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits.
GE Measurement & Control Solutions Sentinel LCT Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement Benefits Extremely reliable and highly accurate flowmeter, designed specifically
More informationWhat is CFSE? What is a CFSE Endorsement?
ENDORSEMENT PROGRAM The CFSE endorsement program helps current holders of CFSE and CFSP certification build /demonstrate expertise and knowledge in specific focus areas of functional safety. What is CFSE?
More informationCR9971 2 Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use
ROBERTS Sound for Generations CR9971 2 Band Auto Set Dual Alarm Clock Radio Please read this manual before use Contents Contents... 1 Controls...2-5 Switching on... 6 Setting the time manually... 6 Setting
More informationRisk-Based Monitoring
Risk-Based Monitoring Evolutions in monitoring approaches Voorkomen is beter dan genezen! Roelf Zondag 1 wat is Risk-Based Monitoring? en waarom doen we het? en doen we het al? en wat is lastig hieraan?
More informationMaximizer Synergy. info@adafi.be BE 0415.642.030. Houwaartstraat 200/1 BE 3270 Scherpenheuvel. Tel: +32 495 300612 Fax: +32 13 777372
Maximizer Synergy Adafi Software is een samenwerking gestart met Advoco Solutions, een Maximizer Business Partner uit Groot Brittannië. Advoco Solutions heeft een technologie ontwikkeld, genaamd Synergy,
More informationPerformance Based Gas Detection System Design for Hydrocarbon Storage Tank Systems
Performance Based Gas Detection System Design for Hydrocarbon Storage Tank Systems Srinivasan N. Ganesan, M.S., P.E. MENA Region Manager, Kenexis DMCC, Dubai, UAE Edward M. Marszal, PE, ISA 84 Expert ABSTRACT
More informationOGH: : 11g in de praktijk
OGH: : 11g in de praktijk Real Application Testing SPREKER : E-MAIL : PATRICK MUNNE PMUNNE@TRANSFER-SOLUTIONS.COM DATUM : 14-09-2010 WWW.TRANSFER-SOLUTIONS.COM Real Application Testing Uitleg Real Application
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 5 mm
0102 Model Number Features 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching
More informationconventional system operation
conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than
More informationSUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS
SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences
More informationSIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen. 61508 Compliance of Actuators and Life Cycle Considerations. SAMSON AG Dr.
SIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen SAMSON AG Dr. Thomas Karte 61508 Compliance of Actuators and Life Cycle Considerations 2015-04-23 SAMSON AG Dr. Karte - 61508 Compliance of
More informationTechnical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface
Release date: 06-0- 09: Date of issue: 06-0- 009_eng.xml Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service
More informationTelephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
More informationMSAN-001 X-Band Microwave Motion Sensor Module Application Note
1. Introduction HB Series of microwave motion sensor module are X-Band Mono-static DRO Doppler transceiver front-end module. These modules are designed for movement detection, like intruder alarms, occupancy
More informationkey- precision Tecum cuil Ludere ipsae. Possem Precision level detection When space and price matter Pointek CLS 100
Pointek CLS 100 Compact design and short insertion length. Ideal for constricted spaces and for small vessels or pipes up to 100 mm (4 ). Tecum cuil Ludere ipsae. Possem Precision level detection When
More informationDC400 Dispensing Cutoff System
DC400 Dispensing Cutoff System DC404 and DC406 Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
More informationDATA SHEET. TDA1510AQ 24 W BTL or 2 x 12 W stereo car radio power amplifier INTEGRATED CIRCUITS
INTEGRATED CIRCUITS DATA SHEET 24 W BTL or 2 x 12 W stereo car radio File under Integrated Circuits, IC01 January 1992 GENERAL DESCRIPTION The is a class-b integrated output amplifier encapsulated in a
More informationAssuring the Cloud. Hans Bootsma Deloitte Risk Services hbootsma@deloitte.nl +31 (0)6 1098 0182
Assuring the Cloud Hans Bootsma Deloitte Risk Services hbootsma@deloitte.nl +31 (0)6 1098 0182 Need for Assurance in Cloud Computing Demand Fast go to market Support innovation Lower costs Access everywhere
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationDATA SHEET. TDA1518BQ 24 W BTL or 2 x 12 watt stereo car radio power amplifier INTEGRATED CIRCUITS
INTEGRATED CIRCUITS DATA SHEET File under Integrated Circuits, IC01 July 1994 GENERAL DESCRIPTION The is an integrated class-b output amplifier in a 13-lead single-in-line (SIL) plastic power package.
More informationShort Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
More informationL-LAS-TB-CL serie. laser light curtains for inline measuring tasks
L-LAS-TB-CL serie laser light curtains for inline measuring tasks Maximum distance 2.000 mm Measurement range 6 up to 98 mm Resolution up to 4 µm up to 1,5 khz scan rate 0-10 V or 4-20 ma analogue output
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 4 mm
0102 Model Number Features 4 mm non-flush Usable up to SIL 3 acc. to IEC 61508 Application Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs,
More informationPHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, 18 80 W Compact and T5c fluorescent lamps
Product description Noise-free precise control via DSI signal or switchdim CELMA energy class A1 1) Interfaces DSI switchdim Integrated SMART-Interface Functions Optimum filament heating in any dimmer
More informationISpac isolators. the perfect system
ISpac isolators the perfect system 2 safe isolation Handling flammable and potentially explosive substances is part and parcel of everyday operations in many branches of industry. However, it is not possible
More informationManual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
More informationATL Fuel Level Sender Probes
T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of
More informationHow To Design A Showcontrol System For A Theater School
Showcontrol System Design Oktober 2015 Theaterschool OTT-2 1 System Design Principles 1. Ensure Safety 2. The show must go on 3. Simpler is always better 4. Strive for elegance 5. Complexity is inevitable;
More informationTooway 2015 prices / prijslijst
Tooway Nederland Bergstraat 25 558BL Waalre +340-223656 mailbox@rian-bv.nl info@internetbysatellite.eu Hardware en B2B prijzen zijn excl.btw. Consumer Abonnement prijzen zijn incl. Btw. Tooway 205 prices
More informationAlgemene Theorie en Vaardigheden 2. April 2014 Theaterschool OTT-2
Les 4 Showcontrol 1 Les 14 System Design Principles 1. Ensure Safety 2. The show must go on 3. Simpler is always better 4. Strive for elegance 5. Complexity is inevitable; convolution is not 6. Leave room
More informationA PROCESS ENGINEERING VIEW OF SAFE AUTOMATION
A PROCESS ENGINEERING VIEW OF SAFE AUTOMATION Published in Chemical Engineering Progress, December 2008. Angela E. Summers, SIS-TECH Solutions, LP This step-by-step procedure applies instrumented safety
More informationJ TB/TW Temperature limiter, temperature monitor
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More informationCertificate: 0000038506 / 20 August 2013
Test report: 936/21219899/B of 28 March 2013 Initial certification: 23 July 2013 Expiry date: 22 July 2018 Publication: BAnz AT 23 July 2013 B4, chapter II, No. 1.1 Approved application The tested AMS
More information6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A
6ES7313-5BF03-0AB0 Page 1 Product data sheet 6ES7313-5BF03-0AB0 SIMATIC S7-300, CPU 313C, COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO 1 PT100, 3 FAST COUNTERS (30 KHZ), INTEGRATED 24V DC POWER SUPPLY,
More informationValue Paper Author: Edgar C. Ramirez. Diverse redundancy used in SIS technology to achieve higher safety integrity
Value Paper Author: Edgar C. Ramirez Diverse redundancy used in SIS technology to achieve higher safety integrity Diverse redundancy used in SIS technology to achieve higher safety integrity Abstract SIS
More informationABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 5 mm
0102 Model Number Features 5 mm non-flush Usable up to SIL 2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 5 mm Installation non-flush
More informationAlarmSense 2-wire detection and alarm system. Product Guide
AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority
More information