FRCC Coordination Procedure. Title: FRCC Reliability Coordinator Contingency Analysis Monitoring Criteria

Size: px
Start display at page:

Download "FRCC Coordination Procedure. Title: FRCC Reliability Coordinator Contingency Analysis Monitoring Criteria"

Transcription

1 A. Purpose: The FRCC Reliability Coordinator (RC) Contingency Analysis (CA) application is essential to maintaining the reliability of the FRCC Bulk Electric System. The application has the capability to adequately monitor and analyze the FRCC Bulk Electric System (BES) elements and a portion of the adjacent RC s BES that could result in exceeding System Operating Limits (SOL) or Interconnection Reliability Operating Limits (IROL) within the FRCC RC Area. The purpose of this procedure is to ensure that the appropriate FRCC Bulk Electric System (BES) elements are accurately identified and monitored in order to assess potential FRCC BES SOL and IROL violation conditions by the FRCC RC agent. B. Applicability: FRCC Reliability Coordinator (RC) FRCC Balancing Authorities (BAs) FRCC Transmission Operators (TOPs) C. Procedure: The contingency and monitored element selection criteria along with the exceptions to those criteria are summarized in Appendix A and Appendix B of this procedure. This procedure along with the appendices has been developed and reviewed by the FRCC Operating Reliability Subcommittee (ORS) and is intended to establish the minimum monitoring bounds for the FRCC RC CA application. Due to the sensitive nature of specific element information, the complete exceptions lists of this procedure are maintained, on a FRCC Reliability Only Group (ROG) version of Appendix A and Appendix B, with access limited to FRCC ROG personnel. 1.0 Developing the RC CA application contingency list: The FRCC Reliability Coordinator (RC) shall maintain the model used for contingency analysis and include, at a minimum, the following elements as contingencies in the CA application: BES generators of 100 MW and above, and BES facilities 100kV and above except transmission lines that are radially fed and transformers with the low side voltage below 115kV. Credible bus outages identified by the TOPs that are approved by ORS and based on the C2 (Breaker Failure) screening analysis in the FRCC summer and winter transmission assessments as listed in Appendix C. Specifically identified SOLs and IROLs in Appendix A of the FRCC-PROC-RC-FAC-011, System Operating Limits Methodology for the Operations Horizons document will be Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 1 of 8

2 monitored in accordance with system conditions. This list may include SOLs and IROLs that cannot be shown as a databank rating or single line rating or specifically identified multiple contingencies (e.g. corridor flow limit, interface limit or voltage limits). This may require temporary or continuous CA application monitoring by the RC Agent depending on system conditions. Monitoring shall be in accordance with FRCC-PROC-RC-FAC-011. Any other specific facilities deemed important to the reliability of the FRCC Bulk Electric System not identified in Appendix A of FRCC-PROC-RC-FAC-011, will be identified on the FRCC RC Contingency Exceptions List, which is maintained on the ROG version of Appendix A of this procedure. 2.0 Developing the RC CA application monitoring list: As transmission system element outages are considered in the CA application, the displayed impact of those outages on facilities will be monitored by the FRCC RC Agent and responses coordinated as appropriate. If a potential violation of a monitored limit occurs in excess of the FRCC minimum acceptable reliability conditions (as defined in the Reliability Process for the FRCC Bulk-Power Electric System), the affected entity will be notified. At a minimum, the FRCC RC Agent will monitor for potential violations on the following elements or facilities, when analyzing impacts of contingencies included in the RC CA application. BES facilities 100kV and above except transmission lines that are radially fed and transformers with the low side voltage below 115kV. Any other facilities deemed important to reliability of the FRCC Bulk Electric System will be identified on the FRCC RC Violation Exceptions List, maintained on the Reliability Only Group (ROG) version of Appendix B of this procedure. Responsibilities RC Agent Responsibilities As warranted by significant system topology changes, the FRCC RC Agent will document a benchmark review of the CA application contingencies to the FRCC RC Contingency Analysis Contingency as described in the ROG version of Appendix A of this procedure. As warranted by significant system topology changes, the FRCC RC Agent will document a benchmark review of the CA application monitored violations to the FRCC RC Contingency Analysis Violation Monitoring as described in the ROG version of Appendix B of this procedure. As warranted by significant system topology changes, the FRCC RC Agent will document a benchmark review of the CA application buss contingencies to the Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 2 of 8

3 FRCC RC Contingency Analysis Violation Monitoring as described in the ROG version of Appendix C of this procedure. Results of the review and any corrective actions will be reported to the FRCC ORS. Operating Reliability Subcommittee (ORS) Responsibilities As warranted by significant system topology changes,, the FRCC ORS will document a review of this procedure, including the minimum criteria and exceptions lists as set forth in the ROG versions of Appendix A and Appendix B of this procedure. This is to ensure that all elements and facilities important to the reliability of the FRCC Bulk Electric System are included in the Reliability analysis supported by the RC CA application. FRCC ORS will evaluate any requests to modify the criteria or exceptions list as set forth in the ROG versions of Appendix A, Appendix B and Appendix C of this procedure. FRCC Operating Entity Responsibilities D. Appendices: As warranted by significant system topology changes, the FRCC Balancing Authorities (BAs) and Transmission Operators (TOPs) will document a benchmark review of their system to the minimum criteria and exceptions lists as set forth in the ROG versions of Appendix A, Appendix B and Appendix C of this procedure, to ensure appropriate contingencies and violations are being monitored by the FRCC RC agents. TOPs shall provide data for IPP generation (100MW or greater) connected to their system BAs shall provide data for IPP generation (100 MW or greater) for which they have firm contracts. Provide notification to the FRCC ORS and the FRCC RC agent if new facilities are placed in service that meet the monitoring criteria set forth in this procedure. Provide written request to the FRCC ORS to include any new facilities on the FRCC RC Contingency Exceptions List, the FRCC RC Violation Exceptions List or the FRCC RC Contingency for Busses List, as set forth in the ROG versions of Appendix A, Appendix B and Appendix C of this procedure. Provide written request to the FRCC ORS to remove any facilities from the FRCC RC Contingency Exceptions List, the FRCC RC Violation Exceptions List or the FRCC RC Contingency for Busses List, as set forth in the ROG versions of Appendix A, Appendix B and Appendix C of this procedure. Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 3 of 8

4 Appendix A: FRCC RC Contingency Analysis Contingency Appendix B: FRCC RC Contingency Analysis Violation Monitoring Appendix C: FRCC RC Contingency Analysis Contingency for Busses Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 4 of 8

5 E. Revision History: Revision Date Action Change Tracking Conversion of prior RRO legacy document Specific reference to FRCC SOL and IROL list monitoring criteria added Changed the contingency list to specifically address BES Added language to add credible bus outages to a new Appendix C Added specific multiples to Appendix B. New Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 5 of 8

6 Appendix A FRCC RC Contingency Analysis Contingency General contingency list criteria: The FRCC Reliability Coordinator (RC) shall maintain the model used for contingency analysis and include, at a minimum, the following elements as contingencies in the CA application: BES generators of 100 MW and above, and BES facilities 100kV and above except transmission lines that are radially fed and transformers with the low side voltage below 115kV. Credible bus outages identified by the TOPs that are approved by ORS and based on the C2 (Breaker Failure) screening analysis in the FRCC Summer and Winter Transmission assessments and listed in Appendix C. Specifically identified SOLs and IROLs in Appendix A of the FRCC-PROC-RC-FAC-011, System Operating Limits Methodology for the Operations Horizons document will be monitored in accordance with system conditions. This list may include SOLs and IROLs that cannot be shown as a databank rating or single line rating or specifically identified multiple contingencies (e.g. corridor flow limit, interface limit or voltage limits). This may require temporary or continuous CA application monitoring by the RC Agent depending on system conditions. Monitoring shall be in accordance with FRCC-PROC-RC-FAC-011. Any other specific facilities deemed important to the reliability of the FRCC Bulk Electric System not identified in Appendix A of FRCC-PROC-RC-FAC-011, will be identified on the FRCC RC Contingency Exceptions List, below FRCC RC Contingency Exceptions List: This list has been created to ensure that appropriate (as determined by ORS) lower voltage element contingencies, corridor threat contingencies and multiple contingencies are documented and available for use by the FRCC RC. The contingencies should be applied to the FRCC Bulk Electric System model by the FRCC RC CA application on an on-going basis or when a specific corridor threat is identified. The current list includes: The information on this list is considered ROG (Reliability Only Group), and is for reliability use only. The actual list is maintained separately with access limited to ROG personnel only. All information is considered ROG (Reliability Only Group), and is for reliability use only *** Do not distribute to non-rog members *** Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 6 of 8

7 Appendix B FRCC RC Contingency Analysis Violation Monitoring General monitored element list criteria: As transmission system element outages are considered in the CA application, the displayed impact of those outages on facilities will be monitored by the FRCC RC Agent and responses coordinated as appropriate. If violation of a monitored limit occurs in excess of the FRCC minimum acceptable reliability conditions (as defined in the Reliability Process for the FRCC Bulk-Power Electric System), the affected entity will be notified. At a minimum, the FRCC RC will monitor for violations on the following elements or facilities when analyzing impacts of contingencies included in the RC CA application. BES facilities 100kV and above except transmission lines that are radially fed and transformers with the low side voltage below 115kV. Any other facilities deemed important to reliability of the FRCC Bulk Electric System or to individual operating entities, will be identified on the FRCC RC Violation Exceptions List, below. FRCC RC Violation Exceptions List: This list has been created to ensure that appropriate monitoring of post-contingency impacts, are included in the FRCC RC Contingency Analysis application monitored element function. The current list includes: The information on this list is considered ROG (Reliability Only Group), and is for reliability use only. The actual list is maintained separately with access limited to ROG personnel only. Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 7 of 8

8 Appendix C FRCC RC Contingency Analysis Contingency for Busses The FRCC RC Agent has the capability to add busses to its real-time Contingency List. The busses below have been screened through the semi-annual FRCC Summer and Winter Assessments as part of the C2 ( breaker failure) screening analysis. Based on the results of the C2 assessment, a TOP can request that the FRCC RC add a particular credible bus outage to the real-time Contingency List in the Contingency Analysis application. Below is a list of the credible bus outages on the real-time Contingency List: Revision Date: 4/12/11 Operating Reliability Subcommittee (ORS) Page 8 of 8

130 FERC 61,163 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER APPROVING STIPULATION AND CONSENT AGREEMENT

130 FERC 61,163 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER APPROVING STIPULATION AND CONSENT AGREEMENT 130 FERC 61,163 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Jon Wellinghoff, Chairman; Marc Spitzer, Philip D. Moeller, and John R. Norris. Florida Blackout Docket

More information

DISCUSSION PAPER: Peak Reliability Performance Metrics

DISCUSSION PAPER: Peak Reliability Performance Metrics DISCUSSION PAPER: Peak Reliability Performance Metrics Executive Summary Performance metrics are critical for any organization in order to encourage improvement, effectiveness and efficiency; to assess

More information

Effective: 2015-03-27 Page 1 of 7

Effective: 2015-03-27 Page 1 of 7 Applicability 1 Section 502.4 applies to: (a) (b) (c) (d) (e) (f) the legal owner of a generating unit; the legal owner of an aggregated generating facility; the legal owner of a transmission facility;

More information

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003 F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify

More information

Energy Management System (EMS) Model Updates and Quality Assurance (QA)

Energy Management System (EMS) Model Updates and Quality Assurance (QA) PJM Manual 3A: Energy Management System (EMS) Model Updates and Quality Assurance (QA) Revision: 10 Effective Date: June 25, 2015 Prepared by: Operation Support Division PJM 2015 PJM 2007 Revision 0, Effective

More information

When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard.

When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard. CIP-002-5 Cyber Security BES Cyber System Categorization When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard. A.

More information

IESO Supply Deliverability Guidelines

IESO Supply Deliverability Guidelines PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents

More information

121 FERC 61,143 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

121 FERC 61,143 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION 121 FERC 61,143 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Joseph T. Kelliher, Chairman; Suedeen G. Kelly, Marc Spitzer, Philip D. Moeller, and Jon Wellinghoff.

More information

NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario

NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario Table of Contents NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario Table of Contents... 2 1. Executive Summary...

More information

NERC s goal with publishing lessons learned is to provide industry with technical and understandable information that assists them with maintaining

NERC s goal with publishing lessons learned is to provide industry with technical and understandable information that assists them with maintaining NERC s goal with publishing lessons learned is to provide industry with technical and understandable information that assists them with maintaining the reliability of the bulk power system Bulk Power

More information

RELIABILITY PLANNING CRITERIA

RELIABILITY PLANNING CRITERIA RELIABILITY PLANNING CRITERIA Version 4.0 01/20/2016 Date Rev. No. Individual Making Edits REVISION HISTORY Reason / Comments 07/01/2013 1 J. Johnson Initial document 06/06/2014 2 R. Chapman Document review;

More information

3. Purpose: To improve the reliability of the Bulk Electric System by requiring the reporting of events by Responsible Entities.

3. Purpose: To improve the reliability of the Bulk Electric System by requiring the reporting of events by Responsible Entities. A. Introduction 1. Title: Event Reporting 2. Number: EOP-004-2 3. Purpose: To improve the reliability of the Bulk Electric System by requiring the reporting of events by Responsible Entities. 4. Applicability:

More information

148 FERC 61,009 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

148 FERC 61,009 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION 148 FERC 61,009 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Cheryl A. LaFleur, Acting Chairman; Philip D. Moeller, John R. Norris, and Tony Clark. Arizona Public

More information

Operating Security Standards

Operating Security Standards Version 1.1 Prishtina December 2009 TABLE OF CONTENTS 1 Introduction... 1 2 Definitions... 1 2.1 General...1 2.1.2 Kosovo Transmission System...1 2.1.3 Circuit...2 2.1.4 The N-1 Criterion...2 2.1.5 Normal

More information

CIP-014-1 Physical Security. Nate Roberts CIP Security Auditor I

CIP-014-1 Physical Security. Nate Roberts CIP Security Auditor I CIP-014-1 Physical Security Nate Roberts CIP Security Auditor I Notes Critical Infrastructure Protection (CIP) Standard CIP-014-1 is currently pending approval by the Federal Energy Regulatory Commission

More information

Summary of CIP Version 5 Standards

Summary of CIP Version 5 Standards Summary of CIP Version 5 Standards In Version 5 of the Critical Infrastructure Protection ( CIP ) Reliability Standards ( CIP Version 5 Standards ), the existing versions of CIP-002 through CIP-009 have

More information

Resource Monitoring and Deliverability Tool Paper

Resource Monitoring and Deliverability Tool Paper Resource Monitoring and Deliverability Tool Paper NWPP MC Phase 3 Operations Integration Work Group 11/30/2014 Page 1 of 16 Table of Contents Executive Summary... 3 1. Purpose... 5 2. Existent Methods

More information

Duke Energy Progress Standards of Conduct Transmission Function Employee Job Titles and Job Descriptions 9/1/13

Duke Energy Progress Standards of Conduct Transmission Function Employee Job Titles and Job Descriptions 9/1/13 Duke Energy Progress Standards of Conduct Transmission Function Employee Job Titles and Job Descriptions 9/1/13 Transmission Operations & Planning Carolinas Power System Operations Director Power System

More information

NERC Cyber Security Standards

NERC Cyber Security Standards SANS January, 2008 Stan Johnson Manager of Situation Awareness and Infrastructure Security Stan.johnson@NERC.net 609-452-8060 Agenda History and Status of Applicable Entities Definitions High Level of

More information

MARKET EVENT REPORT. Scheduling Error Affecting Dispatch of Mintaro Gas Turbine Station. Electricity Market Operations Performance PREPARED BY:

MARKET EVENT REPORT. Scheduling Error Affecting Dispatch of Mintaro Gas Turbine Station. Electricity Market Operations Performance PREPARED BY: Scheduling Error Affecting Dispatch of Mintaro Gas Turbine Station PREPARED BY: Electricity Market Operations Performance DATE: 26 August 2010 Contents 1 Introduction... 3 2 Background... 3 3 Scheduling

More information

Load Dispatcher (Class Code 5223) Task List

Load Dispatcher (Class Code 5223) Task List A. Load Dispatching, General Load Dispatcher (Class Code 5223) Task List 1. Prior to work shift speaks to Load Dispatcher(s), reviews hardcopy and computer logs, and looks at the dispatcher's diagram board

More information

Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications Between the ISO and Local Control Centers

Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications Between the ISO and Local Control Centers Master/LCC Procedure No. 13 - Communications Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications 1. References... 2 2. Background... 3 3. Responsibilities... 3 4. Procedure... 4 4.1

More information

Use Case Task 1-7: Network Equavalents between EMS & Planning

Use Case Task 1-7: Network Equavalents between EMS & Planning Use Case Task 1-2: Transport Contingency Specifications Page 1 Use Case Task 1-7: Equavalents between EMS & 1 Summary: Export Equavalents from the EMS or another application for use by the application(s).

More information

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055 Generation Interconnection Feasibility Study Report-Web Version For PJM Generation Interconnection Request Queue Position Z1-055 South Bend Generation Project March 2014 PJM Interconnection 2014. All rights

More information

16 West Coast Regional Plan

16 West Coast Regional Plan 16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast

More information

PJM Merchant Transmission Request. Queue #R75. Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study

PJM Merchant Transmission Request. Queue #R75. Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study PJM Merchant Transmission Request Queue #R75 Mitchell Shepler Hill 138 Kv Feasibility / System Impact Study 413038v1a March 2007 PJM Interconnection 2007. All rights reserved. Preface The intent of the

More information

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering Title 20 PUBLIC SERVICE COMMISSION Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES Chapter 02 Engineering Authority: Public Utility Companies Article, 2-121, 5-101 and 5-303, Annotated Code of Maryland.

More information

NB Appendix CIP-004-5.1-NB-1 - Cyber Security Personnel & Training

NB Appendix CIP-004-5.1-NB-1 - Cyber Security Personnel & Training This appendix establishes modifications to the FERC approved NERC standard CIP-004-5.1 for its specific application in New Brunswick. This appendix must be read with CIP-004-5.1 to determine a full understanding

More information

TERMS AND CONDITIONS

TERMS AND CONDITIONS Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator

More information

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Prepared By: Transmission Planning Unit Baltimore Gas & Electric Company Table of Contents 1. INTRODUCTION

More information

SOP-RTMKTS.0060.0005 - Test and Approve Operations Software Applications. Contents

SOP-RTMKTS.0060.0005 - Test and Approve Operations Software Applications. Contents SOP-RTMKTS.0060.0005 - Test and Approve Operations Software Applications Contents 1. Objective... 2 2. Background... 2 3. Responsibilities... 3 4. Controls... 4 5. Instructions... 5 5.1 Document Operations

More information

Report to the Minister Responsible for the Qulliq Energy Corporation. Respecting:

Report to the Minister Responsible for the Qulliq Energy Corporation. Respecting: Report to the Minister Responsible for the Qulliq Energy Corporation Respecting: An Application by the Qulliq Energy Corporation For Approval of Major Project Permit to Upgrade the Iqaluit Distribution

More information

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA CROSS SOUND CABLE PROJECT 330MW HVdc INTERCONNECTION BETWEEN NEW HAVEN, CONNECTICUT AND SHOREHAM, NY Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA Subordinate Status Removal and Amendment of Approved

More information

NERC S DEFINITION OF THE BULK ELECTRIC SYSTEM

NERC S DEFINITION OF THE BULK ELECTRIC SYSTEM NERC S DEFINITION OF THE BULK ELECTRIC SYSTEM WHY THE DEFINITION MATTERS, WHY IT S CHANGING, AND WHERE WE STAND AT NERC AND FERC CYNTHIA S. BOGORAD cynthia.bogorad@spiegelmcd.com LATIF M. NURANI latif.nurani@spiegelmcd.com

More information

Item 8: Houston Import RPG Project

Item 8: Houston Import RPG Project : Houston Import RPG Project Jeff Billo Manager, Transmission Planning Board of Directors Meeting April 8, 2014 Study Overview ERCOT has determined that there will be a need for additional import capacity

More information

Power System Security Monitoring, Analysis, and Control. George Gross

Power System Security Monitoring, Analysis, and Control. George Gross ECE 573 Power System Operations and Control Power System Security Monitoring, Analysis, and Control George Gross Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign

More information

Power System Operation Procedure: Short Term Projected Assessment of System Adequacy (ST PASA)

Power System Operation Procedure: Short Term Projected Assessment of System Adequacy (ST PASA) ELECTRICITY INDUSTRY ACT ELECTRICITY INDUSTRY (WHOLESALE ELECTRICITY MARKET) REGULATIONS 2004 WHOLESALE ELECTRICITY MARKET RULES Power System Operation Procedure: Short Term Projected Assessment of System

More information

Job Descriptions. Job Title Reports To Job Description TRANSMISSION SERVICES Manager, Transmission Services. VP Compliance & Standards

Job Descriptions. Job Title Reports To Job Description TRANSMISSION SERVICES Manager, Transmission Services. VP Compliance & Standards Updated July 11, 2013 Job Descriptions Job Title Reports To Job Description TRANSMISSION SERVICES VP Compliance & Standards Develops strategy and business plans for efficient, safe, reliable, regulatorycompliant

More information

Responsibility for Outage Coordination is designated by 4 key artifacts: 1. FERC Order 2000 FERC Order 2000 (Docket No. RM99-2-000; Order No.

Responsibility for Outage Coordination is designated by 4 key artifacts: 1. FERC Order 2000 FERC Order 2000 (Docket No. RM99-2-000; Order No. 1 2 3 4 Responsibility for Outage Coordination is designated by 4 key artifacts: 1. FERC Order 2000 FERC Order 2000 (Docket No. RM99-2-000; Order No. 2000) comments regarding Transmission and Generation

More information

Treasure Valley Electric Plan - Community Advisory Committee

Treasure Valley Electric Plan - Community Advisory Committee Treasure Valley Electric Plan - Community Advisory Committee What is a transmission line and why are they necessary? A transmission line is used to conduct electricity between two points. Without high

More information

Chapter 7 System Operations and Physical Markets

Chapter 7 System Operations and Physical Markets MDP_RUL_0002_07 Market Rules Chapter 7 System Operations and Physical Markets Public Issue Date: June 3, 2015 Library Record No. MDP_RUL_0002_07 Document Name Market Rules for the Ontario Electricity Market

More information

EASTERN INTERCONNECTION RELIABILITY ASSESSMENT GROUP (ERAG) AGREEMENT

EASTERN INTERCONNECTION RELIABILITY ASSESSMENT GROUP (ERAG) AGREEMENT EASTERN INTERCONNECTION RELIABILITY ASSESSMENT GROUP (ERAG) AGREEMENT THIS AGREEMENT ( Agreement ), effective as of August 1, 2006 is entered into by and among the Florida Reliability Coordinating Council,

More information

Alberta Reliability Standard Cyber Security System Security Management CIP-007-AB-5

Alberta Reliability Standard Cyber Security System Security Management CIP-007-AB-5 A. Introduction 1. Title: 2. Number: 3. Purpose: To manage system security by specifying select technical, operational, and procedural requirements in support of protecting BES cyber systems against compromise

More information

ATTACHMENT G. Network Operating Agreement

ATTACHMENT G. Network Operating Agreement ATTACHMENT G Network Operating Agreement 1. PURPOSE OF NETWORK OPERATING AGREEMENT The purpose of this Agreement is to identify contractual requirements related to Network Integration Transmission Service

More information

References... 4. Appendices... 5. I. INTRODUCTION... 6 A. Background... 6 B. Standards... 6

References... 4. Appendices... 5. I. INTRODUCTION... 6 A. Background... 6 B. Standards... 6 ISO New England Operating Procedure No. 14 - Technical Requirements for Generators, Demand Resources, Asset Related Demands and Alternative Technology Regulation Resources Effective Date: January 29, 2015

More information

How To Operate The Williston Uvls

How To Operate The Williston Uvls WND Winter Operating Guide 2012/2013 1 WND Operating Study Using EQ-890-2012WIN- FINAL.sav developed through the 890 process Got load updates from MDU, Central Power, UM G&T Made several topology updates

More information

TRANSMISSION ALTERNATIVES CONSIDERED

TRANSMISSION ALTERNATIVES CONSIDERED EB-00-0 Tab Page of TRANSMISSION ALTERNATIVES CONSIDERED In determining the proposed facilities, Hydro One and the West GTA LDCs investigated six options to address the two needs identified in this Application

More information

GLOSSARY. Glossary of Terms for Capacity Based Demand Response PUBLIC. Issue 3.0 GOT-1

GLOSSARY. Glossary of Terms for Capacity Based Demand Response PUBLIC. Issue 3.0 GOT-1 PUBLIC GOT-1 GLOSSARY Glossary of Terms for Capacity Based Demand Response Issue 3.0 This document provides a glossary of terms with definitions used in the Capacity Based Demand Response program. Public

More information

System Operator Certification Program Administrative Guidelines

System Operator Certification Program Administrative Guidelines System Operator Certification Program Send your comments to soccep@nerc.com by September 24, 2004 Maintaining NERC System Operator Credential Through the Use of Continuing Education Credit Hours North

More information

Generation and Transmission Interconnection Process

Generation and Transmission Interconnection Process PJM Manual 14A Generation and Transmission Interconnection Process Revision: 18 Effective Date: January 28, 2016 Prepared by Planning Division Generation Interconnection Department PJM 2016 Table of Contents

More information

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives (Required per CPUC Decision No. C10-1328) Final Report (Submitted with Public Service s 2011 ERP) Executive Summary The objective

More information

Kent Active System Management (KASM) Oct 2015 / Matthieu Michel

Kent Active System Management (KASM) Oct 2015 / Matthieu Michel Kent Active System Management (KASM) Oct 2015 / Matthieu Michel Project Background (update): D Heat Map: SPN D Connection Offers Accepted (Cumulative) 1W D Heat map (June 2015) SPN D Connection Offers

More information

149 FERC 61,140 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 40. [Docket No. RM14-15-000; Order No.

149 FERC 61,140 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 40. [Docket No. RM14-15-000; Order No. 149 FERC 61,140 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION 18 CFR Part 40 [Docket No. RM14-15-000; Order No. 802] Physical Security Reliability Standard (Issued November 20, 2014) AGENCY:

More information

A. Introduction. B. Requirements. Standard PER-005-1 System Personnel Training

A. Introduction. B. Requirements. Standard PER-005-1 System Personnel Training A. Introduction 1. Title: System Personnel Training 2. Number: PER-005-1 3. Purpose: To ensure that System Operators performing real-time, reliability-related tasks on the North American Bulk Electric

More information

Physical Security Reliability Standard Implementation

Physical Security Reliability Standard Implementation Physical Security Reliability Standard Implementation Tobias Whitney, Manager of CIP Compliance (NERC) Carl Herron, Physical Security Leader (NERC) NERC Sub-Committee Meeting New Orleans, Louisiana CIP-014

More information

OE-417 ELECTRIC EMERGENCY INCIDENT AND DISTURBANCE REPORT...

OE-417 ELECTRIC EMERGENCY INCIDENT AND DISTURBANCE REPORT... U.S. DEPARTMENT OF ENERGY OFFICE OF ELECTRICITY DELIVERY AND ENERGY RELIABILITY Washington, D.C. 20585 OMB No. 1901-0288 Expiration Date: 03/31/2018 Burden Per Response: 2.16 hours Revised: November 2014

More information

Preliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines

Preliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines Preliminary Feasibility Assessment For The Rio Tinto Alcan to BCH Transfer Limit of 460 MW With 50% Series Compensation on Both KMO KIT lines Report : ASP2010-T001 July 2010 Asset Strategy & Planning,

More information

Post Operational Readiness. Operational Services and Performance

Post Operational Readiness. Operational Services and Performance Post Operational Readiness Confirmation i Post Operations Certificate 19 th November 2012 Dave Carroll Operational Services and Performance EirGrid Overview Process Pre-Requisites 1. Performance Monitoring

More information

Federal Energy Regulatory Commission. Small Entity Compliance Guide Mandatory Reliability Standards (Order No. 693)

Federal Energy Regulatory Commission. Small Entity Compliance Guide Mandatory Reliability Standards (Order No. 693) Federal Energy Regulatory Commission Small Entity Compliance Guide Mandatory Reliability Standards (Order No. 693) This Guide is prepared in accordance with the requirements of section 212 of the Small

More information

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION FEASIBILITY STUDY FOR PROPOSED XXXXXXXX GENERATION ON THE SIERRA BLANCA-FARMER 69 KV LINE

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION FEASIBILITY STUDY FOR PROPOSED XXXXXXXX GENERATION ON THE SIERRA BLANCA-FARMER 69 KV LINE EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION FEASIBILITY STUDY FOR PROPOSED XXXXXXXX GENERATION ON THE SIERRA BLANCA-FARMER 69 KV LINE El Paso Electric Company System Planning Department April

More information

Updated November 20, 2015. Director, System Planning

Updated November 20, 2015. Director, System Planning Updated November 20, 2015 Job Descriptions Job Title Reports To Job Description SYSTEM PLANNING & SERVICES VP Compliance Manages the system planning and services staff. The director is responsible for

More information

E-Commerce Security Perimeter (ESP) Identification and Access Control Process

E-Commerce Security Perimeter (ESP) Identification and Access Control Process Electronic Security Perimeter (ESP) Identification and Access Control Process 1. Introduction. A. This document outlines a multi-step process for identifying and protecting ESPs pursuant to the North American

More information

Robust Adaptive Topology Control

Robust Adaptive Topology Control Robust Adaptive Topology Control Mladen Kezunovic, PI Texas A&M University Kory W. Hedman, Co-PI Arizona State University January 14-15, 2015 System Integration Robust Adaptive Topology Control (RATC)

More information

Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment

Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment March 20, 2009 Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment Table of Contents:

More information

Section 1: Executive Summary

Section 1: Executive Summary Section 1: Executive Summary SECTION 1: EXECUTIVE SUMMARY 1.1 SECTION PURPOSE This report has been prepared for the Nevada Energy Assistance Corporation (NEAC), a 501(c)(3) non-profit agency; in support

More information

TDI's NYC Merchant CHPE Transmission Project with POI at Astoria (NYISO Queue #305) Deliverability Analysis

TDI's NYC Merchant CHPE Transmission Project with POI at Astoria (NYISO Queue #305) Deliverability Analysis R103-11 TDI's NYC Merchant CHPE Transmission Project with POI at Astoria (NYISO Queue #305) Deliverability Analysis Prepared for Transmission Developers, Inc. Submitted by: Larry Eng, Staff Consultant

More information

Alberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5

Alberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5 A. Introduction 1. Title: 2. Number: 3. Purpose: To specify consistent and sustainable security management controls that establish responsibility and accountability to protect BES cyber systems against

More information

This document should be reviewed at least every two years.

This document should be reviewed at least every two years. 1.0 Change Control Version Date Modification Author(s) Reviews and Approvals by Issue 1 06 August 2007 Initial Document Philip J. Tatro David Wright Issue 2 29 February Removed Confidential from Philip

More information

Network Consulting for Power Grid Optimization

Network Consulting for Power Grid Optimization Network Consulting for Power Grid Optimization Project experience in India Network Consulting Competences Page 1 Our worldwide representation Manchester The Hague Denver Schenectady San Diego Houston Mexico

More information

Public Utilities and Their Reliability in Florida - History

Public Utilities and Their Reliability in Florida - History UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Remedying Undue Discrimination Through Open Access Transmission Service And Standard Electricity Market Design GridFlorida, LLC Docket No.

More information

Transmission Function Employees Job Titles and Descriptions 18 C.F.R 358.7(f)(1)

Transmission Function Employees Job Titles and Descriptions 18 C.F.R 358.7(f)(1) Date of Last Change to the Provided Information August 27 th, 2015 Director, Transmission Operations The employee in this position is responsible for effectively managing the operation of FirstEnergy Utilities

More information

SPECIFICATION COG-2007

SPECIFICATION COG-2007 Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On

More information

TRANSMISSION & DISTRIBUTION PLANNING CRITERIA & GUIDELINES

TRANSMISSION & DISTRIBUTION PLANNING CRITERIA & GUIDELINES TRANSMISSION & DISTRIBUTION PLANNING CRITERIA & GUIDELINES Issued: September 20, 2010 Revision 3 TABLE OF CONTENTS 09/20/10 I. INTRODUCTION... 1 II. DOCUMENT REVIEW AND UPDATE PROCESS... 1 A. MAJOR REVISION

More information

2012 Workers Compensation Data Call Summary Insurance Oversight Part A

2012 Workers Compensation Data Call Summary Insurance Oversight Part A 2012 Workers Compensation Data Call Summary Insurance Oversight Part A INTRODUCTION: Revisions to the Illinois Workers Compensation Act (820 ILCS 305/29) in the fall of 2011 required the Department of

More information

Alberta Reliability Standard Cyber Security Personnel & Training CIP-004-AB-5.1

Alberta Reliability Standard Cyber Security Personnel & Training CIP-004-AB-5.1 Alberta Reliability Stard A. Introduction 1. Title: 2. Number: 3. Purpose: To minimize the risk against compromise that could lead to misoperation or instability in the bulk electric system from individuals

More information

N-1-1 Contingency Analysis using PowerWorld Simulator

N-1-1 Contingency Analysis using PowerWorld Simulator N-1-1 Contingency nalysis using PowerWorld Simulator uthor: PowerWorld Corporation Scott R. Dahman, P.E. Date: March 24, 2010 October 25, 2012 (revised) Table of Contents Background and Objective... 2

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

Dynamic Security Assessment in the Future Grid. Vijay Vittal Ira A. Fulton Chair Professor Arizona State University

Dynamic Security Assessment in the Future Grid. Vijay Vittal Ira A. Fulton Chair Professor Arizona State University 1 Dynamic Security Assessment in the Future Grid Vijay Vittal Ira A. Fulton Chair Professor Arizona State University 2 Key requirements for DSA Need to perform DSA as close to real time as possible Need

More information

Southern California Edison Revised Cal. PUC Sheet No. 59134-E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No.

Southern California Edison Revised Cal. PUC Sheet No. 59134-E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No. Southern California Edison Revised Cal. PUC Sheet No. 59134-E Rosemead, California (U 338-E) Cancelling Revised Cal. PUC Sheet No. 58300-E Schedule TOU-8-RBU Sheet 1 APPLICABILITY Applicable to the additional

More information

Alberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1

Alberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1 A. Introduction 1. Title: 2. Number: 3. Purpose: To prevent and detect unauthorized changes to BES cyber systems by specifying configuration change management and vulnerability assessment requirements

More information

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION'^^ j E DIRECT TESTIMONY RAJESH GUPTA PROJECT MANAGER, ENTERGY SERVICES, INC.

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION'^^ j E DIRECT TESTIMONY RAJESH GUPTA PROJECT MANAGER, ENTERGY SERVICES, INC. BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION'^^ j E s : D IN THE MATTER OF THE APPLICATION OF ENTERGY ARKANSAS, INC. FOR A CERTIFICATE OF ENVIRONMENTAL COMPATIBILITY AND PUBLIC NEED TO CONSTRUCT AND OPERATE

More information

Future of Electric Distribution Dialogue

Future of Electric Distribution Dialogue Future of Electric Distribution Dialogue Webinar Series Session I: State of U.S. Electric Distribution July 11, 2012 2:00 3:30 p.m. EDT Session I: State of U.S. Electric Distribution 2:00 p.m. Opening

More information

Outage Scheduling Manual

Outage Scheduling Manual MANUAL 29 Outage Scheduling Manual July 2015 Version: 4.3.1 Effective Date: 07/29/2015 Committee Acceptance: 6/11/2015 OC This document was prepared by: NYISO Energy Market Operations New York Independent

More information

Midwest Reliability Organization Procedure For NERC PRC-012

Midwest Reliability Organization Procedure For NERC PRC-012 Midwest Reliability Organization Procedure For NERC PRC-012 A. Introduction The following procedure developed by the MRO Protective Relay Subcommittee (PRS) and Transmission Assessment Subcommittee (TAS)

More information

Request for Quote For CA Single Sign-On Renewal_3-16_JT

Request for Quote For CA Single Sign-On Renewal_3-16_JT Electric Reliability Council of Texas, Inc. (ERCOT) Contract Administration and Procurement Request for Quote For CA Single Sign-On Renewal_3-16_JT Date of Release: March 4, 2016 1 1 GENERAL INFORMATION

More information

Risks and Controls for VAR-001-4 and EOP-004-2. Richard Shiflett Ruchi Ankleshwaria

Risks and Controls for VAR-001-4 and EOP-004-2. Richard Shiflett Ruchi Ankleshwaria Risks and Controls for VAR-001-4 and EOP-004-2 Richard Shiflett Ruchi Ankleshwaria 2 Introductions Richard Shiflett Compliance Risk Engineer Joined WECC in February 2014 11 years experience with Bureau

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

Attached are the Board materials in relation to these agenda items. Item 4.3 1 ERCOT Public

Attached are the Board materials in relation to these agenda items. Item 4.3 1 ERCOT Public The Human Resources & Governance (HR&G) Committee is expected to consider HR&G Committee Agenda Item 4.3: Recommendation regarding Proposed 2016 ERCOT Key Performance Indicators (s) at its meeting on December

More information

State Of California's Energy Bill

State Of California's Energy Bill 2750 Monroe Boulevard Valley Forge Corporate Center Audubon, PA 19403 James M. Burlew Counsel Telephone: (610) 666-4345 Fax (610) 666-8211 Email Address: james.burlew@pjm.com December 15, 2015 The Honorable

More information

4.1.1 Generator Owner 4.1.2 Transmission Owner that owns synchronous condenser(s)

4.1.1 Generator Owner 4.1.2 Transmission Owner that owns synchronous condenser(s) A. Introduction 1. Title: Verification and Data Reporting of Generator Real and Reactive Power Capability and Synchronous Condenser Reactive Power Capability 2. Number: MOD-025-2 3. Purpose: To ensure

More information

Generator Interconnection and Deliverability Study Methodology Technical Paper

Generator Interconnection and Deliverability Study Methodology Technical Paper Generator Interconnection and Deliverability Study Methodology Technical Paper July 2, 2013 Generator Interconnection and Deliverability Study Methodology Table of Contents Introduction... 1 Section One:

More information

SERVICE CLASSIFICATION NO. 14-RA STANDBY SERVICE

SERVICE CLASSIFICATION NO. 14-RA STANDBY SERVICE Fourth Revised Leaf No. 135 Consolidated Edison Company Superseding Second Revised Leaf No. 135 (Third Revised Leaf No. 135 Canceled) Applicable to Use of Service for SERVICE CLASSIFICATION NO. 14-RA STANDBY

More information

Section 4: Scheduling Philosophy & Tools

Section 4: Scheduling Philosophy & Tools Welcome to the Scheduling Philosophy & Tools section of the PJM Manual for Scheduling Operations. In this section you will find the following information: A description of the PJM OI s scheduling philosophy

More information

Transmission Related Station Power Use at Substations

Transmission Related Station Power Use at Substations Transmission Related Station Power Use at Substations BUSINESS PRACTICE This Business Practice identifies the cost responsibility for energy consumption at substations by American Transmission Company

More information

CONGESTION MANAGEMENT POLICY

CONGESTION MANAGEMENT POLICY 1 (8) CONGESTION MANAGEMENT POLICY Contents 1 General... 2 2 Principles of congestion management... 2 3 Congestion management in the Finnish transmission grid... 3 3.1 Normal situation... 3 3.2 Planned

More information

Southwest Power Pool SPP REGIONAL COMPLIANCE WORKING GROUP (RCWG) CONFERENCE CALL. August 7, 2015 MINUTES

Southwest Power Pool SPP REGIONAL COMPLIANCE WORKING GROUP (RCWG) CONFERENCE CALL. August 7, 2015 MINUTES Southwest Power Pool SPP REGIONAL COMPLIANCE WORKING GROUP (RCWG) CONFERENCE CALL Agenda Item 1 Administrative Items August 7, 2015 MINUTES Chair Jennifer Flandermeyer called the meeting to order at 2:00

More information

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS LIST OF CONTENT 1. INTRODUCTION... 1 2. HARMONIC VOLTAGE ASSESSMENT REQUIREMENT IN THE UK... 2 3. THE ASSESSMENT... 2 3.1. SYSTEM MODELLING...3 3.2.

More information

REAL TIME DYNAMICS MONITORING SYSTEM (RTDMS ) AND PHASOR GRID DYNAMICS ANALYZER (PGDA) USER TRAINING FOR ERCOT

REAL TIME DYNAMICS MONITORING SYSTEM (RTDMS ) AND PHASOR GRID DYNAMICS ANALYZER (PGDA) USER TRAINING FOR ERCOT REAL TIME DYNAMICS MONITORING SYSTEM (RTDMS ) AND PHASOR GRID DYNAMICS ANALYZER (PGDA) USER TRAINING FOR ERCOT SEPTEMBER 16-17, 2014 Electric Power Group. Built upon GRID-3P platform, U.S. Patent 7,233,843,

More information

Network Upgrades andSIAs Under California Tariff Clarifications

Network Upgrades andSIAs Under California Tariff Clarifications California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 July 11, 2013 Re: California Independent

More information

Northport - Norwalk Harbor Cable (NNC) Tie line

Northport - Norwalk Harbor Cable (NNC) Tie line September 9, 008 Northport - Norwalk Harbor Cable (NNC) Tie line Technical Assessment of Operating up to NNC Inter Tie STE Ratings Executive Summary Three (3) 38kV submarine cable circuits (Lines 60, 60,

More information