Prompt Engineering applies successfully CFD analysis on large Server Room for a simulation driven Energy saving approach.

Size: px
Start display at page:

Download "Prompt Engineering applies successfully CFD analysis on large Server Room for a simulation driven Energy saving approach."

Transcription

1 Prompt Engineering applies successfully CFD analysis on large Server Room for a simulation driven Energy saving approach.. ABSTRACT The Energy Saving approach is the target of this case story. The problem here faced is the evaluation of the Heating, Ventilation and Air-Conditioning (HVAC) system performances for a data center of an important Italian bank. Currently the data center floor layouts are designed using empirical guidelines based on limited measurements. These guidelines do not consider the complex fluid dynamics processes that control the flow rate distribution. Computational simulation can be used for a quick setup of any proposed layout, any desired placement of CRAC units and perforated tiles, and any imagined failure scenario. The computational trialand-error process is preferable for two reasons. Simulation is much faster and more economical than building an actual layout. Second, the computed results provide not only the flow rate distribution but also the underlying velocity and pressure fields and thus explain the physics behind the flow rate variation. This understanding is useful in guiding the computational trial-and-error process in the optimum direction. 2. INTRODUCTION Large-scale data centers (~2,m2) will be the major energy consumers of the next generation. The trend towards deployment of computer systems in large numbers, in very dense configurations in racks in a data center, has resulted in very high power densities at room level. Energy consumption of data centers can be severely increased by inadequate air handling systems and rack layouts that allow the hot and d air streams to mix. Special attention must be paid to the distribution of the cooling air. In raised-floor data centers, the distribution of the air flow through the perforated tiles is governed by the size of the plenum, the arrangement and open area of the perforated tiles, the placement and flow rates of CRAC units, and the under-floor blockages like cables and pipes. The complex flow in the plenum sets up a pressure distribution, which controls the flow through the perforated tiles. Moreover due to the interactive effect of different parameters, the resulting flow distribution is usually not uniform. This means that the computer servers in some areas get too much air, while others get too little. Whenever the cooling-air requirements of any server are not met, its cooling is compromised. The necessary and sufficient condition for good thermal management is supplying the required airflow through the perforated tiles located at the inlet of each computer server. By means of the CFD simulation one can demonstrate some best practices in airflow management: using blanking panels, floor layout, eliminating cable obstructions, hot/d aisle containment, bypass and re-circulation reduction are first important steps to get ready for high ambient datacenter operation. A non-dimensional parameters to evaluate the thermal design and performance of large-scale data centers is used. Prompt Engineering S.r.l. Via Livorno, 6 \ 44 Torino (TO) T \ F \ info@prompt-engineering.com

2 3. DATA CENTER COOLING INFRASTRUCTURE The miniaturization of semiconductor devices and integration of several functionalities on a single microprocessor chip has resulted in very high power densities at chip level. The deployment of large number of these ultrathin servers, in very high densities in computer racks, has resulted in to 5 KW racks. To enable pervasive computing, thousands of racks are expected to reside in future data centers. A data center, thus characterized by high-density deployment of computer racks, can itself be viewed as a computer. One now has to view the data center as the computer, where the walls are the enclosures and the racks are akin to electronic devices dissipating heat. Numerical modeling to optimize the layout of the racks (heat loads) and the airflow vents was proposed. The densely packed unit systems (i.e the racks) have significant flow resistance and coupled with a lack of space for accommodating the air moving devices, it may not be uncommon to observe racks that exhaust air with a higher temperature difference. Figure is a simplified representation of a traditional data center with under floor cool air distribution. Figure Typical Data Center Configuration The hot exhaust air from the EIA (Electronics Industries Association) racks is cooled by recirculating the air through modular computer room air conditioning units (CRAC). Multiple CRAC units, sized to extract the total heat load in the data center, are located within the data center or in close proximity. The cool air is recirculated back to the racks through vented tiles in the raised under-floor plenum. A properly devised and applied vent tile allows the air to be delivered with adequate momentum to reach the inlet of the systems located at the top of the racks. Conventionally, the racks are laid out in hot aisle and d aisle format as shown in Figure with supply air inlet vents in d aisles. The air movers pressurize the plenum with cool air. The cool air enters the data center through vented tiles near the inlet of the racks. We can assert that temperature gradients and flow patterns need to be analyzed for a given layout of equipment to assure appropriate air inlet specifications to the systems. The exhaust air from the racks and the inlet air to the racks have to be managed in such a way that the cascading effect of pre-heated air does not result in violating inlet air specifications to the systems. Such intuitive equipment layout does not alleviate the need of numerical modeling to produce a thermally appropriate Prompt Engineering S.r.l. Via Livorno, 6 \ 44 Torino (TO) T \ F \ info@prompt-engineering.com

3 layout of a data center. A massive thermal data monitoring and CFD modeling is a must to understanding the optimal layout of a room. 4. ENERGY SAVING APPROACH: MONITORING & SIMULATION The Energy Saving approach is the target of this case story. The problem here faced is the evaluation of the Heating, Ventilation and Air-Conditioning (HVAC) system performances for a data center of an important filial bank in Turin. First some considerations have been made about the geometry contest: the main dimension of the datacenter, the positioning of the racks and CRACs and the layout of cables in the under-floor have been studied. Hence implementing the numerical model has followed. This consisted in three major steps: data acquisition: i.e. the thermal data monitoring and thermography analysis; building-up the CFD modeling; model correlation what if analysis A) Data Center Geometry The room, object of the study, measures 3.25 m2 in the x-z plane and has a 3.28 m (3 feet) ceiling. There are 3 rows of racks oriented in the z-direction as shown in figure 2. The rows of racks are arranged in a front-to-front, back-to-back orientation such that hot and d aisles are created. Quadri elettrici Quadri elettrici Aria: input condizionata Aria: in ciro nella sala Aria calda da condizionare Quadri elettrici Quadri elettrici Prompt Engineering S.r.l. Via Livorno, 6 \ 44 Torino (TO) T \ F \ info@prompt-engineering.com

4 Figure 2 Data Center Layout B) Thermal data acquisition By means of a sensors monitoring and thermography pictures a thermal data acquisition has been performed. In figure 3 is shown the points layout thorough the datacenter. In particular, the red sensors read the hot air returning at the CRACs while the blue ones read the d air (the supply air) going into the plenum floor QE A CDZ A2 CDZ B2 CDZ A3 CDZ A3 QE A2 CDZ A4 V V V I4c V I23 I4b I I4 V2 V2 V3 EMC P595 Cs IBM SAN KMsw BIB KM b spr V3 IBM rame DS83 DL4 SEP VTS V4 DS83 S32 S8 BIB 2 KM b2 2 frame Cs fo V4 SAN P KM P S S23 S2 I5 S27 YF spr2 P595 I9 S9 V5 CDZ IBM SEP Y325 V5 3 frame BIB 3 KM b3 Tlc B5 5 frame com P DS8 S V6 SAN2 I I3 2 frame Blade c V6 BIB 4 spr3 S4 com Coms I2 I3 CS V7 SQ Tlc I26 B8 sia V7 w BIB 5 S7 com2 c blade I28 S S3 I27 fems V8 TLC CDZ S3b BIB P Rete CS V8 sep Tlc 4 V9 A BIB 6 exp new Rete V9 I2 BIBsw as4 S2 disp. sep p57- TLC5 VA S9 BIB 7 exp2 S3 VA new exp6 tape S3 S28 was ns52s5 S2 VB CS2 S8 tlc6 VB P595 BIB 8 exp3 Cent. TLC sep I28b sep VC KMB test was Serv. iseries VC exp5 exp4 Com. tlc7 VD sep VD VE VE I8b I5b VF I2 I8 VF CDZ B6 && && I9 VG CDZ A6 CDZ B5 CDZ A5 CDZ B4 VG QE B QE B2 VH Hour/Minute x-axis Hide all sensor data Help Sala 8 - piano CCM Figure 3 Thermal Sensors Layout S2 32 mq. Thanks to these thermal data it has been possible to point out some important considerations towards both the way of how the real HVAC system was working and how to set the boundary conditions to be used for the virtual model. Indeed, a carefully inspection allowed to trace some CRACs' anomalies: a malfunction evaluation is qualitatively shown in figure 4. It is simply to note that only four out twelve of the air conditioning were working as the standards claim. The information and considerations aforementioned were useful during the what if analysis followed after the built-up of the numerical model. Prompt Engineering S.r.l. Via Livorno, 6 \ 44 Torino (TO) T \ F \ info@prompt-engineering.com

5 Figure 4 HVAC System State of Art C) CFD Modeling, Assumptions and Key Measures The CFD modeling was conducted with the intent on gaining understanding of flow patterns and establishing a maximum value of inlet air temperature into the compartments modeled in the rack. The simulation was conducted using computational fluid dynamics tool called scstream from CRADLE-CFD. In the model, the numerical computational domain was the overall room. The room was modeled as adiabatic with no-slip boundary conditions. The revised k-epsilon model was used to account for the large scale turbulence within the room. About 5.. grid cells were arrayed across the solution domain. Prompt Engineering S.r.l. Via Livorno, 6 \ 44 Torino (TO) T \ F \ info@prompt-engineering.com

6 D) Model correlation Once built-up, the virtual model has been then correlated with the experimental data in order to allow trial-and-error virtual analyses. This step, also known as model validation it s rock bottom layer for the subsequent analysis and optimizations. Figure 5: Measured vs Simulated results on different locations As shown, the numerical model is well correlated in a wide range of measuring points. The validated model will be used in the subsequent what if analysis phase. Quantifying the efficiency of the whole HVAC system is a task that may be accomplished introducing the so called Supply Heat index, a dimensionless parameter measuring how much mixed is the air in the room. In an optimization loop process, it s mandatory to introduce indexes and parameters as a metric. Prompt Engineering S.r.l. Via Livorno, 6 \ 44 Torino (TO) T \ F \ info@prompt-engineering.com

7 E) What if analysis (next step) Having as starting point all the conclusions gathered during the monitoring step, some basic improvement to be introduced have been thought in order increase the system thermal efficiency. Two simple configurations have been taken in consideration: increasing the area of the vent tiles switching off he CRACs with anomalies In our virtual environment, these new configuration will be easily ranked as per the SHI parameter mentioned above. 5. CONCLUSIONS The Prompt Engineering approach based on the measure-simulation-optimizationrealization paradigm, brings to reliable and stable solutions. Especially in the case of high complexity systems, such as Server Rooms, Surgery Rooms, in which the system off time means high costs, it is mandatory reduce as much as possible every uncertainly. Simulations may reduce those uncertainly and, in the meanwhile, help engineers in performing effective what if analysis achieving optimal solutions. Moreover the virtual approach, widely used in the other engineering fields (from transportation to electronics, aerospace, ) is the enabler in finding new design spaces (that means new unconventional solutions) that can be the most effective in efficiency and cost reduction. Prompt Engineering S.r.l. Via Livorno, 6 \ 44 Torino (TO) T \ F \ info@prompt-engineering.com

Boosting the Energy efficiency of a Server Room: experimental + virtual approach.

Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Nowadays, the increase in computing power allows the successful applications of the CFD simulation methods in civil environments.

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Using CFD for optimal thermal management and cooling design in data centers

Using CFD for optimal thermal management and cooling design in data centers www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Rack Hygiene. Data Center White Paper. Executive Summary

Rack Hygiene. Data Center White Paper. Executive Summary Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,

More information

Effect of Rack Server Population on Temperatures in Data Centers

Effect of Rack Server Population on Temperatures in Data Centers Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers

W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY Rajat Ghosh, Pramod Kumar Vikneshan Sundaralingam Yogendra Joshi yogendra.joshi@me.gatech.edu G.W. Woodruff School

More information

HP Data Center Services

HP Data Center Services HP Data Center Services HP Technology Services - Per Event Services Technical data Enterprise-class data center facility infrastructures need to support both current IT objectives and new equipment and

More information

TRANSIENT AIR TEMPERATURE MEASUREMENTS IN A DATA CENTER

TRANSIENT AIR TEMPERATURE MEASUREMENTS IN A DATA CENTER Proceedings of the 21st National & 10TH ISHMT-ASME Heat and Mass Transfer Conference December 27-30, 2011, IIT Madras, India Paper ID: ISHMT_USA_013 TRANSIENT AIR TEMPERATURE MEASUREMENTS IN A DATA CENTER

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Statement Of Work Professional Services

Statement Of Work Professional Services Statement Of Work Professional Services Data Center Cooling Analysis using CFD Data Center Cooling Analysis Using Computational Fluid Dynamics Service 1.0 Executive Summary Table of Contents 1.0 Executive

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Control Strategies for Plenum Optimization in Raised Floor Data Centers

Control Strategies for Plenum Optimization in Raised Floor Data Centers Control Strategies for Plenum Optimization in aised Floor Data Centers Keke Chen, Clifford C. Federspiel, David M. Auslander, Cullen E. Bash, Chandrakant D. Patel Enterprise Software and Systems Laboratory

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS Paper Presented at ITHERM 2004 Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems June 1-4, Las Vegas, NV RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES

More information

Mobile Visual Analytics for Data Center Power and Cooling Management

Mobile Visual Analytics for Data Center Power and Cooling Management Mobile Visual Analytics for Data Center Power and Cooling Management Ratnesh Sharma, Ming Hao, Ravigopal Vennelakanti, Manish Gupta, Umeshwar Dayal, Cullen Bash, Chandrakant Patel, Deepa Naik, A Jayakumar,

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013

Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013 Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Computational Fluid Dynamics (CFD) can be used to numerically

More information

Strategies for Deploying Blade Servers in Existing Data Centers

Strategies for Deploying Blade Servers in Existing Data Centers Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling

More information

Analysis and Performance Prediction of Data Centre with Different Configurations using CFD

Analysis and Performance Prediction of Data Centre with Different Configurations using CFD Analysis and Performance Prediction of Data Centre with Different Configurations using CFD Mohammed Faisal K, PG Scholar Department of Mechanical Engineering, M. A College of Engg Kothamangalam,.. Ernakulam

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

11 Top Tips for Energy-Efficient Data Center Design and Operation

11 Top Tips for Energy-Efficient Data Center Design and Operation 11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal

More information

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational

More information

Data centers have been cooled for many years by delivering

Data centers have been cooled for many years by delivering The Increasing Challenge of Data Center Design and Management: Is CFD a Must? Mark Seymour, Christopher Aldham, Matthew Warner, Hassan Moezzi Future Facilities, San Jose, California, USA Mark Seymour,

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Thinking Outside the Box Server Design for Data Center Optimization

Thinking Outside the Box Server Design for Data Center Optimization Thinking Outside the Box Server Design for Data Center Optimization Marie Ross, Senior Applications Engineer Tom Gregory, Consultant Engineer October 2013 The benefits of analyzing thermal performance

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Energy Performance Optimization of Server Room HVAC System

Energy Performance Optimization of Server Room HVAC System International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION

Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use

More information

Application of CFD modelling to the Design of Modern Data Centres

Application of CFD modelling to the Design of Modern Data Centres Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of

More information

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency WHITE PAPER Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency 20A Dunklee Road Bow, NH 03304 USA 2007. All rights reserved. Sensatronics is a registered trademark of. 1 Abstract

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

Reducing the Annual Cost of a Telecommunications Data Center

Reducing the Annual Cost of a Telecommunications Data Center Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers This article appeared in the International Journal of Heating, Ventilation, Air-Conditioning, and Refrigeration Research, Volume 9, Number 2, April 2003, pp. 153-166. Use of Computational Fluid Dynamics

More information

Thermal Management of Datacenter

Thermal Management of Datacenter Thermal Management of Datacenter Qinghui Tang 1 Preliminaries What is data center What is thermal management Why does Intel Care Why Computer Science 2 Typical layout of a datacenter Rack outlet temperature

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

abstract about the GREEn GRiD

abstract about the GREEn GRiD Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.

More information

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

Measure Server delta- T using AUDIT- BUDDY

Measure Server delta- T using AUDIT- BUDDY Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009 IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

Local Temperature Control in Data Center Cooling: Part I, Correlation Matrix

Local Temperature Control in Data Center Cooling: Part I, Correlation Matrix Local Temperature Control in Data Center Cooling: Part I, Correlation Matrix Keke Chen, David M. Auslander, Cullen E. Bash, Chandrakant D. Patel Enterprise Software and Systems Laboratory HP Laboratories

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures

More information

Exergy-based Performance Metrics to Evaluate Irreversibility in Data Centre Environment Airspace

Exergy-based Performance Metrics to Evaluate Irreversibility in Data Centre Environment Airspace Seventh International Conference on Computational Fluid Dynamics (ICCFD7), Big Island, Hawaii, July 9-13, 2012 ICCFD7-3004 Exergy-based Performance Metrics to Evaluate Irreversibility in Data Centre Environment

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

FNT EXPERT PAPER. // Data Center Efficiency AUTHOR. Using CFD to Optimize Cooling in Design and Operation. www.fntsoftware.com

FNT EXPERT PAPER. // Data Center Efficiency AUTHOR. Using CFD to Optimize Cooling in Design and Operation. www.fntsoftware.com FNT EXPERT PAPER AUTHOR Oliver Lindner Head of Business Line DCIM FNT GmbH // Data Center Efficiency Using CFD to Optimize Cooling in Design and Operation Energy is the biggest cost factor with the highest

More information

MEASUREMENTS AND PREDICTIONS OF THE FLOW DISTRIBUTION THROUGH PERFORATED TILES IN RAISED-FLOOR DATA CENTERS

MEASUREMENTS AND PREDICTIONS OF THE FLOW DISTRIBUTION THROUGH PERFORATED TILES IN RAISED-FLOOR DATA CENTERS Proceedings of IPACK 01 The Pacific Rim/ASME International Electronic Packaging Technical Conference and Exhibition July 8 13, 2001, Kauai, Hawaii, USA IPACK2001-15728 MEASUREMENTS AND PREDICTIONS OF THE

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant

Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that

More information

Virtual Data Centre Design A blueprint for success

Virtual Data Centre Design A blueprint for success Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

HPC TCO: Cooling and Computer Room Efficiency

HPC TCO: Cooling and Computer Room Efficiency HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:

More information

Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center

Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center White Paper 121 Revision 1 by James W. VanGilder, P.E., APC by Schneider Electric Roger R. Schmidt, Ph.D., P.E., IBM Corporation

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information