1 Infrastructure Master Plan Strategy Update Rich Dewey Vice President, Information Technology & CIO New York Independent System Operator Budget and Priorities Working Group August 25, 2009
2 Background The Carman Road, Guilderland Power Control Center (PCC) was built in 1969 to support New York Power Pool operations Several minor renovations have been performed to address office space needs, computer room space requirements, and physical security concerns; control room technology has not been significantly updated The facility requires remediation for various environmental factors; asbestos, ground water leakage, and mold In 2008, a project was proposed to address several deficiencies: Temporary expansion office space is at end of life; occupancy permit expired Computer room facilities are inadequate to support full redundancy with KCC Control room configuration does not meet certain NERC CIP standards 2
3 Facilities Plan Goals Provide a sufficient facility infrastructure for a power control facility that meets the needs of today, and is designed to run the power grid of the future Deliver tools, technology, and facilities to maximize the Operation Department s ability to reliably operate the grid and administer markets Flexible design capable of adapting to changing reliability responsibilities and / or NERC requirements Design facilities that maximize the organization s efficiency Expand the data center capacity to enable full redundancy across sites, achieve highest level of reliability within computing environment (cooling, power, mechanical, and communications) Provide necessary business continuity space to minimize business interruption during crisis 3
4 Project Progress High level architectural concepts have been developed Full spectrum of construction options assessed Results of related business planning activities have been incorporated in the design concepts Control room design Building infrastructure redundancy Business continuity Multiple financing options pursued and considered Preliminary financing option exists with finite window Project plans, options, and cost estimates have been revised in light of additional factors 4
5 Facilities Plan Options Reviewed Scenario One: Original 2008 limited expansion of Guilderland facility. Estimates did not include necessary control room modifications. Option does not meet reliability or expansion criteria. Scenario Two: Expand the Guilderland facility to house an optimal Primary Control Center and data center. Update the East Greenbush building infrastructure to support greater data center redundancy for power and cooling. Scenario Three: Scenario Four: New building at the East Greenbush site to house a new optimal Primary Control Center. Expand the Guilderland facility to house a new data center, provide additional business continuity office space, and update building infrastructure to support greater data center redundancy for power and cooling. New building at alternate site to house an optimal Primary Control Center and data center. Update the East Greenbush building infrastructure to support greater data center redundancy for power and cooling. 5
6 Plan Enhancement Summary Control room expansion to allow for configuration of up to ten (10) desks and 17 seats on control room floor with full video display capabilities Lower voltage system monitoring requirements Smart Grid expansion capabilities Emergency situations or special conditions Data center infrastructure enhanced to provide maximum redundancy for power supply, cooling, and communications Data communications design to support desired capacity / redundancy between control centers, and to facilitate power system evolution and Smart Grid development Single-site / campus configuration to permit maximized level of efficiency and teamwork for NYISO staff 6
7 Single Campus Site Plan 7
8 Scenario Feature Comparison Scenario 2 Scenario 3 1. Building Square Footage (Gross) 209,500 ft 2 245,300 ft 2 2. Plan Staff Seats 544 seats 521 seats 2a. Maximum Staff Seats 544 seats 580 seats 3. Plan Control Room Seats 17 seats 17 seats 3a. Maximum Control Room Seats 17 seats 21 seats 4. Construction Phases 8 phases 7 phases 5. Construction Duration 34 months 22 months 8
9 Total Project Cost Estimates East Greenbush Control Center Construction, Electrical, Mechanical $27,900,000 Control Room, Video Display, Security $ 5,200,000 Design Team, CM, Contingencies $ 8,300,000 Interim Deliverables (2009) $(3,000,000) Subtotal Design & Construction $38,400,000 Facilities Equipment, Infrastructure $ 1,000,000 IT Network, Move, Telemetry, AV $ 5,500,000 Video Graphics Design $ 700,000 Security Improvements $ 200,000 Subtotal IT Infrastructure $ 7,400,000 * Grand Project Total $45,800,000 Total project cost difference negligible between Guilderland or East Greenbush PCC * - Items traditionally included as part of IT Infrastructure budget. 9
10 ISO Cost Comparison ISO-NE $45 Million Includes construction costs for a new combined Data and Control Center up to migrating hardware and software (in operation) PJM $33 Million Includes construction costs for a new combined Data and Alternate Control Center up to migrating hardware and software (just completed) ERCOT $42 - $47 Million Includes construction costs for a new combined Data and Control Center up to migrating hardware and software (proposed) CAISO $160 Million New corporate headquarters building (recently announced) 10
11 Construction Project Benefits Common Benefits: Enhanced security features of physical structure Enhanced dispatcher training capabilities and business continuity infrastructure Better system availability through increased redundancy of support systems (power, cooling, mechanical, etc.) Enlarged control room for improved grid management capabilities and future expansion Improved power grid management capabilities through video system expansion Additional Benefits for Scenario 3 Single Campus: Improved staff efficiency through co-location at one campus Opportunity to enhance security due to single campus configuration Recommendation: Initiate project to build a new control room on East Greenbush site; establish entire NYISO business on a single campus 11
San Diego Gas & Electric Company FERC Order 717 Transmission Function Employee Job Descriptions June 4, 2015. Electric Grid Operations
San Diego Gas & Electric Company FERC Order 717 Transmission Function Employee Job Descriptions June 4, 2015 Electric Grid Operations Director Electric Grid Operations: Responsible for overall transmission
More informationSan Diego Gas & Electric Company FERC Order 717 Transmission Function Employee Job Descriptions August 10, 2015. Electric Grid Operations
San Diego Gas & Electric Company FERC Order 717 Transmission Function Employee Job Descriptions August 10, 2015 Electric Grid Operations Director Electric Grid Operations: Responsible for overall transmission
More informationSan Diego Gas & Electric Company FERC Order 717 Transmission Function Employee Job Descriptions. Electric Grid Operations
San Diego Gas & Electric Company FERC Order 717 Transmission Function Employee Job Descriptions Electric Grid Operations Director Electric Grid Operations: Responsible for overall transmission system operations
More informationNew York State of the Market System - NYISO Success Project
Auxiliary Market Products Additional Capacity Zones The NYISO and stakeholders are developing the rationale in 2010 for creating additional capacity zones, identified as a recommendation in the 2009 State
More informationBELL LABS ADVISORY SERVICE FOR SMART GRID NETWORK TRANSFORMATION STRATEGIC PLANNING FOR THE MODERNIZATION OF UTILITY COMMUNICATIONS NETWORKS
BELL LABS ADVISORY SERVICE FOR SMART GRID NETWORK TRANSFORMATION STRATEGIC PLANNING FOR THE MODERNIZATION OF UTILITY COMMUNICATIONS NETWORKS APPLICATION NOTE SUMMARY Bell Labs Advisory Service for Smart
More informationU.S. DEPARTMENT OF COMMERCE NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
U.S. DEPARTMENT OF COMMERCE NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY ) Developing a Framework ) To Improve ) Docket No. 130208119-3119-01 Critical Infrastructure Cybersecurity ) ) RESPONSE OF THE
More informationPalmyra Public Library Library Building Planning Update February 12, 2012 - Rich Bowra, Library Consultant
Palmyra Public Library Library Building Planning Update February 12, 2012 - Rich Bowra, Library Consultant Introduction This update will provide the library with a number of insights into the new building
More informationBridging the Missing Money Gap Solutions for competitive power cash flow shortfalls
IHS ENERGY Multiclient Study Bridging the Missing Money Gap Solutions for competitive power cash flow shortfalls This major research study identifies the causes of competitive power cash flow shortfalls,
More informationISO/RTO Council Comments on National Institute of Standards and Technology Proposed Smart Grid Interoperability Standards
ISO/RTO Council Comments on National Institute of Standards and Technology Proposed Smart Grid Interoperability Standards Pursuant to the Notice posted in the Federal Register on June 9, 2009, the ISO/RTO
More informationNodal Exchange Contract Specifications
Nodal Exchange Contract Specifications Monthly Day Ahead On-Peak Power Contract Specification Cash Settled Financial On-Peak Power. Financial On-Peak, [PJM/NYISO/MISO/MISO-RTO/ISO- NE/CAISO/ERCOT] [Nodal
More informationAshley Clarke Hosted Desktop. Business Name
Ashley Clarke Hosted Desktop Business Name Our Partner s Technology Partner Ashley Clarke s Hosted Desktop is a full featured Windows 8 style experience delivered from the cloud. One of the key advantages
More information08 October, 2014. Renovation Projects at. East Vincent Elementary School + East Coventry Elementary School. Inspiring Excellence. Inspired Students.
08 Octoer, 2014 Renovation Projects at Elementary School + Elementary School Inspiring Excellence. Inspired Students. 1 1 Traditional Renovation Renovations and Additions to Both Sites Independent approach
More informationBorough President and City Council Capital Funding Requests FY 2009
Borough President and City Council Capital Funding Requests FY 2009 CIP Number Phase* Request $ Classroom Development GR-0928061514 DCE $1,088,000 Expansion of Campus Security Systems GR-0504070756 DCE
More informationInformation for Charter Schools. The following six requirements cannot be waived by a charter school:
Information for Charter Schools Site, Facility, and School Codes There are three codes associated with any school. The site code references the property on which an educational facility is located. Site
More informationGenerator Interconnection and Deliverability Study Methodology Technical Paper
Generator Interconnection and Deliverability Study Methodology Technical Paper July 2, 2013 Generator Interconnection and Deliverability Study Methodology Table of Contents Introduction... 1 Section One:
More informationNERC Alert System Overview
NERC Alert System Overview Todd Thompson, CIP Investigator todd.thompson@nerc.net Chris Lada, Situation Awareness Coordinator chris.lada@nerc.net About NERC: Mission To ensure the reliability of the North
More informationHealthcare 101 Committee Member James E. Sykes, AIA, LEED AP BD+C MorrisSwitzer Environments for Health, LLC JSykes@MorrisSwitzer.
Healthcare 101: Master Planning Presenter Eduardo S. Egea, CAAPPR, AIA, NCARB Senior Vice President / Associate Principal Director of Healthcare for the Caribbean and Latin America HKS Architects, Inc.
More informationSecurity and regulatory challenges for leveraging cloud computing in power systems
1 Security and regulatory challenges for leveraging cloud computing in power systems Can you trust the Cloud? Edgardo Luzcando NYISO July 2015 2 Can you trust the Cloud? It depends on your ability to meet
More informationInstitute for Business Continuity Training 1623 Military Road, # 377 Niagara Falls, NY 14304-1745
ECP - 601: Effective Business Continuity Management: ISO 22301 This 3-day course provides an intensive, hands-on workshop covering all major aspects for the design of an effective Business Continuity Plan
More information2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
More informationWork Space and Office Furniture Standards
Work Space and Office Furniture Standards June 2013 HISTORY AND CURRENT UNDERSTANDING Interior building space is a precious and finite resource at most universities, including Notre Dame. In 2008 an assessment
More informationHow do you design maximum data security?
How do you design maximum data security? Integrated infrastructure solutions for data centers Answers for industry. 2 Siemens a system integrator with universal expertise. Data is the lifeblood of every
More informationAudit of the Data Center Consolidation Initiative at NARA. OIG Draft Audit Report No. 12-09. May 10, 2012
Audit of the Data Center Consolidation Initiative at NARA OIG Draft Audit Report No. 12-09 May 10, 2012 Table of Contents Executive Summary... 3 Background... 4 Objectives, Scope, Methodology... 7 Audit
More informationTransmission Grid Reliability And Performance Monitoring
Transmission Grid Reliability And Performance Monitoring NARUC s Summer Committee Meetings July 29, 2002 Portland, Oregon by Vikram S. Budhraja President, Electric Power Group, LLC Chair, Consortium for
More informationProposed Project For Exide Technologies Bristol, Tennessee - New NEPA Analysis
MEMORANDUM FOR NEPA FILE FROM: SUBJECT: MARK LUSK NEPA DOCUMENT MANAGER Supplement Analysis for the Exide Technologies' Proposed Project under the Electric Drive Vehicle Battery and Component Manufacturing
More informationBusiness Energy Efficiency. Webinar August 29, 2012
Business Energy Efficiency Webinar August 29, 2012 Today s presenters and some notes... John Pirko LeClairRyan Greg Booth PowerServices, Inc. Roy Palk LeClairRyan Welcome. With the high number of attendees,
More informationSAMPLE WORK BREAKDOWN STRUCTURES VARIOUS TYPES OF PROJECT
Applications Development Project Sample WBS Management and support Provide project management Provide quality control Conduct meetings and reviews Materials and supplies Travel and living costs Miscellaneous
More informationChabot-Las Positas Community College District Bond Measure Technology Improvements Supplement to Capital Improvement Program
Chabot-Las Positas Community College District Bond Measure Technology Improvements Supplement to Capital Improvement Program Guidelines for Technology Estimates: The Capital Improvement Program for both
More informationWright State University Information Security
Wright State University Information Security Controls Policy Title: Category: Audience: Reason for Revision: Information Security Framework Information Technology WSU Faculty and Staff N/A Created / Modified
More informationWork Space and Office Furniture Standards January 2014
Work Space and Office Furniture Standards January 2014 HISTORY AND CURRENT UNDERSTANDING Interior building space is a precious and finite resource at most universities, including Notre Dame. In 2008 an
More informationPROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER
UNIVERSITY OF WASHINGTON OFFICE OF THE VICE PROVOST PLANNING AND BUDGETING Capital and Space Planning PROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER JULY 31, 2006 University of Washington
More informationMilestone Solution Partner IT Infrastructure Components Certification Summary
Milestone Solution Partner IT Infrastructure Components Certification Summary Dell FS8600 NAS Storage 12-1-2014 Table of Contents Introduction:... 2 Dell Storage Architecture:... 3 Certified Products:...
More informationOIT Cloud Strategy 2011 Enabling Technology Solutions Efficiently, Effectively, and Elegantly
OIT Cloud Strategy 2011 Enabling Technology Solutions Efficiently, Effectively, and Elegantly 10/24/2011 Office of Information Technology Table of Contents Executive Summary... 3 The Colorado Cloud...
More informationCounty Of Sonoma Agenda Item Summary Report
County Of Sonoma Agenda Item Summary Report Department: General Services Contact: Rob Kambak Phone: (707) 565-3211 Board Date: 10/27/2009 4/5 Vote Required Deadline for Board Action: AGENDA SHORT TITLE:
More informationTRANSMISSION OPERATIONS (August 5, 2010)
TRANSMISSION OPERATIONS (August 5, 2010) Managing Director Transmission Operations: Paul B. Johnson The Managing Director - Transmission Operations is responsible for the safe, reliable, costeffective,
More informationCan Your Data Center Infrastructure Handle the Heat of High Density? 5 Ways to Test Your Data Center Infrastructure before Installing Blades
Can Your Data Center Infrastructure Handle the Heat of High Density? 5 Ways to Test Your Data Center Infrastructure before Installing Blades Can Your Data Center Infrastructure Handle the Heat of High
More informationPost Occupancy Evaluation (POE) Technical Instructions
1.0 Purpose These technical instructions define the typical steps required by HHS personnel in the use of the. The POE consists of a detailed and systematic assessment of a facility that is operational
More informationTexas transformed. Achieving significant savings through a new electricity market management system
Texas transformed Achieving significant savings through a new electricity market management system KHOSROW MOSLEHI The state of Texas has long been the center of energy activities in the United States,
More informationUniversity of Massachusetts Medical School's Data Center Relocation For the period July 1, 2008 through August 31, 2010
` Official Audit Report Issued September 30, 2011 University of Massachusetts Medical School's Data Center Relocation For the period July 1, 2008 through August 31, 2010 State House Room 230 Boston, MA
More informationISACA North Dallas Chapter
ISACA rth Dallas Chapter Business Continuity Planning Observations of Critical Infrastructure Environments Ron Blume, P.E. Ron.blume@dyonyx.com 214-280-8925 Focus of Discussion Business Impact Analysis
More informationAdministrative or Research Faculty Job Description. Position Title Requested: Assistant Director for Residence Life of Housing Operations
Administrative or Research Faculty Job Description Position Title Requested: Assistant Director for Residence Life of Housing Operations Date of Description: 1/28/16 Supervisor Title: Director of Housing
More informationDATA CENTERS AND CRITICAL FACILITIES
DATA CENTERS AND CRITICAL FACILITIES 01 MEETING COMPLEX FACILITY DESIGN NEEDS As a leader in the data center and critical facility market since the beginning days of the dot.com era, we understand the
More information2015 Project Schedule Milestone Update
2015 Schedule Milestone Update Robb Pike Director, & Product Management New York Independent System Operator Ryan Smith Senior Manager, Enterprise Product & Management New York Independent System Operator
More informationServer Consolidation. Report to the Joint Legislative Oversight Committee on Information Technology
Server Consolidation Report to the Joint Legislative Oversight Committee on Information Technology Chris Estes State Chief Information Officer December 2013 This page left blank intentionally Contents
More informationWhen to Leverage Video as a Platform A Guide to Optimizing the Retail Environment
When to Leverage Video as a Platform A Guide to Optimizing the Retail Environment Contents S1 An Industry in Transition Over the past few years, retail has seen seismic changes in how the customer shops.
More informationEvolution of Control for the Smart Transmission Grid
Evolution of Control for the Smart Transmission Grid Anjan Bose Washington State University Pullman, WA SCE Smart Grid Research Symposium California Institute Of Technology October, 2011 The Past (before
More informationHalton Regional Police Service Public Agenda Recommendation Report
Halton Regional Police Service Public Agenda Recommendation Report To: Chairman and Police Service Board Members From: Chief Stephen J. Tanner Subject: SINGLE SOURCE BUCHANAN TECHNOLOGIES Report #: P15-5-CPS-R-01
More informationCO 2 Emissions from Electricity Generation and Imports in the Regional Greenhouse Gas Initiative: 2010 Monitoring Report
CO 2 Emissions from Electricity Generation and Imports in the Regional Greenhouse Gas Initiative: 2010 Monitoring Report August 6, 2012 1 This report was prepared on behalf of the states participating
More informationSLA. Co-Managed. Do-It-Yourself
SLA Do-It-Yourself Co-Managed Co-Managed Fully Managed Operational Application Support DB Support Storage Planning Capacity planning Change Management Release Management Pro Services Systems Monitoring
More informationThe new edge of the network: Preparing your network for the consumerization of IT. Geoff Mattie Global Solutions Architect Dell Inc.
The new edge of the network: Preparing your network for the consumerization of IT Geoff Mattie Global Solutions Architect Dell Inc. The edge of your network is expanding, and your work force expects the
More informationCompleted. Document Name. NERC CIP Requirements CIP-002 Critical Cyber Asset Identification R1 Critical Asset Identifaction Method
NERC CIP Requirements CIP-002 Critical Cyber Asset Identification R1 Critical Asset Identifaction Method R2 Critical Asset Identification R3 Critical Cyber Asset Identification Procedures and Evaluation
More informationMidwest Reliability Organization Procedure For NERC PRC-012
Midwest Reliability Organization Procedure For NERC PRC-012 A. Introduction The following procedure developed by the MRO Protective Relay Subcommittee (PRS) and Transmission Assessment Subcommittee (TAS)
More informationProject Charter and Scope Statement
Prepared by: Mike Schmidt Version: 1.0 Last Revision Date: April 14, 2010 Create Date: May 6, 2010 EXECUTIVE SUMMARY... 3 1 INTRODUCTION... 4 2 PROJECT OBJECTIVES... 4 2.1 MISSION... 4 2.2 OBJECTIVES...
More informationBuilding Technologies. Access Control. SiPass integrated Fully expandable system that grows with your business
s Building Technologies Access Control SiPass integrated Fully expandable system that grows with your business SiPass integrated : a system, that leaves nothing to be desired. SiPass integrated is the
More informationCommercial Building Valuation Report
INSURED University of Houston - Victoria Effective Date: Expiration Date: Cost as of: 09/2010 BUILDING 1 217 - University Center 77901 Location Adjustments Climatic Region: High Wind Region: Seismic Zone:
More informationMaster Plan Update and EIR Amendment
Master Plan Update and EIR Amendment Los Angeles Trade Technical College Master Plan Update and EIR Amendment HARBOR FREEWAY LOS ANGELES TRADE TECHNICAL COLLEGE (HWY 110) MASTER PLAN EIR REVIEW AND UPDATE
More informationGlobal Headquarters: 5 Speen Street Framingham, MA 01701 USA P.508.872.8200 F.508.935.4015 www.idc.com
WHITE PAPER Solutions for the Datacenter's Thermal Challenges Sponsored by: IBM and Intel Jed Scaramella January 2007 Matthew Eastwood IDC OPINION Global Headquarters: 5 Speen Street Framingham, MA 01701
More informationClinical Scheduling Software http://www.clinicalplacement.org
Mid-Michigan Innovation Team Learning Communities Presented by Spicer Group / East Central Michigan RSA for Healthcare February 5, 2008 For more information contact: Leslie J. Roth, LLC rothleslie@charter.net
More information2015 2019 Strategic Plan New York Independent System Operator
2015 2019 Strategic Plan New York Independent System Operator NYISO markets deliver significant benefits by coordinating the commitment and dispatch of generation to ensure that resources are started and
More informationPreliminary Project Description
Auxiliary Market Products Additional Capacity Zones The NYISO and stakeholders are developing the rationale in 2010 for creating additional capacity zones, identified as a recommendation in the 2009 State
More informationNew York Independent System Operator
New York Independent System Operator Carman Road Data Center Study October 15, 2010 Experience you can trust. Copyright 2010, KEMA, Inc. The information contained in this document is the exclusive, confidential
More informationGrid of the Future. Integration of Renewables Energy Storage Smart Grid. Presentation by David Hawkins Lead Renewables Power Engineer Grid Operations
Grid of the Future Integration of Renewables Energy Storage Smart Grid Presentation by David Hawkins Lead Renewables Power Engineer Grid Operations Grid of the Future Current Power System Gen. Trans. Dist.Cust.
More informationModernize your Monitor Pro software with less risk, less cost and less effort
Modernize your Monitor Pro software with less risk, less cost and less effort Schneider Electric announces end of life for Monitor Pro With the release of Monitor Pro version 7.6, Schneider Electric has
More informationGovernance. What s a Governance?
Governance What s a Governance? Governance FERC - Federal Energy Regulatory Commission NERC - North American Electric Reliability Council. NPCC - Northeast Power Coordinating Council NYSRC - New York State
More informationCOLOCATION A BUYERS GUIDE
COLOCATION A BUYERS GUIDE INTRODUCTION Colocation in a data centre offers organisations a place to securely house their IT equipment, as opposed to storing and running it on-site, which can be both expensive
More informationCO 2 Emissions from Electricity Generation and Imports in the Regional Greenhouse Gas Initiative: 2012 Monitoring Report
CO 2 from Electricity Generation and Imports in the Regional Greenhouse Gas Initiative: 2012 Monitoring Report August 11, 2014 1 This report was prepared on behalf of the states participating in the second
More information10 Hurdles preventing increasing utilization of video conferencing
User s Perspective 10 Hurdles preventing increasing utilization of video conferencing 1. Number of people that know video conferencing is available. 2. Number of people that know they can have mixed environment
More informationENGINEERING COMPETENCIES ENTRY LEVEL ENGINEER. Occupation Specific Technical Requirements
ENGINEERING COMPETENCIES ENTRY LEVEL ENGINEER Responsible for performing entry level engineering analysis, design, plan, review and inspection for small to medium projects and/or designated segments of
More informationPerformance Metrics. For Independent System Operators And Regional Transmission Organizations
Performance Metrics For Independent System Operators And Regional Transmission Organizations A Report to Congress In Response to Recommendations of the United States Government Accountability Office April
More informationMISSISSIPPI DEPARTMENT OF HEALTH Division of Health Planning and Resource Development May 2007. Staff Analysis
MISSISSIPPI DEPARTMENT OF HEALTH Division of Health Planning and Resource Development May 2007 CON Review: HG-RC-0407-007 Southwest Mississippi Regional Medical Center Capital Expenditure: $8,597,238 Location:
More informationTemplate for Submission of Comments on Convergence Bidding and Bid Cost Recovery
Template for Submission of Comments on Convergence Bidding and Bid Cost Recovery The CAISO is requesting written comments to presentations and documents discussed at the October 16 th Convergence Bidding
More informationEXECUTIVE REPORT. Can Your Data Center Infrastructure Handle the Heat of High Density?
EXECUTIVE REPORT Can Your Data Center Infrastructure Handle the Heat of High Density? If you re losing sleep wondering how your company can migrate to high density computing architectures, you re not alone.
More informationPHYSICAL PLANT FACILITIES, PLANNING, & CONSTRUCTION DEPARMENTAL PROCEDURES
PHYSICAL PLANT FACILITIES, PLANNING, & CONSTRUCTION DEPARMENTAL PROCEDURES Section: Administration Effective date: July 1, 2014 Contractors & Professionals Procedure Subject: FPC -04 Performance Number:
More informationCMS Policy for Configuration Management
Chief Information Officer Centers for Medicare & Medicaid Services CMS Policy for Configuration April 2012 Document Number: CMS-CIO-POL-MGT01-01 TABLE OF CONTENTS 1. PURPOSE...1 2. BACKGROUND...1 3. CONFIGURATION
More informationThe Natural Gas-Electric Interface: Summary of Four Natural Gas-Electric Interdependency Assessments WIEB Staff November 30, 2012
Introduction. The Natural Gas-Electric Interface: Summary of Four Natural Gas-Electric Interdependency Assessments WIEB Staff November 30, 2012 The increased reliance on natural gas as the primary fuel
More informationDESIGN RECOMMENDATIONS AND CRITERIA FOR EMERGENCY OPERATIONS CENTERS
DESIGN RECOMMENDATIONS AND CRITERIA FOR EMERGENCY OPERATIONS CENTERS Michigan State Police Emergency Management Division February 2003 The purpose of this guidance is to help local jurisdictions improve
More informationStatus of Demand Response in Europe. Jessica Stromback, Smart Energy Demand Coalition EPFL Lausanne Switzerland Sept 10 th, 2015
Status of Demand Response in Europe Jessica Stromback, Smart Energy Demand Coalition EPFL Lausanne Switzerland Sept 10 th, 2015 The Smart Energy Demand Coalition (SEDC) is an European Industry Association
More informationDemand Response Management System ABB Smart Grid solution for demand response programs, distributed energy management and commercial operations
Demand Response Management System ABB Smart Grid solution for demand response programs, distributed energy management and commercial operations Utility Smart Grid programs seek to increase operational
More informationPUBLIC RELEASE PATENT AND TRADEMARK OFFICE. Inadequate Contractor Transition Risks Increased System Cost and Delays
PUBLIC RELEASE PATENT AND TRADEMARK OFFICE Inadequate Contractor Transition Risks Increased System Cost and Delays Inspection Report No. OSE-10084-8-0001 / December 1997 Office of Systems Evaluation PTO
More informationPowering Your Datacenter
Powering Your Datacenter 560 MISSION STREET, SUITE 2900 SAN FRANCISCO, CA 94105 TEL 415-738-6500 FAX 415-738-6501 WWW.DIGITALREALTYTRUST.COM 2323 BRYAN STREET, SUITE 2300 DALLAS, TX 75201 877-DRT-DATA
More informationGeneration and Transmission Interconnection Process
PJM Manual 14A Generation and Transmission Interconnection Process Revision: 18 Effective Date: January 28, 2016 Prepared by Planning Division Generation Interconnection Department PJM 2016 Table of Contents
More informationLast revised: September 1, 2014 TRANSMISSION FUNCTION TITLES AND JOB DESCRIPTIONS
Last revised: September 1, 2014 TRANSMISSION FUNCTION TITLES AND JOB DESCRIPTIONS EVP, Chief Operations Officer, has primary responsibility for the overall planning, operations and control of the transmission
More informationThe Financial Planning Analysis and Reporting System (FPARS) Project: Implementation Status Update
STAFF REPORT ACTION REQUIRED The Financial Planning Analysis and Reporting System (FPARS) Project: Implementation Status Update Date: March 24, 2014 To: From: Wards: Reference Number: Government Management
More informationOracle Utilities Customer Care and Billing
Customer Care and Billing Utilities are faced with a rapidly changing industry and increasing expectations from their customers. Adapting to these factors with existing customer information systems likely
More informationLR120 Load Runner 12.0 Essentials Instructor-Led Training Version 12.0
LR120 Load Runner 12.0 Essentials Instructor-Led Training Version 12.0 Overview This five-day course introduces students to LoadRunner 12.0. The course covers topics about the Virtual User Generator (VuGen),
More informationFY 2012 MILITARY CONSTRUCTION PROJECT DATA MW EA MW EA EA LS
1. COMPONENT UNCLASSIFIED Ft. Belvoir, VA 4. PROJECT TITLE Technology Center Third Floor Fit-Out 5. PROGRAM ELEMENT 6. CATEGORY CODE 131 7. PROJECT NUMBER -013 8. PROJECT COST ($000) $54,625 9. COST ESTIMATES
More information2009 Product Enhancements
Energy Marketplace Product Enhancements Comprehensive Bid Management System Phase 4 & 5 The Comprehensive Bid Management System project will address the pressing need to stabilize and modernize NYISO's
More informationNYISO 2004 Projects Summary
NYISO Projects Summary Budget, Standards & Performance subcommittee meeting October 10, 2003 Table of Contents Project Number A541 A543 A556 A559 A564 A573 A574 A577 A600 A619 A620 A625 A630 A636 A647
More informationConvergence Bidding Stakeholder Conference Call
Convergence Bidding Stakeholder Conference Call Margaret Miller Senior Market Design & Policy Specialist Convergence Bidding Stakeholder Conference Call August 13, 2009 Agenda 1:00 1:15 - Plan for Stakeholder
More informationUNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION
UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Reliability Technical Conference Docket No. AD16-15-000 Prepared Statement of Mark Rothleder on behalf of the California Independent System
More informationBRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
More informationWork Space and Office Furniture Standards December 2014
Work Space and Office Furniture Standards December 2014 HISTORY Interior building space is a precious and finite resource at most universities, including Notre Dame. In 2008 an assessment of administrative
More informationFiscal Year 2015-16 Information Technology Request
PROGRAM PLAN STATUS and OIT BEST PRACTICES 2016-016 Approved Program Plan? N/A Date Approved: The university says that the project design follows best practices set forth by the datacenter equipment manufacturers
More information2015 HSC Information and Digital Technology Networking and hardware Marking Guidelines
015 HSC Information and Digital Technology Networking and hardware Marking Guidelines Section I Multiple-choice Answer Key Question Answer 1 B C 3 B 4 A 5 B 6 D 7 D 8 A 9 A 10 C 11 D 1 A 13 C 14 B 15 B
More informationSAMPLE IT CONTINGENCY PLAN FORMAT
SAMPLE IT CONTINGENCY PLAN FORMAT This sample format provides a template for preparing an information technology (IT) contingency plan. The template is intended to be used as a guide, and the Contingency
More informationITS Plans for Bond Measure. J. Methe
ITS Plans for Bond Measure J. Methe Objectives of March Review Ensure ITS expansion provides improved systems access, performance, and stability for the Colleges as technology becomes an integral part
More informationREQUEST FOR PROPOSALS
REQUEST FOR PROPOSALS Design Build Services for Information Technology/ Security for Achievement Prep Public Charter School - Wahler Campus Redevelopment Project Issued: Friday, December 19 th, 2014 IMPORTANT
More informationNIST Cloud Computing Program Activities
NIST Cloud Computing Program Overview The NIST Cloud Computing Program includes Strategic and Tactical efforts which were initiated in parallel, and are integrated as shown below: NIST Cloud Computing
More informationPanel Session: Lessons Learned in Smart Grid Cybersecurity
PNNL-SA-91587 Panel Session: Lessons Learned in Smart Grid Cybersecurity TCIPG Industry Workshop Jeff Dagle, PE Chief Electrical Engineer Advanced Power and Energy Systems Pacific Northwest National Laboratory
More information2 0 1 7-2 1 F I V E Y E A R C A P I T A L O U T L A Y P L A N ( 2 0 1 7-1 8 F I R S T F U N D I N G Y E A R )
Print Date: 5/13/2015 Page: 1 2 0 1 7-2 1 F I V E Y E A R C A P I T A L O U T L A Y P L A N ( 2 0 1 7-1 8 F I R S T F U N D I N G Y E A R ) Los Rios CCD Prepared in reference to the Community College Construction
More information