1 BROAD INITIATIVES/SHARP FOCUS - CUTS ELECTRICITY CONSUMPTION 15% VICTOR GIALANELLA SITE FACILITIES MANAGER EXXON CHEMICAL COMPANY LINDEN, NJ ABSTRACT Analysis of electrical consumption can payout in reduced energy costs. Continuous monitoring of electrical usage coupled with improvements and optimization in system(s) operations can have a favorable impact on annual operating expenditures. Further, participation in local utility rebate programs to reduce electrical consumption will enhance funding of energy efficient programs. OVERVIEW In 1994, Exxon Chemical Company's Linden Technology Center (LTC) formed an Energy Reduction Committee whose charge included the assessment and development of various optimization and energy reduction ideas. The Committee recommended implementing two (2) significant capital projects; namely, the installation of energy efficiency lighting and the shutdown during "oft hours" of electrical consumers which had no impact on base client operations. As a result of these efforts, LTC has reduced its total electrical consumption significantly in recent years. In 1996, electrical usage declined 15% relative to 1995 consumption. Taking into account occupancy consolidations, it has been estimated that electrical usage declined 12% due solely to these two (2) thrusts. LTC SITE BACKGROUND The Linden Technology Center (LTC) is a 75 acre, 45-year old complex located in Linden, Union County, New Jersey, approximately 15 miles WSW of New York City. Today, facilities management operates approximately 540k SF of office, laboratory and pilot plant space. This includes one (1) laboratory/office complex, three (3) office buildings, five (5) pilot plant structures, and one (I) engine testing facility, known as MADS. Figure 1 presents a plan view of the site. Historically, LTC was the primary hub of research development for many operating affiliates of Exxon Corporation. In recent years (since 1993), LTC has been in a consolidation mode due to organizational restructuring and changes in research focus. These developments have provided many challenges in facilities management, especially in the area of operating costs where the focus has been to reduce expenditures in order to remain a competitive site. LTC is a relatively "old" facility (most buildings constructed circa ). Automated control flexibility is not inherent in the design of the site's utilities infrastructure nor in the design of air systems servicing the various buildings within the complex... LEGEND: ~ :~~~~~:.nnl 1mB ~-:"~c::~u c=i ~:."-AM' :~~~: CJ :':~DC:~. Figure I. Exxon Chemical Company's Linden Technology Center Site Map 15

2 Further, capacity changes to original operating systems over the last four (4) decades did not optimize system(s) performance; generally, such changes accounted for incremental requirements ~ only. This "approach" has resulted in overcapacity and energy inefficiencies. AIR CIRCULATION - A SIGNIFICANT PORTION OF LTC'S ELECTRICAL DEMAND Circulating air to the various buildings within the LTC complex utilizes electricity, and this process demands a significant portion of LTC's annual electrical consumption. With the exception of one (1) building, LTC's structures deploy a "oncethrough" air system design, requiring, on average, twelve (12) air changes per hour (typical design standards for laboratory and pilot plant areas). To help put the demand to just circulate air into perspective, the following simplification quantifies the electrical load and cost for a "once through" air process servicing a hypothetical building equal to LTC's net operating area. Let's assume LTC's 540k SF operating area were housed as one (1) structure seven (7) feet high, requiring twelve (12) air changes per hour. The air supply system servicing such a structure would equate to an intake fan capacity of -750k cfm. Assuming the building were "in balance", i.e. no significant internal positive or negative pressure, the exhaust system would exfiltrate 750k cfm as well. Based on an average 3" WG static pressure and a 65% fan efficiency, total system driver capacity would equate to approximately 825 kw. Operating such a system 24 hours per day, 365 days per year, at an average unit rate of 7.5 cents/kwh, electrical consumption would total 7.25M kwh and electricity costs would total approximately $550k. This represents -35% of LTC's electrical consumption and annual electrical bill--just to circulate air. LTC'S ANNUAL ELECTRICAL CONSUMPTION - "CUT' VARIOUS WAYS LTC's electrical cost profile is shown in Figure 2. Electrical consumption for the same period is shown in Figure 3. Historically, electrical ex-penditures represent approximately 15% of LTC's overall "space" operating budget (rent). Figure 4 presents a pie-ehart of how electricity is consumed within the LTC complex. Figure 5 highlights current "on-hours" vs. "off-hours" consumption ("off-hours" takes into account consumption on weekdays between 6 p.m. through 6 a.m., weekends and holidays). Figures 6 and 7 highlight electrical usage during a "typical" non-summer two (2) week period, and clearly illustrate the progress achieved in reducing electrical consumption at LTC over the course of Analysis of the "what, when and why" of operations during the non-summer timeframe served as the basis for changes in operations which led to shutting down air supply and exhaust systems during the "off-hours" via a combination of automated and manual shutdowns. The consumption differential shown in Figures 6 and 7 equates to an annual reduction of -3.0M kwh in electrical usage and a savings of $225k in electrical costs. $2,500,000., $2,000,000 $1,500,000 $1,000,000 $500,000 so Figure 2. Ex..xon Chemical Company's Linden Technology Center Historical Electrical Costs 16

3 , , ,000 20,000,000 15,000, Figure 3. Exxon Chemical Company's Linden Technology Center Historical Electrical Usage Air Circulation 35 /0 c:::7' '" "I ' Site utlllues mmeralr Intrastrucl1.lre Conditioning Pilot Plant Process 20'''' 15% Consumption 15% Lights, Computers, Daytime Needs 15% Figure 4. How Electricity is Consumed at LTC "On Hours" Demand 40'''' "Off Hours" Usage 60% Figure 5. "Off-Hours" vs."on-hours" Consumption 17

4 February 4-19, 1996 WeekS 6 and ,- _ _ H ~ ~ II '1/ '1/ N ~ lis i u! ~ ~! iii ~ ~ iii " iii ;; Figure 6. Daily Electrical Consumption (1996) February WeekS 6 and 7 'ooor li\ li\ li\ 1:: ;: I:: ~ ~ ~ ~ n $ ~ i iii ~ r,;; iii iii iii Figure 7. Daily Electrical Consumption (1997) 18

5 "OFF-HOURS" SHUTDOWNS Historically, LTC had operated HVAC equipment (i.e. supply fans, exhaust fans, chillers) servicing buildings 24 hours per day, seven (7) days per week. By reducing the air flow within some buildings and by changing the time of day HVAC equipment operated, LTC reduced energy consumption without impacting site operations and its client base. In February 1996, LTC installed metering capabilities which enabled facilities management to monitor power consumption daily. This analytical tool served as the basis for further understanding base and peak loads. The data highlighted that "offhours" electrical consumption was a significant portion of LTC's power usage (-.{j0%). Subsequently, in 2Q96, LTC adopted a more aggressive initiative to revise its operating strategy, and began to manually shutdown non-critical electrical consumers on all weekends and one day during the week. Graphs visually depicted these changes in "off-hour" consumption. This thrust led to capital appropriations totaling $165k which automated the shutdown of certain electrical consumers across the LTC site. ENERGY EFFICIENT LIGHTING In 1994 and 1995, LTC appropriated (capital) $375k to realize savings in electrical consumption via energy efficiency lighting. This effort consisted primarily of evaluating light levels in offices, laboratories, hallways, equipment rooms and other spaces to determine lumen output and color. The project(s) took about one (1) year to complete. During the basis development phase, an inventory of all fluorescent lighting fix1ures (-4500) and light level readings was performed in order to detennine whether replacement or retrofitting fixtures would be required. As part of this energy reduction step, LTC participated in the local utility company's rebate program to achieve a minimum average reduction in consumption of 200 kw per day during the summer peak period. Also, as part of this focus, LTC was instrumental in the development and implementation of the recycling of all mercury-containing bulbs in conjunction with the local utilities authority and chambers of commerce. In fact, LTC hosted the inaugural industrial fluorescent light collection. Figure 8 summarizes energy saved and the project investment return during calendar years 1995 through 1997 for LTC's main laboratory/office complex ,- ----,..._00 71lOOO " 8." """'" co : ~ :JXDl 5.-J,ooo.oo SJO.ooo.oo $20, """" '0000,...,... 1_kWh Reduced -$ Returned I "'.00 Figure 8. Ex..xon Chemical Company's Linden Technology Center Lighting Project 1995 through

6 1997 PROGRESS The primary focus in 1997 was to monilor and "tweak" operating conditions and strategies. "OfThour" shutdowns were extended. Air flow measurements were taken for the officellaboratory complex and one (1) office structure deploying "once through" air. Various engineering studies were initiated to recalculate and optimize air supply and exhaust quantities. Field activities included minor changes to fan belts and sheaves to meet reduced air requirements. As a result of these eftorts, electrical usage in 1997 continued to decline. YE97 consumption totaled 19.3 M kwh vs M kwh in 1996, about a 3% reduction electrical costs declined S95k relative to 1996 (S1405k vs. S1500k), a 6.7% reduction. Reduction in peak usage during the summer months resulted in lower overall costs when compared to the actual decline in consumption GOALS Facilities management intends to further reduce electrical consumption in 1998 by continuing to implement recommended changes in operating strategies. "OfT-hours" shutdowns will be extended to include all weekdays vs. one (1) weekday per week. Optimizing air supply and exhaust requirements servicing the main office/laboratory complex will be completed by lq98. More aggressive monitoring of electrical usage in pilot plant areas will provide additional energy reduction opportunities. From a cost standpoint, LTC facilities management's target is to rcduce electrical expenditures SlOOk relative to 1997's YE bookings (to S1300k). CONCLUSIONS LTC's electrical consumption has declined significantly in 1996 and 1997 relative to 1995 as a result of the thrusts highlighted above. A total reduction of 8.0M kwh in electrical consumption has been realized over the last two (2) years, and electrical costs have decreased S700k relative to 1995 base expendilures. Adoption of the stralegies applied at LTC by olher companies within the chemical industry, especially at technology sites, can payout favorably in reducing electrical consumption and costs. 20

Simplified M&V Guidelines for Lighting Efficiency Measures

Simplified M&V Guidelines for Lighting Efficiency Measures 1 Simplified M&V Guidelines for Lighting Efficiency Measures Overview This measurement and verification (M&V) procedure is appropriate for projects that involve the replacement of existing fixtures, lamps,

More information

Overview. PG&E and Energy Efficiency. CA Energy Efficiency Regulatory & Policy Roadmap. Financing Options for Efficiency & Demand Response

Overview. PG&E and Energy Efficiency. CA Energy Efficiency Regulatory & Policy Roadmap. Financing Options for Efficiency & Demand Response Overcoming Financial Barriers to Energy Efficiency April 6, 2010 Overview PG&E and Energy Efficiency CA Energy Efficiency Regulatory & Policy Roadmap Financing Options for Efficiency & Demand Response

More information

Small Business Services. Custom Measure Impact Evaluation

Small Business Services. Custom Measure Impact Evaluation National Grid USA Small Business Services Custom Measure Impact Evaluation March 23, 2007 Prepared for: National Grid USA Service Company, Inc. 55 Bearfoot Road Northborough, MA 01532 Prepared by: RLW

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

NEW COMMERCIAL Rates. Understanding the. Commercial Customers

NEW COMMERCIAL Rates. Understanding the. Commercial Customers Understanding the NEW COMMERCIAL Rates The Austin City Council increased Austin Energy s base rates, which pay for operations and maintenance, for the first time in 18 years. The new rates, which amount

More information

Energy Tariffs and Associated Charges

Energy Tariffs and Associated Charges Energy Tariffs and Associated Charges As permitted by Ergon Energy www.ergon.com.au The tariffs applied to the on-supply arrangement are in-line with the local area retailer s standing offer (Ergon Energy).

More information

Environmental Sustainability in 90 Days

Environmental Sustainability in 90 Days Environmental Sustainability in 90 Days The Global IWMS Leader 2008 TRIRIGA INC. TRIRIGA Real Estate Environmental Sustainability August 13, 2008 Ed Lubieniecki, Managing Director, RealFoundations Barbry

More information

Q1 2011 Utility Rebate Report. Houston, TX

Q1 2011 Utility Rebate Report. Houston, TX Q1 2011 Utility Rebate Report A service of the Sustainable Corporate Real Estate Roundtable Houston, TX April 7, 2011 (Captures regulations through March 31, 2011) This Report is one of a series of reports

More information

Q1 2011 Utility Rebate Report. Fort Worth, TX

Q1 2011 Utility Rebate Report. Fort Worth, TX Q1 2011 Utility Rebate Report A service of the Sustainable Corporate Real Estate Roundtable Fort Worth, TX April 7, 2011 (Captures regulations through March 31, 2011) This Report is one of a series of

More information

SAVANNAH-CHATHAM COUNTY BOARD OF EDUCATION Internal Audit Department 208 Bull Street, Room 310 Savannah, GA 31401

SAVANNAH-CHATHAM COUNTY BOARD OF EDUCATION Internal Audit Department 208 Bull Street, Room 310 Savannah, GA 31401 SAVANNAH-CHATHAM COUNTY BOARD OF EDUCATION Internal Audit Department 208 Bull Street, Room 310 Savannah, GA 31401 To: Through: From: Board of Education Dr. Thomas B. Lockamy, Jr., Superintendent Vanessa

More information

Worship Facility Matching Grant Program 2010 Program Manual

Worship Facility Matching Grant Program 2010 Program Manual Worship Facility Matching Grant Program 2010 Program Manual Chapter 1 Introduction TABLE OF CONTENTS 1 1 INTRODUCTION 4 1.1 DEFINITIONS... 4 1.2 PROGRAM GOALS... 4 1.3 PROGRAM PARTICIPANTS... 5 1.3.1 PROGRAM

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Catalyst RTU Controller Study Report

Catalyst RTU Controller Study Report Catalyst RTU Controller Study Report Sacramento Municipal Utility District December 15, 2014 Prepared by: Daniel J. Chapmand, ADM and Bruce Baccei, SMUD Project # ET13SMUD1037 The information in this report

More information

RHODE ISLAND SMALL BUSINESS ENERGY EFFICIENCY PROGRAM PRESCRIPTIVE LIGHTING STUDY

RHODE ISLAND SMALL BUSINESS ENERGY EFFICIENCY PROGRAM PRESCRIPTIVE LIGHTING STUDY RHODE ISLAND SMALL BUSINESS ENERGY EFFICIENCY PROGRAM PRESCRIPTIVE LIGHTING STUDY Final Report National Grid Prepared by DNV GL Date: July, 2015 Prepared by: Jeff Zynda, Sr. Consultant I (PM) Verified

More information

Next Generation Lead by Example Programs:

Next Generation Lead by Example Programs: Next Generation Lead by Example Programs: Maximizing Savings in Public Buildings MISSISSIPPI Blake Kelly, MDA Energy and Natural Resources Division National Governors Association Energy Efficiency Workshop

More information

Energy Efficiency. Science, Technology and Telecommunications Committee July 19, 2010

Energy Efficiency. Science, Technology and Telecommunications Committee July 19, 2010 Energy Efficiency Science, Technology and Telecommunications Committee July 19, 2010 Energy Efficiency Programs Residential Commercial EUEA Requirements: 5% by 2014 10% by 2020 Residential Lighting Refrigerator-Recycling

More information

Silicon Valley Power 2015-2016 Data Center Program Rebate Application

Silicon Valley Power 2015-2016 Data Center Program Rebate Application Contact Information Silicon Valley Power Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information

More information

LED Lighting Program Program Manual. Overview. 1. Eligibility

LED Lighting Program Program Manual. Overview. 1. Eligibility LED Lighting Program Program Manual Overview The LED Lighting Program was developed by American Electric Power subsidiary (henceforth referred to as AEP ) Southwestern Electric Power Company (henceforth

More information

Integrating Demand Response in Third Party Implemented Energy Efficiency Programs

Integrating Demand Response in Third Party Implemented Energy Efficiency Programs Integrating Demand Response in Third Party Implemented Energy Efficiency Programs Cody Coeckelenbergh, Solaris Technical Kimberly Rodriguez, Southern California Edison Douglas White, Trane Ingersoll Rand

More information

Shedding Light on Unexpected Market Response to High Bay Retrofits

Shedding Light on Unexpected Market Response to High Bay Retrofits Shedding Light on Unexpected Market Response to High Bay Retrofits Wendy Tobiasson and Bill Biesemeyer, KEMA Services, Inc. Steve Baab, ComEd/Exelon Wayne Dobberpuhl, Arizona Public Service Co. Mary Ann

More information

New Hampshire Utilities. New Hampshire Small Business Energy Solutions Program Impact Evaluation. Final Report. September 2004.

New Hampshire Utilities. New Hampshire Small Business Energy Solutions Program Impact Evaluation. Final Report. September 2004. New Hampshire Utilities New Hampshire Small Business Energy Solutions Program Impact Evaluation Final Report September 2004 Prepared by 179 Main Street, 3rd Floor Middletown, CT 06457 New Hampshire Utilities

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

New Jersey Clean Energy Programs. TRC, C&I Market Manager December 15, 2011

New Jersey Clean Energy Programs. TRC, C&I Market Manager December 15, 2011 New Jersey Clean Energy Programs TRC, C&I Market Manager December 15, 2011 NJCEP Overview NJ SmartStart Incentives Local Government Energy Audit P4P Direct Install NJ SmartStart Programs New Construction,

More information

Oakland County Executive Department of Facilities Management. Energy Management Procedures October 5, 2009

Oakland County Executive Department of Facilities Management. Energy Management Procedures October 5, 2009 Oakland County Executive Department of Facilities Management Energy Management Procedures October 5, 2009 1. Goal The acquisition and management of energy is fundamental to the mission and operation of

More information

Switching Energy Providers and PECO Smart Ideas. March 23, 2011

Switching Energy Providers and PECO Smart Ideas. March 23, 2011 Switching Energy Providers and PECO Smart Ideas March 23, 2011 Agenda Market Changes Taking Advantage of Competition PECO Smart Ideas for your home Questions Market Changes Utility Functions Before deregulation,

More information

Commercial & Municipal Retrofit 2015 VFD Rebate

Commercial & Municipal Retrofit 2015 VFD Rebate 2015 VFD Rebate Section A: MEMBER INFORMATION Member Name Electric Account Number Rate Number Facility Address City State Zip Code Service Location Identification Email Mailing Address (if different from

More information

What is the Impact of Utility Demand Charges on a DCFC Host?

What is the Impact of Utility Demand Charges on a DCFC Host? What is the Impact of Utility Demand Charges on a DCFC Host? June 2015 Key Conclusions Demand charges associated with 50 to 60-kW high power charging of a direct current (DC) fast charger (DCFC) can have

More information

DATA DRIVEN SUSTAINABILITY

DATA DRIVEN SUSTAINABILITY DATA DRIVEN SUSTAINABILITY It s Easier than You Think Pam Metcalf Dan Moore Sofi Armenakian Jason Townsend DATA DRIVEN SUSTAINABILITY Overview Dashboard Project Best Practices Overview 53 Year Old Community

More information

Colorado Springs Utilities

Colorado Springs Utilities CASE STUDY Colorado Springs Utilities A City Prepared for an Uncertain Future: Colorado Springs Utilities Balances Water Conservation and Revenue Stability In partnership with SUMMARY Colorado Springs

More information

Measurement & Verification Plan

Measurement & Verification Plan Measurement & Verification Plan University of Florida UF-# Project Name City, Florida Insert Project Rendering/Photo Here Prepared By: University of Florida Department of Facilities, Planning & construction

More information

Top 5 Trends in Data Center Energy Efficiency

Top 5 Trends in Data Center Energy Efficiency Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,

More information

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems

More information

OCCUPANCY MATCHING. Chris E. Taylor, MSEE, CEM, Installation Energy Manager Naval Air Station Whidbey Island, WA

OCCUPANCY MATCHING. Chris E. Taylor, MSEE, CEM, Installation Energy Manager Naval Air Station Whidbey Island, WA OCCUPANCY MATCHING Chris E. Taylor, MSEE, CEM, Installation Energy Manager Naval Air Station Whidbey Island, WA Abstract Naval Air Station Whidbey Island, WA saved over $500,000 (10.5%) last year in energy

More information

Company name Date submitted. Building address City State ZIP. E-mail* Building Sq. Ft.

Company name Date submitted. Building address City State ZIP. E-mail* Building Sq. Ft. Recommissioning Application Business Customer Information Company name Date submitted Building address City State ZIP Mailing address (if different) City State ZIP Contact person (print) Phone Fax E-mail*

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

Rules of Thumb Energy Efficiency in Buildings

Rules of Thumb Energy Efficiency in Buildings Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split

More information

Pilot Program Description: Building EMIS

Pilot Program Description: Building EMIS Pilot Program Description: Introduction Over time building systems do not operate as efficiently as they once did, using more energy than they should in order to satisfy occupant comfort and lighting requirements.

More information

Commercial/Office Space

Commercial/Office Space C A S E S T U D I E S Commercial/Office Space Newmark Knight Frank Making -Efficiency Their Standard Orange Health Care Center Gets an -Efficiency Check-up 1 Long Wharf Drive in New Haven owned by Newmark

More information

Cornell University Chilled Water Best Management Practices Program

Cornell University Chilled Water Best Management Practices Program Cornell University Chilled Water Best Management Practices Program Prepared by: Cornell University Facilities Services Energy and Sustainability Utilities Report Date: 29 January 2014 Report Number: 2014_LSC_BMP

More information

HVAC Air Systems. Recirculation Air System Types

HVAC Air Systems. Recirculation Air System Types HVAC Air Systems Recirculation Air System Types Summary Recirculation air handler fan energy can account for 10 to 30% of total cleanroom energy use. There are three fundamental recirculation system configurations:

More information

Technical Description of the Stockton College Geothermal HVAC Retrofit

Technical Description of the Stockton College Geothermal HVAC Retrofit Technical Description of the Stockton College Geothermal HVAC Retrofit Harold E. Taylor *, Lynn F. Stiles and William Hemphill December 1997 ABSTRACT The need to replace old, worn out and obsolete Heating,

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

A heat pump system with a latent heat storage utilizing seawater installed in an aquarium

A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics

More information

Potential Savings with Events2HVAC Event Automation Software

Potential Savings with Events2HVAC Event Automation Software Potential Savings with Events2HVAC Event Automation Software September 2010 Introduction The Events2HVAC event automation software is the energy and labor saving bridge between your facility's event/room

More information

Utility Energy Efficiency Developments in the States and DC. Laura Furrey, JD, PE ACEEE March 2010

Utility Energy Efficiency Developments in the States and DC. Laura Furrey, JD, PE ACEEE March 2010 Utility Energy Efficiency Developments in the States and DC Laura Furrey, JD, PE ACEEE March 2010 1 The American Council for an Energy Efficient Economy (ACEEE) Non-governmental organization (NGO) dedicated

More information

DVRPC Sustainable Skylines. January 31, 2011

DVRPC Sustainable Skylines. January 31, 2011 DVRPC Sustainable Skylines January 31, 2011 WELCOME! We put our energy into helping you save energy and money. Today s Agenda PEeo. An Exelon Company Market Changes PECO Smart Ideas for your business PECO

More information

Case Study. Crown Melbourne & BUENO Systems: Energy and Operational Savings Across a Multi-Use Entertainment Complex.

Case Study. Crown Melbourne & BUENO Systems: Energy and Operational Savings Across a Multi-Use Entertainment Complex. Case Study Crown Melbourne & BUENO Systems: Energy and Operational Savings Across a Multi-Use Entertainment Complex Version 1.0 June 2015 Find What Matters Crown Melbourne Analytics-Driven Energy and Operational

More information

LEED Breadth. Introduction

LEED Breadth. Introduction LEED Breadth Introduction As of January 2007, the project team has attempted to achieve a total of 50 points under the Leadership in Energy and Environmental Design for New Construction (LEED-NC) rating

More information

The Basics of Digital Signage and Energy Consumption by Gregory Young

The Basics of Digital Signage and Energy Consumption by Gregory Young The Basics of Digital Signage and Energy Consumption by Gregory Young In the world of outdoor advertising, successive technological and stylistic advancements have prompted cities and states to rethink

More information

Easy Save Plus Energy Efficiency Program Paul Geary

Easy Save Plus Energy Efficiency Program Paul Geary Easy Save Plus Energy Efficiency Program Paul Geary ESP Prescriptive Measures Air Conditioners and Heat pumps Programmable T-stats Chillers Lighting Delamping, Occ. Sensors, Exit signs, CFL T12 to Standard

More information

Energy Audits. Good energy management begins with an energy audit

Energy Audits. Good energy management begins with an energy audit Energy Audits Good energy management begins with an energy audit Effective management of energy-consuming systems can lead to significant cost and energy savings as well as increased comfort, lower maintenance

More information

ENERGY SOLUTIONS FOR BUSINESS CUSTOMERS

ENERGY SOLUTIONS FOR BUSINESS CUSTOMERS ENERGY SOLUTIONS FOR BUSINESS CUSTOMERS Electric League, March 25, 2016 Lori Moen Manager Solutions Design and Managment AGENDA 1. What is Customer Energy Solutions? 2. What do we do? 3. How do you work

More information

RESEARCH BRIEF. Savings and Operational Efficiencies for the Industrial/Warehouse Environment

RESEARCH BRIEF. Savings and Operational Efficiencies for the Industrial/Warehouse Environment Savings and Operational Efficiencies for the Industrial/Warehouse Environment October, 2015 3 Internet of Things Savings and Operational Efficiencies for the Industrial/ Warehouse Environment THE (IoT)

More information

The Smart Grid: Utility Master Energy & Sustainability Planning

The Smart Grid: Utility Master Energy & Sustainability Planning The Smart Grid: Utility Master Energy & Sustainability Planning Gene Rodrigues Director, Customer Energy Efficiency & Solar Southern California Edison CMAA Long Beach, CA May 5, 2011 About Southern California

More information

Understanding Time-of-Use and Demand. 2011San Diego Gas & Electric Company. All copyright and trademark rights reserved.

Understanding Time-of-Use and Demand. 2011San Diego Gas & Electric Company. All copyright and trademark rights reserved. Understanding Time-of-Use and Demand 2011San Diego Gas & Electric Company. All copyright and trademark rights reserved. Agenda Rate Overview How do Time Of Use Rates Work? What is Demand? Tips on Managing

More information

Energy Benchmarking Report for Lakeside Middle School. Millville, NJ

Energy Benchmarking Report for Lakeside Middle School. Millville, NJ Energy Benchmarking Report for Lakeside Middle School Millville, NJ (for the period: June 1, 2008 through May 31, 2009) Prepared by: Background & Findings: The New Jersey Clean Energy Program (NJCEP) developed

More information

Quantifying the Benefits Of Dynamic Pricing In the Mass Market

Quantifying the Benefits Of Dynamic Pricing In the Mass Market Quantifying the Benefits Of Dynamic Pricing In the Mass Market Prepared by: Ahmad Faruqui, Ph.D. and Lisa Wood, Ph.D. The Brattle Group Prepared for: Edison Electric Institute January 2008 The Brattle

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Energy Conservation. City of Fort Worth Business Smart Program

Energy Conservation. City of Fort Worth Business Smart Program City of Fort Worth Business Smart Program Energy Conservation Conserving energy in your organization s daily operations is an important step towards saving money, but also reducing the need for the generation

More information

The Empire State Building Creating a Replicable Model for Energy Efficiency Reinvestment

The Empire State Building Creating a Replicable Model for Energy Efficiency Reinvestment The Empire State Building Creating a Replicable Model for Energy Efficiency Reinvestment The Empire State Building Create a transparent, replicable, quantitative program for cost justified energy efficiency

More information

SMUD CUSTOMER PROGRAMS AND SERVICES. Ed Hamzawi Implementation Supervisor Energy Efficiency Programs May, 2010

SMUD CUSTOMER PROGRAMS AND SERVICES. Ed Hamzawi Implementation Supervisor Energy Efficiency Programs May, 2010 SMUD CUSTOMER PROGRAMS AND SERVICES Ed Hamzawi Implementation Supervisor Energy Efficiency Programs May, 2010 1 Customer Programs & Services 1. Vision and Background 2. Energy Efficiency Programs 3. Solar/PV

More information

THE COMED RESIDENTIAL REAL-TIME PRICING PROGRAM GUIDE TO REAL-TIME PRICING

THE COMED RESIDENTIAL REAL-TIME PRICING PROGRAM GUIDE TO REAL-TIME PRICING THE COMED RESIDENTIAL REAL-TIME PRICING PROGRAM GUIDE TO REAL-TIME PRICING 2014-2015 COMED RESIDENTIAL REAL-TIME PRICING PROGRAM GUIDE TO REAL-TIME PRICING CONTENTS ComEd Residential Real-Time Pricing

More information

WAYS TO SAVE ENERGY AND MONEY

WAYS TO SAVE ENERGY AND MONEY WAYS TO SAVE ENERGY AND MONEY RESIDENTIAL PROGRAMS SRP offers a variety of programs and rebates to help customers save energy, save money and increase the comfort of their homes. Program eligibility requirements

More information

The Smart Energy Pricing Evolution at BGE

The Smart Energy Pricing Evolution at BGE The Smart Energy Pricing Evolution at BGE for The 2011 National Town Meeting on Demand Response and Smart Grid 2011 National Town Meeting on Demand Response and Smart Grid Wayne Harbaugh VP Pricing & Regulatory

More information

AircoSaver Energy Savings for At&t Mobility San Diego

AircoSaver Energy Savings for At&t Mobility San Diego Page 1 of 1 AircoSaver Energy Savings for At&t Mobility San Diego Provided by SDG&E and ENERGE Corporation Project Overview Cell sites in San Diego contain electronic equipment cooled with oversized package

More information

Index. a. Personnel...2 b. Sustainability...2 c. Materials Management...3

Index. a. Personnel...2 b. Sustainability...2 c. Materials Management...3 1 Index Executive Summaries a. Personnel...2 b. Sustainability...2 c. Materials Management...3 I. Personnel a. Background...4 b. Application Process...4 c. Departmental Recruiting...6 d. The City Residency

More information

Home Energy Efficiency and Conservation: Call to Action. July 23, 2015 Dave Blake and David Wood REEP Green Solutions

Home Energy Efficiency and Conservation: Call to Action. July 23, 2015 Dave Blake and David Wood REEP Green Solutions Home Energy Efficiency and Conservation: Call to Action July 23, 2015 Dave Blake and David Wood REEP Green Solutions Today s Agenda Background Understanding where you are: Energy Usage EnerGuide Home Energy

More information

Energy Efficiency and Automated Demand Response Program Integration: Time for a Paradigm Shift

Energy Efficiency and Automated Demand Response Program Integration: Time for a Paradigm Shift Energy Efficiency and Automated Demand Response Program Integration: Time for a Paradigm Shift Christine Riker and Kitty Wang, Energy Solutions Fred Yoo, Pacific Gas and Electric Company ABSTRACT The practice

More information

COMMERCIAL HEATING VENTILATION & AIR CONDITIONING (HVAC)

COMMERCIAL HEATING VENTILATION & AIR CONDITIONING (HVAC) COMMERCIAL HEATING VENTILATION & AIR CONDITIONING (HVAC) REBATE FORM Valid July 1 - December 31, 2015 Steps to Getting Your Rebate: 1. Confirm that equipment is eligible. 2. Purchase and install new eligible

More information

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact

More information

HVAC System Optimization

HVAC System Optimization UNITED TECHNOLOGIES CARRIER CORPORATION HVAC System Optimization MAXIMIZING PERFORMANCE, ENERGY SAVINGS & COMFORT Revitalize Your Building s System Sometime between the initial purchase and the need to

More information

Market Potential Study for Water Heater Demand Management

Market Potential Study for Water Heater Demand Management Market Potential Study for Water Heater Demand Management Rebecca Farrell Troutfetter, Frontier Associates LLC, Austin, TX INTRODUCTION Water heating represents between 13 and 17 percent of residential

More information

Large Business Retrofit Program Impact Evaluation in New Hampshire

Large Business Retrofit Program Impact Evaluation in New Hampshire New Hampshire Large Business Retrofit Program Impact Evaluation Final Report New Hampshire Monitoring and Evaluation Team May 11, 2006 TABLE OF CONTENTS SECTION 1...4 1.1 Evaluation Objectives...4 1.2

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Heating & Cooling Efficiency

Heating & Cooling Efficiency Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart

More information

Community Energy and Efficiency Development Fund

Community Energy and Efficiency Development Fund Community Energy and Efficiency Development Fund 2013 Draft Annual Report Submitted by Green Mountain Power November 14, 2014 1 Community Energy and Efficiency Development Fund 2013 Draft Annual Report

More information

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation

More information

Saving Energy For Your Organisation. Top 10 energy saving tips

Saving Energy For Your Organisation. Top 10 energy saving tips Saving Energy For Your Organisation Top 10 energy saving tips How can you increase efficiency, reduce costs and cut your carbon emissions? The UK s Climate Change Act (2008) sets a legally-binding target

More information

2009 Seattle Energy Code Impacts: See below for a recap of Changes in Envelope performance from 2006 to 2009

2009 Seattle Energy Code Impacts: See below for a recap of Changes in Envelope performance from 2006 to 2009 2009 Seattle Energy Code Impacts: Building Envelope Impacts: Below is a Summary of Changes that impact building envelope construction planned for 624 Yale. There are several modifications are required

More information

Best Practice Guide BPGCS007

Best Practice Guide BPGCS007 Best Practice Guide BPGCS007 ENERGY MANAGEMENT Introduction: With rising fuel costs, opening of electricity and gas markets to alternate suppliers and climate change, the requirement to monitor and reduce

More information

Sample Ordinance Consolidating All Rates

Sample Ordinance Consolidating All Rates Sample Ordinance Consolidating All Rates WHEREAS, it is necessary to consolidate all rates charged for utilities and other services provided by the City; and WHEREAS, Chapter 3 of the City Code and other

More information

GETTING STARTED WITH THE MIPOWER MANAGEMENT SYSTEM

GETTING STARTED WITH THE MIPOWER MANAGEMENT SYSTEM GETTING STARTED WITH THE MIPOWER MANAGEMENT SYSTEM This Quick Start guide will help you start using the MiPower Management System provided by Grayson Collin Electric Cooperative. You should create your

More information

FY09 PERFORMANCE PLAN Office of Property Management

FY09 PERFORMANCE PLAN Office of Property Management FY09 PERFORMANCE PLAN MISSION Support the District Government and residents through strategic real estate management, construction and facilities management. SUMMARY OF SERVICES The (OPM) has primary responsibility

More information

Corporate Energy Conservation & Demand Management Plan (CECDMP) 2014-2019

Corporate Energy Conservation & Demand Management Plan (CECDMP) 2014-2019 Corporate Energy Conservation & Demand Management Plan (CECDMP) 2014-2019 Table of Contents Our Commitment to Energy Conservation...1 1.0 Introduction...2 2.0 Energy Supply in Ontario...3 2.1 Energy Supply

More information

City Light Rates 101. Communications & Public Affairs. www.seattle.gov/light

City Light Rates 101. Communications & Public Affairs. www.seattle.gov/light City Light Rates 101 Communications & Public Affairs www.seattle.gov/light INTRODUCTION Conserving Energy for a Sustainable Future RATE SETTING PROCESS CONSISTS OF THREE STEPS Revenue Requirement Cost

More information

ENERGY AUDIT REPORT MINIMUM REQUIREMENTS

ENERGY AUDIT REPORT MINIMUM REQUIREMENTS ENERGY AUDIT REPORT MINIMUM REQUIREMENTS Energy Audit Reports must contain the following: 1) Eligibility Criteria: a) Evidence demonstrating that the Eligibility Criteria were met. 2) Participant Information:

More information

Peralta Energy Oakland, CA 510.459.0827

Peralta Energy Oakland, CA 510.459.0827 Peralta Energy Oakland, CA 510.459.0827 Report version: 1.0 Author: Ben Thompson Report prepared for: Education for Change Public Schools, Oakland CA Properties: School Lazear Academy Cox Academy Learning

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

COMMON COMMERCIAL ELECTRIC RATES

COMMON COMMERCIAL ELECTRIC RATES 2013 COMMON COMMERCIAL ELECTRIC RATES The rate you are currently billed under is listed on your bill. Please review this entire guide to determine which rate is best suited for you. You may have made significant

More information

Return on Investment (ROI),

Return on Investment (ROI), Analyzing the Business Case for UV-LED Curing Part III: Interpreting Results By Jennifer Heathcote This article is the final installment in a three-part series designed to illustrate the process of conducting

More information

Code of Practice for Building Energy Audit

Code of Practice for Building Energy Audit Code of Practice for Building Energy Audit 2012 Code of Practice for Building Energy Audit Table of Contents Page No. 1. Introduction 1 2. Interpretations 1 3. Application 4 4. Technical Compliance with

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

HVAC System Optimization Program Guidelines

HVAC System Optimization Program Guidelines HVAC System Optimization Program Guidelines Sponsored By: And Its Participating Wholesale Utility Customers HVAC System Optimization Program Guidelines The target of this program is HVAC systems in existing

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Building Electricity Management. Energy Monitoring + Ac/ve Energy Management = 10%- 40% energy savings

Building Electricity Management. Energy Monitoring + Ac/ve Energy Management = 10%- 40% energy savings Building Electricity Management Energy Monitoring + Ac/ve Energy Management = 10%- 40% energy savings 1 - CLEER is a non- profit energy consul4ng company and is statewide leader field of energy services

More information

Tysons Sustainability Summit Evidence Based Urban Design. Roger E. Frechette III, PE, LEED-AP

Tysons Sustainability Summit Evidence Based Urban Design. Roger E. Frechette III, PE, LEED-AP Tysons Sustainability Summit Evidence Based Urban Design 2013 Autodesk Roger E. Frechette III, PE, LEED-AP Live in Harmony with Nature Transit Community Energy Waste Air Quality Water Yujiapu Financial

More information

Chapter-5 Introduction to Building Automation System (BAS)

Chapter-5 Introduction to Building Automation System (BAS) Chapter-5 Introduction to Building Automation System (BAS) Chapter-5 Introduction to Building Automation System (BAS) ၅.၁ Introduction Building Automation System(BAS) sub system equipment service monitor

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

DATA CENTER DESIGN OVERVIEW

DATA CENTER DESIGN OVERVIEW DATA CENTER DESIGN OVERVIEW Presented by Horst Pfendt Critical Facilities Round Table 7 th QUARTERLY MEETING December 17, 2004 DATA CENTER DESIGN OVERVIEW INTRODUCTION In the next couple of hours I will

More information

UNDERSTANDING YOUR ELECTRIC BILL

UNDERSTANDING YOUR ELECTRIC BILL UNDERSTANDING YOUR ELECTRIC BILL A GUIDE FOR BUSINESSES IN North Carolina Duke Energy 550 South Tryon Street Charlotte, NC 28202 www.duke-energy.com 120633 10/12 2013 Duke Energy Corporation 12-1478LU

More information