Laboratory Report P Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C

Size: px
Start display at page:

Download "Laboratory Report P12850.03.09. Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C"

Transcription

1 Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C Prepared for: 2100 River Edge Parkway, Suite 175 Atlanta, GA Date of Issuance: March 30, 2009

2 Page 2 of 7 CLIENT INFORMATION: ERD REFERENCE: CLIENT SAMPLES: 2100 River Edge Parkway, Suite 175 Atlanta, GA c/o: Ken Franklin Project #2008.P12850SC Fanfold XPS is a lightweight, 3/8-inch extruded polystyrene foam (XPS) insulation laminated to a plastic facer. Carlisle Sure-Seal EPDM is an elastomeric homogenous roofing membrane used in single-ply roof construction and reroofing applications. Firestone UltraPly TPO is a reinforced thermoplastic polyolefin single ply roof membrane. Firestone RubberGard EPDM is a high-performance rubber compound. Used in ballasted, fully adhered and mechanically attached systems. Carlisle Sure-Weld TPO is a TPO polymer based, polyester reinforced, thermoplastic membrane. GAF EverGuard TPO is a high strength, flexible, thermoplastic membrane. 3M TM Scoth-Weld TM Polystyrene Foam is a fast drying, solvent based, temperature resistant, spray applied adhesive. Tru-Fast DP are #12 drill-point roofing fasteners. Tru-Fast MP3 are 3-inch round metal insulation stress plates. SAMPLE DELIVERY: The named client arranged for shipment of materials to our Columbia, South Carolina laboratory for testing. Materials were received on 12/18/2008, 12/23/2008, 01/06/2009,

3 Page 3 of 7 01/12/2009 and 01/13/2009. TEST DATE(S): 01/07/2009 and 01/14/2009 M-D NOTIFICATION: ERD07037 ERD TECHNICIANS: Charles Phillips, Michael Bloom PROPERTIES: Simulated Wind Uplift Resistance 5 x 9 ft TAS 114, Appendix C STANDARDS: FM Standard 4470, Approval Standard for Class 1 Roof Covers, FM Global, EQUIPMENT: Wind Uplift Trinity ERD 5x9 chamber

4 Page 4 of 7 1. COMPARATIVE MEMBRANE DELAMINATION: 1.1 Membrane delamination tests were conducted on samples of the membrane/adhesive/insulation combinations to determine the comparative performance of each combination in resisting separation of the membrane from the insulation to which it is adhered. The results are used as the basis for selection of the most critical (membrane, adhesive, substrate) combination to be used in the simulated wind uplift pressure tests. 1.2 Specimen Preparation: The center 3 x 6 inch section of a 3 x 20 inch piece of the roof cover is adhered in the specified adhesive to the center of a 14 x 14 inch piece of substrate material, and allowed to cure for maximum 28-days. Upon curing, the specimen is inserted into an angle iron frame, holding the substrate material static and horizontal. Three specimens are prepared for each membrane / adhesive / substrate combination. 1.3 Procedure: The free ends of the roof cover are placed in the upper jaws of a tensile testing machine. Force is applied in a direct line perpendicular to the membrane/substrate interface at a crosshead speed of 2 inch/minute until failure occurs. 1.4 Results: Table 1: Comparative Membrane Delamination Results Substrate Adhesive Roof Cover Average Result (pli) Carlisle Sure-Seal EPDM 2.9 Firestone RubberGard EPDM 2.3 Carlisle Sure-Weld TPO 4.0 GAF EverGuard TPO 6.5 Firestone UltraPly TPO Observations: The critical membrane, adhesive, substrate combination for the EPDM roof cover is RubberGard EPDM in adhesive atop The critical membrane, adhesive, substrate combination for the TPO roof cover is Sure-Weld TPO in adhesive atop.

5 Page 5 of 7 2. SIMULATED WIND UPLIFT RESISTANCE 5 X 9 FT PRESSURE DIFFERENTIAL 2.1 Specimen Preparation: One specimen measuring 6 x 10 ft was constructed for each of the following sample descriptions. The specimen is built atop the specified roof deck and allowed to cool / cure for a minimum of 30 minutes. The simulated wind uplift pressure tests utilize a 5 ft (1.5 m) long by 9 ft (2.7 m) wide aluminum vacuum pressure vessel arranged to apply vacuum air pressure at pre-established standard rates to the topside of the test panel, which forms the bottom of the pressure vessel. Table 2A: Summary of 5 x 9 ft Specimen Construction Sample ID Deck Bottom Insulation Top Insulation Roof Cover Type Attachment Density Membrane Adhesive Rate C-1 22 ga. Grade 33 Steel Min. 1-inch ISO 95 +GL, loose laid 3/8-inch XPS Trufast #12 Fasteners and Insulation Plates 1 per 2 ft 2 RubberGard EPDM 3M Polystyrene Foam Insulation lbs/sq.ft. C-2 22 ga. Grade 33 Steel Min. 1-inch ISO 95 +GL, loose laid 3/8-inch XPS Trufast #12 HD Fasteners and Insulation Plates 1 per 2 ft 2 Sure-Weld TPO 3M Polystyrene Foam Insulation lbs/sq.ft. View of Insulation Attachment

6 Page 6 of Procedure: A net pressure of 30 psf (1.4 kpa) is applied to the test sample and maintained for 1 minute. The pressure is increased to 45 psf (2.2 kpa), then to 60 psf (2.9 kpa) and held for 1 min. after each increment. The pressure is increased in increments of 15 psf (0.7 kpa) every min. until failure occurs. 2.3 Results: Table 2B: Test Results, Sample C-1 Steel/ 1-inch ISO 95 1 per 2 ft 2 RubberGard EPDM in Sample ID: C-1 Failure 75 Failure Time (sec): At Attainment Failure Mode: Passing Bending of Plates and rupture of XPS Board 60 Table 2C: Test Results, Sample C-3 Steel/ 1-inch ISO 95 1 per 2 ft 2 Sure-Weld TPO in Sample ID: C-2 Failure 75 Failure Time (sec): During Increase Failure Mode: Passing Bending of Plates and rupture of XPS Board 60

7 Page 7 of 7 3. OBSERVATIONS & COMMENTS: 3.1 The critical membrane/adhesive combinations were utilized over each type of substrate for the two uplift tests. 3.2 Result for Panel C-1 is applicable to the following membrane / adhesive combinations. Carlisle Sure-Seal EPDM applied in. Firestone RubberGard EPDM applied in. 3.3 Result for Panel C-2 is applicable to the following membrane / adhesive combinations. Carlisle Sure-Weld TPO applied in. GAF EverGuard TPO applied in Firestone UltraPly TPO applied in 3.4 Minimal bond was noted at the stress plate interface with the adhesive. This, coupled with the relatively thin insulation board and flexible roof cover, let to a folding of the insulation plates and rupture of the insulation board. 4. CONCLUSIONS: 4.1 TRINITY ERD has tested the specimens outlined in Table 2A for wind uplift resistance in accordance with FM Standard 4470, Appendix C resulting in the data outlined in Tables 2B and 2C. 4.2 Specimens were constructed using critical roof cover / adhesive combinations based on preliminary criticality analysis. Allowable membrane / adhesive combinations over the insulation substrates are outlined in Section 3. Please contact our office with any questions. Sincerely, TRINITY ERD Larry Good Laboratory Quality Manager Robert Nieminen, P.E. Vice President REPORT HISTORY: Date Event Notes Authorized By: 02/09/2009 DRAFT TO CLIENT FOR CLIENT REVIEW RN 03/30/2009 Final Report Issued None RN This report and the data contained therein is the sole property of Trinity ERD and the named client. This report shall not be reproduced outside Trinity ERD except by the named client without written permission by the named client, in which case the report shall be reproduced in its entirety.

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT NCE Table Application Type Description Page 1A-1 Wood New, Reroof (Tear-Off), Recover C-1 Mechanically Attached Insulation, Bonded Roof Cover 4 1A-2

More information

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2 Standard Practice f Table of Contents 1.0 Introduction...2 2.0 Methodology...2 Appendix A...7 Insulation Board Fastening Patterns 4 feet 4 feet Boards Adhered Membranes...8 Insulation Board Fastening Patterns

More information

Roofing Systems. New Applications / Re-Roofing / Maintenance

Roofing Systems. New Applications / Re-Roofing / Maintenance Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND

More information

CHICAGO ROOFING CONTRACTORS ASSOCIATION

CHICAGO ROOFING CONTRACTORS ASSOCIATION CHICAGO ROOFING CONTRACTORS ASSOCIATION JANUARY 22, 2016 Roofing Claims & Lawsuits Stephen M. Phillips Hendrick, Phillips, Salzman & Flatt, P.C. 230 Peachtree Street, Suite 2500 Atlanta, GA 30303 (404)

More information

CARLISLE S. c a r l i s l e - s y n t e c. c o m

CARLISLE S. c a r l i s l e - s y n t e c. c o m CARLISLE S Roofing Systems c a r l i s l e - s y n t e c. c o m Put 0 Years of Experience to Work for You For more than 0 years, Carlisle SynTec Incorporated has been the trusted provider of the most dependable

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

Firestone RubberGard The EPDM reference

Firestone RubberGard The EPDM reference Firestone RubberGard The EPDM reference EPDM Roofing Systems 1.000.000.000 m 2 of proven performance The Firestone heritage of success and quality is extended to the construction industry through the Firestone

More information

UL Online Certifications Directory

UL Online Certifications Directory UL Online Certifications Directory Home Quick Guide Contact Us UL.com TGFU.R11183 Roofing Systems Page Bottom Roofing Systems See General Information for Roofing Systems PACTIV CORP SUITE 175 2100 RIVEREDGE

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE

Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE I n t r o d u c t i o n t o M o d i Acres of Roofing. Decades of Performance. Over the past 20 years, Firestone Building Products

More information

Class Number 4470. June 2012. 2012 FM Approvals LLC. All rights reserved.

Class Number 4470. June 2012. 2012 FM Approvals LLC. All rights reserved. Approval Standard for Single-Ply, Polymer-Modified Bitumen Sheet, Built-Up Roof (BUR) and Liquid Applied Roof Assemblies for use in Class 1 and Noncombustible Roof Deck Construction Class Number 4470 June

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

CRS Sales & Marketing

CRS Sales & Marketing TPO - Technology CRS Sales & Marketing Presenter: Gena Miller Thank you AIA, Sign In Sheet (1 Hour CEU-HSW) Division of CRS, Inc. (Commercial Roofing Specialties) 5 Locations (4 state of GA, 1 state of

More information

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance

More information

http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wgevxqwtdqtkahqb3dx8wn...

http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wgevxqwtdqtkahqb3dx8wn... Florida Building Code Online http://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wgevxqwtdqtkahqb3dx8wn... Page 1 of 2 8/3/2015 BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats

More information

The existing roof angle change terminations and flashings when sound and intact can be reused.

The existing roof angle change terminations and flashings when sound and intact can be reused. January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing

More information

APIB Test Specification No. 09 WATERPROOFING MEMBRANES SWISS HAIL IMPACT PROTECTION REGISTER HSR. 01.07.2015 / 07-15en Version 1.

APIB Test Specification No. 09 WATERPROOFING MEMBRANES SWISS HAIL IMPACT PROTECTION REGISTER HSR. 01.07.2015 / 07-15en Version 1. Association of Public Insurance Companies (APIB) Association des établissements cantonaux d assurance incendie SWISS HAIL IMPACT PROTECTION REGISTER HSR APIB Test Specification No. 09 WATERPROOFING MEMBRANES

More information

Class Number 4470. April 2010. 2010 FM Approvals LLC. All rights reserved.

Class Number 4470. April 2010. 2010 FM Approvals LLC. All rights reserved. Approval Standard for Single-Ply, Polymer-Modified Bitumen Sheet, Built-Up Roof (BUR) and Liquid Applied Roof Assemblies for use in Class 1 and Noncombustible Roof Deck Construction Class Number 4470 April

More information

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded

More information

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration

More information

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method

More information

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practice Roof Design: Sustainable Energy Efficient Reroofing Presented by Edis Oliver, PE Principal 9511 Lake Creek Parkway Austin,

More information

Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature

Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature Thermal Values Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature relative to changing exterior temperatures. By reducing interior temperature

More information

COMMERCIAL & LOW SLOPED ROOF SPECIALISTS TOTAL NDL SYSTEM MANUFACTURER WARRANTIES

COMMERCIAL & LOW SLOPED ROOF SPECIALISTS TOTAL NDL SYSTEM MANUFACTURER WARRANTIES C COMMERCIAL & LOW SLOPED ROOF SPECIALISTS We are equipped to handle the largest of your commercial roof needs. Whether storm damage or simply needing a new commercial roof due to age, Cobalt allows you

More information

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings. SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.

More information

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com

More information

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the

More information

Test report P 7013-E. InoPaz H2O. Pazkar LTD. Alon Tavor Industrial Zone AFULA 18000 / Israel. J. Magner Dipl.-Ing. N. Machill.

Test report P 7013-E. InoPaz H2O. Pazkar LTD. Alon Tavor Industrial Zone AFULA 18000 / Israel. J. Magner Dipl.-Ing. N. Machill. Kiwa Polymer Institut GmbH Quellenstraße 3 65439 Flörsheim-Wicker Tel. +49 (0)61 45-5 97 10 Fax +49 (0)61 45-5 97 19 www.kiwa.de Test report P 7013-E Testing order: Test of the waterproofing system based

More information

EPDM System Repair and Cleaning

EPDM System Repair and Cleaning EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

COMMERCIAL ROOFING. Learning Objectives. Commercial Roofing Fundamentals May 2, 2012

COMMERCIAL ROOFING. Learning Objectives. Commercial Roofing Fundamentals May 2, 2012 COMMERCIAL ROOFING The Fundamentals Firestone Building Products is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned on completion of this program

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

Creep Behavior of Structural Insulated Panels (SIPs)

Creep Behavior of Structural Insulated Panels (SIPs) Creep Behavior of Structural Insulated Panels (SIPs) Results from a Pilot Study Dwight McDonald Marshall Begel C. Adam Senalik Robert J. Ross Thomas D. Skaggs Borjen Yeh Thomas Williamson United States

More information

CREEK Technical Services, LLC

CREEK Technical Services, LLC EVALUATION REPORT 2010 FLORIDA BUILDING CODE Manufacturer: Henry Company Report Issued February 20, 2013 999 North Sepulveda Blvd., Suite 800 El Segundo, CA 90245 (800) 486-1278 Manufacturing Plants: Quality

More information

also in this issue Automatic Doors for the People Calculating Roof Insulation R-values Waterproofing and Concrete Balconies

also in this issue Automatic Doors for the People Calculating Roof Insulation R-values Waterproofing and Concrete Balconies $7.00 solutions for the construction industry august 2012 56 TH CSI ANNUAL CONVENTION SHOW PREVIEW also in this issue Automatic Doors for the People Calculating Roof Insulation R-values Waterproofing and

More information

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR Nondestructive Evaluation of Outback Steakhouse/Bertucci s Building at 2207 Forest Drive, Annapolis, MD Provided by: HurleyIR On Monday, June 2, 2014, HurleyIR provided a nondestructive evaluation for

More information

Proven roofing SyStemS

Proven roofing SyStemS Proven Roofing Systems Above all. Roofing challenges are never over our heads At GenFlex, we live to tackle and solve the toughest challenges in roofing. The result is a full line of proven, durable roofing

More information

Avoiding the Landfill: The Recycling of Vinyl Roof Membranes

Avoiding the Landfill: The Recycling of Vinyl Roof Membranes Avoiding the Landfill: The Recycling of Vinyl Roof Membranes With its European counterparts blazing the trail, the North American vinyl (PVC) roofing industry has entered a new phase in its commitment

More information

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards

TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19

More information

CARLISLE S ROOFING SYSTEMS EPDM TPO PVC FLEECEBACK ROOF GARDEN

CARLISLE S ROOFING SYSTEMS EPDM TPO PVC FLEECEBACK ROOF GARDEN CARLISLE S ROOFING SYSTEMS EPDM TPO PVC FLEECEBACK ROOF GARDEN Put 50 Years of Experience to Work for You For nearly half a century, Carlisle SynTec has been the trusted provider of the most dependable

More information

HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION

HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION ADVANCED TECHNOLOGY FROM OWENS CORNING TRUMBULL ASPHALT TruLo Lo Odor and TruLo Max asphalt raising the roof on asphalt performance.

More information

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings

More information

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections

More information

Design No. P736 September 26, 2003. Restrained Assembly Ratings 1, 1-1/2 or 2 Hr. (See Items 3, 7 and 8A)

Design No. P736 September 26, 2003. Restrained Assembly Ratings 1, 1-1/2 or 2 Hr. (See Items 3, 7 and 8A) Design No. P736 September 26, 2003 Restrained Ratings 1, 1-1/2 or 2 Hr (See Items 3, 7 and 8A) Ratings 1, 1-1/2 or 2 Hr (See Items 3, 7 and 8A) Beam Ratings 1, 1-1/2 or 2 Hr (See Items 7 and 8A) 1. Beam

More information

SEAMS SEAMING USING SEAM TAPE

SEAMS SEAMING USING SEAM TAPE SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter

More information

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M

AST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test

More information

For every building that matters

For every building that matters Hospitals & healthcare Colleges & universities Municipal & governmental Commercial & cultural For every building that matters For all seasons and many reasons, if your building is important, it deserves

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test

More information

Solicitation DTFACN-11-R-00079 Attachment #9

Solicitation DTFACN-11-R-00079 Attachment #9 These specs are only a general overview of the typical VOR Roof construction. These are for reference only. Each individual project will have its own specifications. 1 VOR Roof Projects IDIQ Solicitation

More information

0845 0098 980 www.nicholsonsts.com

0845 0098 980 www.nicholsonsts.com 0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution

More information

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple

More information

Prices Effective April 1, 2016

Prices Effective April 1, 2016 Domestic U.S. Warranty Pricing Guide Longer term warranties have additional installation requirements and not all warranty terms are available for all roofing specifications. Please refer to the Firestone

More information

Nondestructive Evaluation of. Lockheed Martin Building at. 7152 Windsor BVLD, Windsor Mill, MD. Provided by: HurleyIR

Nondestructive Evaluation of. Lockheed Martin Building at. 7152 Windsor BVLD, Windsor Mill, MD. Provided by: HurleyIR Nondestructive Evaluation of Lockheed Martin Building at 7152 Windsor BVLD, Windsor Mill, MD Provided by: HurleyIR On Monday April 23, 2014, HurleyIR provided a nondestructive evaluation for Ruff Roofers

More information

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC

More information

Building Owners Guide to a Duro-Last System!

Building Owners Guide to a Duro-Last System! Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof

More information

Dynamic Wind Testing of Commercial Roofing Systems

Dynamic Wind Testing of Commercial Roofing Systems Construction Technology Update No. 55 Dynamic Wind Testing of Commercial Roofing Systems by A. Baskaran Single-ply roofs (SPRs) behave differently than built-up roofs and a simple test method is needed

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC. Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its

More information

Predictive Service Life Tests for Roofing Membranes

Predictive Service Life Tests for Roofing Membranes Predictive Service Life Tests for Roofing Membranes ABSTRACT C.G. Cash, D.M. Bailey, A.G. Davies, Jr., A. H. Delgado, D.L. Niles, R.M. Paroli Simpson Gumpertz & Heger Inc, Waltham, MA USA U.S. Army Corps

More information

EPDM. Roofing systems

EPDM. Roofing systems Roofing systems Our Promise Through ongoing interchange of experiences with contractors, Mule-Hide keeps on top of the latest roofing requirements and solutions Trusted in roofing since 1906, Mule-Hide

More information

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side

More information

Maintenance & repair Solutions

Maintenance & repair Solutions Maintenance & repair Solutions low-slope ROOFING We ve got what you need in the sizes you need them and the options to match the results that building owners want Seal-fast Temporary roof sealer Now you

More information

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF... Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,

More information

Georgia State University. Urban Life Building Roof Replacement

Georgia State University. Urban Life Building Roof Replacement ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT

More information

PERIMETER FLASHING. Table of Contents

PERIMETER FLASHING. Table of Contents FM Global Property Loss Prevention Data Sheets 1-49 February 1985 Revised September 2000 Page1of25 PERIMETER FLASHING Table of Contents Page 1.0 SCOPE... 3 1.1 Changes... 3 2.0 LOSS PREVENTION RECOMMENDATIONS...

More information

2011 Dodson Publications, Inc. Page 1 of 6 September 16, 2011 8:19 AM

2011 Dodson Publications, Inc. Page 1 of 6 September 16, 2011 8:19 AM Contractor Makes Quick Work of Colossal Recover Maintenance Contract Helps Land Contractor Huge Reroofing Job in Colorado by Andrew Romano, senior product manager, GAF It s the closest most crews get to

More information

Roofing. Sarnafil S 327-15EL. Polymeric membrane for roof waterproofing. Product Description

Roofing. Sarnafil S 327-15EL. Polymeric membrane for roof waterproofing. Product Description Roofing Product Data Sheet Edition 02.2015 Identification no: 02 09 01 01 201 0 150000 Version no. 04 Sarnafil S 327-15EL Polymeric membrane for roof waterproofing Product Description Sarnafil S 327-15EL

More information

SPECIAL NOTE FOR ASPHALT WATERPROOFING MIX FOR BRIDGE-DECK OVERLAYS AND ADJACENT APPROACHES

SPECIAL NOTE FOR ASPHALT WATERPROOFING MIX FOR BRIDGE-DECK OVERLAYS AND ADJACENT APPROACHES SPECIAL NOTE FOR ASPHALT WATERPROOFING MIX FOR BRIDGE-DECK OVERLAYS AND ADJACENT APPROACHES 1. DESCRIPTION. Asphalt Waterproofing Mix (AWM) is a highly elastomeric, polymermodified, impermeable asphalt

More information

AUTHORIZATION TO MARK

AUTHORIZATION TO MARK AUTHORIZATION TO MARK This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

Landscaping products and amenities /

Landscaping products and amenities / ARMTEC.COM Landscaping products and amenities / PRODUCT GUIDE INNOVATIVE ROOF SLABS CREATE FUNCTIONAL AND ATTRACTIVE SPACES Versatile Superior quality Cost-effective BALLAST-LOK Armtec s Ballast-Lok concrete

More information

Low-slope reroofing guidelines

Low-slope reroofing guidelines Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam

More information

The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois

The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois Wiss, Janney, Elstner Associates, Inc. 10 South LaSalle Street, Suite 2600 Chicago, Illinois 60603 312.372.0555 tel 312.372.0873 fax www.wje.com The Building Group First Tuesdays October 2, 2012 Jason

More information

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom

More information

Seamless Waterproofing. Systems

Seamless Waterproofing. Systems Seamless Waterproofing Systems Pitched/Corrugated Roofs Liquid Rubber Instant Set is the ideal solution for pitched roof waterproofing providing a seamless fully bonded finish. RapidRoof is suited to smaller

More information

INJECTION MOLDING COOLING TIME REDUCTION AND THERMAL STRESS ANALYSIS

INJECTION MOLDING COOLING TIME REDUCTION AND THERMAL STRESS ANALYSIS INJECTION MOLDING COOLING TIME REDUCTION AND THERMAL STRESS ANALYSIS Tom Kimerling University of Massachusetts, Amherst MIE 605 Finite Element Analysis Spring 2002 ABSTRACT A FEA transient thermal structural

More information

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction

More information

3 Installation. 9 Roof Edges... p. 3. 19 10 Wall Terminations... p. 3. 20 11 Membrane Repair... p. 3. 21 12 Miscellaneous... p. 3. 22. 3.

3 Installation. 9 Roof Edges... p. 3. 19 10 Wall Terminations... p. 3. 20 11 Membrane Repair... p. 3. 21 12 Miscellaneous... p. 3. 22. 3. 3 Installation The information provided within this chapter may assist the contractor to install the Firestone UltraPly TPO Systems in accordance with Firestone s requirements. It may also help him and

More information

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This

More information

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing

TEST REPORT. Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4 x 4 and 5 x 5 PVC Porch Posts with Aluminum Reinforcing TEST REPORT Rendered to: LMT-Mercer Group, Inc. For: PRODUCT: 4" x 4" and 5" x 5" PVC Porch Posts with Aluminum Reinforcing Report No.: Report Date: 01/28/14 Test Record Retention Date: 12/20/17 130 Derry

More information

Peel & Seal Self-Stick Roofing Solutions

Peel & Seal Self-Stick Roofing Solutions Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,

More information

Proper roof slope and drainage are important to prevent excessive water accumulation

Proper roof slope and drainage are important to prevent excessive water accumulation Proper roof slope and drainage are important to prevent excessive water accumulation by Jason P. Wilen, AIA, CDT, RRO P onding water sometimes occurs on membrane roof systems as a result of snow, rainfall

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40 TEST REPORT Rendered to: INTEX MILLWORK SOLUTIONS, LLC For: Rigid Cellular PVC Guardrail System Hampton RS40 Report No: Report Date: 07/26/13 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax:

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36. Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth

More information

Air Conditioner Duct Construction & Repair

Air Conditioner Duct Construction & Repair PROPER ROOF AIR CONDITIONER MOUNTING At Newmar, there are two different models of air conditioners available on all towable and motorized units. The different models are the Dometic Brisk and Penguin models,

More information

There has been much written

There has been much written There has been much written recently about the presence of entrapped moisture within a roof assembly. No less than five informative and cautionary articles/bulletins have been written and published within

More information

JM s Commitment to Meeting Your Single Ply Roofing Needs. JM PVC with DuPont Elvaloy KEE (Ketone Ethylene Ester) Single Ply Systems

JM s Commitment to Meeting Your Single Ply Roofing Needs. JM PVC with DuPont Elvaloy KEE (Ketone Ethylene Ester) Single Ply Systems JM s Commitment to Meeting Your Single Ply Roofing Needs Johns Manville Roofing Systems helps you defy the elements with the industry s most comprehensive portfolio of commercial roofing solutions. Our

More information

1.1.2 Polypropylene The polypropylene must be a white opaque film, 1 2 mil thick. Biaxial orientation is preferred.

1.1.2 Polypropylene The polypropylene must be a white opaque film, 1 2 mil thick. Biaxial orientation is preferred. Library of Congress Preservation Directorate Specification Number 700 704 09 Specifications for Pressure Sensitive Adhesive Labels For Application to Single Paper Sheets and Text Pages of Bound Books For

More information

What s Wrong with this Project? Report

What s Wrong with this Project? Report NAHB RESEARCH CENTER INDUSTRY PARTNERSHIP FOR HIGH PERFORMING HOMES Task Order Agreement KNDJ-0-40335-01 Deliverable Task 11.3 What s Wrong with this Project? Report Prepared For: Alliance for Sustainable

More information