2 Regency TAFE, SA An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump July 2008 Prepared by Andrew Pang Andrew Pang & Associates Pty Ltd Phone: Facsimile: bnpang@aapt.net.au for Enrico Sgarbi enacon Holdings Pty Ltd Lobethal, SA

3 INTRODUCTION The aim of this report is to examine the effects of PermaFrost upon the refrigeration system of a two year old Fujitsu heat pump, Model AOT12LSAC. This unit is an inverter type that uses refrigerant R-410A. METHODOLOGY The testing was conducted in a laboratory at Regency TAFE, SA under control conditions. The indoor unit was placed in a room with two operating electric heaters to maintain a constant room temperature. The total heating load of the heaters was 2.25 kw. The condensing unit was placed in another room with an operating air conditioning unit to maintain a constant ambient temperature. The testing procedure included an analysis of the refrigeration system on two occasions: 1) Before the addition of PermaFrost, and 2) After addition of the product. To measure the performance of the refrigeration system, an ETM refrigeration system analyzer was used to data log the operating conditions of the systems during testing. For each test, the analyser collected the data on the following operating conditions over a 10 hour period at one minute interval for the same time period of the day: Power input Cooling capacity Coefficient of Performance, COP Compressor discharge temperature Evaporating temperature and pressure Condensing temperature and pressure Room temperature Ambient temperature TESTING The refrigeration system of the Fujitsu heat pump was first tested on July 3, 2008 before PermaFrost was introduced into the system and then on July 4, 2008 after the treatment. The two yardsticks for comparing the performance of the refrigeration system for the two tests are the ambient temperature and room temperature. The variation in the mean ambient temperature between the pre-test and the post-test was 0.10 %. The variation in the mean room temperature between the pre-test and the post-test was 1.14 %. These variations can be considered as insignificant and, hence, the ambient temperature and room temperature can be assumed to be constant for both tests.

4 The mean power consumption for the period of the pre-test was 6.2 kwh. The mean power consumption for the period of the post-test was 5.6 kwh. RESULTS OF TESTING Detailed results of the operating conditions are provided in the following charts, all found in Appendix A: 1. Pre-treatment Test (July 3, 2008) Chart 1A: Cooling Capacity, Power Input & Coefficient of Performance Chart 2A: Ambient, Room and Evaporating Temperatures Chart 3A: Condensing and Compressor Discharge Temperatures Chart 4A: Evaporator & Condenser Pressures 2. Post-treatment Test (July 4, 2008) Chart 1B: Cooling Capacity, Power Input & Coefficient of Performance Chart 2B: Ambient, Room and Evaporating Temperatures Chart 3B: Condensing and Compressor Discharge Temperatures Chart 4B: Evaporator & Condenser Pressures Observations A comparison of the mean operating conditions for each of the tests are summarised in table below: Test Results : Operating Mean Values Pre-treatment Post-treatment % change Cooling Capacity (kw) Power Input (kw) Coefficient of Performance, COP Percentage Improvement Discharge Temperature ( C) Evaporating Temperature ( C) Condensing Temperature ( C) Condensing Pressure (Bar Gauge) Evaporating Pressure (Bar Gauge) Room Temperature ( C) Ambient Temperature ( C) From this table, a number of observations can be made about the effects of PermaFrost on the Fujitsu heat pump:

5 Cooling capacity increased by % in the post-treatment test. This indicates a significant improvement in heat transfer in the evaporator. Power input decreased by 9.68% in the post-treatment test. This indicates a significant decrease in power consumption by the compressor. The COP (a ratio of the cooling capacity and power input) increased by 31.05% in the post-treatment test. This indicates a significant improvement in the overall system performance. The compressor discharge temperature decreased by 1.94%. The increase in evaporating temperature and pressure further indicates improvement in heat transfer in the evaporator. The variation in the condensing temperature between the pre-test and the post-test was 0.33 %. The variation in the condensing pressure between the pre-test and the post-test was 0.4 %. These variations can be considered as insignificant and, hence, the condensing temperature and pressure can be assumed to be constant for both tests. CONCLUSION The tests carried out on the Fujitsu heat pump, Model AOT12LSAC indicated an improvement in the cooling capacity of 17.4%, a decrease in power input of 9.7% and an overall increase in system performance of 31% after treatment with PermaFrost. The increase in cooling capacity and system performance will result in the compressor using less energy to achieve the same cooling effect on the unit as prior to treatment with Permafrost. The tests showed that for the 10-hour run time on the unit with the heaters in the room as simulated load the power consumption decrease from 6.2 kwh to 5.6 kwh. This represents an energy saving of 9.7%. In practice, the load in the room will vary rather than remain constant as during the tests with the simulated heat load, the heat pump will cycle on and off as the room reaches the set temperature. Hence, with the increase in cooling capacity and system performance after treatment with PermaFrost, the compressor actual run time will be shorter and the energy saving will be greater than the 9.7% achieved during the post test. The salient results are summarised in the bar graphs in Appendix B.

6 Pre Treatment Test July 3, 2008 Appendix A

7 Chart 1A - TAFE, Regency Park SA - Fujitsu R410A Inverter Performance Measurement, Pre PermaFrost 10 Mean value = 3.16 POWER INPUT [kw] Mean value = 0.62 kw COOLING CAPACITY [kw] Mean value = 3.16 kw 9 Before PermaFrost Value July 3, 2008

8 40 Chart 2A - TAFE, Regency Park SA Fujitsu R410A Inverter Operating Temperatures, Pre PermaFrost ROOM TEMP C AMBIENT TEMP C EVAP TEMP C Mean value = C Mean value = C Mean value = C Before PermaFrost Temp [ C] July 3, 2008

9 Chart 3A - TAFE, Regency Park SA Fujitsu R410A Inverter Operating Temperatures, Pre PermaFrost 70 COND C DISCH C Mean value = C Mean value =58.11 C Before PermaFrost Temp C July 3, 2008

10 30 Chart 4A - TAFE, Regency Park SA Fujitsu R410A Inverter Operating Temperatures, Pre PermaFrost EVAP PRESS Bar COND PRESS Bar Mean value = 8.59 Bar Mean value = Bar Before PermaFrost Temp C July 3, 2008

11 Post Treatment Test July 4, 2008 Appendix A

12 10 9 Chart 1B - TAFE, Regency Park SA Fujitsu R410A Inverter Performance Measurement, Post PermaFrost POWER INPUT [kw] COOLING CAPACITY kw Mean value = 3.71 Mean value = 0.56 kw Mean value = 3.71 kw AfterPermaFrost t Value July 4, 2008

13 40 Chart 2B - TAFE, Regency Park SA Fujitsu R410A Inverter Operating Temperatures, Post PermaFrost ROOM TEMP C AMBIENT TEMP C EVAP TEMP C Mean value = C Mean value = C Mean value = 16.3 C AfterPermaFrost Temp [ C] July 4, 2008

14 65 Chart 3B - TAFE, Regency Park SA Fujitsu R410A Inverter Operating Temperatures, Post PermaFrost COND C DISCH C Mean value =50.94 C Mean value = C AfterPermaFrost Temp C July 4, 2008

15 30 Mean value = 8.84 Bar Chart 4B - TAFE, Regency Park SA Fujitsu R410A Inverter Operating Temperatures, Post PermaFrost EVAP PRESS Bar COND PRESS Bar Mean value = 22.5 Bar AfterPermaFrost Temp C July 4, 2008

16 Performance Comparison Pre: July 3, 2008 & Post: July 4, 2008 Appendix B

17 TAFE, Regency Park SA - Fujitsu R410A Inverter Pre & Post PermaFrost Comparison, Cooling Capacity Cooling Capacity (kw) Linear (Cooling Capacity (kw)) kw Pre treatment Post treatment

18 TAFE, RegencyPark SA Fujitsu R410AInverter Pre & Post PermaFrost Comparison, System Performance Cooling Capacity (kw) Power Input (kw) Value Pre treatment Post treatment

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling for Simultaneous Heating and Cooling F. Sustainable Energy Centre, University of South Australia Mawson Lakes Boulevard, Mawson Lakes 5095 AUSTRALIA E-mail: Frank.@UniSA.edu.au Abstract The high efficiency

More information

2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124

2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124 Appendix 2B: Chiller Test Results...119 2B.1 Chilled-Water Return (and Supply) Temperature...119 2B.2 Chilled-Water Flow... 122 2B.3 Cooling-Water Supply Temperature / Flow... 124 2B.4 Pressure/Temperature...

More information

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

More information

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment

More information

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Experimental Analysis of a Variable Capacity Heat Pump System Focusing on

More information

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015 p.ginies@danfoss.

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015 p.ginies@danfoss. Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant Pierre Ginies, Next Heat Pump Generation 2015 p.ginies@danfoss.com Danfoss Commercial Compressors Leading compressor R&D and manufacturing

More information

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

More information

Research on annual energy consumption of packaged air-conditioning units

Research on annual energy consumption of packaged air-conditioning units Research on annual energy consumption of packaged air-conditioning units Graduate School of Frontier Sciences The University of Tokyo Eiji Hihara, Jianfeng Wang June 4, 2004 in Yokohama, Japan. Research

More information

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ 1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ ISO 9001 ISO 14001 Certified number : 01 100 89394 Certified number : 01 104 9245101 Fujitsu General (Thailand) Co.,

More information

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets 2 Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets - Extending Use of New Heat Pump System in Cold Regions

More information

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant

More information

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient

More information

How to choose a heat pump and use it wisely

How to choose a heat pump and use it wisely How to choose a heat pump and use it wisely Contents How does a heat pump work? 2 Insulating your home 3 Heat loss in the home Not all heat pumps are created equal 4 Choosing a heat pump 4 Choosing by

More information

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory

More information

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Low GWP Replacements for R404A in Commercial Refrigeration Applications Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, Samuel.YanaMotta@honeywell.com Abstract

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Dr. Nguyen Nguyen An, HUST CONTENTS Energy consumption to produce hot water in residential

More information

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents

More information

Commercial Hot Water. Make a difference...

Commercial Hot Water. Make a difference... Commercial Hot Water Make a difference... heat S O L A R pumps The Company Quantum Energy Technologies The Quantum story is based on innovation and the quest to harness renewable energy to produce sustainable

More information

Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump

Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump s.doty 10-2014 White Paper #30 Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump System Switches Fuels Automatically for Economy. What is an Air-Source Heat Pump? A heat pump is a modified air conditioning

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE P (5, EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE Ronald H. Howell, Professor Luis Rosario, Graduate Student Antonio Bula, Graduate Student Department of Mechanical Engineering

More information

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can

More information

How To Save Energy With High Pressure Control

How To Save Energy With High Pressure Control Energy savings in commercial refrigeration equipment : High Pressure Control July 2011/White paper by Christophe Borlein AFF and IIF-IIR member Make the most of your energy Summary Executive summary I

More information

Waste Heat Recovery through Air Conditioning System

Waste Heat Recovery through Air Conditioning System International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn : 2278-800X, www.ijerd.com Volume 5, Issue 3 (December 2012), PP. 87-92 Waste Heat Recovery through Air Conditioning

More information

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A Int. J. Mech. Eng. & Rob. Res. 213 Jyoti Soni and R C Gupta, 213 Research Paper ISSN 2278 149 www.ijmerr.com Vol. 2, No. 1, January 213 213 IJMERR. All Rights Reserved PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION

More information

Data Center RD&D at EPRI

Data Center RD&D at EPRI Data Center RD&D at EPRI Mukesh Khattar Technical Executive Critical facilities Round Table Meeting Palo Alto, CA 16 October 2015 EPRI Focus for Data Centers RD&D Address problems facing the member electric

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES M. Bantle 1, I. Tolstorebrov, T. M. Eikevik 2 1 Department of Energy Efficiency, SINTEF Energy Research, Trondheim, Norway,

More information

Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998

Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998 ABC FOUR CORNERS Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998 Reverse Cycle, High Wall Mounted, Non-Ducted, Single Phase, Single Split System Air Conditioner OPTICAL ACC-25V2 Report No. 30W-07-0038-TRP-221466-0

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS 1 HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS Jørn Stene SINTEF Energy Research, 7465 Trondheim, Norway Jorn.Stene@sintef.no In hotels, hospitals,

More information

RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump

RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump RESEARCH HIGHLIGHT December 2014 Technical Series 14-102 Performance Assessment of a Cold-Climate Air Source Heat Pump INTRODUCTION Most Canadians are familiar with air source heat pump technology in the

More information

Maintenance for Energy Efficiency

Maintenance for Energy Efficiency Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

Split units TH with hermetic compressors

Split units TH with hermetic compressors Split units TH with compressors Refrigeration units in split variant. Available with screw or solder terminal. Condensing unit with sound insulated weatherproof housing for outdoor installation. Split

More information

Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests

Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests August 26, 2015 REPORT #E15-294 Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests Prepared by: Energy 350 107 SE Washington St., Suite 145 Portland, OR 97214 Northwest Energy

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

Commercial Gas Heat Pump - VRF

Commercial Gas Heat Pump - VRF SANYO GHP Introduction Commercial Gas Heat Pump - VRF 01.12.2011 Agenda 1. SANYO GHP History 2. SANYO GHP Range 3. GHP Market Position 4. 2-WAY 5. GHP Power 6. 3-WAY 7. EER/COP 8. Water Heat Exchanger

More information

Model-Based Approach for Optimizing a Data Center Centralized Cooling System

Model-Based Approach for Optimizing a Data Center Centralized Cooling System Model-Based Approach for Optimizing a Data Center Centralized Cooling System Monem H. Beitelmal, Chandrakant D. Patel Enterprise Software and Systems Laboratory HP Laboratories Palo Alto HPL-6-67 April

More information

EHPA Testing Regulation

EHPA Testing Regulation EHPA Testing Regulation Testing of Air/Water Heat Pumps Terms, Test Conditions and Test Method based on EN 14511-1 through 4 Supplemental requirements for granting the international quality label for heat

More information

marine/bespoke split applications

marine/bespoke split applications split applications marine/bespoke evaporators, condensers and split air conditioning systems suitable for a multitude of applications such as coastal, extreme high and low ambients, harsh dusty environments

More information

SOLAR COOLING WITH ICE STORAGE

SOLAR COOLING WITH ICE STORAGE SOLAR COOLING WITH ICE STORAGE Beth Magerman Patrick Phelan Arizona State University 95 N. College Ave Tempe, Arizona, 8581 bmagerma@asu.edu phelan@asu.edu ABSTRACT An investigation is undertaken of a

More information

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India. International Journal of Emerging Trends in Engineering and Development Issue 3, Vol. (January 23) EFFECT OF SUB COOLING AND SUPERHEATING ON VAPOUR COMPRESSION REFRIGERATION SYSTEMS USING 22 ALTERNATIVE

More information

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: Simon.Ho@irco.com 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable

More information

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE Satish Joshi Managing Director CONTENTS 1. INTRODUCTION, APPLICATIONS 2. TECHNOLOGY, PROJECTS DONE, COST COMPARISION 3. HEAT PUMPS IN THE RENEWABLES DIRECTIVE,

More information

Daikin Altherma hybrid heat pump. The natural combination

Daikin Altherma hybrid heat pump. The natural combination Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient

More information

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

Simulation of a small size solar assisted adsorption air conditioning system for residential applications Heat Powered Cycles Conference 2009 2009 Simulation of a small size solar assisted adsorption air conditioning system for residential applications Salvatore Vasta, Andrea Frazzica, Gaetano Maggio, Alessio

More information

Natural geothermal energy.

Natural geothermal energy. ROTEX ground source heat pump Natural geothermal energy. ROTEX HPU ground the ground source heat pump that heats with free geothermal energy. Compact, environmentally responsible and uniquely efficient.

More information

Engineering Specifications

Engineering Specifications Engineering Specifications NORDIC W-85-H-B-*S-PD Water to Water Heat Pump Single-Stage R134a Nominal 7.5 Ton With Double Wall Condenser for Domestic Hot Water Production Maritime Geothermal Ltd. P.O. Box

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Air-sourced 90 Hot Water Supplying Heat Pump HEM-90A Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

Research on the Air Conditioning Water Heater System

Research on the Air Conditioning Water Heater System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric

More information

Over 30% 2-40 TR. Air Conditioning Danfoss compressors For comfort and precise cooling. www.danfoss.com. energy savings

Over 30% 2-40 TR. Air Conditioning Danfoss compressors For comfort and precise cooling. www.danfoss.com. energy savings MAKING MODERN LIVING POSSIBLE Air Conditioning Danfoss compressors For comfort and precise cooling With scroll and reciprocating technologies Over 30% energy savings with Danfoss inverter scrolls accelerate

More information

THE REPLACEMENT OF R-22

THE REPLACEMENT OF R-22 ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT

More information

Inverter and programmable controls in heat pump applications

Inverter and programmable controls in heat pump applications Inverter and programmable controls in heat pump applications Biagio Lamanna Application Competence Centre Manager Product Development Process CAREL INDUSTRIES Srl 3rd EHPA European Heat Pump Forum Brussels

More information

Silicagel-water adsorption cooling prototype system for mobile air conditioning

Silicagel-water adsorption cooling prototype system for mobile air conditioning Silicagel-water adsorption cooling prototype system for mobile air conditioning R. de Boer S.F. Smeding S. Mola Paper to be presented at the Heat Powered Cycles Conference 09 Berlin, 7 to 9 September 2009

More information

Hines Property Management, NYC

Hines Property Management, NYC Energy Science Division Hines Property Management, NYC Energy Performance Report Summary Results PermaFrost NMR Performance Report Hines - Data Center Chiller January, 2012 This Hines Property Management

More information

HEATING GLASGOW UNIVERSITY WITH RIVER SOURCED HEAT PUMPS

HEATING GLASGOW UNIVERSITY WITH RIVER SOURCED HEAT PUMPS HEATING GLASGOW UNIVERSITY WITH RIVER SOURCED HEAT PUMPS A. MCCONKEY *, A. POON-KING **, Z. YU University of Glasgow, G12 8QQ, Glasgow, United Kingdom *E-mail:amcconkey551@hotmail.co.uk; **E-mail: andrewpoonking@hotmail.com

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

The HVAC Service Assistant

The HVAC Service Assistant Technology Report The HVAC Service Assistant A Tool for Reducing Electrical Power Demand and Energy Consumption Commercial Residential Introduction Traditionally, verifying the success and impact of HVAC

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

Daikin Altherma. hybrid heat pump. The natural combination

Daikin Altherma. hybrid heat pump. The natural combination Daikin Altherma hybrid heat pump The natural combination Why choose Daikin? As an industry leader, Daikin combines broad experience, technical innovation and responsive customer service to help you meet

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine G Vicatos J Gryzagoridis S Wang Department of Mechanical Engineering,

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

Heating & Cooling Efficiency

Heating & Cooling Efficiency Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart

More information

Optimization of combined heating and cooling in Supermarkets

Optimization of combined heating and cooling in Supermarkets Optimization of combined heating and cooling in Supermarkets Funder-Kristensen T. 1 ; Fösel G. 2 and Bjerg P. 3 1 Ph.d. Head of Public & Industry Affairs, Danfoss, Nordborg, 6430, Denmark. 2 Dipl.-Ing.

More information

FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS

FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS D. Datta and S. A. Tassou Department of Mechanical Engineering, Brunel University Uxbridge, Middlesex

More information

Certified HVAC Audit Report Key Takeaways and Implications. Created for: Pets On the Go 445 Logging Road, Building 3 Yardley, PA-19034

Certified HVAC Audit Report Key Takeaways and Implications. Created for: Pets On the Go 445 Logging Road, Building 3 Yardley, PA-19034 Certified HVAC Audit Report Key Takeaways and Implications Created for: Pets On the Go 44 Logging Road, Building 3 Yardley, PA-9034 May, 0 Executive Summary Proposal Generator Demo aims to reduce your

More information

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR

AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR AIR CONDITION & REFRIGERATION INSTALLATION & REPAIR SERVICE CAPACITY (Value) : Rs. 15,40,000/- MONTH AND YEAR : July, 2014 OF PREPARATION PREPARED BY : Sh. Sunil Arora Investigator (Mechanical) 1. INTRODUCTION

More information

The Hybrid tri- genera0on system solar- bio- tric

The Hybrid tri- genera0on system solar- bio- tric The Hybrid tri- genera0on system solar- bio- tric S. Karellas and K. Braimakis sotokar@mail.ntua.gr, mpraim@mail.ntua.gr Na0onal Technical University of Athens 1 st Solar Open Workshop Building Integrated

More information

Schedule 3(A) Room Air Conditioners

Schedule 3(A) Room Air Conditioners Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression

More information

SMM. Installation Operation Maintenance

SMM. Installation Operation Maintenance SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,

More information

Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger

Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 2, Issue 11 (August 2012), PP. 66-70 Performance Improvement of an Air Conditioning

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

The natural ombination

The natural ombination The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,

More information

Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates

Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Arthur Rosenfeld, California Energy Commission Gregory Rosenquist, Lawrence Berkeley National Laboratory C. Keith Rice,

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

8. Heat pumps, heat pipes, cold thermal energy storage

8. Heat pumps, heat pipes, cold thermal energy storage Kylteknik ( KYL ) Refrigeration course # 424503.0 v. 2014 8. Heat pumps, heat pipes, cold thermal energy storage Ron Zevenhoven Åbo Akademi University Thermal and Flow Engineering Laboratory / Värme- och

More information

How To Clean Water From An Ammonia Refrigeration System

How To Clean Water From An Ammonia Refrigeration System Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can

More information

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance Refrigerant Choices for Commercial Refrigeration Finding the Right Balance 2 CONTENTS 1. Executive Summary 1.1. Introduction 4 1.2. Glossary of terms 5 5. Cases configuration 5.1. Introduction 17 5.2.

More information

Time to Rethink Heating

Time to Rethink Heating your comfort. our world. Time to Rethink Heating Daikin Altherma Hybrid heat pump Presented by Stuart Tandy Contents 1. Introducing Daikin 2. The time is right for hybrid 3. Rethink heating 4. How hybrid

More information

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 00 Measurement And Application of Performance Characteristics Of A Free Piston

More information

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs

More information

SEERS International. Hybrid Hot Water Systems. Innovation Technology

SEERS International. Hybrid Hot Water Systems. Innovation Technology SEERS International Hybrid Hot Water Systems Innovation Technology EFFECTS OF GLOBAL WARMING Invented & Manufactured By : Seers International Patent Number: PI-20082195 5 th Generation Hybrid Hot Water

More information