Smoke Detector/Carbon Monoxide Detector Inspections
|
|
- Austen Day
- 7 years ago
- Views:
Transcription
1 MIDDLESEX COUNTY FIRE MARSHAL 1001 Fire Academy Drive Sayreville, NJ (office) (fax) To: All Real Estate Agencies/Home Owners Subject: Smoke Detector/Carbon Monoxide Detector Inspections Attached please find an application for a Smoke Detector/Carbon Monoxide Detector Inspection which is required pursuant to the NJ Uniform Fire Code N.J.A.C. 5: and the Middlesex County Fire Marshal Ordinance when a change in occupancy or ownership occurs. Ten (10) business days or more before closing/change of occupancy: $50.00 Less than ten (10) business days before closing/change of occupancy: $75.00 Less than (4) business days before closing/change of occupancy: $ Re-inspection for failed inspection: $20.00 Failure to be present for scheduled inspection without notification: $75.00 Fees can be very significant if adequate notice is not provided for these inspections. The volume of requested inspections requires complex scheduling. When this law took effect, the county s fire prevention bureau has tried to make this process as easy as possible; however, we are receiving too many requests that do not allow for proper scheduling. The new fees address this problem. Our purpose is to encourage prompt attention to this requirement and adequate scheduling lead time for the inspections. Make checks payable to the Office of the Fire Marshal. Thank you for your cooperation in proper scheduling. Please feel free to contact our office if you should require further assistance. Sincerely, Michael Gallagher Middlesex County Fire Marshal
2 Listed below are the requirements for each Certificate of Inspection: SMOKE ALARMS: Alarms are to be located on every level of a resident (basement, first floor, second floor) excluding crawl spaces and unfinished attics, between sleeping areas such as the kitchen, garage, basement or utility room. In homes with only one sleeping area on one floor, an alarm is to be placed in the hallway within 10 feet of that room. In single family homes with two separate sleeping areas two alarms are required outside each sleeping are within 10 feet of that room. In multi-level homes, alarms are to be located outside sleeping areas and at every finished level of the home. Basement level alarms are to be located in close proximity to the bottom of the basement stairwells. If placed on the wall, the alarms should be six inches down from ceiling but no more than 12 inches. Smoke alarms shall not be older than 10 years or older than the expiration date prescribed by the manufacturer. CARBON MONOXIDE DETECTORS: A carbon monoxide alarms shall be centrally located outside of each separate sleeping area in the immediate vicinity of the bedrooms. Where bedrooms are separated and the audibility of the alarm or detector to occupants within the bedroom area could be seriously impaired, more than one unit may be required. Each alarm shall be located on the wall, ceiling or other location as specified in the installation instructions that accompany the unit. The alarm can either be electric, battery or the plug-in type. It is highly recommended that the alarm be electric or battery type. If you have a combination smoke/carbon alarm, it needs to be placed in accordance with smoke detector placement in sleeping areas. Carbon monoxide alarms shall not be older than 5 years or older than the expiration date prescribed by the manufacturer. FIRE EXTINGUISHERS: One fire extinguisher shall be mounted within 10 feet of the kitchen. The extinguisher shall weigh less than 10lbs. and be an ABC type extinguisher. The extinguisher shall be mounted with the top of the not higher than 10 feet from the floor. The seller of the home shall provide proof of purchase showing that the extinguisher is less than 12 years old. BUILDING NUMBER SIGNS: All required building number signs shall be displaced in a prominent and legible manner, so as to be highly visible from said public or private streets on which the building fronts. Numbers may be placed on curbside mailboxes provided they appear on each side of the mailbox and are at least two (2) inches in height. All other numbers must be at least four (4) inches in height and must be clearly visible from the street. If numbers are painted, the color must contrast with the color of surrounding surfaces. Numbers may be on house doors or screen doors if they are also on another part of the building. In order to receive your Certificate, the location of your smoke/carbon monoxide detectors, building signage and fire extinguisher must all be in compliance with the regulations on all codes. After inspection is complete, your certification is immediately issued. Each certificate is valid for six (6) months.
3 ONE & TWO FAMILY HOMES CERTIFICATION CRITERIA FOR SMOKE DETECTORS AND CO DETECTORS BUILT BEFORE 1977: Battery Detectors BUILT 1977 OR AFTER, BUT BEFORE 1984: Electric Detectors not interconnected BUILT 1984 OR AFTER, BUT BEFORE 1990: Electric Detectors - INTERCONNECTED BUILT 1990 TO PRESENT: Electric Detectors with battery back-up - ALL INTERCONNECTED In each bedroom Note: Only homes built before 1977 need to have the smoke detector at the bottom of the stairwell in basement.
4
5
Instructions for Obtaining a Certificate of Smoke Detector, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance
Princeton Department of Emergency & Safety Services Instructions for Obtaining a Certificate of, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance 1. Obtain an application Download from /forms
More informationRequirements for Smoke/Carbon Monoxide & Fire Extinguisher Certification
Requirements for Smoke/Carbon Monoxide & Fire Extinguisher Certification In order to successfully pass the inspection, your property will need to meet all regulations mandated by the state and municipality.
More informationCERTIFICATE OF COMPLIANCE
CERTIFICATE OF COMPLIANCE (Smoke Detector Inspection) Smoke detectors and carbon monoxide detectors must be in the proper locations and operational. Your house must also be properly numbered in order to
More informationRHODE ISLAND DIVISION OF STATE FIRE MARSHAL
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#
More informationHow To Install A Carbon Monoxide Detector
NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.
More informationSmoke & Carbon Monoxide
A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services www.mass.gov/dfs M.G.L. C 148 S. 26F - THE LAW Massachusetts
More informationSmoke & Carbon Monoxide
A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services PO Box 1025 Stow, MA 01775 978-567-3300 www.mass.gov/dfs
More informationGuide to Massachusetts Smoke & Carbon Monoxide Requirements
Guide to Massachusetts Smoke & Carbon Monoxide Requirements When Selling a One- or Two-Family Residence DEPARTMENT OF FIRE SERVICES Stephen D. Coan State Fire Marshal M.G.L. c 148 s. 26F - The Law Massachusetts
More informationSUBCHAPTER F. SMOKE ALARMS AND FIRE EXTINGUISHERS
SUBCHAPTER F. SMOKE ALARMS AND FIRE EXTINGUISHERS Sec. 92.251. DEFINITIONS. In this subchapter: (1) "Bedroom" means a room designed with the intent that it be used for sleeping purposes. (2) "Dwelling
More information527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
More informationUniversity Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationKITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More information527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
More informationMUNICIPALITY OF KAZABAZUA. SMOKE DETECTORS By-Law number 07-2012
MUNICIPALITY OF KAZABAZUA SMOKE DETECTORS By-Law number 07-2012 Notice of motion : August 7, 2012 Publication : September 9, 2012 Adoption : November 15, 2012 Effective November 15, 2012 Resolution: 2012-09-234
More informationOHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety
OHIO BOARD OF BUILDING STANDARDS Smoke Alarms and Fire Safety Updated January 2016 2 UNDERSTANDING THE TERMINOLOGY Detector. An initiation device suitable for connection to a circuit that has a sensor
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationBOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
More informationHow To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
More informationState of Michigan DEPARTMENT OF HUMAN SERVICES
RICK SNYDER GOVERNOR June 8, 2012 State of Michigan DEPARTMENT OF HUMAN SERVICES BUREAU OF CHILDREN AND ADULT LICENSING MAURA D. CORRIGAN DIRECTOR Buddy Smith Friends and Family, Inc. P O Box 406 Romeo,
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
More informationSMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
More informationBUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
More informationAlarms. State of Wisconsin Rules ss. 101.149(2) and (3) Comm. 62.1200 Comm.21.097
Carbon Monoxide Alarms State of Wisconsin Rules ss. 101.149(2) and (3) Comm. 62.1200 Comm.21.097 Carbon Monoxide Hazards CO, is a colorless, odorless and tasteless, yet highly toxic gas. Its molecules
More informationCarbon Monoxide (CO) Detection PRODUCTS. Accessories Conventional Detectors
Carbon Monoxide (CO) Detection PRODUCTS Accessories Conventional Detectors 2 Complete CO Detection The system-connected CO1224T and CO1224TR CO detectors with RealTest provide early warning by using reliable
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More informationBELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
More informationCity of St. Charles Basement Finish or Remodel
City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct
More informationICC CODE CORNER 2012 IFC Code & Commentary
SECTION 908 EMERGENCY ALARM SYSTEMS 908.1 Group H occupancies. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter
More information2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationBUILDING PERMIT RESIDENTIAL BASEMENT FINISH
BUILDING PERMIT RESIDENTIAL BASEMENT FINISH DOCUMENTS YOU WILL NEED 1. Building Permit Residential Basement Finish Package 2. Contractors copy of state and business license ADDITIONAL FORMS YOU MAY NEED
More informationGeneral Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
More informationKnow Your Smoke Alarm
Know Your Smoke Alarm Updated January 29th 2008 Port Angeles Fire Department, Washington Ver. 1.0 Purpose of Smoke Alarms A smoke detector or smoke alarm is a device that detects smoke and issues an alarm
More informationTable of Contents. Residential Care Facilities Presentation Handout 1
Table of Contents 1. Presentation Outline 2. Selected CBC Codes 3. SFM Interpretations 4. SFM Information Bulletins 5. Pre-Inspection Form 9290 6. Fire Safety Clearance Form 850, My Home Residential Care
More informationFire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
More informationCAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
More informationPractice Note 2006-27
Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two
More informationESTABLISHMENT OF A NEW BUSINESS
ESTABLISHMENT OF A NEW BUSINESS ATTENTION BUSINESS OWNERS Certificate of Occupancy Permit Requirements & Application Prior to any materials associated with your business being moved into the property that
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationUSER S MANUAL. SMDC-16 Digital Control Communicator and SMPC-32 Personal Control
SMDC-16 USER S MANUAL SMDC-16 Digital Control Communicator and SMPC-32 Personal Control Table of Contents General Descriptions Page Description of Your Alarm System 3 Description of Keypads 3 Keypad Maintenance
More informationPUBLIC Law, Chapter 162 LD 550, item 1, 124th Maine State Legislature An Act To Protect Maine Residents from Home Fires and Carbon Monoxide
PLEASE NOTE: Legislative Information cannot perform research, provide legal advice, or interpret Maine law. For legal assistance, please contact a qualified attorney. An Act To Protect Maine Residents
More informationDennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
More informationDanville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE. Alarm Systems. Smoke Detectors. Key and Data Storage Boxes
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE Section Alarm Systems 90.01 Purpose 90.02 Definitions 90.03 Exemptions 90.04 Registration 90.05 Violations; fines
More informationMobile Fire Rescue Department Bureau of Fire Prevention
222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This
More informationCarbon Monoxide Detection in Commercial Buildings (
1 Technical Guideline for School Districts and BOCES to comply with regulations for Carbon Monoxide Detection in Commercial Buildings (Section 1228.4 of Part 1228 of Title 19 NYCRR). General: This document
More informationNY Fire Safety Institute
NY Fire Safety Institute Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness F-80 Definitions and Terminology Established 1995 Preparing
More informationThe United States Fire Administration State-by-State Residential Smoke Alarm Requirements
Smoke Alarms Save Lives. The United States Fire Administration State-by-State Residential Smoke Alarm Requirements Page 2 Introduction As an entity of the Department of Homeland Security's Federal Emergency
More informationResidential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District
More informationCity of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level
More informationState of Michigan DEPARTMENT OF HUMAN SERVICES. Major, Kaylee 1595 Glenwood Lane Ishpeming, MI 49849
RICK SNYDER GOVERNOR March 23, 2015 State of Michigan DEPARTMENT OF HUMAN SERVICES BUREAU OF CHILDREN AND ADULT LICENSING NICK LYON INTERIM DIRECTOR Kaylee Major 1595 Glenwood Lane Ishpeming, MI 49849
More informationFIRE SAFETY REQUIREMENTS
FIRE SAFETY REQUIREMENTS 156.200 GENERALLY. A. Scope. The provisions of this chapter shall govern the minimum conditions and standards for fire safety relating to structures and exterior premises, including
More informationMINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More informationHow To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
More informationVILLAGE OF HUDSON FALLS 220 MAIN STREET HUDSON FALLS, NY 12839 (518) 747-5426 /
John E. Barton Mayor Ellen M. Brayman Clerk/Treasurer VILLAGE OF HUDSON FALLS 220 MAIN STREET HUDSON FALLS, NY 12839 (518) 747-5426 / Trustees: James Gallagher Robert Cook Michael Horrigan Thomas VanAernem
More informationGENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
More informationProposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
More informationMINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES
MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms
More informationRENTAL HOUSING THINGS TENANTS SHOULD KNOW
RENTAL HOUSING THINGS TENANTS SHOULD KNOW Table of Contents RENTAL HOUSING... 2 THINGS TENANTS SHOULD KNOW... 2 FIRE SAFETY IS A MATTER OF LIFE... 2 SMOKE ALARMS:... 2 BUILDING INSPECTION:... 5 GARBAGE
More informationMINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
More informationCommercial Business Licensing Requirements
SPRINGVILLE CITY BUSINESS LICENSING 110 SOUTH MAIN STREET SPRINGVILLE, UT 84663 OFFICE 801.491.7811 Commercial Business Licensing Requirements In our effort to make this application a One-Stop process
More informationThe replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
More informationREQUIREMENTS FOR OBTAINING A THORNBURY TOWNSHIP, DELAWARE COUNTY PERMIT
REQUIREMENTS FOR OBTAINING A THORNBURY TOWNSHIP, DELAWARE COUNTY PERMIT ATTACHED ARE THE REQUIREMENTS FOR OBTAINING A BUILDING PERMIT INCOMPLETE SUBMISSIONS WILL BE RETURNED IN THEIR ENTIRETY -- NO EXCEPTIONS!!
More informationTEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows:
TEXT (CO Detection Commercial Buildings Final) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: Section 1228.4. Carbon Monoxide Detection in Commercial Buildings
More informationSPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
More informationLESSON PLAN 4 6-8 FIRE PREVENTION AND SAFETY
The Science of Fire-Suppression and Fire-Warning Systems Activity Fire Insurance Activity Community Service Project Activity KEY TERMS AND CONCEPTS sprinkler system fire codes smoke alarm photoelectric
More informationI.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
More informationBuilding Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings
Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationSingle Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
More informationElectrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationBUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance
More informationINSTALLATION AND OPERATION MANUAL
Photoelectronic Smoke Detector with Built-in Wireless Transmitter INSTALLATION AND OPERATION MANUAL 1 Model # 1008-4 What smoke detectors can do: Smoke detectors are designed to provide early warning of
More informationBasement Finishing 101: The Essential Guide to Finishing Your Basement
Are you tired of walking into a dark, disorganized basement? Do you wish that you had more finished space in your home? Do you want to finish your basement, but don t know where to begin? Do you want to
More informationArapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
More informationFire Facts Smoke Alarms
Fire Facts Smoke Alarms Your chances of dying in a home fire may be reduced by 50 per cent if a working smoke alarm is present in your home. Smoke alarms, when properly installed, tested and maintained,
More informationSITE OVERALL CONDITION COMMENTS
PROPERTY INSPECTION A complete property inspection should be done at the beginning of the academic year, during the holiday break, and at the end of the academic year. Work to prioritize the list of needed
More informationI.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
More informationAdult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION
More informationTHE QUICK START QUICK START GUIDE
THE QUICK START QUICK START GUIDE www.frontpointsecurity.com/support-overview WELCOME FRONTPOINT TO Thank you for choosing Frontpoint for your security needs! We re delighted to have you as a new customer
More informationENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000
AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM
More informationFire precautions in dwellings. Private sector housing Providing homes building communities
Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared
More informationRequired Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
More informationBUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
More informationGENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More information2-WAY WIRELESS SUPERVISED PHOTOELECTRIC SMOKE DETECTOR. Model: EL-4703 INSTALLATION INSTRUCTIONS
2-WAY WIRELESS SUPERVISED PHOTOELECTRIC SMOKE DETECTOR Model: EL-4703 INSTALLATION INSTRUCTIONS GENERAL DESCRIPTION Electronics Line's smoke detector is single station, photoelectric smoke detector with
More informationCITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.
More informationFire Standards & Regulations Are you confused?
Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm
More informationSENATE DOCKET, NO. 2234 FILED ON: 9/24/2015. SENATE... No. The Commonwealth of Massachusetts PRESENTED BY: Anthony W. Petruccelli
SENATE DOCKET, NO. 2234 FILED ON: 9/24/2015 SENATE.............. No. The Commonwealth of Massachusetts PRESENTED BY: Anthony W. Petruccelli To the Honorable Senate and House of Representatives of the Commonwealth
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationEffective June 27, 2015. TEXT (CO Detection Commercial Buildings)
TEXT (CO Detection Commercial Buildings) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: Section 1228.4. Carbon Monoxide Detection in Commercial Buildings (a)
More informationH:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh
Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years
More informationMinimum Housing and Health Standards
APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).
More informationhealthy homes assessment
healthy homes assessment Date of Inspection: Inspector s Name: Agency: Address of Property: Resident s Name: Phone Number: Primary Reason for Visit: Asthma Lead Poisoning Voluntary Referral Other: GENERAL
More informationTruth in Sale of Housing Disclosure Report NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection!
NOTICE - Read Entire Report Carefully. This is not a Buyer's Inspection! Current Owner Name: Mpls City Property Atn Cped (p Contact: Mpls City Property Atn Cped (p Business/Relationship: Owner Address:
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More information