SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P"

Transcription

1 SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P 2 Alarm Levels Bargraph + LED Indication of Gas Concentration Visual and Audible Signalization of Activated Alarm Levels 2 SPDT 5A/250V Output Relays Shock-Proof & Ex-Proof Sensor Housing Intrinsically Safe Shunt Barriers Back-up Accumulator Power Supply (optional) I. APPLICATION The single-channel gas-detector GAS ALARM DG510/1P is purposed for signaling anytime, when concentration of flammable and explosion-hazardous gases exceeds permissible limits. Its application includes mounting in pump units, gas stations, filling stations, dyeing cameras and other areas, where gaspowered equipment is used, or where combustible or toxic vapors and gases are found. The device consists of a microprocessor Control Block, which is to be mounted in areas with normal risk of fire, and a Sensor, which is placed in the hazardous zone. There are two programmable alarm levels for the gas concentration - pre-alarm and alarm level. The measured gas concentration is visualized on the LED bargraph indication in % LEL (lower explosion limit). If the gas concentration exceeds 10% LEL the prealarm level (AL1) and relay output LL are activated. LED AL1 is lighted. The relay output may operate a shut-off valve for stopping the gas flow, switch on a siren or fan, etc. If despite all taken measures the gas concentration exceeds 20% LEL the alarm level (AL2) and relay output HL are activated. A local buzzer is switched on if the gas concentration exceeds one of the alarm levels. The pre-alarm and alarm levels can be individually set. The alarm level cannot be set to a level greater than 50% LEL because of safety precautions. In case of Sensor or Cable Fault the LED "FLT" is lighted and the audible alarm is activated. On customer s request there can be mounted additionally a back-up power supply module, thus guaranteeing continuous working conditions for the gas detector. Switching to the back-up power supply is automatic in case of central power supply failure. The recommended capacity of a 12V accumulator is 6-8Аh. A lighted up Accu LED indicates the charging process of the accumulator from the electricity grid. Gas alarm s explosion-proof operation is guaranteed through shock- and explosion-proof Sensor housing EEx d IIC T5 and intrinsically safe shunt barriers ЕEx i a IIC. DELTA INSTRUMENTS Ltd. 23 A. Saharov blvd., Mladost 1, 1784 Sofia, Bulgaria Tel , , ; Fax: Web Site:

2 II. TECHNICAL SPECIFICATIONS Power Supply 230V, 50Hz Detected Gas methane (natural gas), propane-butane, hydrogen, ammonia, ethylene, organic dissolvent vapors, fuel vapors, etc. Sensor catalytic (pelistor type) Pre-alarm level /АL1/ 10 % LEL programmable in the range 0 < AL1 < AL2 Alarm level /АL2/ 20 % LEL (in the range AL1 < AL2 50% LEL) Pre-alarm level AL1 output SPDT relay, 5A/250V /LL/ Alarm level AL2 output SPDT relay, 5A/250V /HL/ Indication bargraph, LED, 0-50% LEL Ambient temperature for sensors С Ambient temperature for control unit 0 50 С Reaction delay of sensors 20s Back-up power supply (optional) accumulator 12V DC Dimensions of control unit 1/8 DIN ( 96 x 48 x 132 mm ) Protection degree of control unit IP 30 Explosion-proof sensor housing ЕEx d IIC T5 Intrinsically safe shunt barriers EEx i a IIC CONNECTION SCHEME CONNECTION DIAGRAM Sensor cable connection legend: Vcc red wire INPUT white wire GND blue wire

3 Dimensions 96 ( width 48) 92 ( width 44) III. MOUNTING INSTRUCTIONS 3.1. Mount gas-detector to panel or metal construction in an area with normal risk of fire, fixing it by two supplied attaching clamps Connect the sensor to the blue marked intrinsically safe terminals via a 3-wire cable, according to the connection diagram Mount the sensor in explosion-hazardous area vertically (Sintered Filter downwards). When mounting, the following factors have to be considered: relative weight of the detected gas In case of gases with relative weight lower than that of the ambient air, place Sensor above the possible gas leakage location, or at the top possible place, where gas is accumulating. In case of gases, heavier than ambient air, place Sensor below the leakage location, or at the lowest possible place, where gases may accumulate. If there are airflows present, place Sensor between eventual leakage or accumulation locations, and possible combustion source. dust and water presence In areas with a high degree of dust loading, use a dust-proof filter, which at the same time should not obstruct the freeway from gas to sensor. In damp areas a water drop protection has to be made. vibration presence The Sensor is vibration-sensitive and should either be mounted in a place where vibrations are not present, or measures for their reduction have to be taken.

4 IV. OPERATING INSTRUCTIONS 4.1. CONTROL PANEL DESCRIPTION The control panel of the gas-detector consists of a control block for setting the alarm levels and a bargraph, indicating the actual value of gas concentration in % of LEL (lower explosion limit). The 5 LEDs indicate different gas-detector states, as listed in Table 1: NAME POWER FLT AL1 AL2 ACCU Table 1 FUNCTION After turning on the power supply follows an activation process of the sensor for appr. 1 min. During this time the AL1 and AL2 diodes are blinking. When this initialization has finished the both diodes go off, but the POWER LED remains on while there is power supply available. The FLT LED is activated only in case of faulty sensor or cable. Indicates the state of the output relay, corresponding to the pre-alarm level. Lighted up LED means that the relay LL is activated. After pressing the RESET button to deactivate the sound alarm signal the AL1 diode remains blinking. The LL relay stays active until the concentration drops below the set LEL percentage level. Indicates the state of the output relay, corresponding to the alarm level. Lighted up LED means that the relay HL is activated. After pressing the RESET button to deactivate the sound alarm signal the AL2 diode remains blinking. The HL relay stays active until the concentration drops below the set LEL percentage level. It is turned on only while charging the accumulator (only by existent backup power supply) The bargraph indicates the process value of measured concentration 0-50% of the lower explosion limit (LEL) of the corresponding gas. If the concentration has reached over any of the set alarm levels, the corresponding segment of the bargraph scale starts blinking AUDIBLE SIGNALIZATION By exceeding the concentration of the set pre-alarm and alarm levels is activated an integrated sound alarm. For the pre-alarm level AL1 the buzzer emits a short signal every 3 sec, while for the alarm level AL2 the sound signal is continuous. A short beep is emitted also every time when a button from the keypad is pressed VISUALIZING THE SET ALARM LEVELS By pressing the MODE button while in standard operation mode, the display switches to visualization of the set alarm levels. Only the bargraph s segments which correspond to the set alarm levels remain lighted. If the gas concentration is higher than any of the set alarm levels, the corresponding LED remains blinking as well. Another click on the MODE button leads back to standard operation mode.

5 4.4. TESTING THE ALARM OUTPUT RELAYS The output relays can be activated from the control panel in order to test the functionality of connected control mechanisms (siren, air ventilating system, gas-flow closing valve, power supply switching-off, etc.). By holding the TEST button pressed the relays are activated (AL1 and AL2 diodes become lighted up) and by releasing it the relays get deactivated DEACTIVATION OF THE AUDIBLE SIGNALIZATION By any activated alarm level the operator can use the keypad to turn off the sound alarm until the problem is solved. By active alarm state pressing the RESET button turns off the sound signalization until the concentration drops below the set alarm level. After the deactivation of the sound alarm, the corresponding alarm LED starts blinking. The output relays remain open (active) until normalizing the concentration under the set levels PROGRAMMING THE ALARM LEVELS ATTENTION: In the mode of programming the alarm levels the output relays are deactivated and the different LEDs serve as indication of the ongoing level setting regime. While in standard operation mode simultaneous pressing and holding the buttons MODE and ENT activates the mode for programming the alarm levels. - By simultaneously pressed MODE and ENT buttons the LED AL2 starts blinking, which indicates that the device is ready for adjusting the alarm level. The segment of the bargraph, which corresponds to the set alarm level, starts blinking, while the segment for pre-alarm level remains turned on. With buttons and the operator can move the blinking segment up and down the scale to select a new desired value. To save the newly selected value should be pressed the ENT button. Then if the value has been saved successfully the newly set segment should stop blinking. The alarm level can be set only between the value of pre-alarm level and 50% LEL. If the operator doesn t wish to change the alarm level, it is recommended to proceed to the pre-alarm level setting just by pressing the MODE button. - By pressing MODE after entering the mode for programming the alarm levels, the LED AL1 should start blinking, which indicates that the device is in regime for setting the pre-alarm level. Identically a new desired level can be selected by moving the lower blinking segment of the bargraph with and between 0% and the value of AL2 and saved by pressing ENT. - By pressing the MODE button once again, the indication returns to standard mode of operation and the gas-detector starts functioning with the newly selected level values.

6 V. GENERAL CONDITIONS GAS ALARM DG510/1P gas-detector may be used only in applications, approved by its manufacturer - DELTA INSTRUMENTS Ltd. Test and calibration have to be made every 12 months. The test overall performance will be ensured in a best way through a periodical maintenance servicing contract with the manufacturer. Device safe-operation guarantee is not valid, if DG510/1P is maintained with unauthorized personnel or if the corresponding to the term of question Test and Calibration Report is not available. CAUTION! It is absolutely forbidden to disassemble the explosion-proof sensor housing and change safety fuses or other electronic elements, connected to the proper functionality of the intrinsically safe shunt barriers! VII. REPAIR Any repair activities, concerning GAS ALARM DG510/1P Electronic Block and DGS 510 Sensor have to be carried out only in manufacturer DELTA INSTRUMENTS Ltd laboratories.

BX150 Gas Detector. Application. Operation

BX150 Gas Detector. Application. Operation BX50 Gas Detector Application Duomo is recognised in the gas industry for providing a comprehensive range of low cost, high reliability gas detection systems for many applications. We have installed and

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

RGA-4001 Single Zone Gas Leak Detector

RGA-4001 Single Zone Gas Leak Detector Product sheet GS7.61 Gas Detector Type Single Zone Gas Leak Detector are panel/wall mounted gas leak detectors for single zone. The RGA control unit has been designed and built according to European regulations

More information

600-GD & 600-GDL 600 SERIES GAS DETECTOR

600-GD & 600-GDL 600 SERIES GAS DETECTOR 600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING

More information

EX 2000/EX 2000 C/ GD 2000/GDP

EX 2000/EX 2000 C/ GD 2000/GDP Gas detectors EX 2000/EX 2000 C/ GD 2000/GDP 2000 Gas Discrimination (GD 2000 / GDP 2000) Explosimeters/ Catharometers Pocket size Long battery life High reliability New design for Enhanced performance

More information

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject

More information

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

GS150K Gas Detector. Application. Technical Specification. Operation

GS150K Gas Detector. Application. Technical Specification. Operation GS150K Single Zone Detector Application Duomo is recognised within the Gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have installed

More information

PANTHERALERT OPERATION & INSTALLATION MANUAL

PANTHERALERT OPERATION & INSTALLATION MANUAL PANTHERALERT OPERATION & INSTALLATION MANUAL PANTHERALERT Model: PA04 Gas Monitoring & Fire - Alarm & Automatic Cut Off System FUNCTION: to Monitor & Detect gas /fire/heat and to: [1] WARN - by means of

More information

Fire Pump Controllers Remote Alarm Panels

Fire Pump Controllers Remote Alarm Panels Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

BX444 Gas Detector. BX444 Four Zone Gas Detector

BX444 Gas Detector. BX444 Four Zone Gas Detector BX444 Gas Detector BX444 Four Zone Gas Detector Duomo is recognised within the Gas industry for providing a comprehensive range of low cost, high reliability gas detection for many applications. We have

More information

GAS DETECTORS EXPLOSIMETERS/CATHAROMETERS EX 2000/EX 2000 C/GD 2000/GDP Your environment, your safety, let s master them together

GAS DETECTORS EXPLOSIMETERS/CATHAROMETERS EX 2000/EX 2000 C/GD 2000/GDP Your environment, your safety, let s master them together GAS DETECTORS EXPLOSIMETERS/CATHAROMETERS EX 2000/EX 2000 C/GD 2000/GDP 2000 Gas Discrimination (GD 2000 / GDP 2000) Pocket size Long battery life High reliability New design for Enhanced performance Your

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

BEP FD-2 CONTOUR MATRIX FUME DETECTOR

BEP FD-2 CONTOUR MATRIX FUME DETECTOR BEP FD-2 CONTOUR MATRIX FUME DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING GAS SENSORS...3 4 FEATURES...4 5 SPECIFICATION...4 6

More information

BRAVER UPS. (Uninterruptible Power System) User s Manual

BRAVER UPS. (Uninterruptible Power System) User s Manual BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

Fire & Security DETECTORS

Fire & Security DETECTORS Fire & Security DETECTORS Smoke Sensitivity 0.98 ~.0%/ft Obscuration Ceiling Spacing 50 foot rating for heat sensor Temperature Range 10ºC to 50ºC Humidity 0 to 95% RH, no condensation or icing Dimensions

More information

Buckeye Detection Systems Fixed Detection Systems Application Survey

Buckeye Detection Systems Fixed Detection Systems Application Survey Buckeye Detection Systems Fixed Detection Systems Application Survey Channel Partner Representative : Company Name: Representative: BDS Representative: Client Contact Information : Company Name: Company

More information

User s Manual AURORA 1.2K/2.2K

User s Manual AURORA 1.2K/2.2K User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable

More information

DALI RC BASIC SO. Control unit Operating instructions

DALI RC BASIC SO. Control unit Operating instructions DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. SHI SERIES (SHI400, SHI600, SHI1000) Pure Sine Wave Inverter The information presented in this document does

More information

EXPLORER 4 MULTIPOINT

EXPLORER 4 MULTIPOINT EXPLORER 4 MULTIPOINT Sampling gas analyser EXPLORER 4 MULTIPOINT is a sampling gas analyser, with 4 gas detection sensors ( LEL,H2S, O2 CO ) reliable and in accordance of the Rules with 15 sampling points

More information

CO2 Alarm. Operation. Application

CO2 Alarm. Operation. Application CO Alarm 100-77V AC Supply Voltage Two pre-configured alarm and control thresholds Thresholds factory set to customer requirements on dispersive infrared sensing technology Optional internal audible alarm

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

LAMBDA PROBE MODULE ML-2

LAMBDA PROBE MODULE ML-2 LAMBDA PROBE MODULE ML-2 page 2 Spis treści Spis treści 1 General information 4 1.1 Introduction 4 1.2 Contents 4 1.3 Safety precautions 5 1.4 Disposal of old equipment 6 2 Connecting to the system 7 2.1

More information

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.

More information

Fire Alarm System Accessories

Fire Alarm System Accessories Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer

More information

UM-X Field display for continous level sensors

UM-X Field display for continous level sensors Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90

More information

Triple Waveband Infra-Red Flame Detection

Triple Waveband Infra-Red Flame Detection Minerva S200PLUS Ex ia Intrinsically Safe & Ex d Flameproof Solar Blind Flame Detectors Triple Waveband Infra-Red Flame Detection Key Features Unrivalled black body rejection over a wide range of source

More information

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure QUADSCAN II SERIES 7400 ONE TO FOUR CHANNEL RECEIVER QUADSCAN II SERIES 7400 ONE TO FOUR CHANNEL RECEIVER Centralizes Monitoring and Alarming for Gas Transmitters and Fire Detectors. The QuadScan II receiver

More information

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide PIMA Electronic Systems Ltd. 5 Hatzoref Street, Holon 58856, Israel +972-3-5587722 +972-3-5500442 support@pima-alarms.com http://www.pima-alarms.com

More information

LPG and Natural gas leak detectors Series GSX - GSW

LPG and Natural gas leak detectors Series GSX - GSW LPG and Natural gas leak detectors Series GSX - GSW Main features - Suitable for domestic applications - Electronic operation based on microprocessor - Available in the following versions : wall mounting

More information

Gasmesscomputer GMC from Version 1.0. Output Extension RK Data Sheet. Gas Detection and Warning Systems

Gasmesscomputer GMC from Version 1.0. Output Extension RK Data Sheet. Gas Detection and Warning Systems Gasmesscomputer GMC 8420 from Version 1.0 Output Extension RK 8420 Gas Detection and Warning Systems Application The controller Gasmesscomputer GMC 8420, in conjunction with detectors that supply 4-20

More information

WD-AMX Water Detection Controllers

WD-AMX Water Detection Controllers Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation

More information

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw rather than providing multiple choices. The sensor modules used may only be suitable for use with the matching controller so it is wise to read the specifications to make sure the unit suits your application.

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

MT /4 Autorange Digital Multimeter User s Manual

MT /4 Autorange Digital Multimeter User s Manual MT-1232 3-3/4 Autorange Digital Multimeter User s Manual 1 st Edition, 2013 2013 Copyright by Prokit s Industries Co., Ltd. Contents General------------------------------------------------------------------1

More information

SPL 2-00/-01 OPERATION INSTRUCTIONS

SPL 2-00/-01 OPERATION INSTRUCTIONS SPL 2-00/-01 OPERATION INSTRUCTIONS Powerline Ethernet Adapter 500 Mbps EN Read and keep Operation Instructions SPL 2-00/-01 Safety Notes Do NOT use this product near water, for example, in a wet basement

More information

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018 USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and

More information

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.: Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM

More information

TM SmartLIO - Control desk (LocoNet)

TM SmartLIO - Control desk (LocoNet) TM-75461 SmartLIO - Control desk (LocoNet) User's manual 2011 BioDigit Ltd. All rights reserved. It is forbidden to reproduce and/or publish the contents of the present document in any form including electronic

More information

Shunt lock function 3066 Operator Instructions

Shunt lock function 3066 Operator Instructions Shunt lock function 3066 Operator Instructions Version: January 2004 Contents Deactivation unit Deactivation unit Deactivation unit Activation unit with configuration MASTER Alarm System 1.0 Shunt lock

More information

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment

More information

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module 1. General Description 1 2. General Warnings 1 3. Interface 2 4. Temp Alarms Setting 3 5. Programming 3 6. Light Management 4 7. Installation and

More information

COLOR VIDEO DOOR PHONE CDV-71BE/D

COLOR VIDEO DOOR PHONE CDV-71BE/D COLOR VIDEO DOOR PHONE CDV-71BE/D 513-11, Sangdaewon-dong, Jungwon-gu, Seongnam-si, Gyeonggi-do, Korea Int l Business Dept. : Tel.; +82-31-7393-540~550 Fax.; +82-31-745-2133 Web site : www.commax.com Printed

More information

CLASSIFICATION NOTES

CLASSIFICATION NOTES CLASSIFICATION NOTES Type Approval, Installation and Testing of Water Level Detectors on Bulk Carriers and Single Hold Cargo Ships other than Bulk Carriers General Information This edition of the classification

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

450VA/650VA/850VA User s Manual

450VA/650VA/850VA User s Manual 450VA/650VA/850VA User s Manual Line Interactive UPS Uninterruptible Power System Table of Contents Safety Instructions Installation and Operation Specifications System Introduction Software Installation

More information

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,

More information

UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 33 00.00 40 (February 2014) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Instruction and Maintenance Manual

Instruction and Maintenance Manual Instruction and Maintenance Manual GRYF OXY P 0/100/2 PM Contact GRYF HB, spol. s r.o. Cechova 314 Havlickuv Brod 580 01 tel.: +420 569 426 627 fax: +420 569 426 627 Czech Republic www.gryf.eu Technical

More information

Electronic Pressure Switch EDS 300

Electronic Pressure Switch EDS 300 Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5

More information

EEC-9160 Traffic Signal Controller Uninterruptible Power Supply

EEC-9160 Traffic Signal Controller Uninterruptible Power Supply Traffic Light Controller Uninterruptible Power Supply Pure Sinewave Line Interactive UPS Digital with Microprocessor Control Advanced LCD Control Panel Multi-Functional Outdoor UPS Long Back Up to Support

More information

Pressure transmitter (2 wire) / switch for continuous or On/Off Control

Pressure transmitter (2 wire) / switch for continuous or On/Off Control transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

Description. Specifications. Specifications and Ordering Information 3500/63 Hazardous Gas Monitor. Inputs

Description. Specifications. Specifications and Ordering Information 3500/63 Hazardous Gas Monitor. Inputs Specifications and Ordering Information 3500/63 Hazardous Gas Monitor doghouses are all examples of confined spaces where combustible gases could accumulate. Description The 3500/63 Hazardous Gas Monitor

More information

Intruder alarm. Pro 21 TM /Solfà TM. Installation and operating instructions N0064EG2/00

Intruder alarm. Pro 21 TM /Solfà TM. Installation and operating instructions N0064EG2/00 Intruder alarm Pro TM /Solfà TM Installation and operating instructions N00EG/00 Contents General presentation..., Presentation of a system with zones..., Product guide... Typical installation Preparation...

More information

Magnetic field sensor for pneumatic cylinders BIM-IKT-Y1X

Magnetic field sensor for pneumatic cylinders BIM-IKT-Y1X ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Rectangular, height 17 mm Metal, GD-Zn Magnetic-inductive sensor DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6

More information

GSM home alarm system s manual

GSM home alarm system s manual GSM home alarm system s manual I. Main features: 1, Eight wireless LED zone, and four wired zone 2, Two-way to communication 3, The system supports the GSM cell phones, no need the fixed telephone line.

More information

BX616 Portable Multi-gas Detector Using Manual BX616. Portable Multi-gas Detector Using Manual. Amtech Industry Co Ltd

BX616 Portable Multi-gas Detector Using Manual BX616. Portable Multi-gas Detector Using Manual. Amtech Industry Co Ltd BX616 Portable Multi-gas Detector Using Manual Amtech Industry Co Ltd 0 1. Brief Introduction BX616 portable multi-gas detector could detect combustible gas, O2 and other two types toxic gases continuously

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Inductive sensor NI10-M18-Y1X-H1141

Inductive sensor NI10-M18-Y1X-H1141 ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB , GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well

More information

Macurco GD-2B Combustible Gas Detector User Instructions

Macurco GD-2B Combustible Gas Detector User Instructions Macurco GD-2B Combustible Gas Detector User Instructions Important: These User Instructions are to be provided to the homeowner/end user upon product installation. Each person installing or using this

More information

Ultimate-X UKA-series. (6kVA - 10kVA) TRUE ON-LINE DOUBLE CONVERSION UNINTERRUPTIBLE POWER SUPPLY

Ultimate-X UKA-series. (6kVA - 10kVA) TRUE ON-LINE DOUBLE CONVERSION UNINTERRUPTIBLE POWER SUPPLY Ultimate-X UKA-series (6kVA - 10kVA) TRUE ON-LINE DOUBLE CONVERSION UNINTERRUPTIBLE POWER SUPPLY LEN.MAN.UPS.175 Rev.2.00/2011 CONTENTS SAFETY INSTRUCTIONS 1 INTRODUCTION 2 FRONT AND REAR PANEL 4 INSTALLATION

More information

PROXIMITY CARD READERS C-10, C-20, C60, C70

PROXIMITY CARD READERS C-10, C-20, C60, C70 Installation Manual PROXIMITY CARD READERS C-10, C-20, C60, C70 VERSION 1.0 CONTENTS 1. General information................................. 3 2. Technical data......................... 4 3. Connection

More information

User s Guide. Security Systems D220

User s Guide. Security Systems D220 User s Guide Security Systems D220 Table of Contents About This User s Guide... 3 Introduction... 3 Security System Basics... 4 Controlled Points... 5 24-Hour Points... 6 Keypad Keys... 6 Keypad Lights...

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion

More information

Regards from the Team at Rheology Solutions.

Regards from the Team at Rheology Solutions. Rheology Solutions is the sole Australian distributor of this product range and we welcome the opportunity of discussing your application requirements. We hope the information you are seeking is contained

More information

MOBILE CALL GSM alarm system

MOBILE CALL GSM alarm system MOBILE CALL GSM alarm system User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. - 1 - Catalogue: Function Introduction 2 SMS Number

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

E 3 Point. Toxic and Combustible Gas Detector Network Platform (BACnet MS-TP, Modbus) PRODUCT SUBMITTAL ORDERING INFORMATION

E 3 Point. Toxic and Combustible Gas Detector Network Platform (BACnet MS-TP, Modbus) PRODUCT SUBMITTAL ORDERING INFORMATION E 3 Point PRODUCT SUBMITTAL Toxic and Combustible Gas Detector Network Platform (BACnet MS-TP, Modbus) ORDERING INFORMATION Single-Gas, Surface-Mount Base unit only; sensor cartridge sold separately E3SM

More information

SECURITY SYSTEM ADP-CAN

SECURITY SYSTEM ADP-CAN INSTALLATION INSTRUCTION SECURITY SYSTEM ADP-CAN Introduction Motorcar security system ADP-CAN is for motorcars provided with CAN net. It is for the work with the motorcar factory security systems or remote

More information

OMNI 500 Filter Controller Manual Revision: 1.1, February 2011

OMNI 500 Filter Controller Manual Revision: 1.1, February 2011 OMNI 500 Filter Controller Manual Revision: 1.1, February 2011 Table of Contents Page I. Introduction 1 II. Using the Rotary Switches 2 III. Connection of Inputs, Outputs and Power 3 Wiring Schematics

More information

HSTBX616 Portable Multi-gas Detector Using Manual

HSTBX616 Portable Multi-gas Detector Using Manual HSTBX616 Portable Multi-gas Detector Using Manual 0 1. Brief Introduction HSTBX616 portable multi-gas detector could detect combustible gas, O2 and other two types toxic gases continuously and simultaneously.

More information

Operating Instructions

Operating Instructions Operating Instructions Control unit Ex p > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Instructions...3 4 Designated Use...4 5 Technical Data...4 6 Transport, Storage

More information

ISpac isolators. the perfect system

ISpac isolators. the perfect system ISpac isolators the perfect system 2 safe isolation Handling flammable and potentially explosive substances is part and parcel of everyday operations in many branches of industry. However, it is not possible

More information

G 521 GAS DETECTOR WITH REMOTE SENSOR. RFG 361 C1 Eng. COSTER. G RFG 361 C1 Eng MZ Rev. 02

G 521 GAS DETECTOR WITH REMOTE SENSOR. RFG 361 C1 Eng. COSTER. G RFG 361 C1 Eng MZ Rev. 02 GAS DETECTOR WITH REMOTE SENSOR G 521 - RFG 361 C1 Eng. 25.11.08 MZ Rev. 02 G 521 25.11.08 MZ Rev. 02 RFG 361 C1 Eng. Remote sensor for detecting methane, propane-lpg, carbon monoxide (CO) Sensors with

More information

Process Alarm Solutions

Process Alarm Solutions Process Alarm Solutions Reliable Supervision and Control www.selco.com SELCO flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring of electrical

More information

LED-WAV-50W. User Manual Please read the instructions carefully before use

LED-WAV-50W. User Manual Please read the instructions carefully before use LED-WAV-50W User Manual Please read the instructions carefully before use 1A TABLE OF CONTENTS 1. Safety Introductions 1. Safety Instructions WARNING Please read the instructions carefully which includes

More information

Intelligent GSM Auto-Dial Alarm System

Intelligent GSM Auto-Dial Alarm System Auto-dial Alarm System Intelligent GSM Auto-Dial Alarm System Profile For a better understanding of this product, please read this user manual thoroughly before using it. 2013.2.V1.0 Auto-dial Alarm System

More information

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC HOJA TÉCNICA 1400H101 Edición 01 (02 de 08) www.ako.es GENERAL TECHNICAL SPECIFICATIONS Temperature range: -50ºC to +99ºC type: NTC Total accuracy ( + controller): ±1ºC lead extension with cable AKO-15586:

More information

Advanced Fencing and Security Technologies Ltd

Advanced Fencing and Security Technologies Ltd G.M. Advanced Fencing and Security Technologies Ltd P.O. Box 2327 Kfar Sava Industrial Area 44425, Israel Tel +972-9-7662965 Fax + 972-9-7662964 E-mail: info@gmsecurity.com Website: www.gmsecurity.com

More information

GSM ALARM SYSTEM USER MANUAL

GSM ALARM SYSTEM USER MANUAL GSM ALARM SYSTEM USER MANUAL 1. Instruction The alarm system is based on GSM network. With a GSM SIM card, it can be used wherever you want and no need to connect any wire, which is convenient and easy

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information

DELUGE. User Manual Please read the instructions carefully before use. Innovation, Quality, Performance LED-WAV-50W

DELUGE. User Manual Please read the instructions carefully before use. Innovation, Quality, Performance LED-WAV-50W DELUGE LED-WAV-50W Innovation, Quality, Performance User Manual Please read the instructions carefully before use particularly dirty surrounding can cause greater accumulation of dirt on the fixture s

More information

1 Zener barriers - operating instructions. Operating principle. 1.1 Operating principle

1 Zener barriers - operating instructions. Operating principle. 1.1 Operating principle Operating principle Zener barriers - operating instructions Application Zener barriers are used in control and instrumentation systems for the processing of standardised signals, such as 0 ma and 0 V.

More information

API Marine. BMS Presentation. Ballast Measurement Systems

API Marine. BMS Presentation. Ballast Measurement Systems API Marine BMS Presentation Ballast Measurement Systems BMS4 Typical Configuration BMS4 Typical Configuration BMS4 Extended Configuration BMS4 System (24 tanks) Air regulator Terminal block Drain/Air Filter

More information

Business/Home GSM. Alarm System(III) Installation and Users guide

Business/Home GSM. Alarm System(III) Installation and Users guide Business/Home GSM Alarm System(III) Installation and Users guide I. General information: GSM 900/1800/1900 bands, can be used all over the world. Full duplex communication with the base. Monitor environment

More information

Automation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction 1. 2. Software Installation 2

Automation and Systems Technology. LABCONTROL TFM/TPM User Manual TroxMConnect Operating Software. 1. Introduction 1. 2. Software Installation 2 1. Introduction 1 2. Software Installation 2 2.1 System Requirements 2 2.2 TroxMConnect Installation 2 2.3 Connection to the PC 3 3. TroxMConnect Description 4 3.1 Starting the Software 4 3.2 Layout 4

More information

ACTIVE 5 ENGINEERING MANUAL

ACTIVE 5 ENGINEERING MANUAL ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features

More information

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS WG2 Dimensions: LxHXW: 26 x 14.5 x 29.5 cm INTERNAL Alarm Terminals EXTERNAL Alarm Terminals WG2 Control Unit WaterGuard

More information

VAPORIX The Automatic Monitoring System for Active Vapour Recovery

VAPORIX The Automatic Monitoring System for Active Vapour Recovery VAPORIX The Automatic Monitoring System for Active Vapour Recovery SECON VAPORIX-Control VAPORIX-Flow Sensors & Systems Worldwide: FAFNIR GmbH: Innovation with Tradition. Quality and Satisfaction made

More information

FRE207. User s Manual. Dual Slope

FRE207. User s Manual. Dual Slope Dual Slope Laser Level Contents Equipment included in your FRE207 Settop 3 Exterior composition of the FRE207 Settop 4 Battery Charger 5 Instructions 6 Detector 8 Specifications 9 Safety Precautions 10

More information