1 UNIVERSITY OF ALABAMA AT BIRMINGHAM DEPARTMENT OF FACILITIES PLANNING FACiliTIES STANDARD NAME: Fire Alarm and Detection PURPOSE: 1. The general purpose of each FacilitiesStandard is to provide minimalcriteriafor construction materials at Universityfacilities regarding code compliance, warranty, approved products, execution, and uniformity. 2. To protect the health and safety of patients, visitors,students, faculty,and staff, in addition to protecting non-project UABproperty, all construction must be in accordance with NFPA 241 safeguarding construction, alteration, and demolition operations; Standard Building Code, Chapter 33, regarding site work,demolition,and construction;nfpa 101 Ufe Safety Code, and NFPA72 NationalFireAlarmCode. 3. Constructionsafety is the responsibilityof the contractor in accordance withthe regulations and codes of the agency havingjurisdiction,and accordingto the guidelinesadapted by OSHA. 4. The Fire Alann and Detection Facilities Standard establishes a series of guidelines for specifying this particular item on any construction project at the University.This Facilities Standard is not to be regarded as a specification. GENERAL: 1. The Architect/Engineershall identifythe applicable Fire AlarmCodes for each designated area withinthe project. 2. Fire alarm documents shall not be included with the architectural package submittal; these documents must be submitted directlyto the FireSafety Plans Examiner,Cityof Birminghamby the Engineer. Shop drawings must be submittedto the Cityby the FireAlarmVendor. 3. Drawings submitted for review must include room names and numbers, device zones if nonaddressable, and device locations. 4. Shop drawings submitted by the contractor must comply with City of Birminghampublication, "MinimumRequirements for Plan Submittalfor FireSafety Permits". 5. The design, construction,or alteration of fire alarm and detection systems shall conformto the Americanswith DisabilitiesAct(ADA),and other appropriate Codes or Standards. 6. A fire alarm system must be operational in patient care areas at all times. Refer to UAB FacilitiesStandard #16722, ''TemporaryFireAlarm - Hospital". DEVELOPEDBYANDINTENDEDFORUABUSEONLY PAGENO

2 7. The control panel shall be solid-state, modular, microprocessor based, U.L. listed, field programmable, a current model, with English language or LEDdisplays, keyed the same as devices, withclass Bwiringsupervision. 8. The use of "hard-wired"system technology is acceptable ifthe system is eight (8)zones or less, has fewer than 20 indicatingdevices, or has fewer than 50 smoke detectors. 9. The system shall be designed using "addressable" system technology with analog devices or sensors if the system exceeds eight (8) zones, has more than 20 indicatingdevices, has more than 50 smoke detectors, requires "cross-zoning",or complies with the "High-Rise"code. Such buildings shall be provided with an emergency voice/alarm communications system with automatic or manual voice capabilityto provide voice instructionsto the occupants in the event of a fire, tornado, or other alerts. Refer to Section 12 on the next page. The communication format between the control panel and analog devices may be either analog or digital. Digital communicationshould be considered in retrofitprojects where the existing non-shielded wires may be reused ifelectricallysound. 10. HospitalBuildingfire alarm systems shall be connected to the existing ProprietarySupervising FireAlarmStation (Simplex4120 NElWORK &2120 MultiplexSystem) located in the UABCall Center, Second Floor, Lyons-HarrisonResearch Building.The Proprietary Supervising Fire Alarm Station personnel willin tum notifythe City Fire Department and the UABPolice. Use addressable technology and analog devices. The Hospitalis in the process of upgrading the existing system to a Simplex4120 peer-to-peer distributedcontrolsystem and network.a copy of the constructiondocuments should be obtained priorto commencement of design so that the project requirements can be integrated into the existingsystems. NorthPavilionhas a separate Edwards system. Only chimes shall be specified as audio alarming appliances for Hospital patient care areas. 11. For Non-HospitalBuildings,stand-alone type systems shall be used, with trouble and alarm annunciation being transmitted to the UAB Police Telecommunications Center (Proprietary Supervising Station) by way of the UABPhysicalSecurity Unifs Cardkey Security Management System. The ProprietarySupervising FireAlarmStation personnel willin turn notifythe CityFire Department System must providea separate dry contact that is dosed in the normalstate, and open in alarm state, for both trouble and alarm. In addition,ifa buildinghas doors controlledby the Cardkey Access ControlSystem, a separate set of dry contacts (one for alarm and one for trouble, dosed in normalstate, open in alarm state) must be providedto interrupt12v DC at no more than 5 amps, to ensure that buildingwillbe unlockedduringa firealarm. Buildingsthat do not have connection to the UABCardkey Security Management System, the fire alarm panel shall indude a dual-line dialer or digital alarm communication terminal (D.A.C.T.)with the followingprotocol,for connection by way of two digitalcommunicationlines per Code: Osborne HoffmanQuickAlert I Digitalreceiver, transmission format of Hertz, Handshake, 1800 Hertz Data, 20 Baud (DCI, FBII, Franklin, Osbome Hoffman, Sescoa, Varitech,and Vertex, Fast Format).Reportingcodes transmittedby the firealarm panel must be in accordance with the UABPhysical Security Unifs requirements, which are available upon request. 12. Ifno PublicAddress System exists withina building,speakers shall be provided so that digital pre-recorded alarm messages, such as tornado alerts, can be heard throughout the building. DEVELOPED BY AND INTENDED FOR UAB USE ONLY PAGE NO

3 12. If no Public Address System exists within a building, speakers shall be provided so that digital pre-recorded alarm messages, such as tornado alerts, can be heard throughout the building. Neither horns nor chimes are acceptable. UAB Physical Security Unit will initiate the messages by contact closure(s) via the Cardkey Security Management System. One (1) Belden #8723 cable shall be provided for each contact closure. Refer to Facilities Standard 16723, "Security Management System". 13. The Architect/Engineer shall specify a voice/alarm communication system for High Rise Buildings, as well as a two-way telephone communicationservicefor firefighters' use. 14. Manual stations shall be double action, U.L.listed,and keyed the same as the control panel. 15. Ceiling smoke detectors shall be photoelectric,u.l. listed to Standard 268, F.M. approved, EMI & RFI shielded,and shall have alarm LED with functional test switch. 16. Duct detectors shall be photoelectric,u.l. listed, F.M. approved, with auxiliary relay and remote alarm indicator if not addressable. Detector shall be connected directly to fire alarm panels. Connection via HVAC control panels is not acceptable. 17. Heat detectors shall be fixed or fixed rate of rise, U.L. listed, visible trip, non-restorable. The Engineershall consider intelligentmulti-sensordetectors(ionization,photoelectric,and heat). 18. Horns shall be electronic, multiple tone, temporal coded (from control panel or at horn), with audibility levels complyingwithamericanswith DisabilitiesAct Guidelines. 19. Chimes shall be electronic, U.L. listed, single-stroke with audibility levels complying with AmericanswithDisabilitiesAct Guidelines. 20. Visual units shall be U.L listed with candela levels complying with Americans with Disabilities Act Guidelines. CombinationvisuaVaudibleunits may be used. 21. Door holders shall be wall- or floor-mountedwith ceiling-mountedsmoke detectors as required by Code. Combinationsmoke detector/doorcloser units shall not be used. 22. All items of the Fire Alarm System shall be listed as a product of a single fire alarm system manufacturer under the appropriate Underwriters Laboratories, inc. category. The Architect/ Engineer shall state in his Specificationfor new systemsthat the FireAlarm vendor shall furnish UAB on disk with the operating system software information pertaining to maintenance and operation of the system. Also, operation and maintenance manuals shall be furnished at substantial completiontime, prior to closeouttime. 23. Equipment suppliers shall be authorized factory service representatives and shall maintain offices and service facilities withfactorytrained personnelwithin25 miles of the site and provide service within 24 hours. DEVELOPEDBY AND INTENDEDFOR UAB USE ONLY NOT FOROUTSIDE DISTRIBUTION PAGE NO

4 PRODUCTS: 1. Acceptable manufacturers: a) SimplexTime Recorder Company b) Gamewell c) CerberusiPyrotronicsDivisionof Siemens BuildingTechnologies d) Edwards Technology e) NotifierFire Divisionof Honeywell,Inc. EXECUTION: Edwards systems shall be 100% Edwards. HybridEdwards/Siemens-Landis systems are not acceptable. As additions are made to existing systems, those additions shall be provided from the same manufacturer's products as the original installation so that a system Certificationmay be secured according to Codes. 1. Allfire alarm devices shall be circuitedon the floorplans, with conduit and wiringshown based on one vendor's equipment Wiringdrawings shall be revised to incorporatethe actual vendor and equipment purchased. 2. Allwiringshall be in conduit. 3. Allwiringshall be color-coded,withwire numbers at terminations. 4. Allwiringsplices shall be on identifiedterminal strips. Only pressure-type connectors shall be used when attaching stranded wires to terminals. 5. Terminalcabinets, complete withidentifiedterminalstrips, shall be provided. 6. Engraved nameplates shall be provided for description of zones on control panel and remote annunciators, ifapplicable. 7. Shop drawings shall be furnished identifyingall hardware providedwithinthe panels, and wiring connection between controlpanels, terminalstrips, and devices. 8. All components, circuits, system operation, or software functions known to be affected by a software change shall be 100% tested. In addition, 10% of initiatingdevices that are not directly affected by the change, up to a maximumof 50 devices, shall also be tested to verifyproper system operations. NOTE: So that this testing willnot be duplicated in a concurrent project, Hospitalor Campus Maintenance should be consulted before induding in specifications. DEVELOPED BY AND INTENDED FOR UAB USE ONLY PAGE NO

5 A list of buildings with systems connected to the Hospital fire alann system is as follows: Spain Wallace Building Jefferson Tower North Wing West Pavilion Medical Education Building Spain Rehabilitation Addition Civitan Building General Services Building Spain Rehabilitation Center Boshell Building Quarterback Tower/Jefferson Call Center in LHRB Psychiatric Hospital Tower All installation and initial acceptance testing shall be done per NFPA 72 requirements. The contractor shall provide certification in writing with doseout documents that the fire alann system has been installed, the detectors deaned, calibrated, and tested, and that the system functions as intended by the drawings and specifications. The fonn shown in National Fire Alann Code (NFPA 72) shall be used and submittedwith the certificate. 9. Existingsingle station or stand-alone smoke detectors in Student Housingbuildingsthat are UL listed for "Residential" use shall be replaced after 10 years by units listed in "CommerciallResidential" as per NFPA 72. If they are UL listed for "CommerciallResidential" use, no replacement is required. 10. The contractor shall have a fire alann representativepresent at the fire alann system orientation and Fire Marshall Acceptance testing. The contractor shall have the fire alann company verify the suitability of adding new devices to existing circuits and/or panel, and shall provide the necessary additionalhardware and battery calculations. 11. For fire alann system shutdown, UAB Maintenance must be notified 24 hours in advance, in writing, for shutdowns during nonnal working hours, and 72 hours in advance for shutdowns during weekends, holidays, and times other than nonnal working hours. END OF STANDARD Prepared and RE!'Jised by: Reviewed and Recommended by: Approved by. DEVELOPEDBY AND INTENDEDFOR UAB USE ONLY NOT FOROUTSIDE DISTRIBUTION PAGENO

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

New and Existing Fire Alarm & Signaling Systems

New and Existing Fire Alarm & Signaling Systems ORANGE COUNTY FIRE AUTHORITY Planning & Development Services Section 1 Fire Authority Road, Building A, Irvine, CA 92602 714-573-6100 www.ocfa.org New and Existing Fire Alarm & Signaling Systems Guideline

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

Fire Alarm Systems Permit Packet. City of Greer Fire Department

Fire Alarm Systems Permit Packet. City of Greer Fire Department Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

JULY 2013 UCB STANDARDS 16720-1

JULY 2013 UCB STANDARDS 16720-1 SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying

More information

A. This Standard outlines the requirements for an addressable fire detection and alarm system.

A. This Standard outlines the requirements for an addressable fire detection and alarm system. 1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

FIRE ALARM APPLICATION

FIRE ALARM APPLICATION FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:

More information

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification

The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification The Pennsylvania State University ------------- Physical Security Office Intrusion Alarm Performance Specification By PHYSICAL SECURITY OFFICE Group (Access Controls & Electronic Security Programs) and

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

B. NICET: National Institute for Certification in Engineering Technologies.

B. NICET: National Institute for Certification in Engineering Technologies. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00 SECTION 28 31 00 FIRE DETECTION AND ALARM GENERAL This section deals with the fire alarm system, including the control panel and integral equipment, wiring and circuitry, initiating devices, indicating

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

FIRE ALARM AND VOICE COMMUNICATION SYSTEM Request for Qualifications

FIRE ALARM AND VOICE COMMUNICATION SYSTEM Request for Qualifications FIRE ALARM AND VOICE COMMUNICATION SYSTEM Request for Qualifications Proposal Request Joliet Junior College, Illinois Community College District 525 (JJC) is soliciting proposals from vendors for a fire

More information

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011 Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

Faraday Intelligent Fire Detection Systems

Faraday Intelligent Fire Detection Systems Faraday Intelligent Fire Detection Systems Faster detection means better protection for buildings and the people in them. Greater safety and value for new and retrofit applications The right fit Fire safety

More information

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.

More information

City of Columbus Department of Building and Zoning Services

City of Columbus Department of Building and Zoning Services City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning

More information

v 1.42b Conceal-Alarm Information Packet for Fire Alarm System Contractors & Installers Conceal -Alarm

v 1.42b Conceal-Alarm Information Packet for Fire Alarm System Contractors & Installers Conceal -Alarm v 1.42b Conceal-Alarm Information Packet for Fire Alarm System Contractors & Installers Conceal -Alarm Quick Reference Sheet Important Items to Understand > The Conceal-Alarm series product family is compatible

More information

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm

More information

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.

More information

Mobile Fire Rescue Department Bureau of Fire Prevention

Mobile Fire Rescue Department Bureau of Fire Prevention 222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

BASIC FIRE ALARM TRAINING

BASIC FIRE ALARM TRAINING BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate

More information

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14 City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire

More information

COMMISSIONING OF FIRE ALARM SYSTEMS

COMMISSIONING OF FIRE ALARM SYSTEMS COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference

More information

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 1.1 To acquire an installation

More information

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the

More information

NATIONAL FIRE ALARM AND SIGNALING CODE

NATIONAL FIRE ALARM AND SIGNALING CODE GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Fire Alarm Systems Certification

Fire Alarm Systems Certification Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation

More information

Alarm Systems Chapter 2.5

Alarm Systems Chapter 2.5 Alarm Systems Chapter 2.5 Section 2.5-1 Short Title This chapter shall be known and may be cited as an Ordinance Regulating Burglar, Holdup, and Fire Alarm Systems and Users. (Ord. of 2-1-82, 1) Section

More information

FIRE MARSHAL BULLETIN

FIRE MARSHAL BULLETIN NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.

More information

Fire Alarm Submittal Requirements and Acceptance Testing

Fire Alarm Submittal Requirements and Acceptance Testing Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Alarm Submittal Requirements and Acceptance Testing To all Registered

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification

More information

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458 OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal fireprevention@islipny.gov Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus

More information

UBC Technical Guidelines Section 17900 2015 Edition Secure Access: General Standards Page 1 of 7

UBC Technical Guidelines Section 17900 2015 Edition Secure Access: General Standards Page 1 of 7 Page 1 of 7 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 17910, 17920 and 17930.2 Section 17100 Cable Infrastructure Overview, sub sections 1.4.9 and 1.5.3 Section 17110 Communication Rooms, sub section

More information

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

2012 Ontario Building Code Changes Affecting Fire Alarm Systems 2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

Effective June 27, 2015. TEXT (CO Detection Commercial Buildings)

Effective June 27, 2015. TEXT (CO Detection Commercial Buildings) TEXT (CO Detection Commercial Buildings) Part 1228 of Title 19 NYCRR is amended by adding a new section 1228.4, to read as follows: Section 1228.4. Carbon Monoxide Detection in Commercial Buildings (a)

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Communication

More information

PROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA Fire alarm--all types of occupancies. The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

Prepared For: Prepared By: [INSERT DATE]

Prepared For: Prepared By: [INSERT DATE] STANDARD SPECIFICATIONS FOR THE DESIGN AND INSTALLATION OF AUTOMATIC FIRE ALARM SYSTEMS THE UNIVERSITY OF ALABAMA TUSCALOOSA, ALABAMA [INSERT PROJECT NUMBER] [INSERT PROJECT NAME] Prepared For: University

More information

A. 70 National Electrical Code (NEC). B. 72 National Fire Alarm Code. C. 90A Installation of Air Conditioning and Ventilating systems.

A. 70 National Electrical Code (NEC). B. 72 National Fire Alarm Code. C. 90A Installation of Air Conditioning and Ventilating systems. SECTION 280513 % FIRE ALARM SYSTEM 1.0 This section is intended to define the general configuration, layout, installation and testing re quirements for the various fire alarm systems at the University

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work

More information