1 EB Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment life and ensure employee and public safety. Preventive Maintenance represents the work required to enable THESL s distribution assets to function as specified and to promote continued reliable system performance. This work entails the inspection and overhaul of distribution assets, and replacement of specific components at fixed intervals. Preventive Maintenance is described in this tab, and its program requirements are prescribed in THESL s annual Plant Maintenance Manual. Preventive Maintenance is derived from RCM II, which is designed to determine the optimal maintenance tasks for the assets within their operating context. Optimal in this sense means the least costly maintenance tasks that satisfy reliability, safety and environmental requirements. As all preventive maintenance programs are derived from RCM analyses, each program represents the most cost-effective alternative for maintaining a specific class of assets. A more frequent maintenance cycle would lead to over-maintaining of assets, and could actually induce failures; a less frequent cycle would lead to more costly failures over time and over the population of the asset. 0 DISCUSSION Distribution assets and their components are subject to deterioration and failure over time. Appropriate maintenance practices increases the probability that assets will continue to operate as expected over their expected lives and help protect against major equipment failures and associated reliability problems. Maintenance programs are designed to reflect the fact that asset integrity is influenced by factors such as condition, design, location, age and equipment utilization. Asset deterioration usually manifests itself as a decline in equipment performance, which can negatively impact supply to customers.

2 EB Filed: 00 Aug Page of THESL maintenance crews are responsible for carrying out, capturing data on and reporting back on various Preventive Maintenance activities as outlined in THESL s Plant Maintenance Manual. The following paragraphs discuss some of the types of equipment and activities that are addressed under preventative maintenance. A comprehensive explanation of all activities is contained in the Plant Maintenance Manual. Overhead/Underground Distribution Compact Radial Vaults are inspected twice a year and an inspection checklist is completed to identify any deficiencies. A thermograph is taken of all elbows to identify hot spots and is reported on the checklist. A determination is made as to whether these vaults require power washing and, if so, arrangements are made to schedule this activity. 0 Network Protectors are overhauled every three years for those with 0/0V supply and every five years for those with 0/V supply (the differing maintenance frequencies are due to different mean times between failures for the failure modes assessed during the RCM analysis for each protector type). A checklist is completed to verify that the protector was cleaned, relays were replaced, and a function test is performed to verify that loads are picked up automatically. Finally, a protector card is signed and placed on the front door of the protector to clearly identify completion of the maintenance. Three-Phase Gang-Operated Switches are maintained every three years to ensure safe and reliable operation during routine and emergency switching. A Certified Power Lineperson completes a checklist identifying the physical and mechanical condition and verifies the correct blade alignment, blade penetration, travel stops and arc interrupter operation. The switches are then lubricated for efficient operation. Asbestos inspection is performed to identify areas of the plant that contain material that is considered harmful if it becomes friable. THESL is committed to the prevention of illness

3 EB Filed: 00 Aug Page of and injury through the provision and maintenance of healthy and safe working conditions on its premises and due diligence in its inspection activities. THESL endeavors to provide a hazard-free environment and to minimize risks by adherence to all relevant legislation, and where appropriate, through the development and implementation of additional internal standards, programs and procedures. The asbestos inspection is mainly to re-examine high risk locations for the presence of friable asbestos and record the findings for future followup work. When friable asbestos is discovered the work is issued to a contractor for immediate removal. All non-friable asbestos locations are recorded for future removal. The network inspection and maintenance program is typically performed in two stages. Initially, inspection and documenting of deficiencies is conducted. Any minor deficiencies are usually repaired during this inspection. Major deficiencies are documented in the Inspection Report for follow-up repairs in the same year as the inspection. Critical deficiencies that pose a safety hazard or impact system reliability are corrected as soon as possible. 0 Stations THESL Substations use several different types of Circuit Breakers such as Magnetic Air, Air Blast, Vacuum, Sulfur-hexaflouride ( SF ), and Oil. Maintenance cycles vary from three to eight years depending on the type of breaker that each substation contains. These units are inspected for leaks, and tests are performed to ensure that they are functioning properly in order to maintain a reliable flow of power to downstream customers. Carbon dioxide ( CO ) and FM00 (Waterless Fire Protection) fire protection inspections are performed every six months to ensure that the intended functions are maintained, and items such as alarms, sensors, and manual electric dischargers are all operating properly.

4 EB Filed: 00 Aug Page of Power transformer and Primary Load Break Switches ( LBSs ) are used to supply the primary load of a power transformer at Municipal Stations with capacity less than MVA or at customers locations. On the. kv system some LBSs are installed in outdoor enclosures while others are installed in exposed structures. At a customer location, LBSs can be. kv,. kv or kv Load Interrupter Switches ( LISs ). The work to maintain these devices includes cleaning insulators, contacts and gears; checking alignment; and performing operational tests. Stations are another location where friable asbestos can be found. Stations are inspected to identify and record high-risk locations for future follow-up work. 0 External Contracts As is detailed in Exhibit C, Tab, THESL engages a number of external agencies to perform preventive maintenance tasks for several programs. External contractors are engaged to provide these services due to the seasonal nature of the work, and the specialized expertise and equipment required. As an example, insulator washing is required for only two, six-week periods each year. Equipping a THESL crew with a wash truck that only operates twelve weeks per year is not cost-effective because the truck will remain idle for the remaining 0 weeks of the year. As a second example, external forestry contractors are hired for their expertise and experience in tree-trimming services. Until now the tree-trimming (forestry) program followed a three-year pruning cycle to trim trees in close proximity to overhead lines. This program is aimed at improving reliability by reducing forced outages caused by tree contact. Analysing feeder reliability data for tree contacts in previous years determines the pruning cycle. The feeders having the poorest reliability due to vegetation contacts were given the highest priority for trimming. In 00, THESL engaged the services of Davies Consulting Inc. to develop a more sophisticated tree trimming model. This model was delivered in June 00 and is being used to obtain market

5 EB Filed: 00 Aug Page of pricing and terms for tree trimming work in the years 00 and beyond. This new tree trimming model is designed to optimize the trimming cycle for each individual feeder. The washing of porcelain insulators on. kv overhead line poles takes place in areas where insulators experience extraordinary contamination. Regular pressure washing every six months is performed using clean water to remove contaminants that accumulate over time. Dirt, salt and hydrocarbon deposits, when combined with moisture, reduce insulation levels across line insulators and lead to current leakage (tracking) which can increase over time. This contamination can overcome the minimum insulation requirement of the insulator and lead to a flash-over. This insulation failure will trip the upstream protective device and cause a forced outage, which ultimately affects reliability. 0 CO cleaning of pad-mounted switchgear reduces the risk of tracking and, ultimately, switch failure. Switches that are found to be dirty can be cleaned while still energized using CO pellets. Carbon Dioxide is blasted against the switches, releasing the dirt, cleaning the switch, and then evaporating into the atmosphere. Pressure washing and vacuuming out submersible (underground) transformer vaults keep drains from plugging and prevent exposure of transformers to water, salt, contaminants and other debris. This allows transformers to cool properly and prevents premature rusting. Table : 00 to 0 Preventive Maintenance Cost ($ Millions) Preventive Maintenance Costs 00 Historical 00Bridge 00Test 00Test 0Test OH/UG Distribution Assets..... Stations Assets External Contracts Total Preventive Maintenance * Columns may not total due to rounding

6 EB Filed: 00 Aug Page of The total preventive maintenance program cost increased by $. M from 00 to 00. This increase is primarily attributable to the addition of a one-time, asbestos audit program and a more aggressive vegetation management program. The asbestos audit accounted for about $00,000 of the increased costs from 00 to 00. The Ministry of Labour imposed the asbestos audit program requirement to identify and document all sources of friable asbestos within THESL facilities by the end of 00. From 00 to 00, external contract costs increased by about $. M primarily due to increased vegetation management program costs. This cost addresses increased tree-related outages, which are described in additional detail at Exhibit B, Tab, Schedule. Going forward, the new tree trimming model is expected to optimize the trimming program resulting in reliability improvement due to reduced tree-related outages while maintaining annual spending. The Preventive Maintenance program is expected to remain constant though out the test years The cost increases shown in Table are primarily due to the expected inflation for internal labour, vehicles and materials. External contractor costs are expected to follow inflationary trends throughout the period.

SIEMENS Transmission and Distribution

SIEMENS Transmission and Distribution TITLE Long Term Maintenance and Care for S36A E. C. Wright 02/09/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 635. Its aim is to provide guidance

More information

ICM Project Station Infrastructure and Equipment

ICM Project Station Infrastructure and Equipment EB 0 00 Schedule B. ( pages) ICM Project Station Infrastructure and Equipment (THESL) EB 0 00 Schedule B. I EXECUTIVE SUMMARY 0. Project Description Many Municipal Substations (MS) located outside of downtown

More information

Trimming Trees Near Electric Lines. Understanding Niagara Mohawk s Role and Responsibilities

Trimming Trees Near Electric Lines. Understanding Niagara Mohawk s Role and Responsibilities Trimming Trees Near Electric Lines Understanding Niagara Mohawk s Role and Responsibilities Staying Connected If you ve called Niagara Mohawk with a tree-trimming request, you know we ask a lot of questions.

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

Pennsylvania Summer Reliability

Pennsylvania Summer Reliability A. Reliability Enhancement Programs In 2015, Pennsylvania Power Company s ( Penn Power or Company ) reliability plan incorporates projects and programs to enhance overall reliability. The plan is structured

More information

OH&S Management Systems Audit Checklist (NAT, E3)

OH&S Management Systems Audit Checklist (NAT, E3) 3.1.2 3.1.1 Introduction OH&S Management Systems Audit Checklist (NAT, E3) This audit checklist is based on Element 3 (Implementation) of the National Self-Insurers OHS Audit Tool. For a full copy of the

More information

GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT

GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT GUIDELINES FOR HANDLING WATER-DAMAGED ELECTRICAL EQUIPMENT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 1300 NORTH 17 TH STREET, SUITE 1752 ROSSLYN, VIRGINIA 22209 703 841-3200 703 841-5900 FAX WWW.NEMA.ORG

More information

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES 1. Acceptance of Electricity Service By establishing or requesting a POD or by continuing an

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

Vegetation Management Frequently Asked Questions

Vegetation Management Frequently Asked Questions Vegetation Management Frequently Asked Questions Q. Why does AEP Ohio clear vegetation away from power lines? A. AEP Ohio s goal is to provide safe, dependable electric service to its customers. Line clearance

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been

More information

Oncor Storm Restoration Questions/Answers

Oncor Storm Restoration Questions/Answers Oncor Storm Restoration Questions/Answers Oncor understands that electricity is an essential service to today s businesses and homes, and loss of power places a significant burden on everyone. Oncor performs

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services

CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services CONNECTING YOU TO SPECIALIST ELECTRICAL SUPPORT services SpecialistS IN ELECTRICAL SUPPORT SERVICES TO MINING, UTILITIES & industry Ampcontrol is committed to supporting our customers to maintain efficient

More information

GROUNDS MAINTENANCE-WATER USE DFC Environmental Management System

GROUNDS MAINTENANCE-WATER USE DFC Environmental Management System 1.0 Purpose To reduce the amount of water applied to the DFC Grounds in order to conserve water. 2.0 Activity/Department The On-site Landscape Contractor GSA Team 6 3.0 Forms Used Contractor s Daily Quality

More information

National Transportation Safety Board Washington, DC 20594

National Transportation Safety Board Washington, DC 20594 National Transportation Safety Board Washington, DC 20594 Safety Recommendation Mr. Jack Requa Interim General Manager and Chief Executive Officer Washington Metropolitan Area Transit Authority 600 5th

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

ICM Project Underground Infrastructure and Cable

ICM Project Underground Infrastructure and Cable EB 0 00 Tab Schedule B ( pages) ICM Project Underground Infrastructure and Cable Handwell Replacement Segment (THESL) EB 0 00 Tab Schedule B I EXECUTIVE SUMMARY. Project Description 0 The handwell replacement

More information

Vision 2050 An Asset Management Strategy. Jaclyn Cantler Manager, Transmission Planning, PHI

Vision 2050 An Asset Management Strategy. Jaclyn Cantler Manager, Transmission Planning, PHI 1 Vision 2050 An Asset Management Strategy Jaclyn Cantler Manager, Transmission Planning, PHI 2 Agenda Case for Change About Vision 2050 Status Closing System Design Cybersecurity Interface with distributed/dispersed

More information

Litigation Services & Information

Litigation Services & Information Litigation Services & Information Laurence "Lo" Lehman, P.E. Lehman Engineering Company Lehman Engineering has been providing engineering, design, and consulting services for electrical power systems to

More information

BC Hydro will submit its further report by September 16, 2008 as requested in the BCUC's letter of July 21, 2008.

BC Hydro will submit its further report by September 16, 2008 as requested in the BCUC's letter of July 21, 2008. BChydro Joanna Sofield Chief Regulatory Officer Phone: (604) 623-4046 Fax: (604) 623-4407 regulatory.group@bchydro.com August 5,2008 Ms. Erica M. Hamilton Commission Secretary British Columbia Utilities

More information

2014 ELECTRIC SYSTEM RELIABILITY REPORT CITY OF ANAHEIM PUBLIC UTILITIES DEPARTMENT

2014 ELECTRIC SYSTEM RELIABILITY REPORT CITY OF ANAHEIM PUBLIC UTILITIES DEPARTMENT 2014 ELECTRIC SYSTEM RELIABILITY REPORT CITY OF ANAHEIM PUBLIC UTILITIES DEPARTMENT Contents Overview... 3 1.0 Electric System Reliability... 4 1.1 Annual Reliability Data with Utility Comparisons... 4

More information

Evaluating Fire- and Heat-Damaged Electrical Equipment

Evaluating Fire- and Heat-Damaged Electrical Equipment Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat

More information

INSPECTION AND TESTING OF EMERGENCY GENERATORS

INSPECTION AND TESTING OF EMERGENCY GENERATORS INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,

More information

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your

More information

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016 RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.

More information

BUSINESS POLICY ELECTRIC SERVICE PRACTICES SP 1.1 INTRODUCTION

BUSINESS POLICY ELECTRIC SERVICE PRACTICES SP 1.1 INTRODUCTION ELECTRIC SERVICE PRACTICES SP 1.1 INTRODUCTION The Saskatchewan Power Corporation (SaskPower) exists to provide electrical power to its customers. SaskPower's service area extends into most parts of Saskatchewan

More information

Safety Checklist. Apartment buildings and condominiums. AvivaCanada.com/risks

Safety Checklist. Apartment buildings and condominiums. AvivaCanada.com/risks Apartment buildings and condominiums You work hard to maintain your properties. That s why it s important to ensure you re protected from all potential losses especially when they re avoidable. Apartment

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

Storm Ready. 3 Gulf Power Ready for the storm. 4 Be prepared, be safe. 5 Getting the lights back on. 6 Damage to your home s service connection

Storm Ready. 3 Gulf Power Ready for the storm. 4 Be prepared, be safe. 5 Getting the lights back on. 6 Damage to your home s service connection Storm Ready Prep and Safety Power Restoration Your Service Connection Generator Safety Power Outage Map Stay Connected with Gulf Power Storm Ready 3 Gulf Power Ready for the storm 4 Be prepared, be safe

More information

Keeping electrical switchgear safe

Keeping electrical switchgear safe Keeping electrical switchgear safe Keeping electrical switchgear safe Health and Safety Failure of electrical switchgear can cause death, serious injury and major damage. If you own or operate this type

More information

Commercial Roof Management

Commercial Roof Management Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading

More information

contractors, etc. and establish relationships with lease and rental companies.

contractors, etc. and establish relationships with lease and rental companies. The following may serve as a checklist when preparing for a Tropical Storm or Hurricane. Although Tornadoes usually provide little advance warning, locations subject to Tornadoes may apply much of the

More information

ABB Australia Pty Limited. SF 6 gas management solutions Managing SF6 in switchgear installations

ABB Australia Pty Limited. SF 6 gas management solutions Managing SF6 in switchgear installations ABB Australia Pty Limited SF 6 gas management solutions Managing SF6 in switchgear installations A complete SF6 gas management solution, in an efficient and environmentally friendly manner. 2 Power products

More information

Welcome. Xcel Energy. Home. Contact Information. Tear off this portion. Keep for future reference. Customer Service. 24-hour Emergency Hotlines

Welcome. Xcel Energy. Home. Contact Information. Tear off this portion. Keep for future reference. Customer Service. 24-hour Emergency Hotlines Xcel Energy Contact Information Tear off this portion. Keep for future reference. Welcome Home Customer Service --- -hour Emergency Hotlines Electric Emergency/Lights Out --- Gas Emergency/Gas Odor ---

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

Q. Why does OG&E clear vegetation away from power lines? A. Trees that grow into power lines can cause problems in multiple ways:

Q. Why does OG&E clear vegetation away from power lines? A. Trees that grow into power lines can cause problems in multiple ways: Q. Why does OG&E clear vegetation away from power lines? A. Trees that grow into power lines can cause problems in multiple ways: Outages Tree limbs contacting power lines are one of the most common causes

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

Backup Fuel Oil System Decommissioning & Restoration Plan

Backup Fuel Oil System Decommissioning & Restoration Plan Backup Fuel Oil System Page 1 of 19 Overview of Physical Fuel Oil System and Decommissioning Steps The fuel oil system at Milford Power consists of a number of subsystems. These include the following:

More information

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks

More information

Inspections Standard Operating Procedure 5 Aboveground Storage Tanks

Inspections Standard Operating Procedure 5 Aboveground Storage Tanks Aboveground Storage Tanks Aboveground Storage Tank Inspection This Standard Operating Procedure describes the steps that campus units that manage aboveground oil storage tanks (ASTs) or containers must

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Risk-Based Resource Allocation for Distribution System Maintenance

Risk-Based Resource Allocation for Distribution System Maintenance PSERC Risk-Based Resource Allocation for Distribution System Maintenance Final Project Report Power Systems Engineering Research Center A National Science Foundation Industry/University Cooperative Research

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

Prevention through Design: Eliminating Confined Spaces and Minimizing Hazards

Prevention through Design: Eliminating Confined Spaces and Minimizing Hazards Prevention through Design: Eliminating Confined Spaces and Minimizing Hazards American Industrial Hygiene Association Developed by the AIHA Confined Spaces Committee Approved by the AIHA Board of Directors

More information

Elements of an Occupational Health and Safety Program

Elements of an Occupational Health and Safety Program Occupational Health and Safety Division Elements of an Occupational Health and Safety Program Table of Contents Introduction 3 What workplaces must have a program? 5 What criteria must the program meet?

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary Learning Objectives After reviewing this material, the student will be able to: 1. Identify the installations that fall under the scope of the 2015 edition of NFPA 70E. 2. Identify the assessments required

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

Instructions For SF 6 Refill Kit

Instructions For SF 6 Refill Kit S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Instructions For SF 6 Refill Kit TABLE OF CONTENTS Section Page Section Page INTRODUCTION..................................

More information

Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00

Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 E Refrigerant Charging Unit ICOGD 020AH1000 Operating Manual FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 Contents Technical Specifications... 20 Safety... 21 A/C System... 22 Components... 23 Control Panel...

More information

Electrical Predictive and Preventative Maintenance

Electrical Predictive and Preventative Maintenance Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types

More information

Vegetation Management. for Distribution Lines

Vegetation Management. for Distribution Lines Vegetation Management for Distribution Lines Working Hand in Hand with Nature Trees contacting power lines and other electric facilities are the major cause of electric service interruptions, especially

More information

City of Bakersfield Public Works Department Sewer System Management Plan December 2014

City of Bakersfield Public Works Department Sewer System Management Plan December 2014 City of Bakersfield Public Works Department Sewer System Management Plan December 2014 C:\Users\hmayberry\Desktop\SEWER SYSTEM MANAGEMENT PLAN 2014.doc 1 Sewer System Management Plan Index: Section 1 Goals

More information

THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM

THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM Prepared and Presented By: Don Langston President & CEO, Aire Rite Air Conditioning & Refrigeration Inc Setting the Foundation The Refrigeration

More information

Promoting Tree Health and Electric Safety. Important Numbers

Promoting Tree Health and Electric Safety. Important Numbers Promoting Tree Health and Electric Safety Trees and good electric service are both important to our community. Unfortunately, the two aren t always compatible, and OPPD must trim trees for safety purposes,

More information

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

Toronto Hydro-Electric System Limited ( THESL ) 2011-2020 Electrical Distribution Capital Plan

Toronto Hydro-Electric System Limited ( THESL ) 2011-2020 Electrical Distribution Capital Plan Toronto Hydro-Electric System Limited EB-2010-0142 Exhibit D1 Tab 8 Schedule 10 ORIGINAL (33 pages) Toronto Hydro-Electric System Limited ( THESL ) 2011-2020 Electrical Distribution Capital Plan June 2010

More information

COMMON EQUIPMENT FAILURES AND CAUSES. How breakdowns can impact the bottom line. A handy reference guide from Hartford Steam Boiler.

COMMON EQUIPMENT FAILURES AND CAUSES. How breakdowns can impact the bottom line. A handy reference guide from Hartford Steam Boiler. COMMON EQUIPMENT FAILURES AND CAUSES How breakdowns can impact the bottom line. A handy reference guide from Hartford Steam Boiler. A WORLD THAT DEPENDS ON EQUIPMENT. Businesses, institutions and municipalities

More information

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400 OSHA REGULATION: 29 CFR 90.7 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) DATE: 0/5/2008 DATE: /2/202 A. POLICY. This procedure follows requirements set forth in 29 CFR 90.7. 2. It is the policy

More information

The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities

The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities Generator Testing in Nursing Facilities Introduction Recent emergencies and natural disasters have emphasized the need to ensure that nursing facilities have an adequate EPSS in place should the loss of

More information

Safe Work in Confined Spaces

Safe Work in Confined Spaces Safe Work in Confined Spaces This publication is prepared by the Occupational Safety and Health Branch Labour Department Edition November 2010 This publication is issued free of charge and can be obtained

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s

More information

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects

More information

Improving Power Quality Through Distribution Design Improvements

Improving Power Quality Through Distribution Design Improvements Improving Power Quality Through Distribution Design Improvements Tom Short, EPRI PEAC, tshort@epri-peac.com Lee Taylor, Duke Power, lstaylor@duke-energy.com The three most-significant power quality concerns

More information

Houston Service Center Medium Voltage Service and Aftermarket Solutions

Houston Service Center Medium Voltage Service and Aftermarket Solutions Houston Service Center Medium Voltage Service and Aftermarket Solutions Table of contents Introduction...3 Breaker refurbishment...4 Protective relay & control service and support...5 Power Service and

More information

HVAC Repair and Maintenance Strategies by Ron Prager

HVAC Repair and Maintenance Strategies by Ron Prager HVAC Repair and Maintenance Strategies by Ron Prager (Demystifying HVAC) The PRSM editorial board recently raised the question of the best, strategic approach to HVAC maintenance. Of course, there is no

More information

Predictive Maintenance

Predictive Maintenance PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity

More information

WHAT IS INFRARED (IR) THERMOGRAPHY

WHAT IS INFRARED (IR) THERMOGRAPHY WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical

More information

Ultrasound Condition Monitoring

Ultrasound Condition Monitoring Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste

More information

ON-VEHICLE INSPECTION

ON-VEHICLE INSPECTION Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI

More information

Understanding Line Clearing Efforts. Improving service reliability and promoting the health of your trees.

Understanding Line Clearing Efforts. Improving service reliability and promoting the health of your trees. Understanding Line Clearing Efforts Improving service reliability and promoting the health of your trees. Trees are an important part of our environment. That s why American Electric Power (AEP) is committed

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

Considering UNDERGROUND. tampaelectric.com

Considering UNDERGROUND. tampaelectric.com Considering UNDERGROUND Electric Service? tampaelectric.com INTRODUCTION The majority of Tampa Electric s customers receive their electric service through overhead construction, which is the standard type

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

SUPPLY CHAIN SERVICES

SUPPLY CHAIN SERVICES EB-0-0 Exhibit F Schedule Page of SUPPLY CHAIN SERVICES INTRODUCTION Supply Chain supports THESL asset management plans by ensuring that all required goods and services are available when needed. Strong

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

Best Practices for Power Equipment Startup

Best Practices for Power Equipment Startup Frank Waterer, Fellow Engineer, Square D Engineering Services in conjunction with the Square D Critical Power Competency Center 1. Abstract In order for the electrical power distribution systems within

More information

High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd

High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Definition of High Voltage

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Element D Services Plumbing

Element D Services Plumbing Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.

More information

2. OUR NETWORK 4.42 74.74 16 POWERPOLES 2 POWERPOLES. Our distribution network comprises: For every 1 kilometre of powerlines: Essential Energy has

2. OUR NETWORK 4.42 74.74 16 POWERPOLES 2 POWERPOLES. Our distribution network comprises: For every 1 kilometre of powerlines: Essential Energy has 2. OUR NETWORK Essential Energy s network is unique in terms of the geographic area it covers, the terrain it traverses, the vegetation that grows within it and the diversity of weather that passes over

More information

Trees and powerlines. Office of the Technical Regulator. Web: sa.gov.au/energysafe Phone: 8226 5500 Email: dmitre.otr@sa.gov.au

Trees and powerlines. Office of the Technical Regulator. Web: sa.gov.au/energysafe Phone: 8226 5500 Email: dmitre.otr@sa.gov.au Trees and powerlines Office of the Technical Regulator For more energy information: Web: sa.gov.au/energysafe hone: 8226 5500 Email: dmitre.otr@sa.gov.au owerlines are an important part of our everyday

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

Welcome. Xcel Energy HOME. Contact Information. Tear off this portion. Keep for future reference. Customer Service. 24-hour Emergency Hotlines

Welcome. Xcel Energy HOME. Contact Information. Tear off this portion. Keep for future reference. Customer Service. 24-hour Emergency Hotlines Xcel Energy Contact Information Tear off this portion. Keep for future reference. Welcome HOME Customer Service --- -hour Emergency Hotlines Electric Emergency/Lights Out --- Gas Emergency/Gas Odor ---

More information