1 technical standards Offshore Substation HVAC System ETS-09 Rev. 2 Dok Sag 09/1437

2 Revision survey Document title HVAC System Document no Target group Fabrications Contractors and Designer for Offshore substations. Revision Document Writer Reviewer Approver status Init Date Init Date Init Date 1 xomo N/A HRI Approved xomo POD, PJV POD Minor alterations, type errors, rephrases e.t.c. where the meaning of the text is left unchanged are not shown. Revision Appendix no. and description None Document no , case 10/4054 ETS-09 v. 2

3 Table of contents 1. Scope 1 2. References Codes and Standards 1 3. Definitions and Abbreviations Definitions Abbreviations 3 4. Technical Requirements General HVAC Design Basis Indoor Climate Pressurization Air Quality Human Comfort Heating Cooling General Noise and Vibration Out Door Climate Fresh Air Ventilation Fresh air ventilation unit Leakage Ductwork and Components Air Intakes and Exhausts Fans and Motors Moisture Separators and Filters Heating / Cooling Coils Ductwork Dampers Silencers Control System Insulation Installation General Leakage Test, Air flow measurements and Pressure Test Commissioning Certificates / Data books General 12 Document no , case 10/4054 ETS-09 v. 2

4 1. Scope This Technical Standard covers the design and materials for HVAC systems for. Semi-manned offshore substations, in accordance with the definition stipulated in DNV-OS-J201. This ETS specifies requirements and gives recommendations for the indoor climate of offshore substations and for the design and engineering of HVAC systems. It takes into account the requirements for both people and electronic equipment. Compliance is required with all applicable parts of the Codes and Standards specified. The Technical Standard is one of a whole set of Technical Standards. It contains additional Energinet.dk requirements or specifies requirements where the Regulations, Codes and Standards allow alternatives. 2. References 2.1 Codes and Standards DS/EN ISO DS 447 DS 452 DS 474 Eurovent 2/2 SBI /42/EC DNV-OS-J201 Petroleum and Natural gas Industries Offshore production installations Heating, ventilation and airconditioning. Code of Practice for mechanical ventilation installations Code of practice for thermal insulation of technical service and supply systems in buildings Code for Indoor Thermal Climate Air leakage rate in sheet metal air distribution systems Danish Building Research Institute (SBI) Specification 102. Measurements in ventilating systems. Machinery Directive (DK version = 2006/42/EF) Offshore Substations for Wind Farms Document no , case 10/4054 ETS-09 v. 2 1

5 3. Definitions and Abbreviations 3.1 Definitions Moisture separator filter coalesce A single component including weather protection louver / moisture eliminator, a bag or panel coalesce a filter section and if necessary another moisture eliminator or split into separate parts comprising of the above mentioned parts. Air Handling unit (Selfcontained) An air handling unit, located in the space which it serves, which re-circulates the air in that space to the required conditions. A self-contained air handling unit does not normally involve a ducting system. Chilled water unit (Compressor type). Direct expansion (DX) chiller. A unit similar to a direct expansion (DX) chiller but including a heat exchanger which utilises the vaporising refrigerant's latent heat to cool a chilled water circuit to the required temperature. A unit consisting of a compressor and a condenser. The refrigerant vapour is compressed to a certain pressure, condensed to liquid refrigerant and then vaporised, thus utilising the vaporising refrigerant's latent heat in a cooling coil (separate from the chiller). The vaporised refrigerant is returned from the coil to the compressor. Fresh air ventilation unit Fan coil unit An air handling unit in which the fresh air is handled to the required conditions and used as ventilation air. HVAC equipment through which air is re-circulated from the space in which it is located. The purpose of this re-circulation is to cool or heat this air to the conditions required for the space. This unit is normally connected to the chilled water or the DX system. Document no , case 10/4054 ETS-09 v. 2 2

6 Shall: Verbal form used to indicate requirements to be strictly followed in order to conform to the standard and from which no deviation is permitted, unless accepted by all parties. Should: Verbal form used to indicate that among several possibilities one is recommended as particularly suitable, without mentioning or excluding others, or that a certain course of action is preferred but not necessarily required. May: limits of the standard. Verbal form used to indicate a course of action permissible within the Can: material, physical or casual. Verbal form used for statements of possibility and capability, whether 3.2 Abbreviations HVAC Heating, Ventilation and Air Conditioning DS Danish Standard Code of Practice EN European Standard Code of Practice IEC International Electrotechnical Commission ISO International Organisation for Standardization NGTE National Gas Turbine Establishment 4. Technical Requirements 4.1 General Offshore substations may require climatic conditioning (i.e. heating, ventilation and/or air conditioning) in order to maintain the temperature, relative humidity and air quality within defined limits. In this way reliable operation of electronic equipment and human working conditions are enhanced. HVAC systems are generally supplied by specialised Manufacturers as package units or as single components. Standard industrial HVAC equipment should be used. Document no , case 10/4054 ETS-09 v. 2 3

7 It shall be ensured that sufficient space in plant buildings is reserved for HVAC equipment and its ducting. 4.2 HVAC Design Basis A design basis as stipulated in DS/EN ISO shall be prepared by the Contractor. The primary goals of the ventilation system shall be identified, some of the goals are: Prevent ingress of salt particles and salt- water aerosols, if present, into relevant areas through pressurization and installation of efficient moisture eliminators and filter coalesces. Remove generated heat / supply heated air in winter time, and keep a controlled indoor climate in which personnel, plant and systems can operate effectively including smoke control. Ventilation shall be maintained to equipment and rooms that need to be operational during an emergency situation when the main source of power is unavailable, if required. 4.3 Indoor Climate Recommended indoor climate/environmental conditions as given in DS/EN ISO 15138, shall be fulfilled as a minimum. Recommendations given in DS447 can be followed Pressurization Indoor premises/rooms, where required, shall be kept under a relative overpressure to reduce the concentration of salt-water aerosols, dust and water particles and keep the indoor air clean. Pressurization shall be minimum 50 Pa for technical rooms, if required by design, and for the accommodation area within the range of 25 Pa to 65 Pa with respect to outside atmosphere at design wind speed Air Quality Ventilation rates (in terms of changes per hour) shall be determined taking into account the rate of leakage through doors and wall penetrations, the thermal requirements of the rooms and the required airflow to remove polluted air. Rooms should be equipped with pressure control dampers to adjust the pressure in each room to the required level. Workshops on the platform shall be provided for process ventilation if required by the design. Process ventilation can comprise of welding exhaust arms, fans and filters. Exhaust air shall be led to safe areas and well clear of access ways. Document no , case 10/4054 ETS-09 v. 2 4

8 4.3.3 Human Comfort Recommended indoor temperature conditions as given in DS/EN ISO shall be fulfilled as a minimum. Humidity control shall be provided by either the individual self-contained air handling units or by the central fresh air ventilation unit Heating Heating may be required to raise the temperature inside a room to the required level. In the heating capacity calculations the dissipated heat from personnel, lighting and electronic equipment shall not be included. Heat losses through walls, floors and roofs shall be taken into account. Electrical or hot water may be considered as a heating medium for a central heating system. The fresh air ventilation unit and the re-circulation air handling units can, if applicable, be heated through this central heating system. Vital rooms (e.g. control room, instrument auxiliary room, electrical auxiliary room etc.) may be heated through re-circulation air handling units. For other rooms heating can be provided by either individual fan coil units, individual electric after-heaters or a central heating system Cooling Cooling may be required to lower the temperature inside a room to the required level. Cooling capacity calculations should be based on heat gain from sources such as personnel, electronic equipment, lighting, fresh air intake, walls, roofs, windows etc. The heat generated in the rooms shall be removed by supplying cooled air. For cooling of rooms containing vital electronic equipment, self-contained air handling units can be used. Direct expansion (DX) Chillers or chilled water can be applied as a cooling medium. Such units shall be located inside the rooms they serve. Drainage from the unites shall be routed to the drain system. In order to allow for maintenance and failure of such units, redundancy shall be provided. The capacity of the individual self-contained units shall be such that the normal climatic requirements are met even if one unit fails. Document no , case 10/4054 ETS-09 v. 2 5

9 4.3.6 General Duct or unit-mounted heating and cooling coils units shall be automatically temperature-controlled by a duct- or room-mounted sensor modulating a heating/cooling-medium proportional controller. Where both heating and cooling coils are employed, controls shall be interlocked to ensure complementary operation Noise and Vibration Recommended maximum indoor noise levels as given in DS/EN ISO 15138, shall be fulfilled as a minimum. Noise caused by HVAC installations can be reduced by applying one or more of the following: - air duct silencers; - soundproofing of air ducts; - quiet self-contained equipment; To reduce vibration from rotating and vibrating items of equipment they shall be isolated from piping, ducting and structures by means of flexible piping, air duct connectors, vibration isolators, etc. 4.4 Out Door Climate The recommendations stipulated in DS/EN ISO for external meteorological conditions shall be applied by the design. 4.5 Fresh Air Ventilation Fresh air ventilation may be required in order to: provide a minimum fresh air intake quantity per unit of time; maintain an over-pressure in order to prevent the ingress of contaminants; compensate for specific exhausts such as those in, a battery room or workshops. Requirements for fresh air ventilation systems are: A positive flow from outdoors to indoors and back shall be accomplished. The air flow direction shall be such that the flow is from clean rooms, e.g. control room, instrument auxiliary room, telecommunication room and Document no , case 10/4054 ETS-09 v. 2 6

10 computer room, to rooms with air polluting (fouling) equipment e.g. battery room, HVAC machine room and workshops Fresh air ventilation unit Components in fresh air ventilation units shall fulfil demands as stated in previous sections. Air handling units shall fulfil demands as listed in DS/EN ISO Fig 1. Fresh air ventilation unit. 4.6 Leakage Guidelines for the maximum leakage factor given in DS/EN ISO 15138, Eurovent 2/2 and DS447 shall be followed. 4.7 Ductwork and Components Air Intakes and Exhausts HVAC air intakes shall be equipped with efficient weather protection louvers / moisture eliminators. The louvers shall be able to remove the majority of the liquid (rain, sea spray, coarse aerosols), the moisture separation efficiency shall typically be 96 % for droplet sizes of 30 μm and larger at a system velocity of 1 m/s. HVAC air exhausts shall be equipped with efficient weather protection louvers. A screen or mesh sized to provide protection against birds shall be fitted to the air inlet and exhaust ducts. Air intakes and exhausts shall be placed far apart from each other. Inflow from generator exhaust, exhaust from combustion engines, fired units or ventilation exhaust shall be avoided. Document no , case 10/4054 ETS-09 v. 2 7

11 The air intake shall be located in safe area Fans and Motors Fans and motors shall be selected for optimum efficiency with regard to power consumption, sound level and fan efficiency. If reliability of the HVAC system is deemed important, i.e. if cooled air is provided by the HVAC system to remove heat generated from equipment, the air handling units shall be provided with two fans, one duty and one stand-by to ensure ventilation if a fan fails. Shut off dampers shall be placed upstream the fans and non-return dampers downstream the fans, in case of repair of a fan, the fan shall be able to be dismantled without air backflow from the fan running, see. Fig.1. Automatic switch over between duty and standby fan shall be provided. Signal of air flow failure in the ducts, via flow switches in the ducts, or automatic switch over from duty to stand-by fan shall be provided Moisture Separators and Filters Efficient moisture separators and filters shall be installed in the HVAC system air intake. The moisture removal and filtration function can be incorporated into a single component including weather protection louver/moisture eliminator, a bag or panel coalesce, a filter section and possibly another moisture eliminator or split into separate parts comprising of the above mentioned parts. An efficient moisture separator can be split into 3 stages as described below: Stage 1 is the bulk water removal stage. In this stage the majority of the liquid (rain, sea spray, coarse aerosols) entering the intake is removed and drained away. Stage 1 is typically a vane separator/weather protection louver. Stage 2 is the coalescence stage, where fine aerosols that have penetrated the first stage are coalesced to form larger droplets that can be easily removed by the third stage. Stage 2 is often a filtration stage designed to remove dust and other solid particulate. Stage 3 is typically a vane separator or similar, which stops any concentrated saline solution that has passed through Stages 1 and 2. The entrained liquid is captured and removed from the intake by a manometrically sealed drainage system. Arrangements can vary dependant on the manufacturer, guidelines to typical air filtration requirements for various rooms can be found in DS/EN ISO Document no , case 10/4054 ETS-09 v. 2 8

12 The louver / filter/ coalesce separator should be able to reduce the salt-in-air content at the output to 0.01 x 10-6 by mass against the NGTE (National Gas Turbine Establishment) Standard 30 knot aerosol. The pressure drop across moisture separators and filters shall be kept at a minimum Heating / Cooling Coils Electrical heaters Electrical heaters shall fulfil guidelines given in DS/EN ISO All heaters shall be installed with high air temperature or high element-surface temperature thermal cut-outs. Cooling Coils Cooling coils can be of direct expansion refrigerant or fluid type. Cooling coils shall be selected to avoid moisture carry-over into the air stream. Cooling coils shall be provided with frost protection and surface temperature shall be measured, i.e. the cooling coil shall be placed downstream the heater, to prevent freezing of the coil in winter conditions. Water pipes crossing rooms with electrical equipment should be avoided where possible. If not possible electrical equipment shall be screened against splash and spray in case of a rupture Ductwork Ducts, equipment and supports placed outside enclosures shall be designed to withstand offshore conditions, wind loads shall be taken into account and ducts shall be made of corrosion resistant material, stainless steel. Ducts and supports placed inside enclosures shall be made of materials with a lifetime equal to the design lifetime of the platform. Guidelines for ductwork and materials as listed in DS/EN shall be followed. Recommended maximum velocities in duct systems as given in DS/EN ISO shall be fulfilled. Duct systems shall be designed to fulfil the acoustic requirements and requirements for the maximum air leakage percentage as given in DS447. Duct systems should be self balancing as far as possible; where this is not the case flow balancing dampers shall be installed. Document no , case 10/4054 ETS-09 v. 2 9

13 4.7.6 Dampers Dampers shall fulfil guidelines given in DS/EN ISO Fire dampers Fire dampers shall be able to maintain fire-rated barriers when penetrated by HVAC ducts. Proximity or limit switches to indicate status closed and/or open positions shall be installed on the fire dampers. The dampers shall be kept in open position by a pneumatic single-action springreturn actuator or a spring-return electric motor depending on if it is supplied with air or electric power. In case of loss of air or electric power the dampers shall close. A thermal device shall be installed to activate the damper actuator and close the damper in the event of an unacceptable temperature rise in the duct. Pressure-relief dampers Pressure-relief dampers shall be controlled automatically by tension spring or counterbalance weight, set to restrict blade opening until a preset pressure is exceeded Silencers Silencers and sound attenuators shall be selected to reduce duct carried noise from ventilation fans, dampers or other noise sources in the ventilation system. Recommended HVAC noise limits given in DS/EN ISO shall be fulfilled as a minimum Control System A local control system (such as a programmable RIO) for the HVAC system shall be installed. The local control system shall be linked up to the platforms main control system via a communication bus from where the HVAC system is monitored and all control functions can be accessed. All important information on temperature, air flow failure, equipment failure and status on the system shall be collected. The HVAC system shall be accessible via an IP-connection. Status indicators and operations shall be available via this web interface. The connection shall be accessible via a standard browser (e.g Internet Explore). The following controls, indicators and alarms should be present: Controls The following controls should, as minimum, be provided: Start/stop fans, Automatic changeover switch with selector for each duty/standby fan, Open/Close of dampers, and change of temperature set-points. Document no , case 10/4054 ETS-09 v. 2 10

14 Indicators The following indicators should as minimum be provided: Run/Stop/Tripped fans, Filter dirty, On/tripped heater, lamp test, On/tripped each package equipment item, Open each fire/gas damper, Close each fire/gas damper, Loss of pressurization any area requiring pressurization, temperature readouts. Alarms Alarm should as minimum be given for: Fan trip, heater trip, filter dirty, package equipment trip, loss of pressurization, fire damper operating-mode failure, high/low temperatures Insulation Ducts placed indoor shall be insulated against condensation, heat loss and fire, see Insulation guidance DS/EN ISO Insulating materials shall be fire resistant. 4.8 Installation General Installation guidance as specified in DS/EN ISO should be followed Leakage Test, Air flow measurements and Pressure Test Leakage test, air flow measurements and pressure test should be carried out in accordance with relevant codes such as Eurovent 2/2, SBI specification 102 and relevant DS/EN codes of practice A report with all measured values, method, and place marked up on drawings and instrument type shall be performed and issued. 4.9 Commissioning The HVAC system shall be commissioned in accordance with the project requirements, at the latest before load-out. Unless otherwise specified by the Employer, the Supplier of the HVAC system shall provide all test equipment required to commission and maintain the whole HVAC system. Commissioning procedures should shall as a minimum, but not limited to include: Measurements of design airflows and air temperatures Differential pressures Sound-pressure levels of spaces Document no , case 10/4054 ETS-09 v. 2 11

15 All measurements and settings should be conducted using calibrated instruments, and the results shall be documented in a measurement report. Acceptance of the HVAC plant should not take place until satisfactory measurements and commissioning has been completed. 5. Certificates / Data books 5.1 General Certificates and data for all equipment and parts of the HVAC system shall be collected in Data books. Service procedures and service intervals shall be assembled in a service book. Document no , case 10/4054 ETS-09 v. 2 12

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning NORSOK STANDARD H-001 Rev. 4, Nov. 2001 Heating, ventilation and air-conditioning This NORSOK standard is developed by NTS with broad industry participation. Please note that whilst every effort has been

More information

Data Centres A complete solution to noise control and acoustic packages

Data Centres A complete solution to noise control and acoustic packages Data Centres A complete solution to noise control and acoustic packages Introduction World class noise control. Expertise you can trust. IAC Acoustics is world-renowned for providing cost effective solutions

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D) Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace) UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1

More information

How To Get A Passive House

How To Get A Passive House Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

21.1 Functions, Basic Configuration, and Interfaces

21.1 Functions, Basic Configuration, and Interfaces 21 (6.2.M) Site Services Building 21.1 Functions, Basic Configuration, and Interfaces 21.1.1 Functions The primary functions performed by the site services building are to house, support, provide a suitable

More information

Why is my air conditioner dripping on my customers?

Why is my air conditioner dripping on my customers? De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These

More information

9.4 Air Conditioning, Heating, Cooling and Ventilating Systems

9.4 Air Conditioning, Heating, Cooling and Ventilating Systems 9.4 Air Conditioning, Heating, Cooling and Ventilating Systems 9.4.1 Control Building HVAC The Control Building (C/B) Heating, Ventilating and Air-Conditioning (HVAC) System is divided into two separate

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

air conditioners how to choose a cooling system

air conditioners how to choose a cooling system air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced

More information

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Drives and motors. A guide to using variable-speed drives and motors in retail environments Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable

More information

Engineering Onboard Climate Control. Experience for optimal design

Engineering Onboard Climate Control. Experience for optimal design Engineering Onboard Climate Control Experience for optimal design O F F S H O R e H v a c - R A d v a n t a g e s 2 K n o w l e d g e f o r o p t i m a l e f f i c i e n c y The BRONSWERK Advantage BRONSWERK

More information

10 tips for getting more reliability from your air-conditioning system [reliability]

10 tips for getting more reliability from your air-conditioning system [reliability] 10 tips for getting more reliability from your air-conditioning system [reliability] A guide for installers, specifiers, contractors and architects February 2010 10 tips for getting more reliability from

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

HEATER, AIR CONDITIONING AND VENTILATION

HEATER, AIR CONDITIONING AND VENTILATION 55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT

More information

Action Plan Template HVAC Page 1

Action Plan Template HVAC Page 1 Action Plan Template HVAC Page 1 Once Establish expected HVAC system efficiency - Write down the expected efficiency of HVAC systems to use as a baseline - Add this information to maintenance plan documentation

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

PLUG and PLAY VRV Connection

PLUG and PLAY VRV Connection PLUG and PLAY VRV Connection All seasons Perfect c mfort Heating Air Conditioning Applied Systems Refrigeration Pricelist 2010 Air Handling Units for > VRV Indoor units and Air Handling Units on single

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly

More information

Kompressoren. Adsorption Dryer AD

Kompressoren. Adsorption Dryer AD Kompressoren Adsorption Dryer AD Adsorption Drying: why? Modern industries require compressed air that is increasingly filtered with low dew point and condensate. Today, the equipment is more sophisticated

More information

FOXAIR 60/50 ALL MODELS

FOXAIR 60/50 ALL MODELS FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

Scope of Work. See www.sei.ie for resources available

Scope of Work. See www.sei.ie for resources available HVAC SWG Summary Background Pool energy-efficiency knowledge Increase cost-competitiveness Develop resources aimed at assisting in reducing HVAC energy consumption Address barriers to energy-saving HVAC

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

Maintenance for Energy Efficiency

Maintenance for Energy Efficiency Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark

More information

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions

More information

Cooking at the Speed of light!

Cooking at the Speed of light! Cooking at the Infrared Cooking & Colouring Infrabaker is a modular infrared continuous cooking system developed by Infrabaker International. The machine is designed to cook and/or put colour on a wide

More information

Energy Efficiency. Bars & RestauRants. www.energia.ie

Energy Efficiency. Bars & RestauRants. www.energia.ie Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could

More information

Ventilation for buildings Energy performance of buildings Guidelines for inspection of air-conditioning systems

Ventilation for buildings Energy performance of buildings Guidelines for inspection of air-conditioning systems CEN/TC 156 Date: 2006-05 pren 15240 CEN/TC 156 Secretariat: BSI Ventilation for buildings Energy performance of buildings Guidelines for inspection of air-conditioning systems ICS: Descriptors: Document

More information

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air

More information

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL

More information

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient

More information

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay

Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay Original HVAC Units: Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue Photo Essay One fan motor draws air from the lower section of the unit,

More information

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you

More information

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

Johnson Air-Rotation Systems

Johnson Air-Rotation Systems AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high

More information

Heat Pumps for Swimming Pools

Heat Pumps for Swimming Pools Page 1 of 5 Heat Pumps for Swimming Pools This factsheet provides members with invaluable information about heat pumps and their use for heating swimming pool water. There is a consumer factsheet already

More information

Center for Energy Education Laboratory

Center for Energy Education Laboratory Paper ID #7072 Center for Energy Education Laboratory Dr. Robert Gilbert, Sinclair Community College Robert B. Gilbert, Ph.D., LEED AP, BA, is an Associate Professor of Energy Management Technology, and

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

MODEL: DV72. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual. Configuration Left Hand Right Hand

MODEL: DV72. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual. Configuration Left Hand Right Hand 9041381- Issue 6 4/11 MODEL: DV72 Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual Commissioning Data: to be completed by the installer Date of installation: Configuration

More information

Cool air quietly and efficiently. A guide to buying and operating an air conditioner

Cool air quietly and efficiently. A guide to buying and operating an air conditioner Cool air quietly and efficiently A guide to buying and operating an air conditioner Cool air quietly and efficiently Noise from air conditioners can be a serious issue between neighbours. If an air conditioner

More information

Tips on Saving Energy in Your Business

Tips on Saving Energy in Your Business Fact Sheet #3 Tips on Saving Energy in Your Business In this fact sheet you will discover: Quick and easy changes to save energy. Cost effective ways to reduce your heating, cooling, lighting and office

More information

New Trends in the Field of Automobile Air Conditioning

New Trends in the Field of Automobile Air Conditioning New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic

More information

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil Answer: (1) Condenser coil See the video. A.R.E. Building Systems Study Guide

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

School of Human Ecology Building UW Madison, Wisconsin. By Arnold & O Sheridan, Inc. A&O Project No. 001175 Draft Report 01/12/01 revised

School of Human Ecology Building UW Madison, Wisconsin. By Arnold & O Sheridan, Inc. A&O Project No. 001175 Draft Report 01/12/01 revised School of Human Ecology Building UW Madison, Wisconsin By Arnold & O Sheridan, Inc. A&O Project No. 001175 Draft Report 01/12/01 revised HEATING, VENTILATING AND AIR CONDITIONING SYSTEM REPORT Introduction

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information