1 BROMPTON CEMETERY COnSERVATION PLAN: APPENDIX 3 High level roof inspection. Condition & Options Study The Royal Parks organised a Cherry Picker survey at Brompton Cemetery on 05th November 2014 to enable a visual inspection of the roofs of the Chapel, North Lodge, Colonnades and South Lodge. It was a cold, dry and sunny day. In attendance were: Catherine Cavanagh Sally Prothero Richard Davies Rachel James Robert Stevenson Russell Mundy (Part) Rik Fox (Part) The Royal Parks LDA MRDA MRDA The Friends of Brompton Cemetery Mundy Roofing Morton Partnership, Structural Engineers The lead dome to the Chapel is looking rather tired. As a minimum the gutters must be cleared of leaves and silt biannually. Splits in the lead are forming and repairs are required to the bottom half of the dome where the lead is dropping. Given the cost of access it is recommended that a programme of replacing the lead is considered. The roof is not leaking currently but it is coming to the end of its life. The roofs to the north lodge look in reasonable condition. A schedule of repairs will be prepared. Missing slates, of which there were a couple, should be replaced immediately. Moss build up should be cleaned off and there are areas of stone repairs and repointing required. The south lodge has a slate butterfly roof over the southern section. To the northern part there is a lead roof that is in good condition. Water ingress appears to be through the cracked parapets. The colonnade roofs were covered in Sarnafil within the last ten years or so. The south east colonnade roof was accessed. The roof covering is in good condition. A small tear was noted that should be repaired (under guarantee?) In conclusion the Chapel roof presents the most pressing priority. AUTHORS: MRDA REF: DATE: MRDA Architects & Conservation Consultants 2410_cherry picker survey 04th February 2015 rev B: PLANNING

2 was built in the early 1840s. It is Grade II* Listed. The lead roof dome was inspected from the cherry picker and the parapet gutter. The void between the inner and outer parts of the dome was accessed via the small hatch in the vertical up-stand on the west side of the dome. Water ingress: inside the chapel areas of water damage are visible. Paint has peeled and plaster spalled. These leaks are historic and not current. The pattern indicates that the water ingress was through the gutter (fig 2). Previous repairs: apart from the annual gutter clearance, Caroline McDonagh of TRP, reports that there has been no work on the dome roof in the last 8 to 9 years. Repairs are thought to have taken place in the 1990s, although the extent is unclear and in the late 1970s when the chapel roof was scaffolded and extensively repaired (fig 3). The parapet gutter: water was ponding in the gutters when we accessed the roof. This was due to silt build up around the outlets. The water drained away when the silt was cleared. If the gutters fill with water it will get under the lead and the timber substrate will rot - particularly as the steps in the gutter are less than would be specified today. If the gutter lining is replaced it should be re-engineered to provide higher stepsbetween bays. The gutters should be cleared bi-annually. The lead dome: the bottom half of the dome has been extensively repaired. The lead panels have dropped necessitating replacement of many edge clips and panel fixings. The top edge fixings are not visible, however if the lead has dropped they will probably be torn and the cover lap between the upper and lower panels insufficient. The lead repairs to the vertical up-stands at the bottom of the dome indicate the lead had cracked. Minor cracking was noted at the bottom of a couple of the lead rolls at the foot of the dome. The open joints of the lead rolls have been filled with mastic, not a recommended solution but which was presumably done to stem leaks. The mastic is compressible so the lead can move - the design life of the mastic is not known. An area of the lead at the bottom of the dome was rolled back, the boards underneath were dry, however the lead has become rather crystalline and is now becoming difficult to re-work / repair. The lead to the top half of the dome is in a more reasonable condition (fig 11) although a closer inspection may yield more defects. Inside the dome void: (figs 16 & 17) the space between the inner and outer dome is accessible by two small hatches on the E and W side. These are a tight fit, limiting access. The interior was dry and well ventilated and the dead birds and pigeon droppings were not extensive or recent. Evidence of former water ingress includes staining of timbers and some rotten supports, which appear to have been replaced. The roof-light: (figs 13,14 & 15) the single glazing curves in two direction. One pane is cracked. The roof-light has been repaired with tape / flash band which should be replaced. Lower roofs: (figs. 18, 19, 20) the roofs to the side wings have been replaced with standing seam aluminum roofing. Some cracking of lead flashings were noted. The roofs seem in satisfactory condition. Generally the lead to the dome is looking a bit baggy. The roof is not leaking at present but is coming to the end of its life. There are three possibilities: 1: Clear gutters bi-annually to ensure water does not pond in them. 2: Scaffold and repair the existing roof. To include the roof-light 3: Scaffold and replace the lead to the dome. Repair the rooflight. Given the costs of access scaffold (tbc) we recommend that the lead is replaced rather than repaired - an extensive scaffold will be required for both repairs and replacement and the lead appears to be coming to the end of its life. High level masonry repairs should be carried out at the same time. Listed Building consent will be required. A further inspection from a cherry picker is required to develop the proposed scope of work and specification. The cherry picker should be of a size to view in more detail the cupola and roof at the head of the dome.

3 fig.1 North elevation, as existing fig.2 Chapel interior; water damage (historic) fig.3 Chapel with scaffold. 1979

4 fig.4 Replacement patch fixings & clips. Repairs to rolls fig.5 Ponding in gutters fig.6 Split in mastic repair

5 fig.7 Lead has dropped at high level. fig.8 Replacement clips, mastic to free edge of lead rolls (full height) fig.9 New clips and patch fixings where lead sheet has dropped

6 fig.10 Crack to edge of lead roll fig.11 Top half of lead is in better condition fig.12 Replacement clips and repairs to bottom of dome

7 fig.13 Rooflight. fig.14 Flash band to glazing bars fig.15 Exposed wood to bottom of rooflight

8 fig.16 Interior of dome fig.17 Underside of rooflight

9 fig.18 East wing: standing seam roof fig.19 West wing: standing seam roof fig.20 North porch: lead roof

10 The North Lodge was built in It is Grade II* listed. The central section of the roof and the mono pitches to either side are accessible through the roof hatch. The roofs to the side wings are accessible only via a cherry picker or scaffold making access to clean gutters etc. difficult. Should roof hatches be added? The roofs to the north lodge look in reasonable condition. A schedule of repairs will be prepared. Missing slates, of which there were a couple, should be replaced immediately. Moss build up should be cleaned off and there are areas of stone repairs and repointing required. External access only Access possible via roof hatch External access only fig.21 North Lodge. South elevation fig.22 East wing. Low roof. Slipped slate rhs The North Lodge fig.23 Gatehouse. Central roof with access dormer

11 fig.24 Central Gatehouse, East wing. Low roof fig.25 Open joint in parapet fig.26 Delaminating stone The North Lodge

12 fig.27 North Lodge. West wing. Low roof fig.28 Damaged chimney pot, West wing fig.29 Moss build up The North Lodge

13 The South Lodge and Police box are unlisted. The South Lodge has an area of slated roof and an area of leaded roof (looks failry recent) with flet on the small rear extension. Ongoping leaks are reported and damp aptches are visible internally in the south part of the lodge and the toilet. The cvalley will leak when it fills up with leaves and water appears to be getting in via the cracked parapets. Neither of these roofs appeared to have been cleared for some time, judging by build up of debris and litter/clutter on roof of police box. The flowering ivy is invasive and needs cutting back, although not killed as it is good for insects. TRP to check that South Lodge and Police Box are included in gutter cleaning schedule. TRP to consider cutting back trees overhanging roofs and prune ivy over South Lodge fig.30 South Lodge. General view fig.31 South Lodge. Internal staining fig.33 South Lodge. Roofs fig.32 Police Box. General view The South Lodge & Police Box

14 fig.38 South Lodge. Parapet fig.34 South Lodge. Valley gutter fig.38 South Lodge. Open joints in parapet fig.35 South Lodge. Extension. Felt roof fig.36 Police Box The South Lodge & Police Box

15 the Central Colonnades date form They are Grade II* listed. The colonnade roofs were covered in Sarnafil within the last ten years or so. The south east colonnade roof was accessed from the cherry picker. The roof covering is in good condition. A small tear was noted that should be repaired (under guarantee?) Areas of stone repairs and cracked flaunching were noted. fig.39 Over view from Chapel roof fig.40 Over view from Chapel roof fig.41 Cracked cement flaunching fig.42 Split single ply membrane The Central Colonnades

Rainwater Goods and Drains. Roofs

Rainwater Goods and Drains. Roofs SPAB Faith in Maintenance SPAB, 37 Spital Square, London E1 6DY. Tel: 0207 456 0913 Email: info@spabfim.org.uk The SPAB is a charitable company limited by guarantee registered in England and Wales. Company

More information

Bituminous Sheet Flat Roofs: Their repair and maintenance

Bituminous Sheet Flat Roofs: Their repair and maintenance Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and

More information

Ubiflex. Non-lead flashing system

Ubiflex. Non-lead flashing system Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof

More information

Your guide to home maintenance. Flat Roofs

Your guide to home maintenance. Flat Roofs Your guide to home maintenance Flat Roofs Your guide to home maintenance is a series of information leaflets that gives you all the information you need to keep your home in tiptop condition. Flat Roofs

More information

Safeguarding our clients interests. Active Roof Leaks

Safeguarding our clients interests. Active Roof Leaks Safeguarding our clients interests. Active Roof Leaks Vendor Requirements Visually inspect the roof for any damages Exterior inspection of the roof and gutters Interior ceiling inspection Interior attic

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

ROOFS - Guidance for Repair, Maintenance and Replacement

ROOFS - Guidance for Repair, Maintenance and Replacement ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed

More information

INDIAN HEAD ELEMENTARY SCHOOL

INDIAN HEAD ELEMENTARY SCHOOL ROOF ASSESSMENT REPORT INDIAN HEAD ELEMENTARY SCHOOL NOVEMBER 08, 2010 PREPARED FOR: FACILITIES DEPARTMENT WHITMAN HANSON REGIONAL SCHOOL DISTRICT 1. Purpose This Roofing Assessment Report provides a summary

More information

RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002

RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002 RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002 INDEX New Build Flat and Pitched Roofs Rainwater Goods Porches to Existing Buildings / Covered Links etc, Between Buildings Floors /

More information

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035 Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí

More information

StuccoSpec Moisture Testing Inspection

StuccoSpec Moisture Testing Inspection e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

Non Invasive Roof Leak Detection Using Infrared Thermography

Non Invasive Roof Leak Detection Using Infrared Thermography Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing

More information

Commercial Roof Management

Commercial Roof Management Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading

More information

BUNKER HILL ELEMENTARY SCHOOL

BUNKER HILL ELEMENTARY SCHOOL INITIAL YEAR BUILT 1970 BUILDING AREA 98,200 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 387 WARD 5 PROPOSED PROGRAM CAPACITY 750 Site Plan BUNKER HILL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

Damp Causes and Solutions

Damp Causes and Solutions Damp Causes and Solutions The subject of damp in buildings invites much comment and speculation. The issue is often misunderstood and proposed solutions are often expensive, damaging, and usually affect

More information

Melbourne balcony Assessments

Melbourne balcony Assessments Balcony Assessment Melbourne balcony Assessments Address: SAMPLE Date: Assessor: Luke O Neill Registered Builder DBL-C 31305 Assessment Guidelines This is an assessment of balcony and elements as presented

More information

Clear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015

Clear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015 Clear Fork Valley Local School District Roofing Repairs Spring/Summer 2015 Instructions to Bidders: Public Notice To Bidders (ORC 3313.46) Notice is hereby given that sealed bids will be received at the

More information

Site Inspection Report

Site Inspection Report Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G

More information

Improvements are also an investment producing a better place to live and very often increase the value of a property.

Improvements are also an investment producing a better place to live and very often increase the value of a property. MAINTENANCE AND REPAIR OF YOUR PROPERTY ADVICE FOR HOMEOWNERS For most people their house is the biggest investment they make. Timely repairs and maintenance are very important in preserving the property

More information

18 Church Street. This building adjoins number 16 and is again a grade II listed building. The building has a ground floor shop with a flat above.

18 Church Street. This building adjoins number 16 and is again a grade II listed building. The building has a ground floor shop with a flat above. 10 18 Church Street This building adjoins number 16 and is again a grade II listed building. The building has a ground floor shop with a flat above. Replacement of original sash windows and a new scantle

More information

Classic Products, Inc. ClickLock Standing Seam Installation Manual

Classic Products, Inc. ClickLock Standing Seam Installation Manual Classic Products, Inc. ClickLock Standing Seam Installation Manual Classic Products, Inc. 8510 Industry Park Drive Piqua, OH 45356 800.543.8938 Table of Contents page Introduction 1. 1 Starter. 2. 1 Panels.

More information

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It

More information

Roof Damage Reconveys 2014

Roof Damage Reconveys 2014 Roof Damage Reconveys 2014 1 Vendor Requirements Vendors are required to visually inspect the roof for any damages Exterior Inspection of Roof and Gutters Interior Ceiling Inspection Interior Attic/Crawl

More information

Planning & Building Control Division. Development. East Ayrshire Planning. Design Guidance

Planning & Building Control Division. Development. East Ayrshire Planning. Design Guidance Planning & Building Control Division Design Guidance 1 East Ayrshire Planning Design Guidance Householder Development 1 EAST AYRSHIRE PLANNING: DESIGN GUIDANCE Design of the built environment can affect

More information

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.

Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00. Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...

More information

Historic Buildings - A Guide to Owners

Historic Buildings - A Guide to Owners Historic Buildings - A Guide to Owners This leaflet is a guide for current and prospective owners of historic buildings and in particular listed buildings. A listed building is one included on the List

More information

Reference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls

Reference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto

More information

Memorandum. July 16, 2008. To: Plan Commission City of Madison

Memorandum. July 16, 2008. To: Plan Commission City of Madison Memorandum July 16, 2008 To: Plan Commission City of Madison From: Marc Schellpfeffer Engberg Anderson Re: Structural/Architectural Assessment of Homes for Proposed Demolition Findorff Yards Office Lofts

More information

Total Home Inspection Checklist

Total Home Inspection Checklist Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are

More information

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER

More information

Maintenance & Inspection Guide

Maintenance & Inspection Guide ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance

More information

Rooflight INSTALLATION INSTRUCTIONS

Rooflight INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Rooflight These instructions should be used for: Installing Permanent Trickle Ventilation: Constructing & Waterproofing a Timber Upstand Curb: Installing & Waterproofing Proprietary

More information

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No. Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering

More information

Property Inspection Report

Property Inspection Report Property Inspection Report LOCATED AT: 123 Address DFW, TX PREPARED EXCLUSIVELY FOR: Sample Report INSPECTED ON: Saturday, July 18, 2015 Inspector, Zach Faris - TREC #21548 INSPECT TX PROPERTY INSPECTION

More information

Thank You! Owner Aaron Perry! Email info@exteriorproinc.com! 2936 Clifty Drive! Madison IN 47250! (855) 274-0444! (812) 274-0444!

Thank You! Owner Aaron Perry! Email info@exteriorproinc.com! 2936 Clifty Drive! Madison IN 47250! (855) 274-0444! (812) 274-0444! A properly installed and maintained flat roof can be one of a building s biggest assets while a leaking or failing roof can quickly become a building s biggest expense. We ve put this simple guide together

More information

PRE-PURCHASE INSPECTION REPORT

PRE-PURCHASE INSPECTION REPORT PRE-PURCHASE INSPECTION REPORT PREPARED FOR: PROPERTY ADDRESS: Waiheke Island DATE: 21 November 2012 Page 1 of 13 (a) This is a report of a visual only, non-invasive inspection of the areas of the building

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Advice Series. the maintenance and repair of historic buildings

Advice Series. the maintenance and repair of historic buildings Advice Series the maintenance and repair of historic buildings Jacqui Donnelly - Architectural Conservation Advisor, Department of the Environment, Heritage & Local Government Current publications in the

More information

SCHEDULE OF CONDITION

SCHEDULE OF CONDITION JOB REFERENCE: SCHEDULE OF CONDITION Islington, London. N1 XXX FOR Miss X Prepared by: INDEPENDENT CHARTERED SURVEYORS Marketing by: Islington, London. N1 XXX CONTENTS SCHEDULE OF CONDITION Elevations

More information

Assessment Report for Windmill Rehabilitation Project. Anne Curren, Town Clerk Town of North Castle 15 Bedford Road Armonk, New York 10504

Assessment Report for Windmill Rehabilitation Project. Anne Curren, Town Clerk Town of North Castle 15 Bedford Road Armonk, New York 10504 Assessment Report for Windmill Rehabilitation Project Anne Curren, Town Clerk Town of North Castle 15 Bedford Road Armonk, New York 10504 Investigation and Documentation MAP employees measured all three

More information

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36. Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,

More information

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building

More information

Prelease Schedule of Condition and Want of Repairs at Milton Keynes for May

Prelease Schedule of Condition and Want of Repairs at Milton Keynes for May Prelease Schedule of Condition and Want of Repairs at Milton Keynes for May Instruction To carry out Inspection of the Industrial Unit, to identify areas of repair to the Unit at commencement of the Lease.

More information

PETERSONS WATERFRONT CONDOMINIUMS

PETERSONS WATERFRONT CONDOMINIUMS CONSULT DESIGN CONSTRUCT PETERSONS WATERFRONT CONDOMINIUMS 103 Park Street Chelan, Washington Findings Summary Report Prepared for: Petersons Waterfront Condominium Association March 21, 2014 J2 Project

More information

Big Stone County Courthouse Slate Roof Shingle Replacement. Request For Proposals

Big Stone County Courthouse Slate Roof Shingle Replacement. Request For Proposals Big Stone County Courthouse Slate Roof Shingle Replacement Request For Proposals Proposals must be delivered in person or mail by: 12:00 P.M., August 28, 2013 Faxed proposals will not be accepted Return

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 BROWNSVILLE STRUCTURES STUDY July 2012 Prepared by LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 TABLE OF CONTENTS I. SUMMARY OF BUILDING ANALYSIS.. 1 II. INDIVIDUAL BUILDING

More information

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof! Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing

More information

Crescent Valley High School Roof Investigation

Crescent Valley High School Roof Investigation Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

Home Warranty Inspection Report

Home Warranty Inspection Report Scope of the Inspection 1111 Sample Dr. home warranty inspection 2/30/2006 Home Warranty Inspection Report 1111 Sample Dr., Detroit, MI 48223 Inspection Date: February 30, 2006 Client: Alfred E. Neumann

More information

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single

More information

FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS

FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO

More information

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,

More information

Contacts: Head of Development Management Tel 0191 211 5629. Team Manager Urban Design and Conservation Tel 0191 277 7190

Contacts: Head of Development Management Tel 0191 211 5629. Team Manager Urban Design and Conservation Tel 0191 277 7190 Contacts: Head of Development Management Tel 0191 211 5629 Team Manager Urban Design and Conservation Tel 0191 277 7190 Write to: Development Management Environment and Regeneration Directorate Civic Centre

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

ELIGIBLE REPAIR PROJECT PARAMETERS

ELIGIBLE REPAIR PROJECT PARAMETERS THE DISTRICT MUNICIPALITY OF MUSKOKA ONTARIO RENOVATES PROGRAM FOR HOMEOWNERS ELIGIBLE REPAIR PROJECT PARAMETERS 1. To have your project considered and payment processed, all projects requiring a Building

More information

Replacement Windows and Doors

Replacement Windows and Doors Replacement Windows and Doors Short Policy Guide: Need for Planning Permission and Listed Building Consent For Replacement Windows and Doors Produced by City Development Department, Dundee City Council,

More information

How To Repair A House

How To Repair A House Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

Commercial Roof Inspection Form

Commercial Roof Inspection Form Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building

More information

BLACK JACK ALL WEATHER ROOF COATING

BLACK JACK ALL WEATHER ROOF COATING PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.

More information

CONDITION OF QUALITY ITEMS

CONDITION OF QUALITY ITEMS CONDITION OF QUALITY ITEMS FOUNDATION Always look for moisture problems and any bulges or irregularities in the walls. Lines on the walls or floors may indicate water problems. Have these been cured? If

More information

Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose

Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5 1. Purpose The purpose of this practice note is to address the incidence of deck and roof membrane

More information

Facility Assessment for. 11801 East Main Street, Huntley, IL

Facility Assessment for. 11801 East Main Street, Huntley, IL Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested

More information

EXECUTIVE SUMMARY. Bzar Groat Market Newcastle Upon Tyne. Date of inspection:

EXECUTIVE SUMMARY. Bzar Groat Market Newcastle Upon Tyne. Date of inspection: EXECUTIVE SUMMARY Bzar Groat Market Newcastle Upon Tyne On behalf of: Client Name Date of inspection: Reference: 05.194/CDL CONTENTS Page No EXECUTIVE SUMMARY 1 APPENDICES APPENDIX 1 PHOTOGRAPHIC SUMMARY

More information

Windbrooke Townhome Association, Inc. Maintenance & Service Responsibility Chart

Windbrooke Townhome Association, Inc. Maintenance & Service Responsibility Chart Roof Siding Chimney Doors and Windows Building Maintenance Repair and restoration of interior damage caused by roof leak; repair or replacement of structural supports under the roof decking and sheathing

More information

Date: March 7, 2006 Report for [removed]

Date: March 7, 2006 Report for [removed] Date: March 7, 2006 Report for [removed] The Preservation Resource Center Of New Orleans, in conjunction the National Trust for Historic Preservation, has conducted a condition survey of your property.

More information

WATERPROOFING FOR CONCRETE STRUCTURES

WATERPROOFING FOR CONCRETE STRUCTURES MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck

More information

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment

More information

Delving into drains. Reprinted with permission from PROFESSIONAL ROOFING magazine. December 2012 by the National Roofing Contractors Association.

Delving into drains. Reprinted with permission from PROFESSIONAL ROOFING magazine. December 2012 by the National Roofing Contractors Association. Delving into drains Reprinted with permission from PROFESSIONAL ROOFING magazine. December 2012 by the National Roofing Contractors Association. Installing retrofit roof drains can help you increase sales

More information

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET

More information

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS HIGH SCHOOL REPAIRS AND UPGRADES SITE Construction Estimate = $100,000

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:

More information

What to Do About Your Roof and How to Hire a Roofing Contractor

What to Do About Your Roof and How to Hire a Roofing Contractor ROOFI NG What to Do About Your Roof and How to Hire a Roofing Contractor On those rare occasions when it rains in Arizona and you have a leak, you may wonder if you need a brand new roof, especially if

More information

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared

More information

Architectural Condition Survey

Architectural Condition Survey Architectural Condition Survey Santa Fe Railroad / AMTRAK Depot, Lawrence. Kansas for the City of Lawrence, 2002 Survey: (student) PI: William Carswell, Associate Dean, School of Architecture, University

More information

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Building Foundation and Structure

Building Foundation and Structure Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original

More information

STRUCTURAL ASSESSMENT

STRUCTURAL ASSESSMENT STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha

More information

Preventing Ice Dams on Roofs

Preventing Ice Dams on Roofs Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the

More information

PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007

PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007 PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT November 2007 PURPOSE OF INVESTIGATION Determine possible locations of moisture intrusion into and through facade. Determine cause of horizontal and vertical

More information

If you touch buildings, YOU can benefit from the Moisture Encounter Plus

If you touch buildings, YOU can benefit from the Moisture Encounter Plus If you touch buildings, YOU can benefit from the Moisture Encounter Plus In our experience, whatever it is you are doing working on buildings, at some time you have to deal with moisture Surveying, roofing,

More information

ROOF INSPECTION REPORT

ROOF INSPECTION REPORT ROOF INSPECTION REPORT Date: October 9, 2012 Requesting Firm: FIRST CHOICE INSPECTIONS Santiago Salazar Address: 447 Chilberg Court, San Jose, CA 95133 Phone #: 408-771-7563 Roof Inspected At: 1465 Gerlach

More information

423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT

423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT Urgent Needs II City of Baltimore No. 1099 423 NORTH HOWARD ST. 423 North Howard Street (circa 1880) is a multi-story building constructed second in row south of Franklin Street and between the vacant

More information

Each style of building is characterized by a different style of roof. Recognize the style and preserve it during repairs or replacement.

Each style of building is characterized by a different style of roof. Recognize the style and preserve it during repairs or replacement. PRACTICAL CONSERVATION GUIDELINE SAINT JOHN HERITAGE CONSERVATION AREAS INTRODUCTION The size, shape and slope of the roof create the building silhouette. The roofing materials contribute texture and pattern.

More information

Prestige Home Inspection LLC

Prestige Home Inspection LLC Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No. Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two

More information

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.

More information

HOME INSPECTION CHECKLIST

HOME INSPECTION CHECKLIST CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways

More information

Select Radiators Installation Guide

Select Radiators Installation Guide Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall

More information

English Heritage Methodology and Guidance for Surveying Listed Buildings

English Heritage Methodology and Guidance for Surveying Listed Buildings English Heritage Methodology and Guidance for Surveying Listed Buildings A listed building is a building (or structure) that has been designated as being of special architectural or historic significance.

More information