Gravity Sanitary Sewer Pipe Material Comparison. Jeff Boschert, P.E. National Clay Pipe Institute

Size: px
Start display at page:

Download "Gravity Sanitary Sewer Pipe Material Comparison. Jeff Boschert, P.E. National Clay Pipe Institute"

Transcription

1 Gravity Sanitary Sewer Pipe Material Comparison Jeff Boschert, P.E. National Clay Pipe Institute National Clay Pipe Institute, 2013

2 Presentation Outline A. Introduction to Modern Day Vitrified Clay Pipe B. Gravity Sanitary Pipe Material Characteristics Compared Side by Side 1. Structural Properties 2. Pipe Service Life 3. Corrosion Resistance 4. Abrasion Resistance 5. Field Acceptance Testing 6. Environmental Impact 7. Jointing System

3 Vitrified Clay Body Evolution Laminations within cross section Average Compressive Strength = 18,000 psi (125 MPa)

4 Vitrified Clay Pipe is the Predominant Jacking Pipe in the United States for Guided Boring Video is not available in PDF format. Please click here to view on the NCPI YouTube Channel.

5

6

7

8 Static Pipe Bursting

9

10

11

12 Sewer Authorities Who Are Specifying Vitrified Clay Pipe New York Los Angeles Chicago Phoenix Philadelphia Cleveland Minneapolis San Francisco Sacramento Area Sewer Dist., CA Sioux City Seattle Omaha New Castle County, DE Buckeye, AZ

13 George Cowan, P.E., Assistant Commissioner- Infrastructures Division, New York City Dept. of Design and Construction For new pipe, our preference is clay pipe.we believe our biggest expense is digging the trench, so we feel it s worth the extra cost to get what we believe is the best pipe. Source: Roundtable Discussion; pp Trenchless Technology Magazine; JULY 2006

14 Section 1 Structural Properties

15 Rigid Pipe Open Trench Design Determining Predicted Load (W c ) Determining Field Supporting Strength FSS = Pipe Strength x Bedding Factor Calculating Safety Factor Safety Factor = Field Supporting Strength Predicted Load

16 Rigid Pipe Load Equation Wc B d W c = Total Predicted Load C d = Load Calculation Coefficient w = Soil Weight B d = Trench Width at Crown W c = C d wb d 2

17

18

19

20 Flexible Pipe Deflection Equation % Deflection = ΔX = D L KW c r 3 I E r 3 Where: ΔX = Horizontal deflection of pipe (inches) D L = Deflection Lag Factor (1.0 or 1.5 Typical) K = Bedding Constant (0.1 Typical) W c = Prism Load = Weight of soil over pipe (lbs./inch) r = Mean radius of the pipe (inches) E = Modulus of Elasticity of pipe material (psi) I = Moment of Inertia of the pipe wall per unit length (inch 3 ) E = Modulus of Soil Reaction (psi) Source: Handbook of PVC Pipe, Equation 7.8, Chapter 7, page 228 Uni-Bell PVC Pipe Association, 2001

21

22 Thermoplastic Materials Degrade with Age The main feature of plastics and polymer composites is that their physical, mechanical, thermal and chemical properties are strongly time and temperature dependent. Source: Dr. Mehdi Farshad: Plastic Pipe Systems: Failure Investigation and Diagnosis 2006

23 When considering the design and development of a plastic component, it is imperative that designers and engineers fully understand the fundamental nature of plastics. They should know that plastics are non-linear, visco-elastic materials with temperature/ time-dependant properties. Plastics physically and chemically age, and are susceptible to chemical attack, environmental stress cracking (ESC), and weathering. Source: Long-Term Testing Critical for Material Selection; Chris O Conner; pp Modern Plastics Worldwide; October 2007

24 Even untouched, these cultural symbols will inevitably grow brittle, warp and crack.... The problem of polymer materials in museums is getting to be bigger and bigger" Source: WARP SPEED, The Dallas Morning News, August 28, 2000; Sue Goetinck Ambrose; Science writer; page 2F

25

26 Type 1 Soils: Rock, cemented soils, 95% standard proctor, sands and gravels with in place densities of 70% or higher Type 2 Soils: sands and gravels with in place densities of 40 to 70%, silts or 85% standard proctor or higher Type 3 Soils: Peat or other organic soils, elastic silts, low density silty or clayey soils with a density below 85%, low density cohesionless soils with an in place density below 40% Source: Pipeline Installation, Amster Howard, 1996 Chapter 5

27 Section 2 Pipe Service Life

28 Vitrified Clay Pipe is the only sewer pipe material recognized by the U.S. Army Corps of Engineers with a 100 year service life. Clay Pipe is perhaps the most inert of the common pipe materials in terms of corrosion, and it is very resistant to abrasion. A 100- year service life may be assumed for most clay pipe installations. Source: Life Cycle Cost for Drainage Structures, US Army Corps of Engineers, 1988

29

30 8-Inch VCP Installed Prior to Years Old! Video is not available in PDF format. Please click here to view on the NCPI YouTube Channel.

31

32

33

34

35 10-Inch PVC Installed in 1991 Video is not available in PDF format. Please click here to view on the NCPI YouTube Channel. Replaced with 10-Inch VCP in 2009

36 Section 3 Corrosion Resistance

37 Chemical Resistance Sewerage generates Hydrogen Sulfide which is converted to Sulfuric Acid in the sewers. - Both Vitrified Clay and Thermoplastic pipe materials are resistant to Sulfuric Acid. Solvent based chemicals - Thermoplastic materials are susceptible to corrosion.

38 Chemical Resistance Comparison Material Normal domestic sewage Trade effluent Soil At normal Containing fats and At sustained environment temperature Organic oils high temp. containing Acids Alkalis solvents Vegetable Mineral Acids Alkalis Sulphates Acids Vitrified Clay pipes and fittings S S S S S S O O S S Polyethylene O O S X O O X O S S PVC O S S X O O X X S S Glass Reinforced Polyester (GRP) O P P X O O X X O O S = Specially suitable P = May require special protection O = Normally suitable X = Expert advice desirable, e.g. from specialist or manufacturer Source: Pipelines: An Overview, Loai Na amani

39 Chemicals Affecting PVC, PE & Fiberglass Pipe > PPI identifies 116 Chemicals that PVC is not resistant to. And another 155 Chemicals are listed as no data available. > PPI identifies 20 Chemicals that PE is not resistant to. And another 198 Chemicals are listed as no data available. > Hobas identifies 143 Chemicals that fiberglass is not resistant to. And another 138 Chemicals are listed as no data currently available. Sources: Chemical Resistance of Thermoplastic Piping Materials, Plastics Pipe Institute, September, 2007 The Complete HOBAS Guide, Hobas Pipe USA, Appendix F, Corrosion Resistance Guide, pp

40 Vitrified Clay Pipe is inert The only chemical that may damage VCP is Hydrofluoric Acid (HF).

41 Section 4 Abrasion Resistance

42 Abrasion Resistance Testing of Sewer Pipe Materials The tests were obtained by rotating pipe sections at a rate of 2.5 fps for 500 hours. The abrasive charge consisted of 7 pounds of #67 (ASTM D 448) limestone aggregate and 6.6 pounds of water which was changed every 48 hours. Pipe (All 8 Diameter) Wall Thickness Abraded Percent Abraded Vitrified Clay Solid Wall PVC Solid Wall PVC with bulk fillers Profile Wall PVC (a) PVC Truss (a) ABS Truss (a) lining Note (a): Complete Abrasion through the interior Pipe Stiffness Test (ASTM D Diameter) Pipe Minimum Required After Abrasion % Under Minimum Solid Wall PVC (ASTM D 3034) 46 psi 32.1 psi 30.2 % Solid Wall PVC (ASTM F 789) 46 psi 19.2 psi 58.3 % Profile Wall PVC 46 psi 28.6 psi 37.8 % PVC Truss (ASTM D 2680) 200 psi psi 23.7 % ABS Truss (ASTM D 2680) 200 psi psi 28.3 %

43 Definition of Fillers in PVC Resin Fillers are particulate materials that when added to the resin extend its volume and lower costs. Source: Modern Plastics World Encyclopedia 2001, Page C-14

44 Greenbook PVC Filler Specification Additives and fillers, including but not limited to stabilizers, antioxidants, lubricants, colorants, etc., shall not exceed 10 parts by weight per 100 of PVC resin in the compound. Source: Greenbook Standard Specifications for Public Works Construction 2012 Edition, Section Cell Classification, page 169

45 Section 5 Field Acceptance Testing

46 Rigid Pipe Acceptance Testing ASTM C Low Pressure Air Test

47 Flexible Pipe Deflection Testing Deflection Mandrel Laser Profiling

48

49 Laser Profiling of a Flexible Conduit Video is not available in PDF format. Please click here to view on the NCPI YouTube Channel. Video courtesy of Cues, Inc

50 Pipe x axis = 7.936

51 Pipe y axis = 7.874

52 Measurements x = 7.936; y = Average is: ASTM D 3034 SDR-35 is (+/ ) ASTM D 3034 Standard Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings (Table X1.1) Size Average Inside Diameter Base Inside Diameter 7.5% Deflection Mandrel

53 Actual Manufactured Average I.D inches 10.2% of Actual Pipe Diameter Base I.D inches ASTM D % Mandrel 7.09 inches (calculated from Base I.D.)

54 Section 6 Environmental Impact

55 Green Certification Programs There are over 400 sustainable products standards and/or certifications on the market.

56 Multi-Attribute Certified Sustainable Products Multi-attribute sustainable products have the highest market value because they advance the triple bottom line: Environment, Economy and Social Equity. SMaRT incorporates 41 single attribute standards.

57 SMaRT Certification System Sustainable Materials Rating Technology (SMaRT) Similar to the LEED system for building components, it is a transparent, third party certification program that considers the triple bottom line of environmental, social and economic costs. The SMaRT standard analyzes the impacts of a product s entire lifecycle, from raw materials extraction to manufacturing and transportation through end-use, disposal or recycling.

58 SMaRT Products Contribute to LEED Points Directly & Indirectly Direct LEED Contribution SMaRT Certified Sustainable are approved for LEED Innovation in Design (ID) Credits up to 2 pts total, Accessories Pilot Credit 43- Certified Products / EPDs, & LCA Pilot Credit. Lighting Phillips T8 Lamps Paints & Coatings AkzoNobel Powder Coating - Platinum Electrical Distribution Eaton Busway Eaton Lighting Control Panel Eaton UPS ELECTRICAL Philips T8 Lamps Gold Eaton Uninterrupted Power System Gold Eaton Busway - Gold Infrastructure Vitrified Clay Pipe Gold Ductile Iron Pipe Gold HARDWARE / FLOORING Forbo Linoleum - Platinum Forbo Furniture Linoleum - Platinum Forbo Bulletin Board Linoleum - Platinum Milliken Modular Carpet Tile Platinum Copeland Furniture Silver Durham Furniture Inc. Silver Harden Furniture Silver West Bros Furniture Silver Brown Street Furniture / Vermont Tubbs Silver Indirect LEED Contribution SMaRT Certified products can help contribute to your recycled content, energy reduction/management, lighting and more to earn points for your LEED Structure Forbo Bulletin Board Marmoleum - Gold Office Furniture Knoll Chairs Knoll File Systems Knoll Storage Systems Knoll Wood Surface Furniture Knoll ReGeneration EPD Forbo Furniture Marmoleum Doors Securall Doors - Gold Flooring Forbo Marmoleum - Platinum Milliken Carpet - Platinum Milliken Tile - Platinum FURNITURE Knoll Life Chair - Gold Knoll Chadwick Chair - Gold Knoll Generation Chair Platinum Knoll ReGeneration EPD Knoll Moment Chair - Gold Knoll Calibre Files Furniture Systems Gold Knoll Calibre Mobile Pedestal Furniture Systems Gold Knoll Calibre Fixed Pedestal Furniture Systems Gold Knoll Calibre Overhead Storage Furniture Systems Gold Knoll Calibre Storage Closet Furniture Systems Gold Knoll Template Wood Surfaces Furniture Systems Gold Knoll Template Steel Surfaces Furniture Systems Gold Knoll Template Glass Surfaces Furniture Systems Gold

59

60 PVC is one of the most environmentally hazardous consumer materials ever produced. PVC is the antithesis of a green building material. Efforts to speed adoption of safer, viable substitute building materials can have significant, tangible benefits for human health and the environment. Source: Environmental Impacts of Polyvinyl Chloride Building Materials Joe Thornton, Ph.D.

61 THE ENVISION RATING SYSTEM

62 Envision was developed in joint collaboration between the Zofnass Program for Sustainable Infrastructure at the Harvard University Graduate School of Design and the Institute for Sustainable Infrastructure. The Institute for Sustainable Infrastructure is a not-for-profit education and research organization founded by the American Public Works Association, the American Council of Engineering Companies and the American Society of Civil Engineers.

63

64 Section 7 Jointing Systems

65 Yesterday s Jointing Systems Arkansas Oct 1922

66 Yesterday s Jointing Systems Arkansas Oct 1922

67 Clay Joints Last Century & This Century

68

69 The Solution to Pollution is Dilution Source: American Sewerage Practice by Metcalf and Eddy, 1935

70 Polyurethane Compression Joint

71 O-Ring Compression Joint

72 O-Ring Compression Joint Assembly Video is not available in PDF format. Please click here to view on the NCPI YouTube Channel.

73 Plastics Two Major Categories: 1. Thermoset or thermosetting plastics. Once cooled and hardened, these plastics retain their shapes and cannot return to their original form. They are hard and durable. Thermosets can be used for auto parts, aircraft parts and tires. Examples include polyurethanes, polyesters, and epoxy resins. 2. Thermoplastics. Less rigid than thermosets, thermoplastics can soften upon heating and return to their original form. They are easily molded and extruded into films, fibers and packaging. Examples include polyethylene (PE), polypropylene (PP) and polyvinyl chloride (PVC). THESE MATERIALS CHANGE WITH AGE.

74 ASTM C 425 Joint Performance Verification The Joint shall not leak. Assembled pipe sections are filled with water and pressurized Shear Loaded 150 lbf/inch of nominal diameter Deflected to simulate extreme settlement

75 University of Houston Compression Joint Testing Tested 30 inch VCP, RCP,PVC, and FRP pipe. Using an external pressurized bladder assembled joints were tested in straight alignment, angular deflection, and shear load. Straight and Angular Deflection Tests: All pipe passed the 7 psi external test pressure without leakage. Shear Load Test: Only VCP exceeded the test protocol of 4500 lbs without leakage.

76 Joint Shear Load Test Shear Load (lbs) PVC FRP RCP VCP 0 30 inch Pipe Material Shear Load Test: The PVC and FRP pipe were tested at lower shear load values at the request of the plastic pipe industry.

77

78

79 NCPI is on the Road To join us for a small group demonstration in your area, please contact our office at: (262) or info@ncpi.org

80 Questions? Jeff Boschert, P.E. National Clay Pipe Institute (314) Cell National Clay Pipe Institute, 2013

PVC PIPE PERFORMANCE FACTORS

PVC PIPE PERFORMANCE FACTORS PVC PIPE PERFORMANCE FACTORS PVC pipe, like all flexible pipe products, is very dependent on the surrounding soil for its structural capacity, in addition, the pipe material must have sufficient inherent

More information

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. Furnish and install all storm drains, including manholes, inlets, service lines and other appurtenant

More information

Royal Seal Gasketed Sewer Pipe

Royal Seal Gasketed Sewer Pipe Royal Seal Gasketed Sewer Pipe Royal Seal Gasketed Sewer Pipe Royal Seal gasketed sewer pipe with our specially designed Double Seal Locked-In (DSLI ) gasket is an extremely durable pipe with a leak proof

More information

Module 3: Sewer Material Lecture 3: Sewer Material

Module 3: Sewer Material Lecture 3: Sewer Material Module 3: Sewer Material Lecture 3: Sewer Material [NPTEL, IIT Kharagpur, Prof. M.M.Ghangrekar, Department of Civil Engineering Page 1 3.0 SEWER MATERIAL 3.1 Important Factors Considered for Selecting

More information

Module 3 : Sewer Material. Lecture 3 : Sewer Material

Module 3 : Sewer Material. Lecture 3 : Sewer Material 1 P age Module 3 : Sewer Material Lecture 3 : Sewer Material 2 P age 3.1 Important Factors Considered for Selecting Material for Sewer Following factors should be considered before selecting material for

More information

SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO)

SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO) SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO) 1 Intent: The intent of trenchless sewer pipe Insertion is to rehabilitate the existing sewer

More information

SECTION 5: SANITARY SEWER SYSTEM DESIGN

SECTION 5: SANITARY SEWER SYSTEM DESIGN SECTION 5: SANITARY SEWER SYSTEM DESIGN 5.01 GENERAL Sanitary sewer improvements shall be designed to serve the ultimate level of City development as defined in the General Plan and the Wastewater Facilities

More information

INDEX. Sec. No. Items Page Nos.

INDEX. Sec. No. Items Page Nos. INDEX Sec. No. Items Page Nos. 1. Types of Pipe............... MSSP- 2 2. Concrete Pipe............... MSSP- 2 thru MSSP-3 3. ABS and PVC Truss Pipe............... MSSP- 3 4. ABS and PVC Solid Wall Pipe...............

More information

Flowtite Jacking Pipe

Flowtite Jacking Pipe U.S. COMPOSITE PIPE SOUTH, LLC. MEMBER OF KTI PIPE GROUP OF COMPANIES Flowtite Jacking Pipe 18585 Samuels Rd. Zachary, La. 70791 PH. 225-658-6166 Fax 225-658-0947 www.flowtitepipe.com Flowtite GRP Pipe

More information

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE 6.01 SCOPE The work covered by this section of the specifications consists of the furnishing of all plant, labor, materials, equipment and supervision and performing all operations involved in the construction

More information

Final Report. Sacramento County Sanitation District No. 1. Engineering Sustainability of Piping Materials

Final Report. Sacramento County Sanitation District No. 1. Engineering Sustainability of Piping Materials Final Report Sacramento County Sanitation District No. 1 Engineering Sustainability of Piping Materials Vitrified Clay Pipe (VCP) and Polyvinyl Chloride (PVC) Pipe: A Comparison By: Kurt N. Ohlinger, Ph.D.,

More information

HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS

HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS Shiwei William Guan, Ph.D. Vice President, R&D and International Business Madison Chemical Industries Inc. 490

More information

Native InDesign 2890 SaniTite Brochure 1/8" 100 300 CMYK April 17, 07

Native InDesign 2890 SaniTite Brochure 1/8 100 300 CMYK April 17, 07 Sanitary Sewer Pipe Tough pipe for a tough environment SaniTite Sanitary Sewer Pipe delivers the features that engineers, contractors and municipalities demand durability, performance, handling, toughness

More information

Rehabilitation Alternatives. MWEA Collection System Seminar October 1, 2009

Rehabilitation Alternatives. MWEA Collection System Seminar October 1, 2009 Rehabilitation Alternatives MWEA Collection System Seminar October 1, 2009 Overview Types of Rehabilitation Trenchless Categories On-Line Replacement In-Situ Options Selecting the Best Solution Types of

More information

ENGINEERED SOLUTIONS. A2 Liner Pipe for Trenchless Technology

ENGINEERED SOLUTIONS. A2 Liner Pipe for Trenchless Technology ENGINEERED SOLUTIONS A2 Liner Pipe for Trenchless Technology A2 Liner Pipe Restores Deteriorated Sewers Cost-Effective Rehabilitation The increasing rate of sanitary and storm sewer deterioration requires

More information

OAR52 A-1 (September, 1981)

OAR52 A-1 (September, 1981) APPENDIX A SEWER PIPELINES (1) MINIMUM REQUIREMENTS FOR SEWER - PIPELINES (a) Capacity: Sewers shall be of such diameter as to pass without overflow, bypass, or back flow onto damageable property of a

More information

SECTION 15125 HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION

SECTION 15125 HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION SECTION 15125 HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION PART 1 GENERAL.01 SECTION INCLUDES Furnishing and installing 4 inch through 16 inch high density

More information

The Most Advanced Name in Drainage Systems. Sanitary Sewer Pipe

The Most Advanced Name in Drainage Systems. Sanitary Sewer Pipe The Most Advanced Name in Drainage Systems Sanitary Sewer Pipe SaniTite Sanitary Sewer Pipe delivers the features that engineers, contractors and municipalities demand durability, performance, handling,

More information

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials

More information

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY Approved and adopted as Official Document Number 800576 this 10th day of December, 1980 Donald R. Boyd, P.E., Director Water

More information

SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE

SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE PART 1: GENERAL 1.01 SECTION INCLUDES PVC pressure pipe and fabricated fittings in nominal sizes 4-inches through 12-inches with cast iron pipe equivalent

More information

Green Thread Product Data

Green Thread Product Data Green Thread Product Data Applications Dilute Acids Caustics Produced Water Industrial Waste Hot Water Condensate Return Materials and Construction All pipe manufactured by filament winding process using

More information

Installation of Large Diameter Buried Pipes

Installation of Large Diameter Buried Pipes Installation of Large Diameter Buried Pipes Sullivan (Sully) Curran P. E., Executive Director I. Introduction and Scope There is an ongoing need to provide designers, specifiers, engineers, consultants

More information

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS While its use is not required, this checklist has been prepared to provide the field inspector a summary

More information

Culvert Repair, Materials, and Structural Design 4.4-1

Culvert Repair, Materials, and Structural Design 4.4-1 Culvert Repair, Materials, and Structural Design 4.4-1 4.4 Culvert Materials 4.4.1 General Culverts are primarily made with reinforced concrete, corrugated metal, and more recently, solidwall, profile

More information

The surface roughness of the polyurethane lining is 10 times lower than cement-lined pipes.

The surface roughness of the polyurethane lining is 10 times lower than cement-lined pipes. QUALITY INSIDE When it comes to long life piping for drinking water, sewage, industrial water or gas, there is one name that continues to lead the way - ECOPUR by vonroll. Delivering precision-engineered

More information

Structural Testing of GeoPolymer Pipe/Culvert Lining

Structural Testing of GeoPolymer Pipe/Culvert Lining Structural Testing of GeoPolymer Pipe/Culvert Lining Joseph Royer, Ph.D. October 27 th, 2015 What is a GeoPolymer? Not a Plastic Not HDPE/PVC/Epoxy Looks and feels like cement Workability Material Properties

More information

Gasketed PVC Sewer Pipe Durable, Flexible, Reliable Waterworks Products

Gasketed PVC Sewer Pipe Durable, Flexible, Reliable Waterworks Products Gasketed PVC Sewer Pipe Durable, Flexible, Reliable Waterworks Products www.pwpipe.com PWPipe Sewer Pipe Tough, Dependable, and Leak-free. Here s why: Figure 1. PWPipe Gasket Insertion line Bell is an

More information

DISTRIBUTION PIPING MATERIALS: BUILDING HYDRONIC SYSTEM MANAGEMENT. Jim Riley, Texas A&M University February 10, 2015

DISTRIBUTION PIPING MATERIALS: BUILDING HYDRONIC SYSTEM MANAGEMENT. Jim Riley, Texas A&M University February 10, 2015 DISTRIBUTION PIPING MATERIALS: BUILDING HYDRONIC SYSTEM MANAGEMENT Jim Riley, Texas A&M University February 10, 2015 Piping at Texas A&M 2 History of Distribution Piping at Texas A&M Concrete reinforced

More information

DIVISION 4300 STORM DRAINAGE

DIVISION 4300 STORM DRAINAGE DIVISION 4300 STORM DRAINAGE SECTION 4305 STORM SEWER PART 1 - GENERAL 1.01 SCOPE This section covers the construction of storm sewers for the collection and transport of stormwater runoff. 1.02 REFERENCES

More information

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) 55-1 GENERAL The Contractor shall perform all work required by the plans for construction of pipe for storm drains, precast polymer trench drains

More information

PP MASTERTM S T I F F N E S S S N 1 2 R I N G THE NEW POLYPROPYLENE SEWER PIPE SYSTEM

PP MASTERTM S T I F F N E S S S N 1 2 R I N G THE NEW POLYPROPYLENE SEWER PIPE SYSTEM PP MASTERTM R I N G S T I F F N E S S S N 1 2 THE NEW POLYPROPYLENE SEWER PIPE SYSTEM The future today. PP MASTERTM The new standard in sewer construction. A powerful piece of the future: PP MASTER, a

More information

SECTION 724 PIPE CULVERTS

SECTION 724 PIPE CULVERTS SECTION 724 PIPE CULVERTS 724.1 Description. This work shall consist of providing pipe or pipe arch of the diameter or shape designated, laid upon a firm bed and backfilled as specified. Where appropriate

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 1100 SLIP-LINING SANITARY SEWERS

San Antonio Water System Standard Specifications for Construction ITEM NO. 1100 SLIP-LINING SANITARY SEWERS ITEM NO. 1100 SLIP-LINING SANITARY SEWERS 1100.1 DESCRIPTION: This item shall consist of slip-lining sanitary sewer pipe, which is accomplished by pulling or pushing liner pipe into existing sewers by

More information

TABLE OF CONTENTS SECTION 500 SANITARY SEWER AND FORCE MAIN

TABLE OF CONTENTS SECTION 500 SANITARY SEWER AND FORCE MAIN TABLE OF CONTENTS SECTION 500 SANITARY SEWER AND FORCE MAIN Starts on Page 500 GENERAL... 2 501 MATERIALS... 2 502 CONSTRUCTION PROCEDURES... 7 503 ABANDONMENT OF EXISTING SANITARY SEWER FACILITIES...

More information

VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10

VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 SECTION B1: PREPARATION GUIDE B1.1 INTRODUCTION... B1-1

More information

PROCESSING OF VARIOUS MATERIALS

PROCESSING OF VARIOUS MATERIALS 4 PROCESSING OF VARIOUS MATERIALS CHAPTER CONTENTS 4.1 Shaping Processes for Polymers Polymers Manufacturing Processes for Polymers 4.2 Rubber Processing Technology Processing of rubber into finished good

More information

High Density Polyethylene Liners for Rehabilitation of Corroded Pipelines

High Density Polyethylene Liners for Rehabilitation of Corroded Pipelines High Density Polyethylene Liners for Rehabilitation of Corroded Pipelines Jeff Schell General Manager United Pipeline Middle East, Inc. Introduction HDPE Liners A cost effective and environmentally beneficial

More information

Mainline Pipe Rehabilitation Using Cured-in-Place Pipe (CIPP) & Folded Pipe Technology

Mainline Pipe Rehabilitation Using Cured-in-Place Pipe (CIPP) & Folded Pipe Technology 2007 Pumper & Cleaner Environmental Expo International Wednesday February 7, 2007 Mainline Pipe Rehabilitation Using Cured-in-Place Pipe (CIPP) & Folded Pipe Technology What is Cured-In-Place Pipe (CIPP)

More information

Pipeline Replacement using Relining

Pipeline Replacement using Relining Pipeline Replacement using Relining Mark Heathcote, March 2006 Relining of old pipeline systems is becoming an increasingly attractive option to asset owners and operators as an effective alternative to

More information

City of Lincoln, Nebraska STEVENS CREEK BASIN TRUNK SEWER TECHNICAL MEMORANDUM NO. 5 PIPE MATERIAL SELECTION TABLE OF CONTENTS

City of Lincoln, Nebraska STEVENS CREEK BASIN TRUNK SEWER TECHNICAL MEMORANDUM NO. 5 PIPE MATERIAL SELECTION TABLE OF CONTENTS City of Lincoln, Nebraska STEVENS CREEK BASIN TRUNK SEWER TECHNICAL MEMORANDUM NO. 5 PIPE MATERIAL SELECTION TABLE OF CONTENTS Page No. 1.0 INTRODUCTION...2 2.0 PIPE MATERIAL CONSIDERATIONS...3 2.1 RCP...

More information

Letty Arvide-Gomar, PE

Letty Arvide-Gomar, PE Letty Arvide-Gomar, PE Outline DIP History and Applications Corrosion Issues Internal Cleaning Technologies Rehabilitation Options DIP History and Applications Corrosion Issues Internal Cleaning Technologies

More information

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TN 5.14 February 2010 Introduction It may be at times necessary, in an aging infrastructure, to rehabilitate drainage and sanitary lines

More information

SPR PE Steel Reinforced Liner

SPR PE Steel Reinforced Liner ENGINEERED SOLUTIONS SPR PE Steel Reinforced Liner Reline Done Right Contech is your single source for rehabilitation of sanitary & storm sewers, culverts and bridges. Contech Engineered Solutions has

More information

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors. SUBDRAINS AND FOOTING DRAIN COLLECTORS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Subdrains B. Subdrain Cleanouts and Outlets C. Footing Drain Collectors D. Storm Sewer Service and Connections 1.02 DESCRIPTION

More information

100 Year Service Life of Polypropylene And Polyethylene Gravity Sewer Pipes. Summary Technical Report

100 Year Service Life of Polypropylene And Polyethylene Gravity Sewer Pipes. Summary Technical Report December 2014 100 Year Service Life of Polypropylene And Polyethylene Gravity Sewer Pipes A TEPPFA Project in cooperation with Borealis and LyondellBasell Summary Technical Report (Based on Extracts of

More information

60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING 60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed

More information

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES 33 00 00 SITE UTILITIES

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES 33 00 00 SITE UTILITIES SECTION INCLUDES Domestic Water Fire Water Service Water Well Sanitary Sewer Storm Drains Foundation Drainage RELATED SECTIONS 03 30 00 Concrete 21 00 00 Fire Suppression - Sprinklers 22 00 00 Plumbing

More information

Structural Rehabilitation of Rigid Pipes. George McAlpine 1, Affiliate, ASCE

Structural Rehabilitation of Rigid Pipes. George McAlpine 1, Affiliate, ASCE Published in Trenchless Pipeline Projects Proceedings of the Conference American Society of Civil Engineers Held June 8-11, 1997, Boston, Massachusetts Structural Rehabilitation of Rigid Pipes George McAlpine

More information

AGENDA. Pipe Materials / Trends The Reason for Change Design / Standards Pipe Selection Installation Examples Conclusion

AGENDA. Pipe Materials / Trends The Reason for Change Design / Standards Pipe Selection Installation Examples Conclusion AGENDA Pipe Materials / Trends The Reason for Change Design / Standards Pipe Selection Installation Examples Conclusion Water & Sewerage Pipe Materials Flexible Pipes Replacing Rigid Pipes Old Days Vitrified

More information

Industrial Pipeline Integrity Management & Remote Polyurea Pipe Lining Systems.

Industrial Pipeline Integrity Management & Remote Polyurea Pipe Lining Systems. Industrial Pipeline Integrity Management & Remote Polyurea Pipe Lining Systems. Aging pipeline infrastructure and industry s inability to evaluate and inspect has left many engineers and plant managers

More information

SANITARY SEWER SPECIFICATIONS

SANITARY SEWER SPECIFICATIONS SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,

More information

ElastoFlake & ElastoTec

ElastoFlake & ElastoTec ElastoFlake & ElastoTec Relining Group 02 Revolutionally injection casting ElastoFlake, a new material from the Relining Group, is a polymer plastic mass intended for injection casting, which was developed

More information

MANUFACTURER'S CERTIFICATION SCHEDULE 40 PVC PIPE And SCHEDULE 80 PVC PIPE

MANUFACTURER'S CERTIFICATION SCHEDULE 40 PVC PIPE And SCHEDULE 80 PVC PIPE SCHEDULE 40 PVC PIPE And SCHEDULE 80 PVC PIPE PVC materials used in Schedule 40 and Schedule 80 pipe manufactured by Texas United Pipe, Inc., comply with the ASTM Standard D-1784 and are a Type I Grade

More information

X Planning X Quality X Maintenance & Operations

X Planning X Quality X Maintenance & Operations Delaware Department of Transportation Division of Transportation Solutions Design Guidance Memorandum Memorandum Number 1-20 Revised 1. Road Design Manual 2. Bridge Design Manual 3. Utilities Design Manual

More information

Corrosion protection linings. Issue 1

Corrosion protection linings. Issue 1 Corrosion protection linings Issue 1 Introduction While Humes sewerage pipes and products are designed to serve over 100 years in accordance with AS/NZS 4058, we offer corrosion protection linings to increase

More information

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES PART 1 - GENERAL 1.1 SCOPE OF WORK SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED SQUARE TUBE LADDER

More information

Scepter PVC Molded Junction Boxes

Scepter PVC Molded Junction Boxes Scepter PVC Molded Junction Boxes ELECTRICAL SYSTEMS PVC MOLDED JUNCTION BOXES 4" to 12" We build tough products for tough environments Standing Still is Not an Option. We re proud to introduce the NEW

More information

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying

More information

MaxCell Technical Manual Design Parameters

MaxCell Technical Manual Design Parameters MaxCell Technical Manual Design Parameters Breaking Strength by Product Style, lbs Product Style Standard MaxCell Fire Resistant MaxCell Test Method 4 Cell 2,750 2,200 ASTM D 5 Bellcore 5 5.. Cell 2,50

More information

MICRO PLASTICS MOLDED NYLON 6/6 FASTENERS MECHANICAL TEST DATA - UNC - UNF SECTION

MICRO PLASTICS MOLDED NYLON 6/6 FASTENERS MECHANICAL TEST DATA - UNC - UNF SECTION MICRO PLASTICS MOLDED NYLON 6/6 FASTENERS MECHANICAL TEST DATA - UNC - UNF Nylon 6/6 meets MIL-M20693B "A" Type 1, LP410A, and ASTM D789-66 Type 1, GDE 2 All test performed per ASTM specifications. Parts

More information

The Original Carbon Fiber Reinforced Polymer System

The Original Carbon Fiber Reinforced Polymer System Infrastructure The Original Carbon Fiber Reinforced Polymer System Phone: 52.292.39 Toll Free: 866.38.269 Fax: 52.48.5274 282 E. Fort Lowell Rd. Tucson, AZ 8576 www.dowaksausa.com Test results are supported

More information

1.5 Concrete (Part I)

1.5 Concrete (Part I) 1.5 Concrete (Part I) This section covers the following topics. Constituents of Concrete Properties of Hardened Concrete (Part I) 1.5.1 Constituents of Concrete Introduction Concrete is a composite material

More information

Appendix A: Acceptable pipe and fitting materials

Appendix A: Acceptable pipe and fitting materials Watercare Services Limited Water and Code of Practice Content from the NZS 4404:2010 Land development and subdivision infrastructure has been reproduced for use in the Infrastructure Design s Manual for

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER 11 STORM DRAINAGE SECTION 11 GENERAL 11.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. 11.2 Where required. All roofs,

More information

Annular Space Grouting of Slipline Products

Annular Space Grouting of Slipline Products Annular Space Grouting of Slipline Products by David Gellings(, M.APWA & John Jurgens(, M.WWCPA Traditional methods of using neat cement slurries, (Portland cement and water, cement with fly ash or cement

More information

Town House 11265 Center Highway North Huntingdon, PA 15642

Town House 11265 Center Highway North Huntingdon, PA 15642 APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House

More information

STANDARD SPECIFICATIONS SECTION 02701 INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223

STANDARD SPECIFICATIONS SECTION 02701 INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223 STANDARD SPECIFICATIONS SECTION 02701 INSTALLATION OF GRAVITY SEWER PIPELINES PART 1 - GENERAL A. Description This section describes the installation of gravity sewer pipelines fabricated of vitrified

More information

Ultra-Rib PVC Storm Sewer Pipe 8" - 30"

Ultra-Rib PVC Storm Sewer Pipe 8 - 30 Ultra-Rib PVC Storm Sewer Pipe 8" - 30" Ultra-Rib is a PVC Storm Sewer Pipe That Provides Superior Structural Capabilities Waterworks Products PW Eagle s Ultra-Rib is an open profile PVC gravity-flow storm

More information

Ridgistorm-XL - the latest innovative

Ridgistorm-XL - the latest innovative Ridgistorm-XL - the latest innovative solution to SUDS and stormwater management Combined with the technical expertise, knowledge and support of Polypipe, Ridgistorm-XL is designed as a bespoke application

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

Using StrongPIPE Hybrid FRP for PCCP Rehab in Miami-Dade System

Using StrongPIPE Hybrid FRP for PCCP Rehab in Miami-Dade System Using StrongPIPE Hybrid FRP for PCCP Rehab in Miami-Dade System Luis Aguiar Miami-Dade Water & Sewer Department Anna Pridmore, PhD Structural Technologies PROJECT BACKGROUND Miami-Dade Water & Sewer Department

More information

h Sewer Pipe Systems

h Sewer Pipe Systems h Sewer Pipe Systems 2 h Sewer Pipes Innovative Manufacturing Process The first industrial application for HOBAS Pipes was as penstocks for hydroelectric power stations in the 1960s. It was not however

More information

PROVIDING THE SAFE CHOICE FOR UNDERGROUND PIPE RENEWAL, INTEGRITY MANAGEMENT AND ASSET RELIABILITY

PROVIDING THE SAFE CHOICE FOR UNDERGROUND PIPE RENEWAL, INTEGRITY MANAGEMENT AND ASSET RELIABILITY PROVIDING THE SAFE CHOICE FOR UNDERGROUND PIPE RENEWAL, INTEGRITY MANAGEMENT AND ASSET RELIABILITY Cured-In-Place Pipe Pressure & Gravity Lines Pipe Splitting Trenchless Pipe Replacement EcoCast Advanced

More information

The Pipe/Soil Structure Actions and Interactions

The Pipe/Soil Structure Actions and Interactions Chapter 4 The Pipe/Soil Structure Actions and Interactions Lester H. Gabriel, Ph.D., P.E. THE PIPE/SOIL STRUCTURE ACTIONS AND INTERACTIONS Composite Structures Principles of Analysis Predictability of

More information

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS SECTION 200: STORM SEWER CONSTRUCTION STANDARDS Page No. Description 200-2 201 GENERAL 200-2 201.1 SPECIFICATIONS 200-2 201.2 CONNECTION TO EXISTING FACILITIES 200-3 202 MATERIALS 200-3 202.1 PIPES 200-4

More information

Technical Data Sheet February 2014

Technical Data Sheet February 2014 Scotch-Weld Technical Data Sheet February 2014 Product Description s are high performance, two-part acrylic adhesives that offer excellent shear, peel, and impact performance. These toughened products

More information

Tiangang TM BW-10LD (622)

Tiangang TM BW-10LD (622) Tiangang TM BW-10LD Oligomeric Hindered Amine Light Stabilizer (HALS) Poly-(N-β-hydroxyethyl-2,2,6,6-tetramethyl-4-hydroxy-piperidyl-succinate) CAS number 65447-77-0 BW-10LD BW-10LD is a highly effective

More information

REVIEW OF TRENCHLESS TECHNIQUES FOR THE REHABILITATION OF SEWERS. Gerhard (Gerry) P. Muenchmeyer, P.E. Muenchmeyer Associates, LLC

REVIEW OF TRENCHLESS TECHNIQUES FOR THE REHABILITATION OF SEWERS. Gerhard (Gerry) P. Muenchmeyer, P.E. Muenchmeyer Associates, LLC REVIEW OF TRENCHLESS TECHNIQUES FOR THE REHABILITATION OF SEWERS Gerhard (Gerry) P. Muenchmeyer, P.E. Muenchmeyer Associates, LLC What is really out there? DO YOU DIG IT? INDUSTRY CONCERNS UNEXPECTED DEVELOPMENTS

More information

Section 2100-Trenching and Tunneling

Section 2100-Trenching and Tunneling SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial

More information

Section 02702 SEWER PIPE INSTALLATION AND TESTING

Section 02702 SEWER PIPE INSTALLATION AND TESTING PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete

More information

ASTM D 1599 Standard Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings

ASTM D 1599 Standard Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings ASTM D 1599 Standard Test Method for Resistance to Short-Time Hydraulic Pressure of Plastic Pipe, Tubing, and Fittings This test method establishes the short-time hydraulic failure pressure of pipe and

More information

Foam Firmness Measurements IFD For Most Furniture And Bedding Applications

Foam Firmness Measurements IFD For Most Furniture And Bedding Applications INTOUCH is a regular publication of the Polyurethane Foam Association. It covers topics of interest to users of flexible polyurethane foam and is designed as a quick reference e for background information

More information

Resistance of Plastics to Gamma Irradiation

Resistance of Plastics to Gamma Irradiation Elastomers 1 MATERIAL TOLERANCE LEVEL (kgy) COMMENTS Butyl 50 Sheds particulate after irradiation. Ethylene Propylene 100 200 Crosslinks, yellows slightly. Diene Monomer (EPDM) Fluoro Elastomer 50 Avoid

More information

GUIDE TO WINDOW REPAIR & REPLACEMENT FOR HISTORIC PROPERTIES

GUIDE TO WINDOW REPAIR & REPLACEMENT FOR HISTORIC PROPERTIES Approved by City of Phoenix Historic Preservation Commission 8/15/2011 CITY OF PHOENIX PLANNING & DEVELOPMENT DEPARTMENT HISTORIC PRESERVATION OFFICE GUIDE TO WINDOW REPAIR & REPLACEMENT FOR HISTORIC PROPERTIES

More information

REHABILITATION OF UNDERGROUND SEWER LATERAL PIPES WITH CURED-IN-PLACE-PIPE LINER SECTION 02542

REHABILITATION OF UNDERGROUND SEWER LATERAL PIPES WITH CURED-IN-PLACE-PIPE LINER SECTION 02542 1.0 INTENT REHABILITATION OF UNDERGROUND SEWER LATERAL PIPES 1.01 It is the intent of this specification to provide for the reconstruction of pipelines and conduits by the installation of a resin-impregnated

More information

ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. July 1, 2008 Revision 2

ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. July 1, 2008 Revision 2 ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES 1 PART 1 - GENERAL 1.0 GENERAL 1.1 REFERENCES: SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED FIBERGLASS

More information

PC-Concrete Injectable Concrete Anchoring and Repair System

PC-Concrete Injectable Concrete Anchoring and Repair System PC-Concrete Injectable Concrete Anchoring and Repair System DESCRIPTION: PC-Concrete is a two component (1:1 ratio), 100% solids, high modulus, structural epoxy paste. PC-Concrete is a solvent free, no

More information

IS THAT LINER THICK ENOUGH?

IS THAT LINER THICK ENOUGH? IS THAT LINER THICK ENOUGH? Philip McFarlane, Opus International Consultants Ltd ABSTRACT The amount of pipeline rehabilitation being undertaken in New Zealand is increasing each year. Larger diameter

More information

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development 7 SPECIFICATIONS There is currently no Irish specification for construction of drainage works, or water supply works. There are several publications that give guidance on drainage works, such as the Building

More information

GLOBAL MANUFACTURING. ARAUJO, Anna Carla AUG, 2015 Mechanical Engineering Department POLI/COPPE/UFRJ

GLOBAL MANUFACTURING. ARAUJO, Anna Carla AUG, 2015 Mechanical Engineering Department POLI/COPPE/UFRJ GLOBAL MANUFACTURING ARAUJO, Anna Carla AUG, 2015 Mechanical Engineering Department POLI/COPPE/UFRJ Changing Schedule: 5-24/8 - Fabrication of Plastic, Ceramics and Composites 6-26/8 Fabrication of Ceramics

More information

External Wrapping of Steel Riser Pipe. Case Study HJ3 CS200902

External Wrapping of Steel Riser Pipe. Case Study HJ3 CS200902 External Wrapping of Steel Riser Pipe Case Study HJ3 CS200902 Introduction Refineries process a wide variety of petroleum products. As part of the process, they rely on cooling towers, which recycle water

More information

TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe

TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe TN 5.18 October 2015 In sanitary sewer, it is often necessary to use trenchless technology methods to install a casing pipe under high volume roads,

More information

PVC Gasketed & Solvent Weld Pipe

PVC Gasketed & Solvent Weld Pipe PVC Gasketed & Solvent Weld About Royal Building Products Royal Building Products has been in business for over 100 years when Royal Abbotsford, Canada facility started producing clay. With shift in demand

More information

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer The user may choose to adopt part or all of this Model Specification; however, the user should ensure that all parts

More information

Wastewater Capital Projects Management Standard Construction Specification

Wastewater Capital Projects Management Standard Construction Specification CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,

More information

DUCTILE IRON PIPE FOR WASTEWATER APPLICATIONS

DUCTILE IRON PIPE FOR WASTEWATER APPLICATIONS DUCTILE IRON PIPE FOR WASTEWATER APPLICATIONS DUCTILE IRON PIPE FOR WASTEWATER APPLICATIONS The 1972 AMENDMENTS to Public Law 92-500 (the Clean Water Act) established the federal government s largest domestic

More information

Pipes and Fittings for Gravity Sewer Mains. SewerMAX

Pipes and Fittings for Gravity Sewer Mains. SewerMAX SewerMAX High resistance to tree root intrusion and groundwater infiltration lightweight for ease of installation low embodied energy for environmental benefits long service life Excellent chemical resistance

More information

Series 4000 Fiberglass Pipe and Fittings

Series 4000 Fiberglass Pipe and Fittings Series 4000 Fiberglass Pipe and Fittings for corrosive industrial service Uses and applications Listings Performance Acid drains Chemical process piping Corrosive slurries Food processing Geothermal Nonoxidizing

More information

Foam Injection Molding:

Foam Injection Molding: Foam Injection Molding: Unique Process Solutions for Light Weighting Automotive Plastic Parts Steve Braig President & CEO Trexel, Inc. AGENDA Technology Overview > Chemical Foaming > Physical Foaming Foamed

More information