LONG-TERM power system voltage instability has been

Size: px
Start display at page:

Download "LONG-TERM power system voltage instability has been"

Transcription

1 400 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, FEBRUARY 2005 A Knowledge-Based System for Supervision and Control of Regional Voltage Profile and Security Alessandro B. Marques, Glauco N. Taranto, Senior Member, IEEE, and Djalma M. Falcão, Fellow, IEEE Abstract This paper presents a knowledge-based system for supervision and control of regional voltage profile and security using fuzzy logic. The control strategies are defined by system operators based on their experience and on off-line studies, which are translated into rules of a hierarchical fuzzy inference system (FIS). Two hierarchical levels, namely, task-oriented control level (high level) and set-point control level (low level) compose the control structure. The high-level control is comprised of a continuous FIS that updates high-side voltage set points at power plants, and a discrete FIS that switches capacitor/reactor banks at the transmission network. The low level control is comprised of automatic voltage regulators and joint var controllers at the power plants. It is presented a simulation study in the Rio de Janeiro (Rio) Area, an energy importing region part of the South/Southeastern Brazilian system. Index Terms Coordinated voltage control, fuzzy logic, hierarchical control, knowledge-based systems, voltage security. I. INTRODUCTION LONG-TERM power system voltage instability has been object of increasing concern of various electric utilities around the world. The coordinated, maybe automatic, utilization of the various available reactive power sources can be an effective way of mitigating this problem. Electric utilities in some European countries [1] [6] have adopted strategies that maintain an adequate voltage profile at key regions of the system on different loading scenarios. Since the 1980s, the French [1] [3] are utilizing an automatic coordinated voltage control, which is based on three hierarchical levels, namely primary, secondary and tertiary. Control actuation time constants in each level differ one from the other by one order of magnitude. In Italy [4], [5], the coordinated voltage control has some similarities to the French approach. It has been satisfactorily employed nationwide for some years. Coordinated voltage control has also been employed in Belgium since 1998 [6], as a tool to support decisions made by the system operators. In this application, the secondary hierarchical level, as defined by the French proposition, is not utilized. In Brazil, a research project was carried out with the purpose of quantifying the benefits and limitations of applying secondary voltage control schemes using PI-based control structure, as defined by the Europeans, to the Rio Area [7]. Manuscript received October 16, This work was supported in part by CNPq, CAPES, and FAPERJ. Paper no. TPWRS A. B. Marques is with Petrobras, Rio de Janeiro, RJ, Brazil ( abulhoes@br-petrobras.com.br). G. N. Taranto and D. M. Falcão are with Federal University of Rio de Janeiro/COPPE, Rio de Janeiro, RJ, Brazil ( tarang@coep.ufrj.br; falcao@nacad.ufrj.br). Digital Object Identifier /TPWRS Control strategies that maintain the network voltage profile within secure operating limits, and keep the dynamic reactive power reserves maximized over different loading scenarios and network configurations, require an efficient coordination among the reactive power sources [8]. Control actions in opposite directions in a short period of time, inevitably mean unnecessary actions and should be avoided. This paper presents a knowledge-based system for supervision and control of regional voltage profile using fuzzy logic. Control strategies are defined by the system operators based on their experience and on off-line studies, which are translated into rules of a hierarchical fuzzy inference s ystem (FIS). The hierarchical FIS presented in this paper is built upon the work in [9], which dealt only with a FIS for continuous variables. While modern control theory has made modest progress in practice, fuzzy logic control has been rapidly gaining acceptance among practicing engineers [10]. This can be attributed to the fact that fuzzy logic provides a powerful vehicle that allows engineers to incorporate human reasoning in the control algorithm. As opposed to the modern control theory, fuzzy logic design is not based on the mathematical model of the process. The controller designed using fuzzy logic implements human reasoning that has been programmed into fuzzy logic language (membership functions, rules, inference engine, fuzzification and defuzzification) [11]. The use of conventional control methods in coordinated voltage/reactive power control is rather difficult due to highly nonlinear relationship between voltage magnitude and reactive power, and the existence of discrete voltage control equipment. Moreover, the system-dependent transmission voltage control calls for customized solutions. Fuzzy logic control is quite adequate to this application since nonlinear control laws naturally arise from the operational experience coded into fuzzy rules. A number of expert systems have been proposed for reactive power and voltage control [12], [13]. A fuzzy linear programming-based tool to help operators in reactive power and voltage control is described in [14]. More recently, closed-loop fuzzy voltage/var control systems for on-line application have also been presented [10], [15]. The study system analyzed is the Rio de Janeiro (Rio) Area, an energy importing area with a peak load of 6000 MW, which is part of the South/Southeastern Brazilian system. The simulation studies are performed through the use of a fast simulation tool, where the fast transients are assumed to be stable and neglected. Slow-acting voltage mechanisms, such as LTC actuation and overexcitation limiters, are thoroughly modeled. The simulator [16] was developed following the ideas described in [17] /$ IEEE

2 MARQUES et al.: KNOWLEDGE-BASED SYSTEM FOR SUPERVISION AND CONTROL 401 Fig. 1. FIS. II. BASICS OF A FIS FISs are methods for information processing dealing with uncertainty and vagueness based on the theory of fuzzy sets and fuzzy logic [11]. A FIS is based on rules of the following type: Fig. 2. General overview. where x and y are numerical variables and A and B are linguistic variables, i.e., variables that assume linguistic values such as HIGH, LOW, NOT TOO LOW, etc., which are defined by fuzzy sets and their membership functions. Fig. 1 shows the main elements of a FIS that is used in fuzzy logic controllers and signal processing applications. The FIS maps crisp inputs into crisp outputs. The four main elements are the rules, the inference engine, the fuzzifier, and the defuzzifier. Description of the main elements is as follows. Rules: a set of rules as defined before. Fuzzifier: determines the degree of membership of each input in the rule antecedent. If the antecedent has more than one component (proposition), the fuzzy operators AND (min) and OR (max) are used to combined the effects. Inference Engine: determines the degree of validity of the rule consequent and combines the results into the output fuzzy set. The principle assumed is that rules with a low membership degree in the antecedent must have small validity in the consequent. Defuzzifier: determines a crisp output from the fuzzy set produced by the inference engine. Once the rules have been established, a FIS can be viewed as a nonlinear mapping from a crisp input vector to a crisp output vector. III. CONTROL SYSTEM DESCRIPTION Fig. 2 shows a general overview of the proposed two-level supervision and control structure for coordination of task-oriented and set-point controls for regional voltage profile and security. The low-level feedback control is comprised by the generating unit s AVR and by the power plant s JVC. The high-level feedforward control is comprised by a hierarchy of two FIS: there is a FIS that updates the set-points of the high-side voltages at power plants, namely, continuous FIS (CFIS), and another FIS that decides the switching of capacitor and reactor banks at the transmission network, namely, discrete FIS (DFIS). The high-level controller may receive data from the SCADA system and/or from dedicated remote measurements. Depending on the physical characteristics of the power system, a priority list of actions for the continuous and the discrete controls must be chosen. Considering that priority is given to the continuous control 1, this resource is used to exhaustion or used until some limits are reached before any action from the discrete controls is taken. Those limits could be the capability of the machines or some variable on the transmission network, e.g., voltage in a bus other than the generator bus. In such cases, a defensive layer detects the problems and calls for the help of the discrete controls, whenever available. This strategy is conducive to: minimize the number of capacitor/reactor bank switching operations; maximize the generation of reactive power from the line charging of the network in heavy load conditions and to minimize it in light/minimum load conditions; this strategy is especially useful for systems where the loads are fed through very long EHV transmission lines, which is the case of the Rio Area system; hold the voltage at regulated buses smooth most of the time, avoiding excessive spikes caused by the switching of discrete devices. The CFIS and the DFIS are built with rules that come from the experience of system operators and from off-line studies. Fig. 3 shows that the CFIS is subdivided in a FIS for heavy/median load operating conditions and another one for light/minimum load operating conditions. Qualitatively the rules are the same on both FIS, although they can be made different if necessary. The main difference is the voltage set-point values for some busses on the system. The decision, in which FIS information should be processed, may be given by the value of the system demand, the time of day, etc. Fig. 4 shows the internal hierarchical structure of the DFIS subdivided in three layers on which information is processed 1 This control strategy was chosen in order to comply with actual operational practices currently adopted in the studied system (Rio Area).

3 402 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, FEBRUARY 2005 Fig. 3. CFIS. before the final decision is made. Besides the information provided by the SCADA system and/or by the remote measurement system that indicates the status of the switching devices, the DFIS also receives information from the defensive layer. The information from the defensive layer indicates whether static reactive power must be switched on/off. The first and second layers are further subdivided according to the substations where there are capacitor and reactor banks that participate in the coordinated regional voltage control. For each substation there is a corresponding FIS that decides which shunt bank should be switched. The first layer receives information from the defensive layer and outputs vague information for the amount of reactive power to be switched (few, much, too much, etc). The output of the first layer, together with the status of the switching devices in each substation, are the inputs to the second layer. The output of the second layer is a decision of which shunt bank should be switched on/off in each substation. The third layer deliberates the only one device, among the outputs of the second layer that should be switched on/off. The DFIS has underlying rules that checks for switching inconsistencies, i.e., no capacitor bank must be switched on if there are any reactor banks turned on. IV. APPLICATION TO COORDINATED VOLTAGE CONTROL The system studied is an equivalent of the Brazilian South/ Southeastern system modeled with 730 buses, 1146 branches, and 104 generators. The region of interest for the studies is the so-called Rio Area, which consists of the electric utilities Light, Cerj, Escelsa, and part of the Furnas system. It mainly represents the Rio de Janeiro metropolitan area, with a peak load of approximately 6000 MW in the summer time (from January to March). Fig. 5 depicts the bulk power transfer corridors that lead to the Rio Area and the main dynamic reactive power resources for voltage control in the area. In the 500-kV corridor, Marimbondo hydro plant and Angra nuclear plant are the main dynamic reactive sources for voltage control, whereas in the 345-kV corridor, Furnas hydro plant is the main reactive source. Although L.C.Barreto and V.Grande hydro plants are located at the 345-kV corridor, their influence in the Rio Area voltage profile is of less importance. The main sources of Fig. 4. DFIS. dynamic reactive power support within the Rio Area are two Mvar synchronous condensers (SCs) at Grajau station, and the Santa Cruz thermal power plant. The application of a FIS to the coordinated voltage control in the Rio Area is accomplished by a set of rules, which are based on the experience of system operators and on off-line studies done for the area. The voltages at the Adrianopolis 138-kV bus and at the Jacarepagua 138-kV bus, together with the reactive power output of the Grajau SC are the input variables (regulated variables) for the CFIS. The first two variables were chosen as practical operator experience indicates that the voltages in these busses are representative of the voltage profile in the Rio Area. The output of the Grajau SC, on the other hand, was chosen for security reasons, as it is the main dynamic reactive power source in the area. The output variables (control variables) for the CFIS are the high-side voltages at the Marimbondo, Furnas, Santa Cruz, and Angra power plants. Fig. 6 shows the integration of the CFIS with the power system. The CFIS can be viewed as a fuzzy controller. Depending on the values of the monitored variables, some of the rules will be activated and weighted automatically by the fuzzy logic. When the CFIS operates as a decision-aid tool, control actions like increasing/decreasing the high-side voltage at power plants will be displayed to the system operator, who decides to do the action. Two objectives were kept in mind in the process of building the rules. Keep the output voltage of Jacarepagua and Adrianopolis around the desired values established by the electric utilities of the Rio Area. This corresponds to assume a high degree (close to 1) of membership of these voltages to

4 MARQUES et al.: KNOWLEDGE-BASED SYSTEM FOR SUPERVISION AND CONTROL 403 Fig. 5. Main transmission corridors leading to the Rio Area. Fig. 6. Closed-loop system. the fuzzy set represented by the term OK. Fig. 7 shows the set of membership functions of the linguistic variable Jacarepagua 138 kv Voltage. The membership functions shape and overlapping characteristics were chosen by trial-and-error. Keep the Grajau SC reactive power output between zero and Mvar. This corresponds to assume high values for the membership function of the term OK of the linguistic variable Grajau\_Reactive\_Output. Based on the experience in controlling transmission network voltage in the Rio Area from Furnas control room, and on the knowledge of off-line studies for voltage control in the Rio Area, 29 operating rules were built. Extra knowledge-based experience is incorporated into the rules by fine adjustments of the membership functions. Table I shows only seven of these rules. Taking Rule 1 as an example, it translates to the following situation: If Adrianopolis 138-kV voltage is OK (see Fig. 7 for definition), Jacarepagua 138 kv is OK and Grajau SC reactive power output is OK, Then the high-side voltage at Marimbondo, Furnas, Santa Cruz, and Angra power plants must remain at the present values. The fuzzification and the defuzzication methods utilized were the min-max and the centroid, respectively. Fig. 8 shows a typical nonlinear characteristic of the rules for a particular case when the input variables are the voltage at Adrianopolis (kv) and the reactive power output of the Grajau SC

5 404 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, FEBRUARY 2005 Fig. 7. Membership functions for the linguistic variable Jacarepagua 138 kv\_voltage. TABLE I KNOWLEDGE-BASED RULES Fig. 8. Nonlinear control surface. (Mvar), and the output variable is the high-side voltage variation (pu) at the Marimbondo power plant. Due to the existence of very long bulk transmission corridors in the system, in some situations, voltage limit violations are observed in intermediate busses along these corridors. This problem is detected by the Defensive Layer that checks the voltage at all busses along the transmission corridors against operating limits. If any limit violation occurs, an alarm may sound to call the attention of the operators. In this way, a control hierarchy is accomplished, where priority is given to the control actions that eliminate limit violations, even if those are opposed to the control action given by the CFIS. In a actual open-loop implementation of the FIS in the control room, it could be setup to refresh a computer screen every 5 min, displaying to the system operator the actions to be taken. In automatic mode of operation, the FIS could be setup to read information from the SCADA system and send control signals every 20 s using a communication system similar to the one used by the automatic generation control (AGC). FIS development, translated this information into if then else fuzzy rules, with appropriate definitions of the fuzzy sets corresponding to the term set of the respective linguistic variables. These rules were coded into a FIS development system software and tuned (membership function adjustments) by a trialand-error process guided by simulation studies. It was noted that only in a few number of operating conditions was there no agreement among the operators on how to take actions. In these cases, off-line simulation studies were used to decide which set of rules should be included in the FIS. The actual implementation of the control system and extensive use in the field will allow a refinement in the rules database, correcting imperfect control actions that may be detected later on. Rules used for the CFIS and for the DFIS are of different nature. The CFIS rules are based on system-wide information and produces general control actions to set values to network voltage controlled busses. Examples of such rules are given in Table I. The DFIS receives information from the CFIS output and from the defensive layer and takes actions based on the availability of equipment in each substation. These rules are specific for each control layer and substation. Examples of such rules, for the Jacarepagua substation, are given in the following. Example of first layer rule: If Voltage is low and Adrianopolis voltage is not too low and Grajau output is low capacitive, Then switch on large amount of shunt capacitors Example of second layer rule: If Switching on is large amount of shunt capacitors and Number of reactors switched on is zero, Then switch on large capacitor V. KNOWLEDGE ACQUISITION AND CODING The knowledge incorporated into the FISs used in the control system described above was obtained from interviews with power system operators actually involved in real-time voltage control of the Rio Area system, the study of the operational instructions prepared by operational planning engineers, and complemented with off-line simulation studies, when it became necessary. A power system engineer, with reasonable knowledge of VI. SIMULATION RESULTS The system base case corresponds to a heavy load condition taken from the summer of Santa Cruz thermal power plant was assumed not participating in the hierarchical control. The unavailability of this power plant did not alter the rules of the CFIS, since there is some inherit degree of redundancy in the rule set. Table II shows a sequence of events considered during the simulation.

6 MARQUES et al.: KNOWLEDGE-BASED SYSTEM FOR SUPERVISION AND CONTROL 405 TABLE II SEQUENCE OF EVENTS TABLE III AVAILABLE CAPACITOR AND REACTOR BANKS Fig. 10. Angra 500-kV voltage. Fig. 11. Jacarepagua 138-kV voltage. Fig. 9. Marimbondo 500-kV voltage. Table III shows the capacitor and reactor banks that are used for voltage control in the Rio Area and being considered in the DFIS. The size of each bank is established according to its relative size compared to the existing banks in the same substation. For example, a 50-Mvar reactor bank is considered small in the Adrianopolis substation, whereas a 40-Mvar capacitor bank is considered median in the same substation. Table III also shows the number of capacitor and reactor banks that are in operation at the beginning of the simulations. Results shown in Figs are obtained from the fast dynamic mid-, long-term simulation program presented in [16]. In the simulations, the FIS (both CFIS and DFIS) was considered as operating in the automatic control mode with an actuation cycle of 40 s. The figures also show the upper and lower accepted operating limits for the monitored variables. It can be noted that the generating busses have wider ranges (Figs. 9 and 10) than the load busses (Figs. 11 and 12). The load busses have, in addition, a narrower range of desired voltage, not shown in the figures. Based on the simulation results, the following observations can be made. Marimbondo 500 kv (Fig. 9) At the beginning of the simulation, the voltage is over the limit of 550 kv (1.05 pu at the 525-kV base voltage). At the same moment, the voltages within the Rio Area are under their lower limits, Jacarepagua voltage is equal to kv and Adrianopolis voltage is equal to kv (Figs. 11 and 12, respectively). This scenario forces the CFIS to increase the voltage at Marimbondo plant. In this situation, the defensive layer triggers the DFIS. Having the information

7 406 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, FEBRUARY 2005 TABLE IV SWITCHING SEQUENCE Fig. 12. Adrianopolis 138-kV voltage. Fig. 13. Grajau SC reactive power output. given in Table III together with the current operating condition, the DFIS order to switch on a capacitor bank at Jacarepagua. Since the area load is being reduced, Marimbondo high-side voltage is also reduced in order to keep the voltage at the load busses within the desired range. At 700 s, the terminal voltage (not shown in the figure) at Marimbondo reaches its lower operating limit. At this time, the defensive layer triggers the DFIS again, which orders to switch a small capacitor bank at Adrianopolis. After 3000 s, the area load starts to increase, so as Marimbondo voltage. At 3900 s, the high-side voltage reaches its upper limit and the defensive process orders that a small reactor bank in Adrianopolis be switched off. Table IV shows the switching sequence as ordered by the DFIS. Angra 500 kv (Fig. 10) The behavior of the high-side voltage in Angra is similar to Marimbondo s high-side voltage. It is important to remark that at 1800 s, Angra s underexcitation limiter is reached (not shown in the figure). The behavior of the voltage at Furnas power plant was similar to Angra s voltage behavior. Jacarepagua 138 kv (Fig. 11) The arrows in Fig. 11 represent some of the switchings described in Table IV. At 40 s, a capacitor bank in Jacarepagua is switched on because the voltages in the Rio Area are below the desired values. Marimbondo voltage being a little bit above its upper limit corroborates the switching action of a capacitor bank in the Jacarepagua substation. Adrianopolis 138 kv (Fig. 12) The desired range at Adrianopolis substation in heavy load conditions is between 143 and 145 kv. The voltage behavior at Adrianopolis is similar to Jacarepagua s voltage behavior. It is interesting to observe the voltage behavior after 3000 s, when starts the positive load ramp. Note that along the first 1000 s of the positive ramp, the hierarchy prioritizes the voltage control by the generating plants. When Marimbondo reaches its upper limit around 4000 s (see Fig. 9), the control system has no alternative other than to start switching the shunt banks. Grajau SCs (Fig. 13) The reactive power outputs of the SCs remain, most of the time, within the recommended value set by the operating rules, which state that the SCs must operate within the range [ Mvar, zero Mvar] in order to keep a safe dynamic reactive reserve for voltage security. The fast response of the SCs can be observed at 300 s when one of the two circuits of the 500-kV Adriano./C.Paulista trips off. The reactive power output reaches Mvar, and it is reduced to approximately Mvar by the action of the FIS. After 4850 s, the system remain in steady state. VII. CONCLUSION This paper proposes a tool for supporting decisions of a system operator in the coordinated voltage control of transmission networks based on fuzzy logic. This work intends to

8 MARQUES et al.: KNOWLEDGE-BASED SYSTEM FOR SUPERVISION AND CONTROL 407 stimulate the use of fuzzy logic to provide new control functions that are difficult to be accomplished by conventional control. The simulation results performed in the Rio Area indicate that a coordinated voltage control based on rules built from the experience of system operators and from off-line studies are satisfactory. If the FIS were used as an automatic closed-loop controller, system operators would be relieved from doing repetitive daily tasks and be used for more noble tasks. ACKNOWLEDGMENT The authors gratefully acknowledge Mr. C. Braga Gomes for the help with the use of the simulation tool. [12] C. C. Liu and K. Tomsovic, An expert system assisting decision-making of reactive power/voltage control, IEEE Trans. Power Syst., vol. 1, no. 3, pp , Aug [13] S. J. Cheng, O. P. Malik, and G. S. Hope, An expert system for voltage and reactive power control of a power system, IEEE Trans. Power Syst., vol. 3, pp , Nov [14] K. Tomsovic, A fuzzy linear programming approach to the reactive power/voltage control problem, IEEE Trans. Power Syst., vol. 7, pp , Feb [15] S. K. Starret, W. R. A. Ibrahim, B. P. Rust, and A. L. Turner, An on-line fuzzy logic system for voltage/var control and alarm processing, in Proc. IEEE PES 1999 Winter Meeting, Jan. 1999, pp [16] W. J. Causarano, D. M. Falcão, and G. N. Taranto, A fast domain simulation method for voltage stability assessment, in Proc. VI SEPOPE, Salvador, BA, May [17] T. Van Cutsem and C. D. Vournas, Voltage stability analysis in transient and mid-term time scales, IEEE Trans. Power Syst., vol. 11, pp , Feb REFERENCES [1] J. P. Paul, J. Y. Léost, and J. M. Tesseron, Survey of the secondary voltage control in france: Present realization and investigations, IEEE Trans. Power Syst., vol. 2, pp , May [2] H. Vu, P. Pruvot, C. Launnay, and Y. Harmand, An improved voltage control on large-scale power system, IEEE Trans. Power Syst., vol. 11, pp , Aug [3] H. Lefebvre, D. Fragnier, J. Y. Boussion, P. Mallet, and M. Bulot, Secondary coordinated voltage control system: Feedback of EdF, in Proc. IEEE PES Summer Meeting, Seattle, WA, July [4] S. Corsi, P. Marannino, N. Losignore, G. Moreschini, and G. Piccini, Coordination between the reactive power scheduling function and the hierarchical voltage control of the EHV ENEL system, IEEE Trans. Power Syst., vol. 10, pp , May [5] S. Corsi, The secondary voltage regulation in italy, in Proc. IEEE PES Summer Meeting, Seattle, WA, July [6] J. Van Hecke, N. Janssens, J. Deuse, and F. Promel, Coordinated Voltage Control, Experience in Belgium, CIGRÉ Session, Paris, France, Rep , Sept [7] G. N. Taranto, N. Martins, D. M. Falcão, A. C. B. Martins, and M. G. dos Santos, Benefits of applying secondary voltage control schemes to the brazilian system, in Proc. IEEE PES Summer Meeting, Seattle, WA, July [8] W. Xu, Y. Zhang, L. C. P. da Silva, P. Kundur, and A. A. Warrack, Valuation of dynamic reactive power support services for transmission access, IEEE Trans. Power Syst., vol. 16, pp , Nov [9] A. B. Marques, G. N. Taranto, and D. M. Falcão, A supervisory knowledge-based system for monitoring and control of regional voltage profile, in Proc. Porto PowerTech, Porto, Portugal, Sept [10] C. W. Taylor, M. V. Venkatasubramanian, and Y. Chen, Wide-area stability and voltage control, in Proc. VII SEPOPE, Curitiba, Brazil, May [11] T. J. Ross, Fuzzy Logic with Engineering Applications. New York: Mc- Graw-Hill, Alessandro B. Marques was born in Rio de Janeiro, Brazil, in He received the B.Sc. degree in 1998 from CEFET-RJ, Rio de Janeiro, He is presently pursuing the M.Sc. degree at the Federal University of Rio de Janeiro/COPPE. From 1993 to 2001, he was with FURNAS, a major Brazilian electric utility, as a System Operator. Since 2002, he has been with PETROBRAS-BR. Glauco N. Taranto (S 92 M 96 SM 04) was born in Rio de Janeiro, Brazil, in He received the B.Sc. degree in 1988 from the State University of Rio de Janeiro, Rio de Janeiro, the M.Sc. degree in 1991 from the Catholic University of Rio de Janeiro, and the Ph.D. degree in 1994 from Rensselaer Polytechnic Institute, Troy, NY. He is currently an Associate Professor of Electrical Engineering at the Federal University of Rio de Janeiro/COPPE, Brazil. His research interests include power system dynamics and control, intelligent control, and robust control design. Djalma M. Falcão (M 75 SM 96 F 04) received the B.Sc. degree in 1971 from the Federal University of Paraná, Paraná, Brazil, the M.Sc. degree in 1974 from the Federal University of Rio de Janeiro, Rio de Janeiro, Brazil, and the Ph.D. degree in 1981 from UMIST, Manchester, U.K. He is currently a Professor of Electrical Engineering at the Federal University of Rio de Janeiro/COPPE. From 1991 to 1993, he was on sabbatical leave at the University of California, Berkeley. His general research interest is in the area of computer methods for power system simulation, optimization, and control.

Monitoring & Control of Small-scale Renewable Energy Sources

Monitoring & Control of Small-scale Renewable Energy Sources Small Scale Renewable Energy Sources and Energy Saving: 6-17 th July 2009 Monitoring & Control of Small-scale Renewable Energy Sources Dr G A Taylor Brunel Institute of Power Systems Brunel University,

More information

The design and performance of Static Var Compensators for particle accelerators

The design and performance of Static Var Compensators for particle accelerators CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,

More information

Interpretation of Remote Backup Protection Operation for Fault Section Estimation by a Fuzzy Expert System

Interpretation of Remote Backup Protection Operation for Fault Section Estimation by a Fuzzy Expert System Interpretation of Remote Backup Protection Operation for Fault Section Estimation by a Fuzzy Expert System G. Cardoso Jr., J. G. Rolim and H. H. Zürn. Abstract-- A hybrid intelligent system, combining

More information

IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS

IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS Liuxi Zhang and Ali Abur Department of Electrical and Computer Engineering Northeastern University Boston, MA, USA lzhang@ece.neu.edu

More information

Dynamic Security Assessment in the Future Grid. Vijay Vittal Ira A. Fulton Chair Professor Arizona State University

Dynamic Security Assessment in the Future Grid. Vijay Vittal Ira A. Fulton Chair Professor Arizona State University 1 Dynamic Security Assessment in the Future Grid Vijay Vittal Ira A. Fulton Chair Professor Arizona State University 2 Key requirements for DSA Need to perform DSA as close to real time as possible Need

More information

Hybrid processing of SCADA and synchronized phasor measurements for tracking network state

Hybrid processing of SCADA and synchronized phasor measurements for tracking network state IEEE PES General Meeting, Denver, USA, July 2015 1 Hybrid processing of SCADA and synchronized phasor measurements for tracking network state Boris Alcaide-Moreno Claudio Fuerte-Esquivel Universidad Michoacana

More information

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks Mohammad Ali Sandidzadeh School of Railway Engineering, Iran University of Science & Technology, Tehran, Iran Tel: 98-21-7749-1030

More information

4.1.1 Generator Owner 4.1.2 Transmission Owner that owns synchronous condenser(s)

4.1.1 Generator Owner 4.1.2 Transmission Owner that owns synchronous condenser(s) A. Introduction 1. Title: Verification and Data Reporting of Generator Real and Reactive Power Capability and Synchronous Condenser Reactive Power Capability 2. Number: MOD-025-2 3. Purpose: To ensure

More information

Evolution of Control for the Smart Transmission Grid

Evolution of Control for the Smart Transmission Grid Evolution of Control for the Smart Transmission Grid Anjan Bose Washington State University Pullman, WA SCE Smart Grid Research Symposium California Institute Of Technology October, 2011 The Past (before

More information

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Pakistan Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Final Report: Executive Summary - November 2015 for USAID Energy Policy

More information

Droop Control Forhybrid Micro grids With Wind Energy Source

Droop Control Forhybrid Micro grids With Wind Energy Source Droop Control Forhybrid Micro grids With Wind Energy Source [1] Dinesh Kesaboina [2] K.Vaisakh [1][2] Department of Electrical & Electronics Engineering Andhra University College of Engineering Visakhapatnam,

More information

OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT

OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT L.A.F.M. Ferreira, P.M.S. Carvalho IST S.N.C. Grave L.M.F. Barruncho L.A.

More information

IEEE Copyright Statement:

IEEE Copyright Statement: IEEE Copyright Statement: Copyright 2006 IEEE. Reprinted from Proceedings of the IEEE PES General Meeting, Montreal, Canada, June 2006. This material is posted here with permission of the IEEE. Such permission

More information

Wide Area Monitoring Current Continental Europe TSOs Applications Overview

Wide Area Monitoring Current Continental Europe TSOs Applications Overview Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main

More information

EMPLOYEE PERFORMANCE APPRAISAL SYSTEM USING FUZZY LOGIC

EMPLOYEE PERFORMANCE APPRAISAL SYSTEM USING FUZZY LOGIC EMPLOYEE PERFORMANCE APPRAISAL SYSTEM USING FUZZY LOGIC ABSTRACT Adnan Shaout* and Mohamed Khalid Yousif** *The Department of Electrical and Computer Engineering The University of Michigan Dearborn, MI,

More information

Design of Prediction System for Key Performance Indicators in Balanced Scorecard

Design of Prediction System for Key Performance Indicators in Balanced Scorecard Design of Prediction System for Key Performance Indicators in Balanced Scorecard Ahmed Mohamed Abd El-Mongy. Faculty of Systems and Computers Engineering, Al-Azhar University Cairo, Egypt. Alaa el-deen

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

Voltage Stability Improvement using Static Var Compensator in Power Systems

Voltage Stability Improvement using Static Var Compensator in Power Systems Leonardo Journal of Sciences ISSN 1583-0233 Issue 14, January-June 2009 p. 167-172 Voltage Stability Improvement using Static Var Compensator in Power Systems Department of Electrical/Computer Engineering,

More information

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB

More information

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a

More information

Draft Advanced Voltage Control Technology Roadmap

Draft Advanced Voltage Control Technology Roadmap Draft Advanced Voltage Control Technology Roadmap Robert Entriken, Senior Project Manager John Wharton, Executive Director Friday, 20 May 2011 Agenda Future Statements Current Status Functional Gaps Next

More information

Fuzzy Logic Based Reactivity Control in Nuclear Power Plants

Fuzzy Logic Based Reactivity Control in Nuclear Power Plants Fuzzy Logic Based Reactivity Control in Nuclear Power Plants Narrendar.R.C 1, Tilak 2 P.G. Student, Department of Mechatronics Engineering, VIT University, Vellore, India 1 P.G. Student, Department of

More information

Mladen Kezunovic Texas A&M University

Mladen Kezunovic Texas A&M University INTEGRATING DATA AND SHARING INFORMATION FROM VARIOUS IEDs TO IMPROVE MONITORING, CONDITION-BASED DIAGNOSTIC, MAINTENANCE, ASSET MANAGEMENT AND OPERATION TASKS Introduction Mladen Kezunovic Texas A&M University

More information

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran

More information

Project Management Efficiency A Fuzzy Logic Approach

Project Management Efficiency A Fuzzy Logic Approach Project Management Efficiency A Fuzzy Logic Approach Vinay Kumar Nassa, Sri Krishan Yadav Abstract Fuzzy logic is a relatively new technique for solving engineering control problems. This technique can

More information

Web-Based Economic Optimization Tools for Reducing Operating Costs

Web-Based Economic Optimization Tools for Reducing Operating Costs Web-Based Economic Tools for Reducing Operating Costs Authors: Keywords: Abstract: Jeffery Williams Power & Water Solutions, Inc. David Egelston Power & Water Solutions, Inc. Browsers, Economics, Linear

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION Power systems form the largest man made complex system. It basically consists of generating sources, transmission network and distribution centers. Secure and economic operation

More information

Optimal Power Flow Analysis of Energy Storage for Congestion Relief, Emissions Reduction, and Cost Savings

Optimal Power Flow Analysis of Energy Storage for Congestion Relief, Emissions Reduction, and Cost Savings 1 Optimal Power Flow Analysis of Energy Storage for Congestion Relief, Emissions Reduction, and Cost Savings Zhouxing Hu, Student Member, IEEE, and Ward T. Jewell, Fellow, IEEE Abstract AC optimal power

More information

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives (Required per CPUC Decision No. C10-1328) Final Report (Submitted with Public Service s 2011 ERP) Executive Summary The objective

More information

Implementation of Fuzzy and PID Controller to Water Level System using LabView

Implementation of Fuzzy and PID Controller to Water Level System using LabView Implementation of Fuzzy and PID Controller to Water Level System using LabView Laith Abed Sabri, Ph.D University of Baghdad AL-Khwarizmi college of Engineering Hussein Ahmed AL-Mshat University of Baghdad

More information

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN(E): 31-8843; ISSN(P): 347-4599 Vol. 3, Issue 9, Sep 015, 7-18 Impact Journals A COMPARISON ON PERFORMANCE OF TCSC/SSSC

More information

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to

More information

CURRICULUM VITAE. José Wanderley Marangon Lima

CURRICULUM VITAE. José Wanderley Marangon Lima CURRICULUM VITAE José Wanderley Marangon Lima Personal Data Name: José Wanderley Marangon Lima Institution: Federal University at Itajubá - UNIFEI Address: Av. BPS, 1303 37500-903 Itajubá MG Phone: +55

More information

Hybrid Modeling and Control of a Power Plant using State Flow Technique with Application

Hybrid Modeling and Control of a Power Plant using State Flow Technique with Application Hybrid Modeling and Control of a Power Plant using State Flow Technique with Application Marwa M. Abdulmoneim 1, Magdy A. S. Aboelela 2, Hassen T. Dorrah 3 1 Master Degree Student, Cairo University, Faculty

More information

STATCOM Application at VELCO Essex Substation

STATCOM Application at VELCO Essex Substation STATCOM Application at VELCO Essex Substation Gregory Reed John Paserba Terrence Croasdaile Mitsubishi Electric Power Products, Inc. Warrendale, Pennsylvania, USA Masatoshi Takeda Naoki Morishima Yoshi

More information

CIGRE Task Force 38.02.16 Impact of Interactions Among Power System Controls

CIGRE Task Force 38.02.16 Impact of Interactions Among Power System Controls CIGRE Task Force 38.02.16 Impact of Interactions Among Power System Controls Nelson Martins (Convenor) Members Nelson Martins CEPEL Brazil Göran Andersson Royal Institute of Technology Sweden Sandro Corsi

More information

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?

More information

System Protection Schemes in Eastern Denmark

System Protection Schemes in Eastern Denmark System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives

More information

Analysis of Load Frequency Control Performance Assessment Criteria

Analysis of Load Frequency Control Performance Assessment Criteria 520 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 16, NO. 3, AUGUST 2001 Analysis of Load Frequency Control Performance Assessment Criteria George Gross, Fellow, IEEE and Jeong Woo Lee Abstract This paper presents

More information

Introduction to Fuzzy Control

Introduction to Fuzzy Control Introduction to Fuzzy Control Marcelo Godoy Simoes Colorado School of Mines Engineering Division 1610 Illinois Street Golden, Colorado 80401-1887 USA Abstract In the last few years the applications of

More information

Email: mod_modaber@yahoo.com. 2Azerbaijan Shahid Madani University. This paper is extracted from the M.Sc. Thesis

Email: mod_modaber@yahoo.com. 2Azerbaijan Shahid Madani University. This paper is extracted from the M.Sc. Thesis Introduce an Optimal Pricing Strategy Using the Parameter of "Contingency Analysis" Neplan Software in the Power Market Case Study (Azerbaijan Electricity Network) ABSTRACT Jalil Modabe 1, Navid Taghizadegan

More information

Fuzzy Logic Based Revised Defect Rating for Software Lifecycle Performance. Prediction Using GMR

Fuzzy Logic Based Revised Defect Rating for Software Lifecycle Performance. Prediction Using GMR BIJIT - BVICAM s International Journal of Information Technology Bharati Vidyapeeth s Institute of Computer Applications and Management (BVICAM), New Delhi Fuzzy Logic Based Revised Defect Rating for Software

More information

A FUZZY LOGIC APPROACH FOR SALES FORECASTING

A FUZZY LOGIC APPROACH FOR SALES FORECASTING A FUZZY LOGIC APPROACH FOR SALES FORECASTING ABSTRACT Sales forecasting proved to be very important in marketing where managers need to learn from historical data. Many methods have become available for

More information

AMI and DA Convergence: Enabling Energy Savings through Voltage Conservation

AMI and DA Convergence: Enabling Energy Savings through Voltage Conservation AMI and DA Convergence: Enabling Energy Savings through Voltage Conservation September 2010 Prepared for: By Sierra Energy Group The Research & Analysis Division of Energy Central Table of Contents Executive

More information

Problems often have a certain amount of uncertainty, possibly due to: Incompleteness of information about the environment,

Problems often have a certain amount of uncertainty, possibly due to: Incompleteness of information about the environment, Uncertainty Problems often have a certain amount of uncertainty, possibly due to: Incompleteness of information about the environment, E.g., loss of sensory information such as vision Incorrectness in

More information

REMOTE SYSTEM FOR MONITORING AND CONTROL OF CONTROLLED AREA OF NUCLEAR INSTALLATION

REMOTE SYSTEM FOR MONITORING AND CONTROL OF CONTROLLED AREA OF NUCLEAR INSTALLATION 2011 International Nuclear Atlantic Conference - INAC 2011 Belo Horizonte,MG, Brazil, October 24-28, 2011 ASSOCIAÇÃO BRASILEIRA DE ENERGIA NUCLEAR - ABEN ISBN: 978-85-99141-04-5 REMOTE SYSTEM FOR MONITORING

More information

FULL ELECTRICAL LNG PLANTS: HIGHEST AVAILABILITY AND ENERGY EFFICIENCY THROUGH OVERALL SYSTEM DESIGN

FULL ELECTRICAL LNG PLANTS: HIGHEST AVAILABILITY AND ENERGY EFFICIENCY THROUGH OVERALL SYSTEM DESIGN FULL ELECTRICAL LN PLANTS: HIHEST AVAILABILITY AND ENERY EFFICIENCY THROUH OVERALL SYSTEM DESIN Dr. Edwin Lerch Siemens A Infrastructure and Cities Sector, IC S SE PTI, ermany Phone: 49-9131-7-34052 Fax:

More information

Study on Differential Protection of Transmission Line Using Wireless Communication

Study on Differential Protection of Transmission Line Using Wireless Communication Study on Differential Protection of Transmission Line Using Wireless Communication George John.P 1, Agna Prince 2, Akhila.K.K 3, Guy Marcel 4, Harikrishnan.P 5 Professor, Dept. of EEE, MA Engineering College,

More information

Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique

Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique Simulation of VSI-Fed Variable Speed Drive Using PI-Fuzzy based SVM-DTC Technique B.Hemanth Kumar 1, Dr.G.V.Marutheshwar 2 PG Student,EEE S.V. College of Engineering Tirupati Senior Professor,EEE dept.

More information

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS LIST OF CONTENT 1. INTRODUCTION... 1 2. HARMONIC VOLTAGE ASSESSMENT REQUIREMENT IN THE UK... 2 3. THE ASSESSMENT... 2 3.1. SYSTEM MODELLING...3 3.2.

More information

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003 F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify

More information

Testing and Evaluating New Software Solutions for Automated Analysis of Protective Relay Operations

Testing and Evaluating New Software Solutions for Automated Analysis of Protective Relay Operations Testing and Evaluating New Software Solutions for Automated Analysis of Protective Relay Operations M. Kezunovic, X. Luo, N. Zhang, and H. Song Abstract This paper presents the test and evaluation environments

More information

Conservation Voltage Reduction (CVR)

Conservation Voltage Reduction (CVR) Conservation Voltage Reduction (CVR) Nicholas Abi-Samra Senior Vice President October 15, 2013 DNV GL Energy Table of Contents What does CVR do? Why Does CVR Work? DNV GL s CVR Project Experience Needs

More information

Application of GA for Optimal Location of FACTS Devices for Steady State Voltage Stability Enhancement of Power System

Application of GA for Optimal Location of FACTS Devices for Steady State Voltage Stability Enhancement of Power System I.J. Intelligent Systems and Applications, 2014, 03, 69-75 Published Online February 2014 in MECS (http://www.mecs-press.org/) DOI: 10.5815/ijisa.2014.03.07 Application of GA for Optimal Location of Devices

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Maximization versus environmental compliance

Maximization versus environmental compliance Maximization versus environmental compliance Increase use of alternative fuels with no risk for quality and environment Reprint from World Cement March 2005 Dr. Eduardo Gallestey, ABB, Switzerland, discusses

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM E.Babu 1,R.Subramanian 2 1, Department of Electrical and electronics engg 2 Department of Electrical

More information

16 West Coast Regional Plan

16 West Coast Regional Plan 16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast

More information

Data Mining to Characterize Signatures of Impending System Events or Performance from PMU Measurements

Data Mining to Characterize Signatures of Impending System Events or Performance from PMU Measurements Data Mining to Characterize Signatures of Impending System Events or Performance from PMU Measurements Final Project Report Power Systems Engineering Research Center Empowering Minds to Engineer the Future

More information

Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East

Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East The 4 th International Conference on Power Transmission & Distribution Technology 2003 14-16 October, 2003, Changsha 2003 Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East Abhay Kumar Mats

More information

Power System Security in Market Clearing and Dispatch Mechanisms

Power System Security in Market Clearing and Dispatch Mechanisms 1 Power System Security in Market Clearing and Dispatch Mechanisms Claudio A. Cañizares, Senior Member, IEEE, Sameh K. M. Kodsi, Student Member, IEEE Abstract This paper presents and discusses some typical

More information

Distributed Real-Time Dynamic Security Assessment Using Intelligent Techniques

Distributed Real-Time Dynamic Security Assessment Using Intelligent Techniques IEEE ISGT Asia 2013 1569818101 Distributed Real-Time Dynamic Security Assessment Using Intelligent Techniques Karthik Kumar, Theodoros Kyriakidis, Maher Kayal, Rachid Cherkaoui Electronics Laboratory &

More information

2012 San Francisco Colloquium

2012 San Francisco Colloquium 2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters

More information

DEVELOPMENT OF FUZZY LOGIC MODEL FOR LEADERSHIP COMPETENCIES ASSESSMENT CASE STUDY: KHOUZESTAN STEEL COMPANY

DEVELOPMENT OF FUZZY LOGIC MODEL FOR LEADERSHIP COMPETENCIES ASSESSMENT CASE STUDY: KHOUZESTAN STEEL COMPANY DEVELOPMENT OF FUZZY LOGIC MODEL FOR LEADERSHIP COMPETENCIES ASSESSMENT CASE STUDY: KHOUZESTAN STEEL COMPANY 1 MOHAMMAD-ALI AFSHARKAZEMI, 2 DARIUSH GHOLAMZADEH, 3 AZADEH TAHVILDAR KHAZANEH 1 Department

More information

RESUME. Rashid Alammari, Ph.D Associate Professor

RESUME. Rashid Alammari, Ph.D Associate Professor RESUME Date: November 2010 Personal Data Name & Mailing Address Rashid Alammari, Ph.D Associate Professor Department of Electrical Engineering College of Engineering Qatar University P.O. Box 2713 Doha,

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.

More information

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal May 24 MW Variable Speed Drives for Aurélie Bocquel APCG / 4BOC4 (MW-Goldisthal 1-5-24).PPT MW Variable Speed Drives for Content Major benefits of the cyclo-converter driven doubly-fed induction machines

More information

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink Transient analysis of integrated solar/diesel hybrid power system using ATLAB Simulink Takyin Taky Chan School of Electrical Engineering Victoria University PO Box 14428 C, elbourne 81, Australia. Taky.Chan@vu.edu.au

More information

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit

More information

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Prepared By: Transmission Planning Unit Baltimore Gas & Electric Company Table of Contents 1. INTRODUCTION

More information

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

Impact of electric vehicles on the IEEE 34 node distribution infrastructure International Journal of Smart Grid and Clean Energy Impact of electric vehicles on the IEEE 34 node distribution infrastructure Zeming Jiang *, Laith Shalalfeh, Mohammed J. Beshir a Department of Electrical

More information

A Flexible Machine Learning Environment for Steady State Security Assessment of Power Systems

A Flexible Machine Learning Environment for Steady State Security Assessment of Power Systems A Flexible Machine Learning Environment for Steady State Security Assessment of Power Systems D. D. Semitekos, N. M. Avouris, G. B. Giannakopoulos University of Patras, ECE Department, GR-265 00 Rio Patras,

More information

Oscillation Monitoring System

Oscillation Monitoring System Oscillation Monitoring System Mani V. Venkatasubramanian Washington State University Pullman WA Oscillation Monitoring System IEEE C37.118 Real-time PMU data stream TCP or UDP OpenPDC OMS SQL server OMS

More information

Real Time Traffic Balancing in Cellular Network by Multi- Criteria Handoff Algorithm Using Fuzzy Logic

Real Time Traffic Balancing in Cellular Network by Multi- Criteria Handoff Algorithm Using Fuzzy Logic Real Time Traffic Balancing in Cellular Network by Multi- Criteria Handoff Algorithm Using Fuzzy Logic Solomon.T.Girma 1, Dominic B. O. Konditi 2, Edward N. Ndungu 3 1 Department of Electrical Engineering,

More information

When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard.

When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard. CIP-002-5 Cyber Security BES Cyber System Categorization When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard. A.

More information

NTC Project: S01-PH10 (formerly I01-P10) 1 Forecasting Women s Apparel Sales Using Mathematical Modeling

NTC Project: S01-PH10 (formerly I01-P10) 1 Forecasting Women s Apparel Sales Using Mathematical Modeling 1 Forecasting Women s Apparel Sales Using Mathematical Modeling Celia Frank* 1, Balaji Vemulapalli 1, Les M. Sztandera 2, Amar Raheja 3 1 School of Textiles and Materials Technology 2 Computer Information

More information

A progressive method to solve large-scale AC Optimal Power Flow with discrete variables and control of the feasibility

A progressive method to solve large-scale AC Optimal Power Flow with discrete variables and control of the feasibility A progressive method to solve large-scale AC Optimal Power Flow with discrete variables and control of the feasibility Manuel Ruiz, Jean Maeght, Alexandre Marié, Patrick Panciatici and Arnaud Renaud manuel.ruiz@artelys.com

More information

Control Development and Modeling for Flexible DC Grids in Modelica

Control Development and Modeling for Flexible DC Grids in Modelica Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, andreas.olenmark@one-nordic.se.

More information

Steady-State Power System Security Analysis with PowerWorld Simulator

Steady-State Power System Security Analysis with PowerWorld Simulator Steady-State Power System Security Analysis with PowerWorld Simulator S: Power System Modeling Methods and Equations 00 South First Street Champaign, Illinois 680 + (7) 384.6330 support@powerworld.com

More information

Electric Power Steering Automation for Autonomous Driving

Electric Power Steering Automation for Autonomous Driving Electric Power Steering Automation for Autonomous Driving J. E. Naranjo, C. González, R. García, T. de Pedro Instituto de Automática Industrial (CSIC) Ctra. Campo Real Km.,2, La Poveda, Arganda del Rey,

More information

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor

More information

Load Balancing in Computer Networks

Load Balancing in Computer Networks Load Balancing in Computer Networks Ming-Chang Huang, S. Hossein Hosseini 1 and K. Vairavan Department of Electrical Engineering and Computer Science University of Wisconsin Milwaukee PO Box 784 Milwaukee,

More information

Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter

Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter Archana.P 1, Karthick.R 2 Pg Scholar [PED], Department of EEE, CSI College of Engineering, Ketti, Tamilnadu, India

More information

ABB Network Manager in Endesa s Energy Management Center

ABB Network Manager in Endesa s Energy Management Center D. G. GESTIÓN DE LA ENERGÍA D. Energía y Logística S. D. Mercados de Contado y Operación Automatic Generation Control (AGC) in Endesa 09 10 13 ABB Network Manager in Endesa s Energy Management Center Contents

More information

ARCHITECTURE OF INDUSTRIAL AUTOMATION SYSTEMS

ARCHITECTURE OF INDUSTRIAL AUTOMATION SYSTEMS ARCHITECTURE OF INDUSTRIAL AUTOMATION SYSTEMS Abdu Idris Omer Taleb M.M., PhD Majmaah University, Kingdom of Saudia Arabia Abstract This article is aimed to name the levels of industrial automation, describes

More information

Guidelines for Large Photovoltaic System Integration

Guidelines for Large Photovoltaic System Integration 1 Guidelines for Large Photovoltaic System Integration Silviu Darie, PhD(EE), PE(EE) Abstract- The paper summarizes the result of a research project funded by the Department of Energy (DOE) in collaboration

More information

A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems

A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems IEEE International Conference on Evolutionary Computation May 4-11 1998, Anchorage, Alaska A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems Sakae Toune, Hiroyuki Fudo,

More information

Introduction to PowerWorld Simulator: Interface and Common Tools

Introduction to PowerWorld Simulator: Interface and Common Tools Introduction to PowerWorld Simulator: Interface and Common Tools 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Fault Analysis Analysis

More information

METHODOLOGICAL CONSIDERATIONS OF DRIVE SYSTEM SIMULATION, WHEN COUPLING FINITE ELEMENT MACHINE MODELS WITH THE CIRCUIT SIMULATOR MODELS OF CONVERTERS.

METHODOLOGICAL CONSIDERATIONS OF DRIVE SYSTEM SIMULATION, WHEN COUPLING FINITE ELEMENT MACHINE MODELS WITH THE CIRCUIT SIMULATOR MODELS OF CONVERTERS. SEDM 24 June 16th - 18th, CPRI (Italy) METHODOLOGICL CONSIDERTIONS OF DRIVE SYSTEM SIMULTION, WHEN COUPLING FINITE ELEMENT MCHINE MODELS WITH THE CIRCUIT SIMULTOR MODELS OF CONVERTERS. Áron Szûcs BB Electrical

More information

Fuzzy decision support system for traffic control centers

Fuzzy decision support system for traffic control centers Delft University of Technology Fac. of Information Technology and Systems Control Systems Engineering Technical report bds:00-08 Fuzzy decision support system for traffic control centers A. Hegyi, B. De

More information

INTELLIGENT DISTRIBUTION NETWORK ANALYSIS AND INFORMATION ARCHITECTURE DESIGN

INTELLIGENT DISTRIBUTION NETWORK ANALYSIS AND INFORMATION ARCHITECTURE DESIGN INTELLIGENT DISTRIBUTION NETWORK ANALYSIS AND INFORMATION ARCHITECTURE DESIGN Yun CHEN SMEPC,State Grid China daddygirl@126.com ABSTRACT From the background of intelligent distribution network construction,

More information

EFFICIENT DATA PRE-PROCESSING FOR DATA MINING

EFFICIENT DATA PRE-PROCESSING FOR DATA MINING EFFICIENT DATA PRE-PROCESSING FOR DATA MINING USING NEURAL NETWORKS JothiKumar.R 1, Sivabalan.R.V 2 1 Research scholar, Noorul Islam University, Nagercoil, India Assistant Professor, Adhiparasakthi College

More information

ANCILLARY SERVICES SUPPLIED TO THE GRID: THE CASE OF THISVI CCGT POWER PLANT (GREECE)

ANCILLARY SERVICES SUPPLIED TO THE GRID: THE CASE OF THISVI CCGT POWER PLANT (GREECE) Claudio Cavandoli, Alessandro Crippa EDISON S.p.A., Engineering Department ANCILLARY SERVICES SUPPLIED TO THE GRID: THE CASE OF THISVI CCGT POWER PLANT (GREECE) 1 ANCILLARY SERVICES SUPPLIED TO THE GRID:

More information

Analysis of the Effect of Tap Changing Transformer on Performance of SVC

Analysis of the Effect of Tap Changing Transformer on Performance of SVC Analysis of the Effect of Tap Changing Transformer on Performance of SVC Dipesh A. Patel 1, Nirav P. Patani 2, Prabhat Kumar 3 1 Senior Lecturer, Electrical Engineering Department, M.L.I.D.S. Bhandu, Gujarat.

More information

DESIGN AND STRUCTURE OF FUZZY LOGIC USING ADAPTIVE ONLINE LEARNING SYSTEMS

DESIGN AND STRUCTURE OF FUZZY LOGIC USING ADAPTIVE ONLINE LEARNING SYSTEMS Abstract: Fuzzy logic has rapidly become one of the most successful of today s technologies for developing sophisticated control systems. The reason for which is very simple. Fuzzy logic addresses such

More information

A Conceptual Approach to Data Visualization for User Interface Design of Smart Grid Operation Tools

A Conceptual Approach to Data Visualization for User Interface Design of Smart Grid Operation Tools A Conceptual Approach to Data Visualization for User Interface Design of Smart Grid Operation Tools Dong-Joo Kang and Sunju Park Yonsei University unlimit0909@hotmail.com, boxenju@yonsei.ac.kr Abstract

More information

Preliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines

Preliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines Preliminary Feasibility Assessment For The Rio Tinto Alcan to BCH Transfer Limit of 460 MW With 50% Series Compensation on Both KMO KIT lines Report : ASP2010-T001 July 2010 Asset Strategy & Planning,

More information

Technology to Control Hybrid Computer Systems

Technology to Control Hybrid Computer Systems INFORMATION TECHNOLOGY Hynomics (formerly HyBrithms Corporation, formerly Sagent Corporation) Technology to Control Hybrid Computer Systems Businesses and industries, both large and small, increasingly

More information