Modbus Register Map: Environmental Management System and Environmental Monitoring Unit A 02/2005

Size: px
Start display at page:

Download "Modbus Register Map: Environmental Management System and Environmental Monitoring Unit 990-0589A 02/2005"

Transcription

1 // Version 102 //Absolute Starting Register Number, (Hexadecimal) Modbus Register Map: Environmental Management System and Environmental Monitoring Unit A 02/2005 Absolute Starting Register Number, (Decimal) Data Point Length Units Valid Response // ISX EMS-EMU2 DEVICE TYPE ISX 1 ENUM 11 = EMS 15 = EMU EMS-EMU2 DEVICE STATUS ISX 1 ENUM 00 = Unknown 02 = Informational 04 = Warning 08 = Critical EMS-EMU2 PROBE 1 TEMP ISX 1 DEGREES Celsius Temperature EMS-EMU2 PROBE 2 TEMP ISX 1 DEGREES Celsius Temperature EMS-EMU2 PROBE 1 HUMIDITY ISX 1 PERCENT Humidity EMS-EMU2 PROBE 2 HUMIDITY ISX 1 PERCENT Humidity EMS-EMU2 ISX RESERVED REGISTERS 250 NA Reserved // EMS EMS-EMU2 DEVICE TYPE 1 ENUM 11 = EMS 15 = EMU EMS-EMU2 DEVICE STATUS 1 ENUM 00 = Unknown 02 = Informational 04 = Warning 08 = Critical EMS-EMU2 NAME 11 ASCII EM Device Name 010D 269 EMS-EMU2 INTERNAL MODEL NUMBER 1 ENUM 01 = EMS 03 = EMU2 010E 270 EMS-EMU2 PRODUCT NUMBER 9 ASCII TBD EMS-EMU2 FIRMWARE REV 6 ASCII TBD 011D 285 EMS-EMU2 HARDWARE REV 9 ASCII TBD EMS-EMU2 MANUFACTURE DATE 6 ASCII TBD 012C 300 EMS-EMU2 SERIAL NUMBER 8 ASCII TBD EMS-EMU2 PROBES OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms EMS SENSORS OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm EMS-EMU2 CONTACTS OVERALL STATE 1 ENUM 02 = Normal 03 = Alarm EMS-EMU2 RELAYS OVERALL STATE 1 ENUM 02 = Normal 03 = Alarm EMS-EMU2 ARUS OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms EMS CHECKLOGLIGHT 1 ENUM 01 = Disabled 02 = Informational 03 = Warning 04 = Severe 013A 314 EMS-EMU2 TEMP DISPLAY TYPE 1 ENUM 01 = Celsius 02 = Farenheit 013B 315 EMS-EMU2 MAJOR ALARM 1 ENUM 01 = On 02 = Off 013C 316 EMS-EMU2 MINOR ALARM 1 ENUM 01 = On 02 = Off 013D 317 EMS HARDWARE STATE (see Note 5.) 1 ENUM 00 = No Alarms 01 = Alink Fault 02 = Connector Sense Fault 013E 318 EMS-EMU2 SYSTEM RESERVED REGISTERS 194 NA Reserved // Probe EMS-EMU2 PROBE 1 NAME 11 ASCII Probe 1 Name 020B 523 EMS-EMU2 PROBE 1 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 020C 524 EMS-EMU2 PROBE 1 LOW TEMP ALARM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 020D 525 EMS-EMU2 PROBE 1 LOW TEMP THOLD 1 DEGREES Probe 1 Low Temperature Threshold 020E 526 EMS-EMU2 PROBE 1 TEMP 1 DEPENDENCY Probe 1 Temperature 020F 527 EMS-EMU2 PROBE 1 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 HIGH TEMP THOLD 1 DEGREES Probe 1 High Temperature Threshold EMS-EMU2 PROBE 1 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 LOW HUM THOLD 1 PERCENT Probe 1 Low Humidity Threshold EMS-EMU2 PROBE 1 HUM 1 PERCENT Probe 1 Humidity EMS-EMU2 PROBE 1 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 HIGH HUM THOLD 1 PERCENT Probe 1 High Humidity Threshold EMS-EMU2 PROBE 1 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 MAXIMUM TEMP THOLD 1 DEGREES Probe 1 Maximum Temperature Threshold EMS-EMU2 PROBE 1 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 MINIMUM TEMP THOLD 1 DEGREES Probe 1 Minimum Temperature Threshold 021A 538 EMS-EMU2 PROBE 1 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 021B 539 EMS-EMU2 PROBE 1 MAXIMUM HUM THOLD 1 PERCENT Probe 1 Maximum Humidity Threshold 021C 540 EMS-EMU2 PROBE 1 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 021D 541 EMS-EMU2 PROBE 1 MINIMUM HUM THOLD 1 DEGREES Probe 1 Minimum Humidity Threshold 021E 542 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 1 Short-term Increasing Variance 021F 543 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING TIME 1 SECONDS Probe 1 Short-term Increasing Time EMS-EMU2 PROBE 1 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 1 Short-term Decreasing Variance EMS-EMU2 PROBE 1 SHORT-TERM DECREASING TIME 1 SECONDS Probe 1 Short-term Decreasing Time EMS-EMU2 PROBE 1 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 1 Long-term Increasing Variance EMS-EMU2 PROBE 1 LONG-TERM INCREASING TIME 1 HOURS Probe 1 Long-term Increasing Time EMS-EMU2 PROBE 1 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 1 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 1 Long-term Increasing Variance EMS-EMU2 PROBE 1 LONG-TERM DECREASING TIME 1 HOURS Probe 1 Long-term Increasing Time EMS-EMU2 PROBE 1 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 022A 554 EMS-EMU2 PROBE 1 RESERVED REGISTERS 22 NA Reserved // Probe EMS-EMU2 PROBE 2 NAME 11 ASCII Probe 2 Name 024B 587 EMS-EMU2 PROBE 2 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 024C 588 EMS-EMU2 PROBE 2 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 024D 589 EMS-EMU2 PROBE 2 LOW TEMP THOLD 1 DEGREES Probe 2 Low Temperature Threshold 024E 590 EMS-EMU2 PROBE 2 TEMP 1 DEPENDENCY Probe 2 Temperature 024F 591 EMS-EMU2 PROBE 2 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 2 HIGH TEMP THOLD 1 DEGREES Probe 2 High Temperature Threshold EMS-EMU2 PROBE 2 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 2 LOW HUM THOLD 1 PERCENT Probe 2 Low Humidity Threshold EMS-EMU2 PROBE 2 HUM 1 PERCENT Probe 2 Humidity EMS-EMU2 PROBE 2 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm

2 EMS-EMU2 PROBE 2 HIGH HUM THOLD 1 PERCENT Probe 2 High Humidity Threshold EMS-EMU2 PROBE 2 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 2 MAXIMUM TEMP THOLD 1 DEGREES Probe 2 Maximum Temperature Threshold EMS-EMU2 PROBE 2 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 2 MINIMUM TEMP THOLD 1 DEGREES Probe 2 Minimum Temperature Threshold 025A 602 EMS-EMU2 PROBE 2 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 025B 603 EMS-EMU2 PROBE 2 MAXIMUM HUM THOLD 1 PERCENT Probe 2 Maximum Humidity Threshold 025C 604 EMS-EMU2 PROBE 2 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 025D 605 EMS-EMU2 PROBE 2 MINIMUM HUM THOLD 1 DEGREES Probe 2 Minimum Humidity Threshold 025E 606 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 2 Short-term Increasing Variance 025F 607 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING TIME 1 SECONDS Probe 2 Short-term Increasing Time EMS-EMU2 PROBE 2 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 2 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 2 Short-term Decreasing Variance EMS-EMU2 PROBE 2 SHORT-TERM DECREASING TIME 1 SECONDS Probe 2 Short-term Decreasing Time EMS-EMU2 PROBE 2 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 2 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 2 Long-term Increasing Variance EMS-EMU2 PROBE 2 LONG-TERM INCREASING TIME 1 HOURS Probe 2 Long-term Increasing Time EMS-EMU2 PROBE 2 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 2 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 2 Long-term Increasing Variance EMS-EMU2 PROBE 2 LONG-TERM DECREASING TIME 1 HOURS Probe 2 Long-term Increasing Time EMS-EMU2 PROBE 2 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 026A 618 EMS-EMU2 PROBE 2 RESERVED REGISTERS 22 NA Reserved // Probe EMS-EMU2 PROBE 3 NAME 11 ASCII Probe 3 Name 028B 651 EMS-EMU2 PROBE 3 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 028C 652 EMS-EMU2 PROBE 3 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 028D 653 EMS-EMU2 PROBE 3 LOW TEMP THOLD 1 DEGREES Probe 3 Low Temperature Threshold 028E 654 EMS-EMU2 PROBE 3 TEMP 1 DEPENDENCY Probe 3 Temperature 028F 655 EMS-EMU2 PROBE 3 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 3 HIGH TEMP THOLD 1 DEGREES Probe 3 High Temperature Threshold EMS-EMU2 PROBE 3 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 3 LOW HUM THOLD 1 PERCENT Probe 3 Low Humidity Threshold EMS-EMU2 PROBE 3 HUM 1 PERCENT Probe 3 Humidity EMS-EMU2 PROBE 3 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 3 HIGH HUM THOLD 1 PERCENT Probe 3 High Humidity Threshold EMS-EMU2 PROBE 3 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 3 MAXIMUM TEMP THOLD 1 DEGREES Probe 3 Maximum Temperature Threshold EMS-EMU2 PROBE 3 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS-EMU2 PROBE 3 MINIMUM TEMP THOLD 1 DEGREES Probe 3 Minimum Temperature Threshold 029A 666 EMS-EMU2 PROBE 3 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 029B 667 EMS-EMU2 PROBE 3 MAXIMUM HUM THOLD 1 PERCENT Probe 3 Maximum Humidity Threshold 029C 668 EMS-EMU2 PROBE 3 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 029D 669 EMS-EMU2 PROBE 3 MINIMUM HUM THOLD 1 DEGREES Probe 3 Minimum Humidity Threshold 029E 670 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 3 Short-term Increasing Variance 029F 671 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING TIME 1 SECONDS Probe 3 Short-term Increasing Time 02A0 672 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A1 673 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 3 Short-term Decreasing Variance 02A2 674 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING TIME 1 SECONDS Probe 3 Short-term Decreasing Time 02A3 675 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A4 676 EMS-EMU2 PROBE 3 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 3 Long-term Increasing Variance 02A5 677 EMS-EMU2 PROBE 3 LONG-TERM INCREASING TIME 1 HOURS Probe 3 Long-term Increasing Time 02A6 678 EMS-EMU2 PROBE 3 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A7 679 EMS-EMU2 PROBE 3 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 3 Long-term Increasing Variance 02A8 680 EMS-EMU2 PROBE 3 LONG-TERM DECREASING TIME 1 HOURS Probe 3 Long-term Increasing Time 02A9 681 EMS-EMU2 PROBE 3 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02AA 682 EMS-EMU2 PROBE 3 RESERVED REGISTERS 22 NA Reserved // Probe 4 02C0 704 EMS-EMU2 PROBE 4 NAME 11 ASCII Probe 4 Name 02CB 715 EMS-EMU2 PROBE 4 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 02CC 716 EMS-EMU2 PROBE 4 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02CD 717 EMS-EMU2 PROBE 4 LOW TEMP THOLD 1 DEGREES Probe 4 Low Temperature Threshold 02CE 718 EMS-EMU2 PROBE 4 TEMP 1 DEPENDENCY Probe 4 Temperature 02CF 719 EMS-EMU2 PROBE 4 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D0 720 EMS-EMU2 PROBE 4 HIGH TEMP THOLD 1 DEGREES Probe 4 High Temperature Threshold 02D1 721 EMS-EMU2 PROBE 4 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D2 722 EMS-EMU2 PROBE 4 LOW HUM THOLD 1 PERCENT Probe 4 Low Humidity Threshold 02D3 723 EMS-EMU2 PROBE 4 HUM 1 PERCENT Probe 4 Humidity 02D4 724 EMS-EMU2 PROBE 4 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D5 725 EMS-EMU2 PROBE 4 HIGH HUM THOLD 1 PERCENT Probe 4 High Humidity Threshold 02D6 726 EMS-EMU2 PROBE 4 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D7 727 EMS-EMU2 PROBE 4 MAXIMUM TEMP THOLD 1 DEGREES Probe 4 Maximum Temperature Threshold 02D8 728 EMS-EMU2 PROBE 4 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D9 729 EMS-EMU2 PROBE 4 MINIMUM TEMP THOLD 1 DEGREES Probe 4 Minimum Temperature Threshold 02DA 730 EMS-EMU2 PROBE 4 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02DB 731 EMS-EMU2 PROBE 4 MAXIMUM HUM THOLD 1 PERCENT Probe 4 Maximum Humidity Threshold 02DC 732 EMS-EMU2 PROBE 4 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02DD 733 EMS-EMU2 PROBE 4 MINIMUM HUM THOLD 1 DEGREES Probe 4 Minimum Humidity Threshold 02DE 734 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 4 Short-term Increasing Variance 02DF 735 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING TIME 1 SECONDS Probe 4 Short-term Increasing Time 02E0 736 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E1 737 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 4 Short-term Decreasing Variance 02E2 738 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING TIME 1 SECONDS Probe 4 Short-term Decreasing Time 02E3 739 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E4 740 EMS-EMU2 PROBE 4 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 4 Long-term Increasing Variance 02E5 741 EMS-EMU2 PROBE 4 LONG-TERM INCREASING TIME 1 HOURS Probe 4 Long-term Increasing Time

3 02E6 742 EMS-EMU2 PROBE 4 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E7 743 EMS-EMU2 PROBE 4 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 4 Long-term Increasing Variance 02E8 744 EMS-EMU2 PROBE 4 LONG-TERM DECREASING TIME 1 HOURS Probe 4 Long-term Increasing Time 02E9 745 EMS-EMU2 PROBE 4 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02EA 746 EMS-EMU2 PROBE 4 RESERVED REGISTERS 22 NA Reserved // Probe EMS PROBE 5 NAME 11 ASCII Probe 5 Name 030B 779 EMS PROBE 5 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 030C 780 EMS PROBE 5 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 030D 781 EMS PROBE 5 LOW TEMP THOLD 1 DEGREES Probe 5 Low Temperature Threshold 030E 782 EMS PROBE 5 TEMP 1 DEPENDENCY Probe 5 Temperature 030F 783 EMS PROBE 5 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 HIGH TEMP THOLD 1 DEGREES Probe 5 High Temperature Threshold EMS PROBE 5 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 LOW HUM THOLD 1 PERCENT Probe 5 Low Humidity Threshold EMS PROBE 5 HUM 1 PERCENT Probe 5 Humidity EMS PROBE 5 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 HIGH HUM THOLD 1 PERCENT Probe 5 High Humidity Threshold EMS PROBE 5 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 MAXIMUM TEMP THOLD 1 DEGREES Probe 5 Maximum Temperature Threshold EMS PROBE 5 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 MINIMUM TEMP THOLD 1 DEGREES Probe 5 Minimum Temperature Threshold 031A 794 EMS PROBE 5 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 031B 795 EMS PROBE 5 MAXIMUM HUM THOLD 1 PERCENT Probe 5 Maximum Humidity Threshold 031C 796 EMS PROBE 5 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 031D 797 EMS PROBE 5 MINIMUM HUM THOLD 1 DEGREES Probe 5 Minimum Humidity Threshold 031E 798 EMS PROBE 5 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 5 Short-term Increasing Variance 031F 799 EMS PROBE 5 SHORT-TERM INCREASING TIME 1 SECONDS Probe 5 Short-term Increasing Time EMS PROBE 5 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 5 Short-term Decreasing Variance EMS PROBE 5 SHORT-TERM DECREASING TIME 1 SECONDS Probe 5 Short-term Decreasing Time EMS PROBE 5 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 5 Long-term Increasing Variance EMS PROBE 5 LONG-TERM INCREASING TIME 1 HOURS Probe 5 Long-term Increasing Time EMS PROBE 5 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 5 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 5 Long-term Increasing Variance EMS PROBE 5 LONG-TERM DECREASING TIME 1 HOURS Probe 5 Long-term Increasing Time EMS PROBE 5 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 032A 810 EMS PROBE 5 RESERVED REGISTERS 22 NA Reserved // Probe EMS PROBE 6 NAME 11 ASCII Probe 6 Name 034B 843 EMS PROBE 6 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 034C 844 EMS PROBE 6 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 034D 845 EMS PROBE 6 LOW TEMP THOLD 1 DEGREES Probe 6 Low Temperature Threshold 034E 846 EMS PROBE 6 TEMP 1 DEPENDENCY Probe 6 Temperature 034F 847 EMS PROBE 6 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 HIGH TEMP THOLD 1 DEGREES Probe 6 High Temperature Threshold EMS PROBE 6 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 LOW HUM THOLD 1 PERCENT Probe 6 Low Humidity Threshold EMS PROBE 6 HUM 1 PERCENT Probe 6 Humidity EMS PROBE 6 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 HIGH HUM THOLD 1 PERCENT Probe 6 High Humidity Threshold EMS PROBE 6 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 MAXIMUM TEMP THOLD 1 DEGREES Probe 6 Maximum Temperature Threshold EMS PROBE 6 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 MINIMUM TEMP THOLD 1 DEGREES Probe 6 Minimum Temperature Threshold 035A 858 EMS PROBE 6 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 035B 859 EMS PROBE 6 MAXIMUM HUM THOLD 1 PERCENT Probe 6 Maximum Humidity Threshold 035C 860 EMS PROBE 6 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 035D 861 EMS PROBE 6 MINIMUM HUM THOLD 1 DEGREES Probe 6 Minimum Humidity Threshold 035E 862 EMS PROBE 6 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 6 Short-term Increasing Variance 035F 863 EMS PROBE 6 SHORT-TERM INCREASING TIME 1 SECONDS Probe 6 Short-term Increasing Time EMS PROBE 6 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 6 Short-term Decreasing Variance EMS PROBE 6 SHORT-TERM DECREASING TIME 1 SECONDS Probe 6 Short-term Decreasing Time EMS PROBE 6 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 6 Long-term Increasing Variance EMS PROBE 6 LONG-TERM INCREASING TIME 1 HOURS Probe 6 Long-term Increasing Time EMS PROBE 6 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 6 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 6 Long-term Increasing Variance EMS PROBE 6 LONG-TERM DECREASING TIME 1 HOURS Probe 6 Long-term Increasing Time EMS PROBE 6 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 036A 874 EMS PROBE 6 RESERVED REGISTERS 22 NA Reserved // Probe EMS PROBE 7 NAME 11 ASCII Probe 7 Name 038B 907 EMS PROBE 7 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 038C 908 EMS PROBE 7 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 038D 909 EMS PROBE 7 LOW TEMP THOLD 1 DEGREES Probe 7 Low Temperature Threshold 038E 910 EMS PROBE 7 TEMP 1 DEPENDENCY Probe 7 Temperature 038F 911 EMS PROBE 7 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 7 HIGH TEMP THOLD 1 DEGREES Probe 7 High Temperature Threshold EMS PROBE 7 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 7 LOW HUM THOLD 1 PERCENT Probe 7 Low Humidity Threshold EMS PROBE 7 HUM 1 PERCENT Probe 7 Humidity EMS PROBE 7 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm

4 EMS PROBE 7 HIGH HUM THOLD 1 PERCENT Probe 7 High Humidity Threshold EMS PROBE 7 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 7 MAXIMUM TEMP THOLD 1 DEGREES Probe 7 Maximum Temperature Threshold EMS PROBE 7 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 7 MINIMUM TEMP THOLD 1 DEGREES Probe 7 Minimum Temperature Threshold 039A 922 EMS PROBE 7 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 039B 923 EMS PROBE 7 MAXIMUM HUM THOLD 1 PERCENT Probe 7 Maximum Humidity Threshold 039C 924 EMS PROBE 7 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 039D 925 EMS PROBE 7 MINIMUM HUM THOLD 1 DEGREES Probe 7 Minimum Humidity Threshold 039E 926 EMS PROBE 7 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 7 Short-term Increasing Variance 039F 927 EMS PROBE 7 SHORT-TERM INCREASING TIME 1 SECONDS Probe 7 Short-term Increasing Time 03A0 928 EMS PROBE 7 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A1 929 EMS PROBE 7 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 7 Short-term Decreasing Variance 03A2 930 EMS PROBE 7 SHORT-TERM DECREASING TIME 1 SECONDS Probe 7 Short-term Decreasing Time 03A3 931 EMS PROBE 7 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A4 932 EMS PROBE 7 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 7 Long-term Increasing Variance 03A5 933 EMS PROBE 7 LONG-TERM INCREASING TIME 1 HOURS Probe 7 Long-term Increasing Time 03A6 934 EMS PROBE 7 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A7 935 EMS PROBE 7 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 7 Long-term Increasing Variance 03A8 936 EMS PROBE 7 LONG-TERM DECREASING TIME 1 HOURS Probe 7 Long-term Increasing Time 03A9 937 EMS PROBE 7 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03AA 938 EMS PROBE 7 RESERVED REGISTERS 22 NA Reserved // Probe 8 03C0 960 EMS PROBE 8 NAME 11 ASCII Probe 8 Name 03CB 971 EMS PROBE 8 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 03CC 972 EMS PROBE 8 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03CD 973 EMS PROBE 8 LOW TEMP THOLD 1 DEGREES Probe 8 Low Temperature Threshold 03CE 974 EMS PROBE 8 TEMP 1 DEPENDENCY Probe 8 Temperature 03CF 975 EMS PROBE 8 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D0 976 EMS PROBE 8 HIGH TEMP THOLD 1 DEGREES Probe 8 High Temperature Threshold 03D1 977 EMS PROBE 8 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D2 978 EMS PROBE 8 LOW HUM THOLD 1 PERCENT Probe 8 Low Humidity Threshold 03D3 979 EMS PROBE 8 HUM 1 PERCENT Probe 8 Humidity 03D4 980 EMS PROBE 8 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D5 981 EMS PROBE 8 HIGH HUM THOLD 1 PERCENT Probe 8 High Humidity Threshold 03D6 982 EMS PROBE 8 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D7 983 EMS PROBE 8 MAXIMUM TEMP THOLD 1 DEGREES Probe 8 Maximum Temperature Threshold 03D8 984 EMS PROBE 8 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D9 985 EMS PROBE 8 MINIMUM TEMP THOLD 1 DEGREES Probe 8 Minimum Temperature Threshold 03DA 986 EMS PROBE 8 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03DB 987 EMS PROBE 8 MAXIMUM HUM THOLD 1 PERCENT Probe 8 Maximum Humidity Threshold 03DC 988 EMS PROBE 8 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03DD 989 EMS PROBE 8 MINIMUM HUM THOLD 1 DEGREES Probe 8 Minimum Humidity Threshold 03DE 990 EMS PROBE 8 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 8 Short-term Increasing Variance 03DF 991 EMS PROBE 8 SHORT-TERM INCREASING TIME 1 SECONDS Probe 8 Short-term Increasing Time 03E0 992 EMS PROBE 8 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E1 993 EMS PROBE 8 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 8 Short-term Decreasing Variance 03E2 994 EMS PROBE 8 SHORT-TERM DECREASING TIME 1 SECONDS Probe 8 Short-term Decreasing Time 03E3 995 EMS PROBE 8 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E4 996 EMS PROBE 8 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 8 Long-term Increasing Variance 03E5 997 EMS PROBE 8 LONG-TERM INCREASING TIME 1 HOURS Probe 8 Long-term Increasing Time 03E6 998 EMS PROBE 8 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E7 999 EMS PROBE 8 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 8 Long-term Increasing Variance 03E EMS PROBE 8 LONG-TERM DECREASING TIME 1 HOURS Probe 8 Long-term Increasing Time 03E EMS PROBE 8 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03EA 1002 EMS PROBE 8 RESERVED REGISTERS 22 NA Reserved // Probe EMS PROBE 9 NAME 11 ASCII Probe 9 Name 040B 1035 EMS PROBE 9 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 040C 1036 EMS PROBE 9 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 040D 1037 EMS PROBE 9 LOW TEMP THOLD 1 DEGREES Probe 9 Low Temperature Threshold 040E 1038 EMS PROBE 9 TEMP 1 DEPENDENCY Probe 9 Temperature 040F 1039 EMS PROBE 9 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 HIGH TEMP THOLD 1 DEGREES Probe 9 High Temperature Threshold EMS PROBE 9 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 LOW HUM THOLD 1 PERCENT Probe 9 Low Humidity Threshold EMS PROBE 9 HUM 1 PERCENT Probe 9 Humidity EMS PROBE 9 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 HIGH HUM THOLD 1 PERCENT Probe 9 High Humidity Threshold EMS PROBE 9 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 MAXIMUM TEMP THOLD 1 DEGREES Probe 9 Maximum Temperature Threshold EMS PROBE 9 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 MINIMUM TEMP THOLD 1 DEGREES Probe 9 Minimum Temperature Threshold 041A 1050 EMS PROBE 9 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 041B 1051 EMS PROBE 9 MAXIMUM HUM THOLD 1 PERCENT Probe 9 Maximum Humidity Threshold 041C 1052 EMS PROBE 9 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 041D 1053 EMS PROBE 9 MINIMUM HUM THOLD 1 DEGREES Probe 9 Minimum Humidity Threshold 041E 1054 EMS PROBE 9 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 9 Short-term Increasing Variance 041F 1055 EMS PROBE 9 SHORT-TERM INCREASING TIME 1 SECONDS Probe 9 Short-term Increasing Time EMS PROBE 9 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 9 Short-term Decreasing Variance EMS PROBE 9 SHORT-TERM DECREASING TIME 1 SECONDS Probe 9 Short-term Decreasing Time EMS PROBE 9 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 9 Long-term Increasing Variance EMS PROBE 9 LONG-TERM INCREASING TIME 1 HOURS Probe 9 Long-term Increasing Time

5 EMS PROBE 9 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 9 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 9 Long-term Increasing Variance EMS PROBE 9 LONG-TERM DECREASING TIME 1 HOURS Probe 9 Long-term Increasing Time EMS-EMU2 PROBE 1 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 042A 1066 EMS PROBE 9 RESERVED REGISTERS 22 NA Reserved // Probe EMS PROBE 10 NAME 11 ASCII Probe 10 Name 044B 1099 EMS PROBE 10 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 044C 1100 EMS PROBE 10 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 044D 1101 EMS PROBE 10 LOW TEMP THOLD 1 DEGREES Probe 10 Low Temperature Threshold 044E 1102 EMS PROBE 10 TEMP 1 DEPENDENCY Probe 10 Temperature 044F 1103 EMS PROBE 10 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 HIGH TEMP THOLD 1 DEGREES Probe 10 High Temperature Threshold EMS PROBE 10 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 LOW HUM THOLD 1 PERCENT Probe 10 Low Humidity Threshold EMS PROBE 10 HUM 1 PERCENT Probe 10 Humidity EMS PROBE 10 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 HIGH HUM THOLD 1 PERCENT Probe 10 High Humidity Threshold EMS PROBE 10 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 MAXIMUM TEMP THOLD 1 DEGREES Probe 10 Maximum Temperature Threshold EMS PROBE 10 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 MINIMUM TEMP THOLD 1 DEGREES Probe 10 Minimum Temperature Threshold 045A 1114 EMS PROBE 10 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 045B 1115 EMS PROBE 10 MAXIMUM HUM THOLD 1 PERCENT Probe 10 Maximum Humidity Threshold 045C 1116 EMS PROBE 10 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 045D 1117 EMS PROBE 10 MINIMUM HUM THOLD 1 DEGREES Probe 10 Minimum Humidity Threshold 045E 1118 EMS PROBE 10 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 10 Short-term Increasing Variance 045F 1119 EMS PROBE 10 SHORT-TERM INCREASING TIME 1 SECONDS Probe 10 Short-term Increasing Time EMS PROBE 10 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 10 Short-term Decreasing Variance EMS PROBE 10 SHORT-TERM DECREASING TIME 1 SECONDS Probe 10 Short-term Decreasing Time EMS PROBE 10 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 10 Long-term Increasing Variance EMS PROBE 10 LONG-TERM INCREASING TIME 1 HOURS Probe 10 Long-term Increasing Time EMS PROBE 10 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS PROBE 10 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 10 Long-term Increasing Variance EMS PROBE 10 LONG-TERM DECREASING TIME 1 HOURS Probe 10 Long-term Increasing Time EMS PROBE 10 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 046A 1130 EMS PROBE 10 RESERVED REGISTERS 22 NA Reserved // Sensor EMS SENSOR 1 DESCRIPTION NAME 3 ASCII Sensor 1 Descriptive Name EMS SENSOR 1 NAME 11 ASCII Sensor 1 Custom Name 048E 1166 EMS SENSOR 1 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 048F 1167 EMS SENSOR 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS SENSOR 1 NORMAL 1 ENUM 01 = Closed 02 = Open EMS SENSOR 1 DELAY 1 SECONDS Sensor 1 Delay EMS SENSOR 1 RESERVED REGISTERS 46 NA Reserved // Sensor 2 04C EMS SENSOR 2 DESCRIPTION NAME 3 ASCII Sensor 2 Descriptive Name 04C EMS SENSOR 2 NAME 11 ASCII Sensor 2 Custom Name 04CE 1230 EMS SENSOR 2 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 04CF 1231 EMS SENSOR 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 04D EMS SENSOR 2 NORMAL 1 ENUM 01 = Closed 02 = Open 04D EMS SENSOR 2 DELAY 1 SECONDS Sensor 2 Delay 04D EMS SENSOR 2 RESERVED REGISTERS 46 NA Reserved // Sensor EMS SENSOR 3 DESCRIPTION NAME 5 ASCII Sensor 3 Descriptive Name EMS SENSOR 3 NAME 11 ASCII Sensor 3 Custom Name EMS SENSOR 3 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed EMS SENSOR 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS SENSOR 3 NORMAL 1 ENUM 01 = Closed 02 = Open EMS SENSOR 3 DELAY 1 SECONDS Sensor 3 Delay EMS SENSOR 3 RESERVED REGISTERS 44 NA Reserved // Sensor EMS SENSOR 4 DESCRIPTION NAME 3 ASCII Sensor 4 Descriptive Name EMS SENSOR 4 NAME 11 ASCII Sensor 4 Custom Name 054E 1358 EMS SENSOR 4 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 054F 1359 EMS SENSOR 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS SENSOR 4 NORMAL 1 ENUM 01 = Closed 02 = Open EMS SENSOR 4 DELAY 1 SECONDS Sensor 4 Delay EMS SENSOR 4 RESERVED REGISTERS 46 NA Reserved // Sensor EMS SENSOR 5 DESCRIPTION NAME 3 ASCII Sensor 5 Descriptive Name EMS SENSOR 5 NAME 11 ASCII Sensor 5 Custom Name 058E 1422 EMS SENSOR 5 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 058F 1423 EMS SENSOR 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm EMS SENSOR 5 NORMAL 1 ENUM 01 = Closed 02 = Open EMS SENSOR 5 DELAY 1 SECONDS Sensor 5 Delay EMS SENSOR 5 RESERVED REGISTERS 46 NA Reserved // Sensor 6 05C EMS SENSOR 6 DESCRIPTION NAME 2 ASCII Sensor 6 Descriptive Name 05C EMS SENSOR 6 NAME 11 ASCII Sensor 6 Custom Name 05CD 1485 EMS SENSOR 6 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 05CE 1486 EMS SENSOR 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 05CF 1487 EMS SENSOR 6 NORMAL 1 ENUM 01 = Closed 02 = Open 05D EMS SENSOR 6 DELAY 1 SECONDS Sensor 6 Delay

6 05D EMS SENSOR 6 RESERVED REGISTERS 47 NA Reserved // Sensor EMS SENSOR 7 DESCRIPTION NAME 2 ASCII Sensor 7 Descriptive Name EMS SENSOR 7 NAME 11 ASCII Sensor 7 Custom Name 060D 1549 EMS SENSOR 7 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 060E 1550 EMS SENSOR 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 060F 1551 EMS SENSOR 7 NORMAL 1 ENUM 01 = Closed 02 = Open EMS SENSOR 7 DELAY 1 SECONDS Sensor 7 Delay EMS SENSOR 7 RESERVED REGISTERS 47 NA Reserved // Contact EMS-EMU2 CONTACT 1 NAME 11 ASCII Contact 1 Name 064B 1611 EMS-EMU2 CONTACT 1 STATE 1 ENUM 01 = Closed 02 = Open 064C 1612 EMS-EMU2 CONTACT 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 064D 1613 EMS-EMU2 CONTACT 1 NORMAL 1 ENUM 01 = Closed 02 = Open 064E 1614 EMS-EMU2 CONTACT 1 RESERVED REGISTERS 50 NA Reserved // Contact EMS-EMU2 CONTACT 2 NAME 11 ASCII Contact 2 Name 068B 1675 EMS-EMU2 CONTACT 2 STATE 1 ENUM 01 = Closed 02 = Open 068C 1676 EMS-EMU2 CONTACT 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 068D 1677 EMS-EMU2 CONTACT 2 NORMAL 1 ENUM 01 = Closed 02 = Open 068E 1678 EMS-EMU2 CONTACT 2 RESERVED REGISTERS 50 NA Reserved // Contact 3 06C EMS-EMU2 CONTACT 3 NAME 11 ASCII Contact 3 Name 06CB 1739 EMS-EMU2 CONTACT 3 STATE 1 ENUM 01 = Closed 02 = Open 06CC 1740 EMS-EMU2 CONTACT 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 06CD 1741 EMS-EMU2 CONTACT 3 NORMAL 1 ENUM 01 = Closed 02 = Open 06CE 1742 EMS-EMU2 CONTACT 3 RESERVED REGISTERS 50 NA Reserved // Contact EMS-EMU2 CONTACT 4 NAME 11 ASCII Contact 4 Name 070B 1803 EMS-EMU2 CONTACT 4 STATE 1 ENUM 01 = Closed 02 = Open 070C 1804 EMS-EMU2 CONTACT 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 070D 1805 EMS-EMU2 CONTACT 4 NORMAL 1 ENUM 01 = Closed 02 = Open 070E 1806 EMS-EMU2 CONTACT 4 RESERVED REGISTERS 50 NA Reserved // Contact EMS CONTACT 5 NAME 11 ASCII Contact 5 Name 074B 1867 EMS CONTACT 5 STATE 1 ENUM 01 = Closed 02 = Open 074C 1868 EMS CONTACT 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 074D 1869 EMS CONTACT 5 NORMAL 1 ENUM 01 = Closed 02 = Open 074E 1870 EMS CONTACT 5 RESERVED REGISTERS 50 NA Reserved // Contact EMS CONTACT 6 NAME 11 ASCII Contact 6 Name 078B 1931 EMS CONTACT 6 STATE 1 ENUM 01 = Closed 02 = Open 078C 1932 EMS CONTACT 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 078D 1933 EMS CONTACT 6 NORMAL 1 ENUM 01 = Closed 02 = Open 078E 1934 EMS CONTACT 6 RESERVED REGISTERS 50 NA Reserved // Contact 7 07C EMS CONTACT 7 NAME 11 ASCII Contact 7 Name 07CB 1995 EMS CONTACT 7 STATE 1 ENUM 01 = Closed 02 = Open 07CC 1996 EMS CONTACT 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 07CD 1997 EMS CONTACT 7 NORMAL 1 ENUM 01 = Closed 02 = Open 07CE 1998 EMS CONTACT 7 RESERVED REGISTERS 50 NA Reserved // Contact EMS CONTACT 8 NAME 11 ASCII Contact 8 Name 080B 2059 EMS CONTACT 8 STATE 1 ENUM 01 = Closed 02 = Open 080C 2060 EMS CONTACT 8 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 080D 2061 EMS CONTACT 8 NORMAL 1 ENUM 01 = Closed 02 = Open 080E 2062 EMS CONTACT 8 RESERVED REGISTERS 50 NA Reserved // Relay EMS-EMU2 RELAY 1 NAME 11 ASCII Relay 1 Name 084B 2123 EMS-EMU2 RELAY 1 STATE 1 ENUM 01 = Closed 02 = Open 084C 2124 EMS-EMU2 RELAY 1 NORMAL 1 ENUM 01 = Closed 02 = Open 084D 2125 EMS-EMU2 RELAY 1 RESERVED REGISTERS 51 NA Reserved // Relay EMS RELAY 2 NAME 11 ASCII Relay 2 Name 088B 2187 EMS RELAY 2 STATE 1 ENUM 01 = Closed 02 = Open 088C 2188 EMS RELAY 2 NORMAL 1 ENUM 01 = Closed 02 = Open 088D 2189 EMS RELAY 2 RESERVED REGISTERS 51 NA Reserved // Outlet 1 08C EMS OUTLET 1 NAME 11 ASCII Outlet 1 Name 08CB 2251 EMS OUTLET 1 STATE 1 ENUM 01 = On 02 = Off 08CC 2252 EMS OUTLET 1 NORMAL 1 ENUM 01 = On 02 = Off 08CD 2253 EMS OUTLET 1 RESERVED REGISTERS 51 NA Reserved // Outlet EMS OUTLET 2 NAME 11 ASCII Outlet 2 Name 090B 2315 EMS OUTLET 2 STATE 1 ENUM 01 = On 02 = Off 090C 2316 EMS OUTLET 2 NORMAL 1 ENUM 01 = On 02 = Off 090D 2317 EMS OUTLET 2 RESERVED REGISTERS 51 NA Reserved // Beacon (or Fan), see Note EMS-EMU2 BEACON STATE 1 ENUM 01 = On 02 = Off 03 = Not Installed EMS-EMU2 BEACON RESERVED REGISTERS 15 NA Reserved // ARU EMS-EMU2 ARU 1 NAME 11 ASCII ARU 1 Name 095B 2395 EMS-EMU2 ARU 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 095C 2396 EMS-EMU2 ARU 1 TEMP1 1 DEGREES ARU 1 - Fan 1 Temperature 095D 2397 EMS-EMU2 ARU 1 TEMP2 1 DEGREES ARU 1 - Fan 2 Temperature 095E 2398 EMS-EMU2 ARU 1 TEMP3 1 DEGREES ARU 1 - Fan 3 Temperature

7 095F 2399 EMS-EMU2 ARU 1 RESERVED 1 NA Reserved EMS-EMU2 ARU 1 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW EMS-EMU2 ARU 1 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM EMS-EMU2 ARU 1 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable EMS-EMU2 ARU 1 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint EMS-EMU2 ARU 1 DIP SWITCH 1 BINARY See Note EMS-EMU2 ARU 1 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature EMS-EMU2 ARU 1 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms EMS-EMU2 ARU 1 RESERVED REGISTERS 41 NA Reserved // ARU EMS-EMU2 ARU 2 NAME 11 ASCII ARU 2 Name 099B 2459 EMS-EMU2 ARU 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 099C 2460 EMS-EMU2 ARU 2 TEMP1 1 DEGREES ARU 2 - Fan 1 Temperature 099D 2461 EMS-EMU2 ARU 2 TEMP2 1 DEGREES ARU 2 - Fan 2 Temperature 099E 2462 EMS-EMU2 ARU 2 TEMP3 1 DEGREES ARU 2 - Fan 3 Temperature 099F 2463 EMS-EMU2 ARU 2 RESERVED 1 NA Reserved 09A EMS-EMU2 ARU 2 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 09A EMS-EMU2 ARU 2 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 09A EMS-EMU2 ARU 2 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 09A EMS-EMU2 ARU 2 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 09A EMS-EMU2 ARU 2 DIP SWITCH 1 BINARY See Note 4. 09A EMS-EMU2 ARU 2 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 09A EMS-EMU2 ARU 2 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 09A EMS-EMU2 ARU 2 RESERVED REGISTERS 41 NA Reserved // ARU 3 09D EMS-EMU2 ARU 3 NAME 11 ASCII ARU 3 Name 09DB 2523 EMS-EMU2 ARU 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 09DC 2524 EMS-EMU2 ARU 3 TEMP1 1 DEGREES ARU 3 - Fan 1 Temperature 09DD 2525 EMS-EMU2 ARU 3 TEMP2 1 DEGREES ARU 3 - Fan 2 Temperature 09DE 2526 EMS-EMU2 ARU 3 TEMP3 1 DEGREES ARU 3 - Fan 3 Temperature 09DF 2527 EMS-EMU2 ARU 3 RESERVED 1 NA Reserved 09E EMS-EMU2 ARU 3 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 09E EMS-EMU2 ARU 3 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 09E EMS-EMU2 ARU 3 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 09E EMS-EMU2 ARU 3 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 09E EMS-EMU2 ARU 3 DIP SWITCH 1 BINARY See Note 4. 09E EMS-EMU2 ARU 3 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 09E EMS-EMU2 ARU 3 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 09E EMS-EMU2 ARU 3 RESERVED REGISTERS 41 NA Reserved // ARU 4 0A EMS-EMU2 ARU 4 NAME 11 ASCII ARU 4 Name 0A1B 2587 EMS-EMU2 ARU 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A1C 2588 EMS-EMU2 ARU 4 TEMP1 1 DEGREES ARU 4 - Fan 1 Temperature 0A1D 2589 EMS-EMU2 ARU 4 TEMP2 1 DEGREES ARU 4 - Fan 2 Temperature 0A1E 2590 EMS-EMU2 ARU 4 TEMP3 1 DEGREES ARU 4 - Fan 3 Temperature 0A1F 2591 EMS-EMU2 ARU 4 RESERVED 1 NA Reserved 0A EMS-EMU2 ARU 4 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0A EMS-EMU2 ARU 4 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0A EMS-EMU2 ARU 4 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0A EMS-EMU2 ARU 4 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0A EMS-EMU2 ARU 4 DIP SWITCH 1 BINARY See Note 4. 0A EMS-EMU2 ARU 4 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0A EMS-EMU2 ARU 4 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0A EMS-EMU2 ARU 4 RESERVED REGISTERS 41 NA Reserved // ARU 5 0A EMS-EMU2 ARU 5 NAME 11 ASCII ARU 5 Name 0A5B 2651 EMS-EMU2 ARU 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A5C 2652 EMS-EMU2 ARU 5 TEMP1 1 DEGREES ARU 5 - Fan 1 Temperature 0A5D 2653 EMS-EMU2 ARU 5 TEMP2 1 DEGREES ARU 5 - Fan 2 Temperature 0A5E 2654 EMS-EMU2 ARU 5 TEMP3 1 DEGREES ARU 5 - Fan 3 Temperature 0A5F 2655 EMS-EMU2 ARU 5 RESERVED 1 NA Reserved 0A EMS-EMU2 ARU 5 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0A EMS-EMU2 ARU 5 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0A EMS-EMU2 ARU 5 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0A EMS-EMU2 ARU 5 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0A EMS-EMU2 ARU 5 DIP SWITCH 1 BINARY See Note 4. 0A EMS-EMU2 ARU 5 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0A EMS-EMU2 ARU 5 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0A EMS-EMU2 ARU 5 RESERVED REGISTERS 41 NA Reserved // ARU 6 0A EMS-EMU2 ARU 6 NAME 11 ASCII ARU 6 Name 0A9B 2715 EMS-EMU2 ARU 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A9C 2716 EMS-EMU2 ARU 6 TEMP1 1 DEGREES ARU 6 - Fan 1 Temperature 0A9D 2717 EMS-EMU2 ARU 6 TEMP2 1 DEGREES ARU 6 - Fan 2 Temperature 0A9E 2718 EMS-EMU2 ARU 6 TEMP3 1 DEGREES ARU 6 - Fan 3 Temperature 0A9F 2719 EMS-EMU2 ARU 6 RESERVED 1 NA Reserved 0AA EMS-EMU2 ARU 6 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0AA EMS-EMU2 ARU 6 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0AA EMS-EMU2 ARU 6 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0AA EMS-EMU2 ARU 6 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0AA EMS-EMU2 ARU 6 DIP SWITCH 1 BINARY See Note 4. 0AA EMS-EMU2 ARU 6 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0AA EMS-EMU2 ARU 6 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0AA EMS-EMU2 ARU 6 RESERVED REGISTERS 41 NA Reserved // ARU 7 0AD EMS-EMU2 ARU 7 NAME 11 ASCII ARU 7 Name

8 0ADB 2779 EMS-EMU2 ARU 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0ADC 2780 EMS-EMU2 ARU 7 TEMP1 1 DEGREES ARU 7 - Fan 1 Temperature 0ADD 2781 EMS-EMU2 ARU 7 TEMP2 1 DEGREES ARU 7 - Fan 2 Temperature 0ADE 2782 EMS-EMU2 ARU 7 TEMP3 1 DEGREES ARU 7 - Fan 3 Temperature 0ADF 2783 EMS-EMU2 ARU 7 RESERVED 1 NA Reserved 0AE EMS-EMU2 ARU 7 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0AE EMS-EMU2 ARU 7 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0AE EMS-EMU2 ARU 7 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0AE EMS-EMU2 ARU 7 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0AE EMS-EMU2 ARU 7 DIP SWITCH 1 BINARY See Note 4. 0AE EMS-EMU2 ARU 7 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0AE EMS-EMU2 ARU 7 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0AE EMS-EMU2 ARU 7 RESERVED REGISTERS 41 NA Reserved // ARU 8 0B EMS-EMU2 ARU 8 NAME 11 ASCII ARU 8 Name 0B1B 2843 EMS-EMU2 ARU 8 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0B1C 2844 EMS-EMU2 ARU 8 TEMP1 1 DEGREES ARU 8 - Fan 1 Temperature 0B1D 2845 EMS-EMU2 ARU 8 TEMP2 1 DEGREES ARU 8 - Fan 2 Temperature 0B1E 2846 EMS-EMU2 ARU 8 TEMP3 1 DEGREES ARU 8 - Fan 3 Temperature 0B1F 2847 EMS-EMU2 ARU 8 RESERVED 1 NA Reserved 0B EMS-EMU2 ARU 8 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0B EMS-EMU2 ARU 8 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0B EMS-EMU2 ARU 8 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0B EMS-EMU2 ARU 8 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0B EMS-EMU2 ARU 8 DIP SWITCH 1 BINARY See Note 4. 0B EMS-EMU2 ARU 8 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0B EMS-EMU2 ARU 8 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0B EMS-EMU2 ARU 8 RESERVED REGISTERS 41 NA Reserved // Logging Registers FFEE APC RX CRC ERRORS 2 LONG RX CRC ERRORS FFF APC RX PACKET COUNTER 2 LONG RX PACKET COUNTER FFF APC TX PACKET COUNTER 2 LONG TX PACKET COUNTER FFF APC SER FRAME ERRORS 2 LONG SER FRAME ERRORS FFF APC SER OVERRUN ERRORS 2 LONG SER OVERRUN ERRORS FFF APC SER PARITY ERRORS 2 LONG SER PARITY ERRORS FFFA APC SER RX15 ERRORS 2 LONG SER RX15 ERRORS FFFC APC SER RX35 ERRORS 2 LONG SER RX35 ERRORS FFFE APC SER BAUD RATE 1 INTEGER SER BAUD RATE // END OF DATA Note 1: The temperature value returned will be either in Celsius or Fahrenheit depending on the value read from Modbus Register EMS TEMP DISPLAY TYPE. Note 2: The "Alarm Map" represents a bit map of the alarm state(s) Only Beacon (or Fan) and Relay1 are available for EMU2. 01 = No Alarms (bit 0) 02 = Major Alarm (bit 1) 04 = Minor Alarm (bit 2) 08 = Outlet 1 Alarm (bit 3) 16 = Outlet 2 Alarm (bit 4) 32 = Beacon (or Fan) Alarm (bit 5) 64 = Relay 1 Alarm (bit 6) 128 = Relay 2 Alarm (bit 7) Note 3. This value may be in units of DEGREES or Kilowatts. Note 4. The 4 least significant bits of this register define the following: 0000 wxyz - w is the temperature override bit. If w is set, the temperature override condition exists. - x is the least significant bit of the 3 bit ARU CAN bus address - y is the middle bit of the 3 bit ARU CAN bus address - z is the most significant bit of the 3 bit ARU CAN bus address Note 5. The Hardware State is defined as follows: 00 = No Fault. 01 = Alink Fault. (Current Overload condition on the Alink ports.) 02 = Sensor Connection Fault.( Motion or Smoke Alarm port does not have the correct sensor.) 03 = Both Alink and Sensor Connection Fault. Note 6. On some model SKUs, Beacon functionality is replaced by a Fan.

Alarm Messages... 15 Clearing the Hardware Alarms... 16. How to Log On... 17 Summary Page... 21 Navigation Menu... 24

Alarm Messages... 15 Clearing the Hardware Alarms... 16. How to Log On... 17 Summary Page... 21 Navigation Menu... 24 Contents Introduction--1 Product Description.................................. 1 Access Procedures................................... 3 How to Recover from a Lost Password..................... 6 Upgrading

More information

Environmental Management System

Environmental Management System Contents Introduction--1 Product Description.................................. 1 Access Procedures................................... 3 How to Recover from a Lost Password..................... 6 Upgrading

More information

Visa Smart Debit/Credit Certificate Authority Public Keys

Visa Smart Debit/Credit Certificate Authority Public Keys CHIP AND NEW TECHNOLOGIES Visa Smart Debit/Credit Certificate Authority Public Keys Overview The EMV standard calls for the use of Public Key technology for offline authentication, for aspects of online

More information

USER S GUIDE. Contents. NetBotz Rack Monitor 200. Introduction--1. Control Console--8

USER S GUIDE. Contents. NetBotz Rack Monitor 200. Introduction--1. Control Console--8 Contents Introduction--1 Product Description....................................... 1 Document Overview....................................... 1 Additional Documentation..................................

More information

Features and Benefits

Features and Benefits Refrigeration 2 eatures and Benefits Based on IR32 Parameters Real Time lock ( RT ) Model Specific (defrost based on real time 7 day 24 hour) HAP (Hazard Analysis and ritical ontrol Point) Alarm Available

More information

The ASCII Character Set

The ASCII Character Set The ASCII Character Set The American Standard Code for Information Interchange or ASCII assigns values between 0 and 255 for upper and lower case letters, numeric digits, punctuation marks and other symbols.

More information

WeatherLink for Alarm Output. Introduction. Hardware Installation and Requirements. Addendum

WeatherLink for Alarm Output. Introduction. Hardware Installation and Requirements. Addendum WeatherLink for Alarm Output Addendum Introduction This Streaming Data Logger is designed to provide an electrical interface between a Vantage Pro2, Vantage Vue, or Vantage Pro weather station console

More information

026-1728 Rev 0 25-AUG-2011. ipro HVAC and Lighting Installation and Operation Manual

026-1728 Rev 0 25-AUG-2011. ipro HVAC and Lighting Installation and Operation Manual 026-1728 Rev 0 25-AUG-2011 ipro HVAC and Lighting Installation and Operation Manual Retail Solutions 3240 Town Point Drive NW, Suite 100 Kennesaw, GA 30144 Phone: 770-425-2724 Fax: 770-425-9319 Table

More information

Community College of Philadelphia Calling Code 218 Employer Scan Client Approved: November 17, 2005 Region (CIRCLE) City MSA

Community College of Philadelphia Calling Code 218 Employer Scan Client Approved: November 17, 2005 Region (CIRCLE) City MSA Community College of Philadelphia Calling Code 218 Employer Scan Client Approved: November 17, 2005 Region (CIRCLE) City MSA Zip V0 V1 V2 Month/ Day/ Year of Contact: Business Name: Address: V3 City: V4

More information

GE Security. FHSD Monitor / Web Server user manual

GE Security. FHSD Monitor / Web Server user manual GE Security FHSD Monitor / Web Server user manual version 1-0 / november 2004 http://www.geindustrial.com/ge-interlogix/emea 2004 GE Interlogix B.V.. All rights reserved. GE Interlogix B.V. grants the

More information

TOTALLY SOLID STATE NON-DIRECTIONAL RADIO BEACONS 190-535 khz

TOTALLY SOLID STATE NON-DIRECTIONAL RADIO BEACONS 190-535 khz TOTALLY SOLID STATE NON-DIRECTIONAL RADIO S 190-535 khz This family of radio transmitters has been developed as extremely efficient, highly reliable Non Directional Beacons. ND2000A/4000A» MODULAR CONSTRUCTION»

More information

Controller Automation, Model II+

Controller Automation, Model II+ Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control

More information

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company USER MANUAL Model 6103 3U ForeFront Alarm Card An ISO-9001 Certified Company Part# 07M6103 Doc# 123011U Rev. A Revised 7/15/03 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 CONTENTS 1.0

More information

APC APPLICATION NOTE #156

APC APPLICATION NOTE #156 #156 StruxureWare Data Center Expert v7.2.0 Building Management System Integration By Kevin Kosko Abstract Building Management Systems (BMS) are implemented in a building's infrastructure to collect data

More information

SERVER CERTIFICATES OF THE VETUMA SERVICE

SERVER CERTIFICATES OF THE VETUMA SERVICE Page 1 Version: 3.5, 4.11.2015 SERVER CERTIFICATES OF THE VETUMA SERVICE 1 (18) Page 2 Version: 3.5, 4.11.2015 Table of Contents 1. Introduction... 3 2. Test Environment... 3 2.1 Vetuma test environment...

More information

www.lascarelectronics.com

www.lascarelectronics.com FEATURES 0-30V d.c. measurement range Logging rates between 1s and 12hr Stores readings Connection via two screw terminals USB interface for set-up and data download User-programmable alarm thresholds

More information

MPC 4. Machinery Protection Card Type MPC 4 FEATURES. Continuous on-line Machinery Protection Card

MPC 4. Machinery Protection Card Type MPC 4 FEATURES. Continuous on-line Machinery Protection Card Machinery Protection Card Type FEATURES Continuous on-line Machinery Protection Card Real-time measurement and monitoring using state-of-the-art DSP techniques Fully VME-compatible slave interface Fully

More information

Technical Overview Add-on Sensors - Smoke Alarm. Get yours direct at: 01491 410913 www.theclimate.co.uk

Technical Overview Add-on Sensors - Smoke Alarm. Get yours direct at: 01491 410913 www.theclimate.co.uk Technical Overview Add-on Sensors - Smoke Alarm Get yours direct at: 01491 410913 www.theclimate.co.uk OVERVIEW This kit contains a standard smoke alarm and relay pattress. The Kidde Smoke Alarm supplied

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL Installation and operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN YOUR FILES FOR FUTURE REFERENCE. IMPROPER

More information

Current Monitoring Kit QUICK START GUIDE

Current Monitoring Kit QUICK START GUIDE Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...

More information

Current Monitoring Kit

Current Monitoring Kit Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added

More information

SERVER CERTIFICATES OF THE VETUMA SERVICE

SERVER CERTIFICATES OF THE VETUMA SERVICE Page 1 Version: 3.4, 19.12.2014 SERVER CERTIFICATES OF THE VETUMA SERVICE 1 (18) Page 2 Version: 3.4, 19.12.2014 Table of Contents 1. Introduction... 3 2. Test Environment... 3 2.1 Vetuma test environment...

More information

IntesisBox Modbus Server SAMSUNG Air Conditioners

IntesisBox Modbus Server SAMSUNG Air Conditioners IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,

More information

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module 1. General Description 1 2. General Warnings 1 3. Interface 2 4. Temp Alarms Setting 3 5. Programming 3 6. Light Management 4 7. Installation and

More information

INSTALLATION OPERATING & MAINTENANCE MANUAL

INSTALLATION OPERATING & MAINTENANCE MANUAL INSTALLATION OPERATING & MAINTENANCE MANUAL Basic Climatic TM Controller Ecologic English November 2002 CONTENTS PAGE GENERAL DESCRIPTION 3 USER INTERFACE 4 The keypad incorporated on the unit 4 The keypad

More information

Energy Management System CANBUS Interface Specification

Energy Management System CANBUS Interface Specification Energy Management System CANBUS Interface Specification Overview The EMS Broadcaster program will export a set of data via a Canbus hardware link. The data set is open and described here to facilitate

More information

EMDX3 Multifunction meter Cat No. 146 69 ModbusTable LGR EN v1.01.xls

EMDX3 Multifunction meter Cat No. 146 69 ModbusTable LGR EN v1.01.xls GENERAL MODBUS TABLE ORGANIZATION Starting of the Starting of the Group s Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 50512 C550

More information

Ambient Temperature In Range Probe X

Ambient Temperature In Range Probe X List of Events This section lists all events that are written to the Event Log. Some of these events can be configured through the Configuring Events to Take Actions page, and these are listed in the first

More information

Kendrick Astro Instruments

Kendrick Astro Instruments Kendrick Astro Instruments Premier Power Controller Remote Control Software Version 2.0 - User Guide - INTRODUCTION...3 Kendrick Premier Power Controller...3 Remote Control Software...4 INSTALLATION...5

More information

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 16400(LED TYPES) EXAMINED BY : FILE NO. CAS-10068 ISSUE : JAN.19,2000 TOTAL PAGE : 7 APPROVED BY:

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 16400(LED TYPES) EXAMINED BY : FILE NO. CAS-10068 ISSUE : JAN.19,2000 TOTAL PAGE : 7 APPROVED BY: EXAMINED BY : FILE NO. CAS-10068 APPROVED BY: EMERGING DISPLAY TECHNOLOGIES CORPORATION ISSUE : JAN.19,2000 TOTAL PAGE : 7 VERSION : 3 CUSTOMER ACCEPTANCE SPECIFICATIONS MODEL NO. : 16400(LED TYPES) FOR

More information

PE6108/PE6208/PE8108/PE8208

PE6108/PE6208/PE8108/PE8208 Energy Intelligence Solutions PE6108/PE6208/PE8108/PE8208 eco PDU Distribution Unit ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency

More information

CROSS REFERENCE. Cross Reference Index 110-122. Cast ID Number 110-111 Connector ID Number 111 Engine ID Number 112-122. 2015 Ford Motor Company 109

CROSS REFERENCE. Cross Reference Index 110-122. Cast ID Number 110-111 Connector ID Number 111 Engine ID Number 112-122. 2015 Ford Motor Company 109 CROSS REFERENCE Cross Reference Index 110-122 Cast ID Number 110-111 Connector ID Number 111 112-122 2015 Ford Motor Company 109 CROSS REFERENCE Cast ID Number Cast ID Ford Service # MC Part # Part Type

More information

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC HOJA TÉCNICA 1400H101 Edición 01 (02 de 08) www.ako.es GENERAL TECHNICAL SPECIFICATIONS Temperature range: -50ºC to +99ºC type: NTC Total accuracy ( + controller): ±1ºC lead extension with cable AKO-15586:

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 20400 (LED TYPES) EXAMINED BY : FILE NO. CAS-10184 ISSUE : DEC.01,1999 TOTAL PAGE : 7 APPROVED BY:

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 20400 (LED TYPES) EXAMINED BY : FILE NO. CAS-10184 ISSUE : DEC.01,1999 TOTAL PAGE : 7 APPROVED BY: EXAMINED BY : FILE NO. CAS-10184 APPROVED BY: EMERGING DISPLAY TECHNOLOGIES CORPORATION ISSUE : DEC.01,1999 TOTAL PAGE : 7 VERSION : 2 CUSTOMER ACCEPTANCE SPECIFICATIONS MODEL NO. : 20400 (LED TYPES) FOR

More information

APPENDIX A: ERROR CODES

APPENDIX A: ERROR CODES APPENDIX A: ERROR 20001 Unable to load a Remove and replace cassette Check the micro-switch located on the inside left wall of the 20002 Low Cash. Replenish the cash If using less than 75 bills, disable

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

Pattern Co. Monkey Trouble Wall Quilt. Size: 48" x 58"

Pattern Co. Monkey Trouble Wall Quilt. Size: 48 x 58 .............................................................................................................................................. Pattern Co..........................................................................................

More information

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Preface Safety warnings To avoid injury, or damage to the Modbus interface, read all installation and configuration instructions in this

More information

PN5212/PN5320/PN7212/PN7320

PN5212/PN5320/PN7212/PN7320 PN522/PN5/PN722/PN7 Over the NET Distribution Units ALTUSEN Over the NET products are Distribution Units that offer outlet level control combined with remote access to give IT administrators the ability

More information

Modbus Tutorial 7/30/01. Tutorial on TTDM-PLUS and TTSIM System Integration using Modbus

Modbus Tutorial 7/30/01. Tutorial on TTDM-PLUS and TTSIM System Integration using Modbus Modbus Tutorial 7/30/01 Tutorial on TTDM-PLUS and TTSIM System Integration using Modbus There are two ways that system integrators can access leak detection information using the Modbus interface: either

More information

NIC Controller & Web Interface

NIC Controller & Web Interface NIC Controller & Web Interface 24 x7 Installation and Technical Support 1-866-240-6614 Page 1 of 37 Version 1.1 Table of Contents 1 OVERVIEW... 3 2 INSTALLATION AND TURN-UP... 3 3 MINIMUM REQUIREMENTS...

More information

How To Run An Nport I5000A Device Server

How To Run An Nport I5000A Device Server NPort IA5000A Series 1, 2, and 4-port serial device servers for industrial automation Enhanced surge protection for serial, LAN, and power 2 KV isolation for serial signals Rugged screw-type terminal blocks

More information

SMART SENSOR COLLECTION

SMART SENSOR COLLECTION TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8

More information

Ademco Vista-20P/First Alert FA-168C Basic Commands

Ademco Vista-20P/First Alert FA-168C Basic Commands Zones 64 total Ademco Vista-20P/First Alert FA-168C Basic Commands Wireless Yes, Zones 09 to 48 + 16 Keyfob Zones (Zones 49 to 64) Batteries Downloadable Partitions 2 12 volt Rechargable inside main Panel,

More information

Configuring Alarms & Relays in the Enhanced Transformer Advantage

Configuring Alarms & Relays in the Enhanced Transformer Advantage Configuring s & Relays in the Enhanced Transformer Advantage The Transformer Advantage product family offers a variety of relay options. Some choices are made when the Advantage is specified and ordered.

More information

Configurator Software Manual

Configurator Software Manual Configurator Software Manual The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications

More information

URL encoding uses hex code prefixed by %. Quoted Printable encoding uses hex code prefixed by =.

URL encoding uses hex code prefixed by %. Quoted Printable encoding uses hex code prefixed by =. ASCII = American National Standard Code for Information Interchange ANSI X3.4 1986 (R1997) (PDF), ANSI INCITS 4 1986 (R1997) (Printed Edition) Coded Character Set 7 Bit American National Standard Code

More information

Configuration of the Sentry firmware parameters used in the Bluetooth solution.

Configuration of the Sentry firmware parameters used in the Bluetooth solution. Server Technology s Monitoring Solution Featuring Bluetooth Wireless Technology and the ST Eye Mobile App (for Android) Part Numbers KIT-STEYE-01 and KIT-STEYE-10 Purpose This technical note provides functional

More information

SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI User Guide

SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI User Guide SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI Simplay-UG-02003-A July 2015 Contents 1. Overview... 4 1.1. SL-8800 HDCP Protocol Analyzer Test Equipment... 4 1.2. HDCP 2.2/HDCP 1.x Protocol Analyzer

More information

Appendix for Tx5xx and P85x1 manuals

Appendix for Tx5xx and P85x1 manuals Appendix for Tx5xx and P85x1 manuals Content Appendix for Tx5xx and P85x1 manuals...1 Content...1 Design of www pages for Tx5xx and P85x1 Ethernet transducers...2 Procedure of creation of www pages for

More information

Mobrey Hydrastep and Hydratect

Mobrey Hydrastep and Hydratect Product Data Sheet August 2015 BP2468, Rev EA Mobrey Hydrastep and Hydratect Water/Steam Monitoring Systems High clarity electronic gauging system for steam drums with options of local and remote indication

More information

pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual

pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee correct installation

More information

Using the STC-1000+ firmware

Using the STC-1000+ firmware Using the STC-1000+ firmware Project home at Github Features Both Fahrenheit and Celsius versions Up to 6 profiles with up to 10 setpoints. Each setpoint can be held for 1 999 hours (i.e. up to ~41 days).

More information

Workshop 7 PC Software - Tracker

Workshop 7 PC Software - Tracker Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output

More information

Table of Contents. 1. Introduction...1. 2. PDU Package...2. 3. Function...3. 4. Installation...5. 5. Web Interface...7

Table of Contents. 1. Introduction...1. 2. PDU Package...2. 3. Function...3. 4. Installation...5. 5. Web Interface...7 PDU User Manual Table of Contents 1. Introduction...1 2. PDU Package...2 3. Function...3 4. Installation...5 5. Web Interface...7 1. Introduction The PDU is an Internet ready device designed and is equipped

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Configurable Events for APC Network Management Card

Configurable Events for APC Network Management Card Configurable s for APC Network Management Card Table of Contents Silcon DP300E Series 3 Smart-UPS / Matrix 7 Symmetra 9 Symmetra 3-Phase 13 Environmental Monitor 21 Configurable s for APC Network Management

More information

Integration Note. Manufacturer: OVERVIEW AND SUPPORTED FEATURES. OMNISTAT 2 (RC-1000 and RC-2000) WIRED MODELS ONLY.

Integration Note. Manufacturer: OVERVIEW AND SUPPORTED FEATURES. OMNISTAT 2 (RC-1000 and RC-2000) WIRED MODELS ONLY. Manufacturer: Model Number(s): Minimum Core Module Version: Comments: HAI Document Revision Date: 4/18/2013 OMNISTAT 2 (RC-1000 and RC-2000) WIRED MODELS ONLY Firmware V. 1.03 Tested Integration Note OVERVIEW

More information

USB3.0 Docking Station. User Manual (DA-70546)

USB3.0 Docking Station. User Manual (DA-70546) USB3.0 Docking Station User Manual (DA-70546) Foreword Congratulations on your purchase of our product! We will show you a new storage concept with safety and convenience It is our pleasure to give you

More information

Technical Information

Technical Information Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1

More information

Modbus Communications for PanelView Terminals

Modbus Communications for PanelView Terminals User Guide Modbus Communications for PanelView Terminals Introduction This document describes how to connect and configure communications for the Modbus versions of the PanelView terminals. This document

More information

IES-3080/3062 Series. Industrial 8-port managed Ethernet switch. Features. Introduction

IES-3080/3062 Series. Industrial 8-port managed Ethernet switch. Features. Introduction IES-3080/3062 Series Features Industrial 8-port managed Ethernet switch Fastest Redundant Ethernet Ring: O-Ring (recovery time < 10ms over 250 units of connection) Open-Ring supports the other vendor s

More information

How to create OpenDocument URL s with SAP BusinessObjects BI 4.0

How to create OpenDocument URL s with SAP BusinessObjects BI 4.0 How to create OpenDocument URL s with SAP BusinessObjects BI 4.0 Creator: Twitter: Blog: Pieter Verstraeten http://www.twitter.com/pverstraeten http://www.pieterverstraeten.com/blog Hi, Thanks for downloading

More information

HTML Codes - Characters and symbols

HTML Codes - Characters and symbols ASCII Codes HTML Codes Conversion References Control Characters English version Versión español Click here to add this link to your favorites. HTML Codes - Characters and symbols Standard ASCII set, HTML

More information

SPC-1. Single Point Controller. Operation Manual

SPC-1. Single Point Controller. Operation Manual SPC-1 Single Point Controller Operation Manual NOTICE: PPM Technology Limited shall not be liable for errors that may appear herein or for incidental or consequential damages in connection with or arising

More information

Dyeing Programmer DP - 01

Dyeing Programmer DP - 01 Dyeing Programmer DP - 01 Display and Controls. 1) Display: 16/2 alphanumeric display 2) Temperature range: 0 to 150 degree. 3) Resolution: 1 degree. 4) Accuracy: +/- 1 degree. 5) Temperature control setting:

More information

Heller Industries, Inc. PN: 689011 Rev-I Heller Oven Windows-XP Software Version log for HC1 controller

Heller Industries, Inc. PN: 689011 Rev-I Heller Oven Windows-XP Software Version log for HC1 controller PN: 689011 RevI Heller Oven WindowsXP Software Version log for HC1 controller Page 1 of 5 Software Version 4.0.0.0 11202005 4.0.0.1 Feb2706 4.0.0.2 Mar2706 4.0.0.3 Apr2706 4.0.0.3a Jun2706 4.0.0.4 7132006

More information

F453. TiF453. User guide 10/11-01 PC

F453. TiF453. User guide 10/11-01 PC F453 TiF453 User guide 10/11-01 PC 2 TiF453 User guide Contents 1. Hardware and Software requirements 4 2. Installation 4 1.1 Minimum Hardware requirements 4 1.2 Minimum Software requirements 4 3. Fundamental

More information

USB-500 Series Stand-Alone, Low-Cost Data Loggers

USB-500 Series Stand-Alone, Low-Cost Data Loggers Stand-Alone, Low-Cost Data Loggers Features Stand-alone, remote data loggers Measure temperature, humidity, voltage, or current 1 or 2 channels Low cost, small size Battery powered Software Included, easy-to-use

More information

Cat Electronic Technician 2015A v1.0 Product Status Report 4/20/2016 2:49 PM

Cat Electronic Technician 2015A v1.0 Product Status Report 4/20/2016 2:49 PM Page 1 of 19 Cat Electronic Technician 2015A v1.0 Product Status Report 2:49 PM Product Status Report Parameter Value Product ID WRK00337 Equipment ID WRK00337 Comments A01-52 C9 330D (THX37891) Parameter

More information

"HIGHER EDUCATION VALUES AND OPINIONS SURVEY" ADVANCED PLACEMENT TEACHERS and GUIDANCE COUNSELORS May-June 1994

HIGHER EDUCATION VALUES AND OPINIONS SURVEY ADVANCED PLACEMENT TEACHERS and GUIDANCE COUNSELORS May-June 1994 "HIGHER EDUCATION VALUES AND OPINIONS SURVEY" ADVANCED PLACEMENT TEACHERS and GUIDANCE COUNSELORS May-June 1994 VARIABLE SURVEY ANSWER NAME QUESTION CATEGORIES Facsimile the original mail questionnaire

More information

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode: COMMUNICATION INSTRUCTION MANUAL TEMPERATURE CONTROLLER KT4, KT8 and KT9 No.KTC1E6 2009.05 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

Technical Support Bulletin Nr.18 Modbus Tips

Technical Support Bulletin Nr.18 Modbus Tips Technical Support Bulletin Nr.18 Modbus Tips Contents! Definitions! Implemented commands! Examples of commands or frames! Calculating the logical area! Reading a signed variable! Example of commands supported

More information

Design of WSN-Based Remote Monitoring System for Environmental Parameters in Substation

Design of WSN-Based Remote Monitoring System for Environmental Parameters in Substation International Journal of Smart Grid and Clean Energy Design of WSN-Based Remote Monitoring System for Environmental Parameters in Substation Aina Hu a *, Huanhuan Wang b, and Jianchen Wan a a Department

More information

E E V R E - R S - O S L O A L R

E E V R E - R S - O S L O A L R Solar Eye User Manual Edition JIANGSU EVER-SOLAR NEW ENERGY CO., LTD. Revision History Date Edition Specification 17/08/2011 1.0 Create File 02/09/2011 1.1 Add Micro SD function description www.ever-solar.com

More information

UPSMON PRO Linux --- User Manual

UPSMON PRO Linux --- User Manual UPSMON PRO Linux --- User Manual Version : 2.1 *Attention : root authority is necessary to execute at Linux here AA. UPSMON PRO Install 2 BB. UPSMON PRO Start 3 CC. UPSMON PRO Status 6 DD. UPSMON PRO Config

More information

MIC-3920/MIC-3921 Intelligent system monitor and alarm module for CompactPCI TM

MIC-3920/MIC-3921 Intelligent system monitor and alarm module for CompactPCI TM MIC-3920/MIC-3921 Intelligent system monitor and alarm module for CompactPCI TM Copyright Notice This document is copyrighted, 1999. All rights are reserved. The original manufacturer reserves the right

More information

COPAN 400M PSM Service GUI User Guide

COPAN 400M PSM Service GUI User Guide COPAN 400M PSM Service GUI User Guide Part #: CPR02588 Revision Level: A01 August 2010 2002-2010 SGI International, Inc. All Rights Reserved. POWER MANAGED RAID and DISK AEROBICS are all registered trademarks

More information

Battery Xplorer Enterprise Software Release Notes 3.2

Battery Xplorer Enterprise Software Release Notes 3.2 Battery Xplorer Enterprise Software Release Notes 3.2 Version 3.2 - DIM imports for UXTMs displays actual string names. - Missing help files added for discharge alarm links in alarm details page. - Spinner

More information

Kurz Instruments Inc. Document 360209-AV Document Title: MFTB Event Code Definitions. MFT B-Series Event Codes

Kurz Instruments Inc. Document 360209-AV Document Title: MFTB Event Code Definitions. MFT B-Series Event Codes MFT B-Series Event Codes The MFT B-series status information is contained in a 4-byte long word (32-bit) Event Code. This Event Code provides a bit-wise mapping of the status of the flow meter with each

More information

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module! Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8

More information

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw rather than providing multiple choices. The sensor modules used may only be suitable for use with the matching controller so it is wise to read the specifications to make sure the unit suits your application.

More information

Product Description... 1 Internal Management Features... 3 Front Panel... 5 Watchdog Features... 7

Product Description... 1 Internal Management Features... 3 Front Panel... 5 Watchdog Features... 7 Contents Introduction--1 Product Description.................................. 1 Internal Management Features........................... 3 Front Panel........................................ 5 Watchdog

More information

Application Note RMF Magic 5.1.0: EMC Array Group and EMC SRDF/A Reporting. July 2009

Application Note RMF Magic 5.1.0: EMC Array Group and EMC SRDF/A Reporting. July 2009 Application Note RMF Magic 5.1.0: EMC Array Group and EMC SRDF/A Reporting July 2009 Summary: This Application Note describes the new functionality in RMF Magic 5.1 that enables more effective monitoring

More information

Temp. & humidity Transmitter Instructions

Temp. & humidity Transmitter Instructions Temp. & humidity Transmitter Instructions AQ3485/AQ3485Y www.aosong.com 1 Product Overview AQ3485/ AQ3485Y outdoor network temperature and humidity transmitter is accurate measurement of relative humidity

More information

ASCII CODES WITH GREEK CHARACTERS

ASCII CODES WITH GREEK CHARACTERS ASCII CODES WITH GREEK CHARACTERS Dec Hex Char Description 0 0 NUL (Null) 1 1 SOH (Start of Header) 2 2 STX (Start of Text) 3 3 ETX (End of Text) 4 4 EOT (End of Transmission) 5 5 ENQ (Enquiry) 6 6 ACK

More information

INSTALLATION MANUAL. Address card EKAC10B

INSTALLATION MANUAL. Address card EKAC10B INSTALLATION MANUAL 88 44 µchiller compact 70 64 4a 4b G G0 power supply G G0 power supply 50 5 50 5 4a 4b 5a 5b 4 5a 5b Installation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO

More information

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 DESCRIPTION CO transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air

More information

QuickSpecs. HP Managed and Unmanaged Notebook Charging Carts. Models HP 30-Notebook Charging Cart

QuickSpecs. HP Managed and Unmanaged Notebook Charging Carts. Models HP 30-Notebook Charging Cart Overview HP Managed and Unmanaged Notebook Charging Carts Models HP 20-Notebook Charging Cart HP 30-Notebook Charging Cart HP 20-Notebook Managed Charging Cart HP 30-Notebook Managed Charging Cart QL488AA#ABA

More information

QuickSpecs. HP Managed Power Distribution Units (mapdu) Overview

QuickSpecs. HP Managed Power Distribution Units (mapdu) Overview Overview Looking for a power distribution unit that meets the demands of high temperature operating environments and provides monitoring and switching capabilities? The HP Managed Power Distribution Unit

More information

USB HID to PS/2 Scan Code Translation Table

USB HID to PS/2 Scan Code Translation Table Key Name HID Usage Page HID Usage ID PS/2 Set 1 Make* PS/2 Set 1 Break* PS/2 Set 2 Make PS/2 Set 2 Break System Power 01 81 E0 5E E0 DE E0 37 E0 F0 37 System Sleep 01 82 E0 5F E0 DF E0 3F E0 F0 3F System

More information

232982 KLQ750CO controller temp/intensity/feedback/24v/usb/rs622/analog trigger

232982 KLQ750CO controller temp/intensity/feedback/24v/usb/rs622/analog trigger RANGE OF PRODUCTS 233393 KLQ750LQ-N LED lightsource Ø4.25/3000K 233394 KLQ750LQ-N LED lightsource Ø4.25/7000K 233154 KLQ750LQ-N LED lightsource Ø4.25/8500K 233258 KLQ750LQ-F LED lightsource Ø4.25/8500K/feedback

More information

Contents. Introduction

Contents. Introduction TION Contents Introduction...1 Basics...2 Main Menu Structure...3 Time Schedule Menu...4 Settings Menu...5 Reports Menu...6 Date / Time Adjustment Menu...7 Introduction TION is an advanced control device

More information

HP Managed and Unmanaged Notebook Charging Carts Overview. Models HP 30-Notebook Charging Cart. HP 30-Notebook Managed Charging Cart

HP Managed and Unmanaged Notebook Charging Carts Overview. Models HP 30-Notebook Charging Cart. HP 30-Notebook Managed Charging Cart Overview Models HP 20-Notebook Charging Cart HP 30-Notebook Charging Cart HP 20-Notebook Managed Charging Cart HP 30-Notebook Managed Charging Cart QL488AA#ABA H4F31AA#ABA QL489AA#ABA QL490AA#ABA Introduction

More information

RadioRA 2 (QS) Lighting and Climate Control. g! 5.4 Fan Controller: g! 6.4.200 RadioRA2 Inclusive Software v5.0.8 or newer

RadioRA 2 (QS) Lighting and Climate Control. g! 5.4 Fan Controller: g! 6.4.200 RadioRA2 Inclusive Software v5.0.8 or newer Manufacturer: Model Number(s): Minimum Core Module Version: Comments: Lutron Document Revision Date: 8/5/2013 OVERVIEW AND SUPPORTED FEATURES Integration Note RadioRA 2 (QS) Lighting and Climate Control

More information

T360 Barbecue. Assembly Manual. 85-3052-6 (G30531) Propane 1 YEAR LIMITED WARRANTY

T360 Barbecue. Assembly Manual. 85-3052-6 (G30531) Propane 1 YEAR LIMITED WARRANTY T360 Barbecue Assembly Manual 85-3052-6 (G30531) Propane 1 YEAR LIMITED WARRANTY READ AND SAVE MANUAL FOR FUTURE REFERENCE. If pre-assembled, leave this manual with unit for consumer s future reference.

More information