List of Criteria developed for Server Room and Data Center Audits.

Size: px
Start display at page:

Download "List of Criteria developed for Server Room and Data Center Audits."

Transcription

1 reliable data center List of Criteria developed for Server Room and Data Center Audits.

2 Preface The list of criteria was developed for server room and data center audits. It is intended to be used as a guideline for planning, implementation and acceptance testing of server rooms and data centers. Nowadays, the physical security and availability of IT is of vital importance to companies as many IT-supported business processes run as real-time applications. Interruptions would immediately result in inconvenient failures and possibly losses in production. Many banks and insurance companies include availability results in their risk assessments for loans and premiums. This new test method from TÜV Rheinland was developed due to growing market demands. It considers the previously known Basel III requirements for IT availability (effective from 2013). Pocket Overview of Classes The list of criteria is based on standards established by the German BSI (Federal Office for Information Security), Uptime Institute, TIA 942 (1) (2) and the publications of the German VdS institution (Property Insurers Association), in particular VdS This list of criteria allows comprehensive testing of IT infrastructure and operation. It is constantly updated. New rules and regulations are added at regular intervals. The list of criteria was developed in cooperation with Dr. Braun Consultants GmbH, Frankfurt am Main, Germany. Server room / data center n n n 2 (n+1) > 400 kva / to 320 kw / 200 m 2 CAT: Electrical supply Supply / medium-voltage supply X X X X X X 2 Transformers X X X X X 2 2 (n + 1) Low-voltage main distribution (LVMD) X X X X X 2 2 (n + 1) Stand-by unit (diesel) Provision X X X 2 2 (n + 1) Uninterruptible power supply unit (UPS) X X X X (n + 1) Data center power distributions X X n + 1 n (n + 1) Rack supply X X Air conditioning Coolers (chillers / cooling system) X X n + 1 n n 2 n 2 (n + 1) Computer room air conditioners X X n + 1 n n 2 n 2 (n + 1) Pump system X n 2 n 2 (n + 1) Piping X X X X Ring Ring Ring Building management system Operational threshold value display /indication X X X X X X Alarm messages by , SMS text message, alarm annunciator X X X X X Data recording X X X Evaluation option (ISO 50001) optional optional optional optional optional optional optional Maintenance Redundancy X X X X X Redundant supply paths X X X Maintenance during operation X X X Maintenance window X X X X

3 Site Selection Architecture / site selection / risks Proximity to flood hazard areas mapped on an official or insurance-related map (distance to coasts and waterways) no requirements not in a flood hazard zone not within 100-year flood hazard area or less than 100 m from 50-year flood hazard area not less than 100 m from 100-year flood hazard area Proximity to major traffic arteries or traffic routes with transport of dangerous goods no requirements no requirements not less than 100 m not less than 800 m Proximity to airports (entry lanes, missed approach procedure) no requirements no requirements not less than 1.6 km not less than 8 km Proximity to large cities (cable routes) no requirements no requirements not greater than 50 km not greater than 15 km Dangerous goods locations (gas pipeline, refineries, flammable liquids storage room) no requirements no requirements not less than 1.6 km not less than 8 km Military facilities and embassies, stadiums, places of assembly and locations/routes of rallies (external risk assessments) no requirements no requirements not less than 1.6 km not less than 8 km EMC active sources (transformer, transformer substation, track, transmitting stations) check check measurements recommended, constructional measures measurements recommended, constructional measures Contaminating emission of noxious substances (ship unloading stations, agricultural production, steel and galvanizing works) must be observed must be observed must be observed must be observed Seismic areas, earthquake zone according to DIN, constant ground vibration, collapse areas of buildings must be observed must be observed must be observed must be observed Third-party users in the building or on the premises (hosting companies) no restrictions possible if companies are non-hazardous possible if all tenants are IT or telecommunications companies possible if all tenants are IT or telecommunications companies

4 Building Construction Architecture / construction / DC & engineering Type of construction according to VdS / DIN (in accordance with applicable standards and guidelines) according to VdS / DIN (in accordance with applicable standards and guidelines) according to VdS / DIN (in accordance with applicable standards and guidelines) according to VdS / DIN (in accordance with applicable standards and guidelines) Walls encompassing the room F 30 - RC 1 F 90 - RC 1 F 90 - TC 2 F 90 - RC 2 Ducts F 30 at least: F 30; recommended: F 90 F 90 F 90 Floors and ceilings F 90 F 90 F 90 F 90 Floor and ceiling loads at least 5,000 N/m² at least 5,000 N/m² at least 10,000 N/m² at least 10,000 N/m² Suspended ceilings if sc exist for air conditioning, difficult to ignite B2 if sc exist for air conditioning, difficult to ignite B2 if sc exist for air conditioning, difficult to ignite B2 if sc exist for air conditioning, difficult to ignite B2 Roofs in accordance with provisions in accordance with provisions in accordance with provisions in accordance with provisions Clear ceiling height approx m approx m approx m to 3.50 m approx m to 3.50 m Clear raised floor height recommended: approx m recommended: approx m recommended: approx m recommended: approx m Raised floor understructure bonded pedestals, suspended U-type stringers bonded pedestals, suspended U-type stringers bonded pedestals, bolted U-type stringers bonded pedestals, bolted U-type stringers Raised floor tile design, incl. labeling and linking of tiles (smoke detection, extinguishing nozzles, water, equipotential bonding) difficult to ignite B1 difficult to ignite B1 difficult to ignite B1/A2 difficult to ignite B1/A2 Vapor barriers for walls and ceiling of server room no requirement no requirement no requirement recommended for data rooms Doors Fire resistance class at least: T30-RS; at least: T30-RS; recommended: T30-RD * recommended: T30-RD at least: T30-RS; recommended: T30-RD at least: T30-RS; recommended: T30-RD Door dimensioning at least 1 m wide and 2.13 m high at least 1.20 m wide and 2.25 m high (recommended height: 2.50 m) at least 1.20 m wide and 2.25 m high (recommended height: 2.50 m) at least 1.20 m wide and 2.25 m high (recommended height: 2.50 m) Single person security interlocks, turnstiles, portals or other systems ensuring that only one person can pass at a time no requirement no requirement yes yes No exterior windows in the server room area if ew exist, additional measures such as foil or auxiliary frames and grilles not permitted not permitted not permitted * T30: 30-minute fire resistance; RS: smoke protection; RD: smoke-proof

5 Building Construction (continued) Design provides protection against electromagnetic radiation no requirement no requirement yes yes Intrusion-resistant doors RC 1 RC 1 RC 2 RC 2 Entry lobby Physically separated from other areas of the data center no requirement yes yes yes Fire lobby separation from other areas of the data center F 30 F 30 / F 90 F 90 F 90 Multiple building entrances with security checks no requirement no requirement yes yes Single person security interlocks, turnstiles, portals or other systems ensuring that only one person can pass at a time no requirement no requirement yes yes Traffic and transport routes at least 1.00 m wide and 2.50 m high at least 1.00 m wide and 2.50 m high at least 1.20 m wide and 2.50 m high at least 1.20 m wide and 2.50 m high Elevators (if necessary) door width at least 1.00 m, cage depth 1.60 m, height at least 2.25 m, carrying capacity at least 1000 kg door width at least 1.00 m, cage depth 1.60 m, height at least 2.25 m, carrying capacity at least 1000 kg door width at least 1.00 m, cage depth 1.60 m, height at least 2.25 m, carrying capacity at least 1000 kg door width at least 1.00 m, cage depth 1.60 m, height at least 2.25 m, carrying capacity at least 1000 kg Parking Are visitor parking and staff parking areas separated from one another? no requirement no requirement yes, physically separated by fence or wall yes, physically separated by fence or wall Are visitor parking and staff parking areas separated from the receiving area? no requirement no requirement yes yes, physically separated by fence or wall Visitor parking in the proximity of data center exterior walls no requirement no requirement 10 m minimum distance 20 m minimum distance, separated by a barrier to prevent vehicles from approaching Administration, offices, security office, building services management system, staff rooms Physically separated from other areas of the data center Fire lobby separation from other areas of the data center F 30 F 30 / F 90 F 90 F 90 Security office Dedicated security office for security equipment and monitoring, incl. protection against break-in or small arms fire no requirement recommended if security office exists recommended recommended

6 Electrical Design Electrical design Total power balance (consider reserves and extensions) Supply by transformer substations 1 1, backup by generator 1, backup by generator 2 recommended, backup by generators System supply / topology spur spur spur, ring recommended spur, ring recommended Medium-voltage switchgear (MV) 1 1 1, recommended; 2, physically separated 2, physically separated Medium-voltage switchgear (MV) Transformers 1 1 1, recommended: 2 2 Stand-by diesel generators recommended 1 1, recommended: 2 2 Fuel stock 8 hours if available 24 hours 48 hours (2 tanks, incl. cross-connections; X-) 72 hours (2 tanks, incl. cross-connections; X-) Terminal for rental unit yes yes, if not available yes, for maintenance yes, for maintenance Low-voltage main distribution (LVMD) 1 1, recommended; 2 for Cat. 2+, maintenance bypass 1, recommended; 2 for Cat. 3+, maintenance bypass 2, maintenance bypass Separation of PS (secure power supply) in LVMD (sealing) or separate room no recommended yes yes System type TN-C/TN-S TN-C/TN-S recommended TN-S TN-S Reactive-current compensation / line filter recommended recommended recommended recommended UPS systems, incl. external bypass / redundancy n n+1, physically separated where necessary n+n, physically separated 2 (n+1), physically separated Battery backup time at least 10 min. (shutdown time) at least 10 min. (shutdown time) at least 10 min., physically separated at least 10 min., physically separated Battery monitoring / monitoring no no recommended yes Load bank for UPS no no provide connection provide connection Supply paths (protected against fire and sabotage) single, no requirement single, protection recommended 1 active and 1 passive, one supply path protected 2 active, at least 1 supply path protected Transfer switches (STS) for IT systems with only 1 power supply unit (dual-powered) no yes, recommended yes yes

7 Electrical Design (continued) Data center subdistributions (SD-UPS), separate supply from LVMD 1 1, recommended: Data center subdistributions (SD normal system) lighting flush-mounted sockets Measuring instruments (residual current measurement), no residual-current circuit breaker in the data center yes, recommended yes, recommended yes yes Rack supply by means of fixed connection or interlocked plug-and-socket connections (CEE) Grounding / equipotential bonding Lightning protection calculation according to VDE 0185 Part 3 Lightning and overvoltage protection lightning (coarse, medium protection) in distribution boards or terminal strips (fine protection) Load and power data measurement / logging / monitoring / supervision recommended recommended yes, measurement and logging yes, measurement and historical values Emergency lighting self-contained luminaires and additionally accumulator hand lamps self-contained luminaires and additionally accumulator hand lamps self-contained luminaires and additionally accumulator hand lamps self-contained luminaires and additionally accumulator hand lamps Escape lighting self-contained luminaires self-contained luminaires self-contained luminaires or central battery system self-contained luminaires or central battery system Selectivity calculation / short-circuit current calculation (network calculation and switch settings)

8 Air Conditioning Total power balance (update) Generator supply of air conditioning system yes, if generator exists yes yes yes Arrangement of IT equipment hot aisle/cold aisle recommended hot aisle/cold aisle hot aisle/cold aisle, recommended: hot aisle or cold aisle containment hot aisle/cold aisle, recommended: hot aisle or cold aisle containment Centralized / decentralized chillers (physically separated if necessary) n n+1 2n 2 (n+1) Recoolers / condensers / cooling towers / pumps n n+1 2n 2 (n+1) Recoolers / condensers / cooling towers (physical protection) Recoolers / condensers / cooling towers (design) outside temperature (higher than 32 C) Computer room air conditioners (CRAC) with operator display per line n n+1 2n 2 (n+1) Installation of computer room air conditioners (optimum airflow and maintenance) in the room in the room / mesh partition at least mesh partition / engineering block at least mesh partition / engineering block Automatic restart when power supply is resumed (chillers and CRACs) Redundant power supply of air conditioning (2 distribution boards and dual-powered) no check if this is necessary yes yes Lightning and overvoltage protection installed Redundant control of all plant components no check if this is necessary yes yes Manual operator control level if control system fails (chillers and CRACs) no recommended recommended recommended Automatic failure detection of a computer room air conditioner (CRAC) Top or bottom Venetian dampers for maintenance and in the event of a failure check if this is necessary check if this is necessary check if this is necessary check if this is necessary Connection to fault signaling system / BMS Condensate drain pan or water barrier under CRAC Chilled water piping system n n n 2n (ring system) Internal/external reserve terminals for mobile reserve units or extensions available no recommended recommended yes Strainer with bypass function yes yes recommended recommended

9 Air Conditioning (continued) Leak detection of piping system (at least pressure sensor) Chilled water pumps (phase-sequence test) n n+1 2n 2n System separation / heat exchanger (primary, secondary) no recommended recommended recommended Cooling water refill unit no recommended yes yes Hot water storage tanks / hydraulic separator system-dependent no check if this is necessary check if this is necessary check if this is necessary Chilled water system standby cooling (municipal water or well water, adiabatic cooling) no check if this is possible check if this is possible check if this is possible Connection of chilled water system pumps to UPS no check if this is necessary check if this is necessary check if this is necessary Lines carrying media in the DC area that are not allocated to data center equipment permitted but not recommended permitted but not recommended not permitted not permitted Drains in the server room for condensation water, humidification check if this is necessary yes yes yes Humidity control and monitoring (indication and historical values) % RH according to ASHRAE % RH according to ASHRAE % RH according to ASHRAE % RH according to ASHRAE Redundant room temperature and humidity monitoring (separate sensors) Outdoor air supply (filter classes G4 F7) no approx to 0.5 x air change / h approx to 0.5 x air change / h approx to 0.5 x air change / h Smoke & contamination detection of outdoor air supply recommended yes, at least smoke yes, test smoke, vicinity yes, test smoke, vicinity Positive pressure in the server room and allocated areas compared to outdoor and non-dc areas no requirement yes yes yes Integration of air conditioning into fire matrix (fire, extinction) System-wide leak detection of piping system / condensate (point detector or sensing cable) Ventilation, cooling of IT infrastructure (stand-by PS system, transformer, LVMD, UPS, batteries, extinguishing system, operating & other adjoining rooms) Consideration of alternative cooling systems (high density), where applicable in-row cooling, cool walls recommended recommended recommended recommended Can the waste heat of the data center be included in other energy balances? (heat pump, heating system etc.) recommended recommended, e.g. diesel preheating recommended, e.g. diesel preheating recommended, e.g. diesel preheating

10 Telecommunications / Cabling IT and telecommunications cabling / general Cabling design developed according to EN ? Requirements planning developed (EN n)? Cabling, racks, cabinets and cable trays comply with the applicable rules and regulations Redundant supplies (2-way) to the building, separated at least 20 m from one another, non-crossing no yes yes yes Redundant provider connection multiple provider connection, central offices, providers have right of way no no yes yes Infeed points protected against sabotage (covers not labeled, signaling contact, ) no no recommended yes Second telecom wiring closet no no yes yes Second wiring closet no no no optional Redundant backbone no no yes yes Redundant horizontal cabling no no no optional Routers and switches have redundant power supply units (alt. transfer switch) and processors no yes yes yes Multiple routers and switches for redundant operation no no yes yes Patch panels, outlets and cables have to be labeled according to ANSI/TIA/EIA-606-A. Cabinets and racks have to be labeled on front and rear Patch cords and jumpers labeled at both ends with the source / destination no yes yes yes Patch panel and patch cable documentation complies with ANSI/TIA/EIA-606-A. no no yes yes Are the lines tap-proof? Do the cable lengths meet the specification (ANSI, TIA 942)?

11 Telecommunications / Cabling (continued) Cable break monitoring of high-availability lines (backup lines)? Overvoltage protection for telecommunications supply cables (CU) Signal lines of energized lines installed separately or separated by separators on the cable trays? no no recommended yes

12 Safety and Security Safety and security / fire alarm and extinguishing systems /general Fire protection concept (incl. IT/infrastructure areas) Design conforming to VdS (fire alarm and extinguishing system), particularly reduced monitor ing areas and adjoining rooms (in accordance with applicable standards and guidelines) Fire matrix, incl. fire dampers Connection to alarm signaling system / BMS (building management system) Forwarding to a permanently manned location (gate keeper, lobby, security office, fire department) Fire detection Central fire alarm system complies with applicable guidelines Fire-alarm call boxes in room and raised floor (where applicable) and IT infrastructure areas Early fire detection systems (ASD aspirating smoke detector) recommended recommended recommended recommended Early fire detection systems (laser or LED) recommended recommended recommended recommended Firefighting Appropriate quantity and type of hand-held fire extinguishers (extinguishing agent) Mobile extinguishing units, e.g. 10, 20, 30 kg CO 2 trolleys no recommended recommended recommended Sprinkler system if necessary pre-controlled (if necessary) pre-controlled (if necessary) pre-controlled (if necessary) Preaction sprinkler system if necessary if necessary if necessary if necessary High-pressure water mist fire protection system option option option option Gas extinguishing system (chemical extinguishing agents: FM200, Novec 1230; gaseous extinguishing agents: CO 2, argon, Argonite, nitrogen, Inergen), incl. loss monitoring Oxygen reduction systems option option option option

13 Safety and Security (continued) Airtightness test (blower door test) Safe control of fire dampers Intrusion detection system / general Security concept zoning / division into areas (incl. DC area and IT infrastructure) The building is used as a data center only Design conforming to VdS (intrusion detection system and field devices) in accordance with applicable standards and guidelines Alarm matrix Connection to alarm signaling system / BMS (building management system) Forwarding to a permanently manned location (gate keeper, lobby, security office, police) Open/closed monitoring of doors (windows, channels, ducts) Monitoring of supply paths and protection against sabotage Monitoring of corridors and doors (passive trap system) Monitoring of rooms (comprehensive) Intrusion detectors at selected locations External access area surveillance (perimeter protection)

14 Safety and Security (continued) Access control system / flow of material / general Security concept zone model (incl. DC area and IT infrastructure) Assignment of access authorization is described in the company s security concept and monitored accordingly through management processes (27001) Design conforming to VdS (access control system and readers / cards) in accordance with applicable standards and guidelines Access authorization is issued in accordance with company policies no recommended yes yes Logging of access requests, incl. recording of unsuccessful attempts / access denied Alarm matrix Connection to alarm signaling system / BMS (building management system) Forwarding to a permanently manned location (gate keeper, lobby, security office) Connection of door opening systems (controllers, motor locks, door openers) to a fail-safe power supply Protection of central processing unit(s) / controllers in access controlled or monitored areas IT and facility staff have access to authorized areas only no recommended recommended yes Door blocking / pass-back / multiple use of access authorization excluded Turnstile no no yes yes Materials are unpacked outside the IT area and checked for foreign objects no recommended yes yes Bullet resistant walls, windows and doors Security counter in the lobby n/a n/a SK 3/NIJ level III (min) SK 3/NIJ level III (min) Security counter in the shipping and receiving area n/a n/a n/a SK 3/NIJ level III (min)

15 Safety and Security (continued) CCTV monitoring Building perimeter and parking no requirements no requirements yes yes Generators n/a n/a yes yes Access controlled doors no requirements no requirements yes yes Server room no requirements no requirements yes yes UPS, telecommunications and equipment rooms MEP rooms no requirements no requirements yes yes CCTV CCTV recording of all events on all cameras no requirements no requirements yes, digital yes, digital The outside areas are monitored by infrared cameras Recording rate (frames per second) n/a n/a 20 frames/sec (min) 20 frames/sec (min) CCTV recording is stored recommended recommended 30 days 30 days Safety equipment and security Water leak detection no yes yes yes Pressure drop in chillers no recommended yes yes Security staff on site no recommended recommended or located close by yes

16 Maintenance Preventative maintenance program Efficient preventative maintenance program (PM / Planned Maintenance), incl. type of maintenance, execution date and maintenance reports PM program includes maintenance activities recommended by manufacturer Detailed description of measures to be implemented when switching from redundancy <_> available and in use no recommended yes yes Complete description of measures for preventative maintenance (e.g., Method of Procedure manual Quality control process installed that confirms the implementation of a) all maintenance activities and b) the quality requirements of PM All PMs are connected to and controlled by a change management system Maintenance contracts for all components and their duration and service level monitoring according to management system (27001) Designated maintenance areas are available Cleaning and cleanliness Computer room floor / raised floor free from dirt and waste The data center is free from combustible materials, mailing boxes, personal belongings such as coffee mugs, microwaves,... Cleaners provide cleaning records to ensure a clean site

17 Maintenance (continued) Maintenance management system Efficient maintenance management system (paper or electronic format) to have a status overview of all maintenance activities (complete / in progress / scheduled) Maintenance list of all components installed (brand, model, date of manufacture, date of installation, characteristics in terms of operation, warranty information / terms and conditions, etc.) Records of tools and spare parts for preventative maintenance Power recording and maintenance trends for: Equipment, history of maintenance activities, calibration necessities, list of critical spare parts and threshold for ordering stock spare parts Manufacturer support List of qualified manufacturers for normal work and emergency measures SLAs describing work package, preventative maintenance program and response times for all critical manufacturers Description of manufacturer s technical support and support for authorized and qualified technicians reporting a fault Life cycle planning Effective process for planning, scheduling and identifying end-of-life elements of important infrastructure components

18 Maintenance (continued) Fault analysis program Compilation of lists of all failures, including date, time, infrastructure components and systems involved, computer system failures, identification of the underlying problem and lessons learned Development of a procedure to avoid underlying problems, evaluation of lessons learned and corrective actions derived from this evaluation Establishment of a trend analysis process recommended recommended recommended recommended Maintenance program Preventative maintenance program and planned maintenance; implementation rate greater than (>) 90 % yes yes n/a n/a Preventative maintenance; implementation rate: 100 % n/a n/a yes yes Efficient, scheduled maintenance program Does a service level agreement with a mobile generator supplier exist and are the response times adequate? yes n/a n/a n/a Continuous / other documentation All acceptance documents are available (fire protection analysis, commissioning documents, approved building application, attestation of conformity for VDI 6022/in accordance with applicable standards and guidelines) Regular generator load takeover tests, incl. reports Acceptance tests before commissioning the data center

19 Planning & Coordination Site policy Documented policy and procedures for the following points: - Performance of employees on site for overall onsite operation (configuration changes, operation under normal, emergency or abnormal conditions) - Site configuration: Configuring site for normal conditions standard operation: Changes in normal operation (e.g., switching chillers) - emergency procedure: Having control over the site under abnormal conditions or events - Change management: a) Control and approval of changes with regard to operational guidelines and b) identification of risks of planned changes Financial management OPEX and CAPEX planning to ensure compliance with TIER requirements OPEX and CAPEX planning to ensure compliance with TIER requirements, made at non-critical site and not in relation to other buildings or groups of buildings no recommended yes yes

20 Planning & Coordination (continued) Site documentation The following documents must be available (on site or accessible) - Working drawings - Operational and maintenance documentation - Records of soil samples, statics, electrical and mechanical design - Switches, electric circuits... - Documentation describing the system settings - Warranty documents and pre-negotiated maintenance contracts - Description of automatic operational sequences (e.g., CRAC standby -> live switchover) The above-listed documents and records are always available on site Operating documents centrally available as a library for on-site staff Master copies and changes are updated and available to operating staff and manufacturers, maintenance companies and planners Capacity management Data center space master plan exists and is permanently checked/supplemented Processes for planning further expansions for space, power, cooling for, e.g., 1/6/12/24/36 months in advance Resource management for floor space, power, cooling capacity and expansion (permanently monitored) no recommended yes yes no recommended yes yes

21 Employees & Training Employees Full-time employees (FTE) or half- or full-time employees of manufacturer who can identify critical states yes n/a n/a n/a Employees or manufacturer support for single-shift operation 5 days a week no yes n/a n/a Escalation and call-out procedure installed for specific employees or manufacturer support for described critical systems or equipment no recommended yes yes Employees on site 24 x 7, at least 1 qualified FTE n/a n/a yes n/a Employees on site 24 x 7, at least 2 qualified FTE for standard support per shift n/a n/a n/a yes Support of technical fields (electrical, control system, building management system, air conditioning) according to operational and maintenance requirements Qualifications Appropriate training of employees, required by law Documented on site training in data center processes and equipment Complete formal training of all employees in a) configuration, operation, hazards for the specific technical areas b) all site regulations, processes, procedures no recommended yes yes Tasks allocated to relevant employees for mainten ance, security, training and computer room engineering Shift personnel qualified for special shift tasks individually or as a shift team n/a n/a yes yes

DATACENTER COLOCATION. Flexible, Secure and Connected

DATACENTER COLOCATION. Flexible, Secure and Connected DATACENTER COLOCATION Flexible, Secure and Connected Flexible Solutions for Your Requirements Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free Choice 10 Good Reasons 12 Our

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.

More information

How To Write An Infrastructural Standard For Data Center Infrastructure

How To Write An Infrastructural Standard For Data Center Infrastructure Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

Technical specifications. Containerized data centre NTR CDC 40f+

Technical specifications. Containerized data centre NTR CDC 40f+ Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power

More information

N O W A V A I L A B L E

N O W A V A I L A B L E N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina S P E C I F I C A T I O N S Contact Doug Hollidge for more information

More information

Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS

Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS Upgrading the PRS datacentres: space requirement S. S. Mathur, GM-IT, CRIS PRS / UTS scenario: then and now Year 2000 PRS: 600 locations UTS: 0 locations Year 2008 PRS 1600 locations E-ticketing Passengers

More information

AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)

AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to

More information

DATACENTER Vienna 1. Scalable, Safe and Innovative

DATACENTER Vienna 1. Scalable, Safe and Innovative DATACENTER Vienna 1 Scalable, Safe and Innovative Designed, built and optimized for the security of your data Contents Your Goals 2 Compound and Buildings 4 Energy Efficiency 6 Security 10 Infrastructure

More information

HealthcareBookings.com Security Set Up

HealthcareBookings.com Security Set Up HealthcareBookings.com Security Set Up Introduction... 2 Overview of the process for using HealthcareBookings.com... 2 Professionals... 2 Patients... 3 Passwords... 4 Hosting Security... 4 Overview of

More information

engineering service Reliable Data Center. With TÜV Rheinland experts

engineering service Reliable Data Center. With TÜV Rheinland experts engineering service Reliable Data Center. With TÜV Rheinland experts It. energy A changed IT landscape brings new challenges. With the ever-growing digitization, the reliability of data centers and server

More information

How To Visit An Internet Data Center

How To Visit An Internet Data Center AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

DATACENTER BERLIN Definitely a Good Perspective

DATACENTER BERLIN Definitely a Good Perspective DATACENTER BERLIN Definitely a Good Perspective We Do not Take any Chances: For the Security of Your IT Systems. Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free Choice 14

More information

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service

vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service vcloud SERVICES vcloud SERVICE Virtual Tech offers competitive pricing on vcloud hosted services at our world class Tier 4 data centre facility fully equipped with redundant power, cooling, internet connectivity

More information

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

DATACENTER MUNICH 2. Munich s Number One Address for Your Data

DATACENTER MUNICH 2. Munich s Number One Address for Your Data DATACENTER MUNICH 2 Munich s Number One Address for Your Data We Use the Latest Technology for the Security of Your Systems Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free

More information

Georgia Tech Aerospace Server French building Server Room. Server Room Policy Handbook: Scope, Processes and Procedure

Georgia Tech Aerospace Server French building Server Room. Server Room Policy Handbook: Scope, Processes and Procedure Georgia Tech Aerospace Server French building Server Room Server Room Policy Handbook: Scope, Processes and Procedure Version History Version/Status Release Date Comments 1.1/Draft 1.2 1.3 1.4 1.5 1.6

More information

Onsite Support: 24/7/365 onsite team. Security: 24/7/365 onsite manned security and CCTV. Monitoring: 24/7/365 Environmental monitoring and management

Onsite Support: 24/7/365 onsite team. Security: 24/7/365 onsite manned security and CCTV. Monitoring: 24/7/365 Environmental monitoring and management Zen DC1 Our Services: Colocation Cloud Solutions Managed Hosting Dedicated Servers Zen DC1 - Key Facts Size: 10,000 sq ft Capacity: 150 rack capacity Ownership: 100% independently owned, operated and managed

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH

Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH Data Center Availability Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH Agenda Security Assessment Uptime Approach Risks and Threats Availability Principles

More information

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls

More information

DATACENTER MÜNCHEN 2. Munich s Number One Address for Your Data

DATACENTER MÜNCHEN 2. Munich s Number One Address for Your Data DATACENTER MÜNCHEN 2 Munich s Number One Address for Your Data We Use the Latest Technology for the Security of Your Systems Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

Data Center Overview Document

Data Center Overview Document Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.

More information

Zone B: comprises of NOC room, reception area, Help Desk area, Call Centre, Testing/Monitoring room. This zone requires approximately 1500 sq. feet.

Zone B: comprises of NOC room, reception area, Help Desk area, Call Centre, Testing/Monitoring room. This zone requires approximately 1500 sq. feet. Annexure 1 Best practices and Guidelines to Physical Security of the State Data Centre The Data Centre should ideally be built in a central location within the building complex. An approximate area of

More information

MARULENG LOCAL MUNICIPALITY

MARULENG LOCAL MUNICIPALITY MARULENG LOCAL MUNICIPALITY Data Centre Physical Access and Environmental Control Policy Draft: Data Centre Access Control and Environmental Policy Page 1 Version Control Version Date Author(s) Details

More information

Previder Datacenters it starts here

Previder Datacenters it starts here Previder Datacenters it starts here Previder Datacenters Introduction Previder has two sustainable, energy efficient and carrier-neutral datacenters in the Netherlands. Both datacenters have a number of

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

LEVEL 3 DATA CENTER ASSESSMENT

LEVEL 3 DATA CENTER ASSESSMENT Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments

More information

AT&T Internet Data Center Site Specification New York III (Secaucus, NJ)

AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) Site Biography Market Area: New York City, New Jersey, Upstate NY and Lower Connecticut Location: Secaucus, NJ 07094 Address: 15

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

Data Centre Services. JT Rue Des Pres Data Centre Facility Product Description

Data Centre Services. JT Rue Des Pres Data Centre Facility Product Description JT Rue Des Pres Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre

More information

NeuStar Ultra Services Physical Security Overview

NeuStar Ultra Services Physical Security Overview NeuStar Ultra Services Physical Security Overview Mission-critical network operations must have the highest standards of quality, security and reliability. NeuStar Ultra Services currently locates its

More information

Data Centre Services. JT First Tower Lane Data Centre Facility Product Description

Data Centre Services. JT First Tower Lane Data Centre Facility Product Description JT First Tower Lane Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room enviroment with protected incoming power supplies, state-of-the-art security

More information

ISO IEC 27002 2005 (17799 2005) INFORMATION SECURITY AUDIT TOOL

ISO IEC 27002 2005 (17799 2005) INFORMATION SECURITY AUDIT TOOL 9.1 USE SECURITY AREAS TO PROTECT FACILITIES 1 GOAL Do you use physical methods to prevent unauthorized access to your organization s information and premises? 2 GOAL Do you use physical methods to prevent

More information

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA

More information

Strategic Data Centre Site Profiles Data Centre Co-Location London North

Strategic Data Centre Site Profiles Data Centre Co-Location London North Strategic Data Centre Site Profiles Data Centre Co-Location London North Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 6 Contents 1. LONDON NORTH...3 1.1 LOCATION...3 1.2 TECHNICAL

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

Current as of 11/10/08 1 of 1

Current as of 11/10/08 1 of 1 BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that

More information

Content Index. 1. General... 3. 2. Location and Building... 4. 3. Telecommunication Feeds... 6. 4. Electric Power... 7. 5. Climate Control...

Content Index. 1. General... 3. 2. Location and Building... 4. 3. Telecommunication Feeds... 6. 4. Electric Power... 7. 5. Climate Control... Content Index 1. General... 3 2. Location and Building... 4 3. Telecommunication Feeds... 6 4. Electric Power... 7 5. Climate Control... 8 6. Safety and Security... 9 7. Internal Procedures... 11 General

More information

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G 100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the

More information

AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx)

AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) Site Biography Market Area: Dallas and Fort Worth Areas of Texas Location: Allen, Tx 75013 Address: 900 Ventura Drive CLLI, POP, NPA/NXX

More information

singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence

singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other

More information

fulfils all requirements for extended protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.

fulfils all requirements for extended protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company Infineon Technologies IT-Services GmbH Lakeside B05 2 9020 Klagenfurt, Österreich to confirm that its

More information

Our Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net

Our Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net Our Hosting Infrastructure An introduction to our Platform, Data Centres and Data Security www.in-tuition.net UK Infrastructure Infrastructure Overview Intuition Networks has provided managed Internet

More information

fufils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.

fufils all requirements for high protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company LVM Versicherung Kolde-Ring 21 48126 Münster, Germany to confirm that its security location Data Center

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

DATACENTER ZURICH. Well Positioned for Security

DATACENTER ZURICH. Well Positioned for Security DATACENTER ZURICH Well Positioned for Security We Design, Build and Operate Data Centres with All Our Energy and with Dedication. Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers

More information

Subject: County of Los Angeles Data Center Space Requirement

Subject: County of Los Angeles Data Center Space Requirement Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,

More information

DATACENTER CAMPUS FRANKFURT. Plan for Every Second

DATACENTER CAMPUS FRANKFURT. Plan for Every Second DATACENTER CAMPUS FRANKFURT Plan for Every Second We Give All Our Energy and Dedication to Create Safe Environments by Making Risks Manageable Contents Your Goals 2 Compound and Buildings 4 Security 6

More information

Data Center Designs and Hospital Operations

Data Center Designs and Hospital Operations Data Center Designs and Hospital Operations Designing for Data Center Availability and the Effect on Daily Operations Joe Harris, PE, RCDD Senior Engineer, AECOM Data Centers and Hospitals June 10, 2015

More information

REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL CONTROL POLICY

REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL CONTROL POLICY LI_M_POPO PROVINCIAL GOVERNMENT :;:ED.JBl-C ()F SO"';-H AFR;IC. ':.,. DEPARTMENT OF CO-OPERATIVE GOVERNANCE, HUMAN SETTLEMENTS & TRADITIONAL AFFAIRS REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL

More information

LDeX Group. Colocation Solutions for High Expectations

LDeX Group. Colocation Solutions for High Expectations LDeX Group Colocation Solutions for High Expectations LDeX1 Units 8 10 The Oxgate Centre, Oxgate Lane, London, NW2 7JA +44 (0)845 370 3510 sales@ldexgroup.co.uk www.ldexgroup.co.uk 5 M VA LDeX1 delivers

More information

fulfils all requirements for very high protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.

fulfils all requirements for very high protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company RWE IT GmbH Hyssenallee 22-30 45128 Essen, Germany to confirm that its security area Data Center Neurath

More information

DATA CENTRE DATA CENTRE MAY 2015

DATA CENTRE DATA CENTRE MAY 2015 DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive

Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive Co-Location Services Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive optimum performance 24x7. SERVICE

More information

Rules of Conduct and Safety

Rules of Conduct and Safety Rules of Conduct and Safety ETISALAT DATA CENTER RULES - V2.4 Contents Definitions... 2 Introduction... 3 Safety Instructions... 3 Upon entering the Data Center... 3 Privacy Notice / Camera Surveillance...

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in August 2002,

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

fulfils all requirements for medium protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.

fulfils all requirements for medium protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages. The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company Stadtwerke München Emmy-Noether-Straße 2 80287 München, Germany to confirm that its security area Main

More information

Server Monitoring & Management Services

Server Monitoring & Management Services Server Monitoring & Management Services Monitor and manage your applications and servers under enterprise-class monitoring solutions, and protect your business from planned and unplanned downtime. ITI

More information

How To Certify A Security Area Datacenter For A Trustworthy Site Infrastructure

How To Certify A Security Area Datacenter For A Trustworthy Site Infrastructure The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company E.ON IT GmbH Treskowstraße 5 30457 Hannover, Germany to confirm that its security area Datacenter T7

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

Data Centre Solutions energy efficient by design

Data Centre Solutions energy efficient by design Data Centre Solutions energy efficient by design Mobile & Modular Data Centre Solutions Agile, Scalable, High Performance Mobile and Modular DC solutions Flexible, scalable high performance mobile & modular

More information

National Aluminium Co. Ltd.

National Aluminium Co. Ltd. National Aluminium Co. Ltd. [NALCO] EXPRESSION OF INTEREST FOR DATA CENTRE CO-LOCATION SERVICES Address for Communication The Project Manager ERP P/1, NALCO BHAWAN NAYAPALLI, BHUBANESWAR 751061 E mail:

More information

ITB2 Datacenters Informationbrochure 2015 Page: 2

ITB2 Datacenters Informationbrochure 2015 Page: 2 ITB2 Datacenters Informationbrochure 2015 ITB2 Datacenters Informationbrochure 2015 Page: 2 ITB2 Datacenters Informationbrochure 2015 Pagina: 3 Index 1. Introduction... 4 2. About ITB2 Datacenters... 4

More information

DATACENTER FRANKFURT 3. Well Served with Fresh Air

DATACENTER FRANKFURT 3. Well Served with Fresh Air DATACENTER FRANKFURT 3 Well Served with Fresh Air New Technology for Chilled Rooms: Indirect Adiabatic External Air Cooling Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free

More information

EXAMPLE OF A DATA CENTRE BUILD

EXAMPLE OF A DATA CENTRE BUILD EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist

More information

Europe s greenest data center

Europe s greenest data center Europe s greenest data center datadock represents the perfect cooperation of humans, machines and nature. In more than three years of planning and construction and with a total budget of over 17 million

More information

Data Center Presentation

Data Center Presentation Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details

More information

Department of Administration DATA CENTER Two Phase Approach Located at the State Defense Building

Department of Administration DATA CENTER Two Phase Approach Located at the State Defense Building DATA CENTER Two Phase Approach Located at the State Defense Building July 17, 2015 Compiled by: Office of Facilities and Property Management 800 SW Jackson, Suite 600 Topeka, Kansas 66612-1216 i I. Programming

More information

Designing the Data Center

Designing the Data Center Designing the Data Center Asef Baddar, RCDD May -, 00 Talking points What are Data Centers? Why Data Centers? The components of the Data Center Approaching the Data Center design Breakdown of the components

More information

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work

More information

Strategic Data Centre Site Profiles. Data Centre Co-Location London East

Strategic Data Centre Site Profiles. Data Centre Co-Location London East Strategic Data Centre Site Profiles Data Centre Co-Location London East Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 5 Contents 1. LONDON EAST...3 1.1 LOCATION...3 1.2 TECHNICAL

More information

North Datacentre - Studley

North Datacentre - Studley North Datacentre - Studley Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. With 15 years of continual operational life, the Studley

More information

Network Router Monitoring & Management Services

Network Router Monitoring & Management Services Network Router Monitoring & Management Services Get different parameters of routers monitored and managed, and protect your business from planned and unplanned downtime. SERVICE DEFINITION: NETWORK ROUTER

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

Dedicated Hosting Services

Dedicated Hosting Services Dedicated Hosting Services Protect and manage your Servers/ Routers/ Switches/ storage devices/ security devices under a highly secure hosting space and get the finest performances out of them. SERVICE

More information

Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support.

Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support. Remote Support Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support. SERVICE DEFINITION: REMOTE SUPPORT SERVICES ITI s Remote Support Service

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

JAWAHARLAL NEHRU UNIVERSITY

JAWAHARLAL NEHRU UNIVERSITY School of Biotechnology JAWAHARLAL NEHRU UNIVERSITY New Delhi 110 067 Tender No. JNU/SBT/DBT-BUILDER/Data Centre/2015-16 Sealed Quotation for the establishment of a Data Centre for High-End Computational

More information

Data Centre Reliability and Redundancy. What do they mean and are you are getting what you need?

Data Centre Reliability and Redundancy. What do they mean and are you are getting what you need? Data Centre Reliability and Redundancy What do they mean and are you are getting what you need? What's the message? Why consider Reliability and Redundancy? How do you know what Reliability and/or Redundancy

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

Frankfurt Data Centre Overview

Frankfurt Data Centre Overview Technical Services Briefing Document Frankfurt Data Centre Overview Version 2.1 Contents Introduction... 3 TelecityGroup Data Centre in Frankfurt... 4 Data Centre Characteristics... 4 Technologies in Use

More information