1 Applied Math Modeling White Paper Using CFD for Data Center Design and Analysis By Liz Marshall and Paul Bemis, Applied Math Modeling Inc., Concord, NH January, 2011 Introduction Computational fluid dynamics (CFD) is the numerical simulation of fluid flow. It can be used to predict fluid velocities, temperatures, and many other variables of interest for a wide variety of application areas. Over the years it has been used to simulate the flow of air over an airplane wing or water past a ship s hull; perform comparative drag analyses of automotive body shapes; predict the time needed to mix two or more liquids; and test strategies for reducing coal plant emissions. It is routinely used to model the flow Figure 1: CFD can be used to illustrate the flow of air, as in this example of hot aisle containment in a data center; flow pathlines are colored by temperature inside buildings of all sizes and rooms with specialized functions. This white paper focuses on how CFD is used for one such class of rooms: data centers (Figure 1). It begins with an overview of CFD basics and then describes how data center components can be represented using numerical methods. The chapter concludes with examples and suggested reading material. 1

2 Computational Fluid Dynamics The goal of a CFD calculation is to predict the highly detailed flow field in some region of interest. The flow field is not just the motion of a fluid: a liquid or a gas or even a collection of small particles, such as sand. CFD can also predict the distribution of temperature and chemicals. It can include other phenomena such as turbulence, timedependence, chemical reaction, evaporation, melting, or freezing. Despite the range of applications, the same general method is used. Conservation equations are solved in small cells that fill the region. The region must therefore be divided into a large number of cells and the equations must be rewritten so that they can be solved in each one. In the next few sections, these two processes are described along with an overview of how the solution is performed and how the results can be viewed and interpreted. The Computational Domain and Mesh A CFD simulation begins with the creation of the problem geometry. The region to be modeled is often called the computational domain, and the geometry consists of the boundaries of that domain and all of the objects contained within. While computer-aided design (CAD) software focuses on the solid objects, CFD focuses on the space inside or in between objects, where the fluid is likely to flow. Many application-specific CFD packages are available nowadays that make geometry creation straightforward. For data center applications, the CFD software has objects available for CRACs, racks, PDUs, perforated floor tiles and other common components, which can be positioned and sized easily within a room. Once the room and contained geometry are created, the entire space needs to be broken up into a large number of small cells where the calculations will be performed and the resulting information stored. The lines and planes that separate these cells are often collectively referred to as the mesh or grid. The cells can be of almost any shape; six-sided hexahedra, five-sided pyramids or prisms, and four-sided tetrahedra are the most common. The task of creating such a mesh can be time-consuming for the CFD analyst, but many automated or semi-automated tools are available in software today. Data center CFD software packages are among those that offer this feature. A typical mesh in a data center is shown in Figure 2. This mesh is non-uniform, which means that the size of the cells varies from region to region, depending on the detail required by the local geometry. Figure 2: The mesh on a planar slice through a data center 2

3 While the mesh in Figure 2 appears Cartesian, with lines at right angles, automatic mesh generators often distort the elements to fit around non-rectangular objects. One example is shown in Figure 3, where the mesh is distorted near the circular object and actually changes from Cartesian to a different style (called O-type) around some of the objects. Automatic meshing algorithms have instructions to deviate from a standard Cartesian format based on the needs imposed by the geometry. Often, a switch to another grid style will result in a reduced cell count in the domain, making the calculation run more quickly. Figure 3 : A Cartesian mesh is used for most of the region and around the two elements in the middle, while O-type grids are used for the rectangular and circular elements on the sides Conservation Equations If a small volume of fluid in motion is considered, two changes to its shape will usually take place. First, the fluid element will translate or rotate in space, and second, it will become distorted, either by a simple stretching along one or more axes, or by arbitrary twisting. The process of translation is referred to as convection, while the process of distortion is related to the presence of gradients in the velocity field and a process called diffusion. In the simplest case, these processes govern the evolution of the fluid from one state to another. Other factors can also contribute to changes in the fluid. For example, heat can cause a gas to expand and rise. Conservation equations include these effects and provide a generalized description of fluid motion. These equations track changes in the fluid that result from convection, diffusion, and sources of the conserved quantity. Conservation equations are coupled, meaning that changes in one variable (say, the temperature) can give rise to changes in other variables (say, the velocity). In most CFD products targeted toward a particular application, such as data center airflow, control of the equations during the solution process is shielded from the software user. Thus while it is important to have an appreciation of the equations behind the scenes, it is usually not necessary to understand the various techniques and controls for solving them. Continuity The equation of continuity is a statement of mass conservation. To understand its origin, consider the flow of a fluid of density through the six faces of a rectangular block, as shown in Figure 4. The block has sides of length x, y, and z and velocity compo- 3

4 Figure 4: A computational cell of volume x y z and velocity components u, v, and w in the x, y, and z directions, respectively nents u, v, and w in each of the three coordinate directions. To ensure conservation of mass, the sum of the mass flowing through all six faces must be zero. u out uin y z vout vin x z w w x y 0 out in Dividing through by ( x y z), the equation can be written as: u v w 0 x y z (1) (2) Momentum Similar logic can be used to construct equations for the conservation of momentum in each of the three coordinate directions. Momentum conservation is more complicated than mass conservation, however. Momentum sources such as gravity and pressure gradients play a role. In addition, a term representing the diffusion of momentum is included. This effect is attributed to gradients in the velocity field. Consider, for example, how a jet of water spreads (momentum diffusion) after being injected into a pool where the water is at rest on either side of the jet. Taking these effects into account, the momentum conservation equation in the x-direction for constantdensity fluids takes the form: u u u u u v w t x y z p u u u x i x y z g F x x (4) or, in differential form for the more generalized case where the density changes in time (t) and space: ( u) ( v) ( w) 0 t x y z (3) Here is the fluid viscosity, g is the acceleration due to gravity, and F represents any additional forces that might be present. The term multiplied by is the diffusion term, described briefly above as one that arises from gradients in the flow field. The three momentum equations (for u, v, and w components of velocity) along with the continuity equation are collectively called the Navier -Stokes equations. The four equations are used to solve for the four unknown variables: 4

5 three velocity components and pressure, even though the pressure appears only in the momentum equation. Numerical solution methods are used to link the equations through the density. Turbulence and Energy In most applications, more than just the Navier-Stokes equations are needed to describe the fluid behavior. If the Reynolds number is high enough, turbulence plays a role. The primary effect of turbulence is to increase diffusion. In the momentum equations, the viscosity effectively increases in the presence of turbulence. Thus water tends to act more like honey. Various approaches to include turbulence in the momentum equations are available. The simplest approach is to add a correction to the viscosity based on local flow and geometric parameters. More involved approaches require the solution of turbulence transport equations. Timedependent calculations can also be done to capture the random fluctuations that result from turbulent behavior. Many enclosed room applications, such as data centers, use the simpler approaches to include the effects of turbulence. In addition to turbulence, temperature can play a role in the flow field if the fluid density varies with temperature (as is the case if the ideal gas law is used). A conservation equation for thermal energy (analogous to that for mass and momentum) must also be solved. If the flow is turbulent, the transport of thermal energy is impacted through the conductivity of the fluid. Turbulence acts to increase the fluid s ability to conduct heat, or in other words, thermal transport through the fluid is more diffusive. Solving the Equations If each cell in the domain has a point at its center, the task of a CFD solver is to obtain a solution for all of the relevant conservation equations at every such point. If the domain is characterized by 100,000 cells and there are five conservation equations being solved, that means that 500,000 solutions must be obtained! These numbers are actually modest by today s standards, where models with tens of millions of cells are common and the physics requires at least seven separate equations to be solved. There are a number of numerical methods in common use by CFD solvers. In short, the differential equations are converted to algebraic equations. To compute how well those equations are balanced in each cell, the values of all variables at the cell faces must be computed. The manner in which those face values are computed differs for different solution approaches. The numerical method, the density of cells, the cell topology, and the nature of the flow field combine to impact the accuracy of the resulting solution. Residuals The set of coupled equations described above cannot be solved exactly. Instead, an iterative solution technique is applied. Roughly speaking, a guess is made for each variable at each point in the domain and the error in each conservation equation is tabulated. That is, the code takes stock of how closely the left side of each equation matches the right side. The cumulative error for each 5

6 equation is called the residual. The goal of the solver is to force the residuals to decrease with each step in the iterative solution process (Figure 5). Once the residuals have fallen below some preset value, the solution is considered converged. Only results from converged solutions are meaningful. Figure 5: Normalized residuals are shown to decrease during the iterative solution procedure continuity Displaying the Results Once a solution is converged, the results can be examined in a number of ways. Consider, however, the fact that there may be thousands or millions of points of data throughout the domain. How can one make sense of it all? One of the simplest ways to examine the results is to do so one plane at a time. Once created, a plane can be used to illustrate contours of a variable or velocity vectors. A plane can be created at some x, y, or z location or at the surface of an object, such as the inlet side of a rack row. An iso-surface, by momentum contrast, is a surface, usually not planar, where one variable has a constant value. For example, an iso-surface of constant temperature can be created and then contours of another variable, such as pressure, can be drawn on that surface. This type of display can convey more complex information than contours of a variable temperature plotted on a flat plane. Pathlines are another popular choice for examining results. These trace the paths of imaginary fluid elements that are released from one surface (say, where air enters a room). Pathlines can be colored by other problem variables, such as temperature, and they can usually be animated. In Figure 6, a raised-floor data center is shown that contains two rows of high density racks in the lower left. The racks are shaded by temperature contours and pathlines, also shaded by temperature, are released from the exhausts of these racks. The results show that one side of the high density racks runs hotter than the other side. As a result, the air returning to one of the CRACs is hotter than that returning to the other, a situation that places an uneven burden on the cooling system. An analysis such as this can illustrate imbalance in a data center that can result from equipment positioning or the presence of underfloor obstructions. 6

7 Overview of the Modeling Process One of the most important uses of CFD is as a planning tool. In this mode, an existing design is modeled and if the predictions are in good agreement with measurements, the assumptions are assumed reasonable and the model is altered to reflect one or more prospective changes. In the automotive industry, for example, such studies are done to test body shapes for aerodynamic characteristics before any metal is bent. The method is ideally suited for data centers where ongoing changes to equipment are routine. Using CFD, a number of scenarios can be studied before any equipment is moved, changed, or added. The success of this approach depends on the accuracy of the CFD model. To test for accuracy, it is a good idea to build a model and compare it against measurements (where Figure 6: A CFD model of a raised-floor data center showing temperatures on the surfaces of the rack rows and pathlines of return air, shaded by temperature available) first. Simple models are a good starting point. In a data center, a simplified model may use average heat loads in the racks, neglect small piping in the supply plenum, and make use of a coarse mesh, for example. A comparison of the simple model results with measurements will usually point to discrepancies, and these can be remedied by modifications to the model on the next pass. A refined model will therefore include more geometric detail and make use of a finer mesh. The choice of what detail to add can best be made by doing the first comparison with a simple model. For example, suppose the simple model neglects all of the small pipes in the supply plenum and treats all of the racks with average heat loads. If the flow distribution through the floor tiles is in good agreement with measurements but certain hot spots in the room are missed, 7

8 tain good agreement with data. In some cases there may not be good agreement with data after multiple refinements, and the root cause(s) should be investigated. Poor agreement could be the result of inaccurate assumptions about the heat loads and flow rates, especially if the fans in the equipment are variable speed fans and the model does not take that into account. Measurements can also be at fault, so analysts should always be aware of the error recorded. Figure 7: A flow chart showing the modeling process, starting with a simple model and refining it as needed before using it for analyzing prospective scenarios chances are that neglecting the small pipes was an acceptable approximation but neglecting the server-level detail in the racks was not. Once a refined model is in good agreement with data, that model can be used as the base case for modifications to the room. A flow chart illustrating this process is presented in Figure 7. Note that more than one refinement to the model may be necessary to ob- Techniques for Modeling Data Center Equipment CFD is used to simulate many different types of applications, and for each, the components that are common to that application are usually treated in a unique way. For example, a light source might be modeled as a volumetric heat source in the geometric shape of the light housing or bulb. A fan might be modeled as a planar area through which a certain flow of air is specified. In data centers, similar approaches are applied to model the components that are familiar to facilities engineers: CRACs, racks of equipment such as servers and switches, UPSs and PDUs, for example. In this section, methods for representing data center equipment are reviewed. 8

9 CRACs Computer room air conditioners (CRACs) or air handlers (CRAHs) are large rectangular objects that draw in warm exhaust air from the heat generating equipment in the room, cool and condition it, and then return it to the room for reuse. Under normal operation, they have a fixed flow rate and are capable of extracting a certain amount of heat from the air. A CFD model of a CRAC usually consists of a rectangular block with one or two fans used to move the air (Figure 8). In one scenario the volume inside the CRAC is not meshed so is not part of the solution domain. A return fan is used to draw ambient air out of the room while a second supply fan operating at the same flow rate is used to supply the cooled air back to the room. Some models of CRAC employ two or three supply fans and a single return fan. In another scenario, the volume inside the CRAC is meshed so that the inside air flow can be simulated. A heat sink is associated with the fluid inside the CRAC and a single fan is used at the supply side, modeled using a fan performance curve. the cold supply air in the room. For nonraised floor data centers, topflow or upflow CRACs are used to supply cold air from the top of the unit, with the return air passing through grilles on one side of the unit near the floor. Upflow CRACs are sometimes used along with downflow CRACs in raised floor data centers. Frontflow or in-row coolers are typically positioned between racks in a data center. They draw warm air from the rack exhausts, often the hot aisle in a hotaisle/cold-aisle arrangement, and produce cooled air out the opposite side, adjacent to the rack intakes. In-row CRACs may be used with or without other types of CRACs in the data center. Overhead cooling, often referred to as supplemental cooling, is available in overhead ceiling-mounted or rackmounted units. As for in-row coolers, these units act locally, circulating and cooling the air from nearby racks of equipment. Despite the many types of CRACs, they can all be modeled using a hollow block and pair of fans with matched flow rates. Fans Downflow, Upflow, In-Row, and Overhead The position of the return and supply fans depends upon the nature of the room and type of cooling application. Raised-floor data centers usually use downflow CRACs, with the supply fans directing the cooled air into the supply plenum beneath the floor and the return fans on the top of the unit. The cooled air enters the room through perforated tiles in the floor. If a ceiling plenum is used for the return air, these CRACs usually extend up to the ceiling plenum so that none of the warm return air has a chance to mix with Figure 8: A CRAC consists of a hollow block, a return fan, and one or more supply fans 9

10 Plug Fans While a great number of CRACs discharge cooled air in a direction normal to the CRAC boundary (straight down for downflow CRACs, for example), plug fans are gaining in popularity. For raised-floor data centers, plug fans extend below the lower surface of the CRAC into the supply plenum where they discharge air radially. Such fans can be modeled using a cylindrical fan in CFD. That is, the fan surface is not a plane but the wall of a cylinder. The volume inside the cylindrical fan is not meshed and is not part of the calculation domain. Cooling Methods While it is a simple matter to specify the temperature of CRAC supply air, most CRACs operate in a more sophisticated manner. In practice, the heat exchanger may cycle on and off so that a certain thermostat temperature is maintained at the CRAC return. In CFD, this can be accomplished using an iterative calculation of the following equation: Q mc T T ) (5) P ( R S Where Q is the amount of heat removed from the air (in SI units of W), m is the mass flow rate of air through the unit (kg/s), c P is the specific heat of air (J/kg-K), and T R and T S are the return and supply temperatures (in K), respectively. An iterative CFD calculation periodically adjusts the supply temperature (T S ) until the return air temperature matches the thermostat temperature. For many CRACs, the manufacturer supplies performance data for the cooling capacity (Q) as a function of return temperature. The relationship in Equation (5) is used, but the value for Q changes for different return temperature ranges. Racks Whereas CRACs extract heat from the air, racks and cabinets full of equipment add heat to the air that passes through them (Figure 9). Servers are rated by their heat load. Assuming a certain temperature rise across a server with a given power rating, Equation (5) can be used to compute the flow rate required to maintain that temperature difference. For example, to maintain a 20 F temperature rise across a server, about 150 CFM of cooling air is needed for every kilowatt of power. Racks can be modeled using their total heat load or by modeling the individual components with blanks and/or gaps in between. Whether a total heat load or equipment-level detail is used, the volume inside a rack need not be modeled. Instead, a matched set of flow boundary conditions can be used that ensures that the same flow rate enters and leaves the rack (or equipment) and that between those matched boundaries a certain temperature rise will occur. The temperature rise can be specified directly or can be the result of a specified heat load. Note that the volume inside a rack can be meshed and modeled, if desired, as in the case of the single-fan CRAC. This choice would be appropriate for analysts looking to model the temperature distribution inside individual servers for a given set of external conditions, for example. Racks can be modeled with air flow from front to rear, front to top, bottom to top, or 10

11 side to side. Flow entering the front can also be split to pass out the rear and top of the unit. Flow exiting from the top of a rack is an acceptable strategy if the rack is modeled with an average heat load. For a rack modeled with individual servers, it is not good modeling practice, because it is difficult to estimate how the air from each of the individual servers contributes to the top exhaust and the cooling of the other equipment. However, if a channel of exhaust air from the back of a rack of equipment is included in the model, the front-to-top flow strategy can be represented. In raised-floor data centers, underfloor cable trays that feed power to the racks do so through cutouts in the floor, which are usually under the racks and characterized by some percent open area. Openings in the floor allow supply air to mix with the air entering through the rack inlets. In CFD simulations, if cable cutouts are important, it is best to model the rack using an average heat load. Otherwise, the air drawn up from the plenum will mix with the cold air entering the server closest to the floor only. PDUs and UPSs In addition to racks, PDUs and UPSs are heat -generating components that require cooling. In raised-floor data centers, the cooling air is drawn through the floor into these units (Figure 9). Alternatively, cold air is drawn into the unit from side grilles. The heated exhaust air exits through the top of the unit. These components can be modeled like racks, using a matched set of openings with the same flow rate applied to both boundaries with heat addition between. They can also be meshed and given a volumetric heat load in the interior. For this modeling method, openings at the bottom and top will allow flow to be drawn up and through the device as a result of natural convection. Figure 9: Racks (right) and PDUs (left) consist of hollow blocks with openings (red or pink) for air flow and a heat gain Perforated Tiles and Ceiling Grilles Perforated tiles (Figure 10) allow the cold air in the supply plenum to enter a raised-floor data center where needed, usually in front of the rack rows. These tiles are characterized by some percent open area which causes a drop in pressure. They also serve to straighten the flow as it passes through. To accomplish these modeling goals, tiles are typically modeled using a thin porous region. The porous region (a volume) is assigned loss coefficients for 11

12 of air can be uniform across the diffuser or have some prescribed profile, such as high in the center and low at the edges. Figure 10: Perforated tiles (purple) are threedimensional objects that can straighten the flow as it passes through the three component directions. By making the loss coefficient much smaller in the direction normal to the floor, flow from the supply plenum will tend to align with that direction as it passes through the region. Cable cutouts on the floor of a data center not underneath racks - are usually modeled in the same manner. Ceiling grilles are partially open tiles in the ceiling. They cause a pressure drop for the flow as it enters the ceiling plenum, but they do not necessarily straighten the flow. Thus they can be modeled by a zero-thickness face or area that has a loss coefficient that gives rise to the appropriate pressure drop. Ducts and Diffusers In non-raised floor data centers, and in some raised-floor data centers, ductwork is used to transport cold (or warm) air as needed. The air is released to the room through diffusers, which can be set to direct the air at an angle or straight down into the room. The velocity To model a duct using CFD, the volume inside the duct can, but need not be meshed and included in the calculation. If the duct volume is not included, assumptions can be made to compute the properties of the air exiting from the diffusers. First, the air from the participating CRACs can be assumed to be well mixed, so the temperature at the diffusers can be computed using a weighted average of that produced by the CRACs. Second, the total mass flow produced by the CRACs can be divided among the diffusers and scaled to match the area of each. An assumption of equal flow rates is good if the diffusers are of similar size and not positioned in the middle of recirculation zones inside the ducts. Diffusers immediately following right-angle bends in the ductwork might not satisfy this requirement as well as those in the middle or at the end of a long section of ductwork. By including the duct volume in the calculation, the temperature and flow rate distributions for all participating diffusers in a duct system will be computed as a result of the flow inside the ducts. What to Include in a Data Center Model For the purpose of the CFD model, a data center is a closed environment with very little leakage of air or heat into or out of the room. This means that all heat produced by equipment in the room must be removed by the cooling units. All of the flow demands of the equipment should (but need not) be met by the cooling units as well. Thus when choosing what items to include in the model, 12

13 the most important are the major heat generating and removing ones, and any objects that contribute to the air circulation: all CRACs, CRAHs, racks of equipment, power generating stations, floor tiles, ceiling grilles, ducts and diffusers. The next level of importance consists of objects that impact either the flow or mixing of air in the room. This group includes baffles that are used for cold or hot aisle containment, turning vanes or other baffles in the plenum used to direct the supply air, plenum blockages and inert (non heat- or flowgenerating) objects in the room. While baffles can be set up to have some percent open area, impermeable baffles should be used with care. If baffles are used to section off an office or closet that does not contribute to the air flow in the room, the CFD solver may have difficulty, since the solution domain should be comprised of only a single connected volume of air. Side rooms that are not participating in the overall flow in the data center should be blocked off using solid objects such as blocks or slab-to-slab columns. Overhead and underfloor cable trays can impact the flow of air but may be deemed unimportant by the analyst, depending upon their size and position. Of less importance are small objects, especially in large data centers. Small pipes in the plenum (less than 3 in diameter, for example) fall into this category. Tables and chairs, filing cabinets and gas cylinders may be deemed too small or too few to make a difference in the flow field. Small heat generating objects, such as overhead lights or laptop-sized control stations may be contributors to the heat load in the room, but their role may be small compared to other equipment. If people are present most of the time in the data center (seated at a desk), their contribution to the heat may also be included. Finally, windows with minimal shading may also play an important role. Examples Two cases are presented in this section to demonstrate how CFD can be used to assess a data center. The first case is a raised-floor data center and the second has a non-raised floor and makes use of ducts and diffusers to distribute the supply air. Raised Floor Data Center The 1800 sq. ft. raised-floor data center shown in Figure 11 has an assortment of racks (light gray in the middle of the room), eight CRACs (dark gray along the walls), five PDUs (dark gray but smaller than the CRACs), and a ceiling plenum return. The downflow CRACs are each modeled with a cooling capacity and flow rate unique to the Figure 11: An isometric view of a raised-floor data with a ceiling return 13

14 unit, and each is set with a thermostat temperature of 75 F. Some of the racks are modeled using an average heat load while others cannot be approximated in this manner so are represented as a collection of servers, blanks and gaps. Each component in the racks is characterized by a heat load, an anticipated temperature rise, and a flow rate, controlled by a fan. The PDUs are assumed to draw air from the plenum and exhaust it out the top. Air is drawn up into the room through perforated floor tiles, all of which have a 25% open area. A summary of the heat loads and cooling capacity in the room suggests that there is 6% excess airflow and 3% excess cooling delivered by the CRACs. Despite the fact that the cooling capacity cuts very close to the heat load, the detailed CFD results indicate that all racks pass the recommended ASHRAE guidelines for inlet temperature falling below 80.6 F (Figure 12). There are a few reasons for this success. First, all perforated tiles are positioned directly in front of rack inlets. Second, there are no underfloor obstructions to divert the flow away from where it is needed. Third, the tiles offer uniform resistance to the flow because they have the same percent open area. The results support this finding: the average flow rate through the tiles is 681 CFM, with a maximum deviation of 14% with most tiles falling well within 8%. While the CRACs are not all the same, all are able to meet their target thermostat temperature to within a few degrees. Figure 12: Contours of temperature on rack and server inlets for the raised-floor data center The room does have some design flaws, however. First, the total cooling capacity of the CRACs is too close to the total heat load in the room. Thus if one of the CRACs were to fail, the others would have difficulty maintaining a 75 F thermostat temperature for the return air. This problem would need to be remedied by replacing one of the CRACs with a different unit. CFD could be used to determine the best choice of CRAC to replace. Second, the absence of underfloor obstructions gives rise to a large recirculation of air in the plenum, as is shown in Figure 13. Often, recirculation patterns such as this cause negative pressures in the eye and result in the flow of air from the room into the plenum. Had the power demands on the racks in the middle of the room been greater, enough supply air might not have been available. Baffles can be used to redirect supply air in a plenum so that recirculation patterns, especially large ones, don t develop and adversely impact the distribution of air through the perforated tiles. 14

15 Figure 13: Pathlines in the supply plenum, shaded by speed; the darker lines represent the more slowly moving supply air, most of which is shown after it enters the room Non-Raised Floor Data Center A non-raised floor data center with four CRACs in a middle aisle is shown in Figure 14. The data center is 800 sq. ft. with a heat density of about 81 W/sq. ft. The rack heat loads vary from 500 W to 4 kw. The CRAC returns are on alternating sides of the units; two face the right side of the room and two face the left side. Supply air mixes in a main duct above the CRACs and is dispensed through diffusers to cold aisles between the rack rows. A summary of the equipment in the room indicates that the CRACs provide 26% excess air and 27% excess cooling than the racks demand. While the room appears to have adequate cooling, the CFD results paint a very different picture. While all of the racks pass the allowable ASHRAE thermal guidelines (59 F to 90 F), none passes the recommended guidelines (64.4 F to 80.6 F). Despite the fact that all of the diffusers introduce cooling air at 60 F, the average maximum temperature delivered to the rack inlets is over 85 F. The reason this design fails is because the exhaust air from the racks circulates over and around the rows and mixes with the supply air on the opposite side. That is, even though there are cold aisles below the diffusers, the aisles are short and wide, allowing the rack exhaust air to infiltrate the cold zone and degrade the cooling air. Furthermore, the CRAC returns are visible to nearby supply ducts, a design that encourages the cooling air to short-circuit back to the CRAC returns before being fully Figure 14: A non-raised floor data center with a center aisle of top-flow CRACs and ducts and diffusers to deliver the supply air to the rack rows 15

16 utilized by the racks. In Figure 15, pathlines released from the rack outlets show how the exhaust air travels over the tops and around the sides of the rack rows so that it can be drawn in by the intake fans on the opposite side. The mixing of exhaust air with the cooler supply air at the inlets raises the temperature of the rack cooling air, especially near the tops and sides of the rack rows. It is interesting to note that a CRAC failure analysis done on this room shows that the performance of the CRACs is the same or better when each one of the CRACs is turned off. This unexpected result is due to the fact that a disabled CRAC will not short-circuit the supply air from the nearest diffuser directly to the CRAC return. This allows more cold air to be available for the pair of rack rows nearest the diffuser(s). Figure 15: Return pathlines, shaded by temperature, show some of the warmed exhaust air being entrained by the rack inlets, effectively raising the temperature of the cooling air Data Center Modeling Best Practices In recent years, several articles have been written on Best Practices for CFD modeling. These recommendations are typically targeted toward CFD analysts who have full control over the mesh generation and solver options. Even so, users of applicationspecific software should also be mindful of certain practices that ensure success. A short summary follows. Avoid putting too much detail into a model on the first pass. Get a general sense of the flow in the room before complicating the model with too many objects or details. Remember that a CFD model is different from a CAD model, where more detail may be better. Avoid small gaps. If a CRAC is 2 from a wall, there is probably no need to model the air between the CRAC and wall. Move the CRAC so that it is flush against the wall in such cases. Start with a coarse mesh solution and progress to a fine mesh only after confirming that the results make sense. Avoid separated regions of air. If adjacent rooms do not contribute to the overall flow in the data center, block them out of the model using a solid object. Understand how to use the software and its limits. Go through the 16

17 recommended training before starting to use the product. By adhering to simple guidelines such as these, most common modeling problems can be avoided. While early CFD software products were most often used by specially trained CFD analysts, today s applicationspecific products can be used successfully by engineers, designers, and technicians with a wide range of backgrounds. When choosing a product, a prospective user should consider ease of use, capabilities to suit a given set of needs, and availability of technical support. For example, if rack-level detail will be an important component of a planned analysis, a product should be chosen that includes this feature. Conclusions and Future Trends With data center managers and designers looking for innovative ways to cut energy costs, CFD is quickly becoming an essential tool of the trade. The flow field in a room can expose problem areas that don t show up in simple heat and flow balance calculations. In addition, trial layout modifications can be quickly evaluated using CFD prior to moving or replacing equipment. CFD is also useful for illustrating the division of labor among the cooling units in a data center and for illustrating the room conditions should one or more of them fail. centers as the loads vary. Dynamic CFD simulations will be able to identify the cooling distribution among CRACs and air handling units as server loads rise and fall with varying activity. In this manner, CFD will contribute to the control system that governs the overall facility cooling, activating certain units while deactivating or simply ramping down others. The potential feedback from such a system will not be instantaneous, but will be sufficient for the timescales typical of these fluctuations. Suggested Reading Two books provide excellent, readable summaries of CFD methodologies. Numerical Heat Transfer and Fluid Flow by Suhas V. Patankar (Hemisphere Publishing Corporation, 1980) is the early standard that has helped guide the growth of the field. An Introduction to Computational Fluid Dynamics, The Finite Volume Method, by H. K. Versteeg and W. Malalasekera (Prentice Hall, 1995, 2007) contains more recent examples and techniques that have been developed since Patankar s book was published. While Patankar focuses on Cartesian (or cylindrical) meshes in his examples, Versteeg and Malalasekera describe other mesh topologies as well. In addition, they provide discussions of some sophisticated physical models such as combustion and radiation. In the future, as computing speeds increase and hardware costs drop, CFD will become more integrated in data center monitoring systems. Rather than just be used for static assessments of data centers, CFD will be used in real time for dynamic models of data 17

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

Reducing the Annual Cost of a Telecommunications Data Center

Reducing the Annual Cost of a Telecommunications Data Center Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

Using CFD for optimal thermal management and cooling design in data centers

Using CFD for optimal thermal management and cooling design in data centers www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics Lecture 6 - Boundary Conditions Applied Computational Fluid Dynamics Instructor: André Bakker http://www.bakker.org André Bakker (2002-2006) Fluent Inc. (2002) 1 Outline Overview. Inlet and outlet boundaries.

More information

ME6130 An introduction to CFD 1-1

ME6130 An introduction to CFD 1-1 ME6130 An introduction to CFD 1-1 What is CFD? Computational fluid dynamics (CFD) is the science of predicting fluid flow, heat and mass transfer, chemical reactions, and related phenomena by solving numerically

More information

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology Dimitrios Sofialidis Technical Manager, SimTec Ltd. Mechanical Engineer, PhD PRACE Autumn School 2013 - Industry

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

OPTIMISE TANK DESIGN USING CFD. Lisa Brown. Parsons Brinckerhoff

OPTIMISE TANK DESIGN USING CFD. Lisa Brown. Parsons Brinckerhoff OPTIMISE TANK DESIGN USING CFD Paper Presented by: Lisa Brown Authors: Lisa Brown, General Manager, Franz Jacobsen, Senior Water Engineer, Parsons Brinckerhoff 72 nd Annual Water Industry Engineers and

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

Application of CFD modelling to the Design of Modern Data Centres

Application of CFD modelling to the Design of Modern Data Centres Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center Sang-Woo Ham 1, Hye-Won Dong 1, Jae-Weon Jeong 1,* 1 Division of Architectural Engineering,

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS

IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Proceedings of IPACK5 ASME InterPACK '5 July 17-, San Francisco, California, USA IPACK5-7373 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Amir Radmehr Innovative Research, Inc. Plymouth, MN, USA

More information

Customer Training Material. Lecture 2. Introduction to. Methodology ANSYS FLUENT. ANSYS, Inc. Proprietary 2010 ANSYS, Inc. All rights reserved.

Customer Training Material. Lecture 2. Introduction to. Methodology ANSYS FLUENT. ANSYS, Inc. Proprietary 2010 ANSYS, Inc. All rights reserved. Lecture 2 Introduction to CFD Methodology Introduction to ANSYS FLUENT L2-1 What is CFD? Computational Fluid Dynamics (CFD) is the science of predicting fluid flow, heat and mass transfer, chemical reactions,

More information

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS Paper Presented at ITHERM 2004 Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems June 1-4, Las Vegas, NV RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)

More information

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers This article appeared in the International Journal of Heating, Ventilation, Air-Conditioning, and Refrigeration Research, Volume 9, Number 2, April 2003, pp. 153-166. Use of Computational Fluid Dynamics

More information

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in

More information

Effect of Rack Server Population on Temperatures in Data Centers

Effect of Rack Server Population on Temperatures in Data Centers Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,

More information

Pushing the limits. Turbine simulation for next-generation turbochargers

Pushing the limits. Turbine simulation for next-generation turbochargers Pushing the limits Turbine simulation for next-generation turbochargers KWOK-KAI SO, BENT PHILLIPSEN, MAGNUS FISCHER Computational fluid dynamics (CFD) has matured and is now an indispensable tool for

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers

W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be

More information

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School

A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

Virtual Data Centre Design A blueprint for success

Virtual Data Centre Design A blueprint for success Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Introduction to CFD Analysis

Introduction to CFD Analysis Introduction to CFD Analysis 2-1 What is CFD? Computational Fluid Dynamics (CFD) is the science of predicting fluid flow, heat and mass transfer, chemical reactions, and related phenomena by solving numerically

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Steady Flow: Laminar and Turbulent in an S-Bend

Steady Flow: Laminar and Turbulent in an S-Bend STAR-CCM+ User Guide 6663 Steady Flow: Laminar and Turbulent in an S-Bend This tutorial demonstrates the flow of an incompressible gas through an s-bend of constant diameter (2 cm), for both laminar and

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation Differential Relations for Fluid Flow In this approach, we apply our four basic conservation laws to an infinitesimally small control volume. The differential approach provides point by point details of

More information

MEASUREMENTS AND PREDICTIONS OF THE FLOW DISTRIBUTION THROUGH PERFORATED TILES IN RAISED-FLOOR DATA CENTERS

MEASUREMENTS AND PREDICTIONS OF THE FLOW DISTRIBUTION THROUGH PERFORATED TILES IN RAISED-FLOOR DATA CENTERS Proceedings of IPACK 01 The Pacific Rim/ASME International Electronic Packaging Technical Conference and Exhibition July 8 13, 2001, Kauai, Hawaii, USA IPACK2001-15728 MEASUREMENTS AND PREDICTIONS OF THE

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

Thinking Outside the Box Server Design for Data Center Optimization

Thinking Outside the Box Server Design for Data Center Optimization Thinking Outside the Box Server Design for Data Center Optimization Marie Ross, Senior Applications Engineer Tom Gregory, Consultant Engineer October 2013 The benefits of analyzing thermal performance

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

COMPUTATIONAL FLOW MODEL OF WESTFALL'S 4000 OPEN CHANNEL MIXER 411527-1R1. By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY

COMPUTATIONAL FLOW MODEL OF WESTFALL'S 4000 OPEN CHANNEL MIXER 411527-1R1. By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY COMPUTATIONAL FLOW MODEL OF WESTFALL'S 4000 OPEN CHANNEL MIXER 411527-1R1 By Kimbal A. Hall, PE Submitted to: WESTFALL MANUFACTURING COMPANY FEBRUARY 2012 ALDEN RESEARCH LABORATORY, INC. 30 Shrewsbury

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Statement Of Work Professional Services

Statement Of Work Professional Services Statement Of Work Professional Services Data Center Cooling Analysis using CFD Data Center Cooling Analysis Using Computational Fluid Dynamics Service 1.0 Executive Summary Table of Contents 1.0 Executive

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

CCTech TM. ICEM-CFD & FLUENT Software Training. Course Brochure. Simulation is The Future

CCTech TM. ICEM-CFD & FLUENT Software Training. Course Brochure. Simulation is The Future . CCTech TM Simulation is The Future ICEM-CFD & FLUENT Software Training Course Brochure About. CCTech Established in 2006 by alumni of IIT Bombay. Our motive is to establish a knowledge centric organization

More information

Control Strategies for Plenum Optimization in Raised Floor Data Centers

Control Strategies for Plenum Optimization in Raised Floor Data Centers Control Strategies for Plenum Optimization in aised Floor Data Centers Keke Chen, Clifford C. Federspiel, David M. Auslander, Cullen E. Bash, Chandrakant D. Patel Enterprise Software and Systems Laboratory

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling

Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Student Intern Earth and Environmental Engineering,

More information

Rack Hygiene. Data Center White Paper. Executive Summary

Rack Hygiene. Data Center White Paper. Executive Summary Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,

More information

Basic Selection & Proper Application of Overhead Air Distribution Devices

Basic Selection & Proper Application of Overhead Air Distribution Devices Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Introduction to CFD Analysis

Introduction to CFD Analysis Introduction to CFD Analysis Introductory FLUENT Training 2006 ANSYS, Inc. All rights reserved. 2006 ANSYS, Inc. All rights reserved. 2-2 What is CFD? Computational fluid dynamics (CFD) is the science

More information

COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE KASTURI RANGAN RAJAGOPALAN

COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE KASTURI RANGAN RAJAGOPALAN COMPARATIVE ANALYSIS OF WIDELY USED AIR CONTAINMENT SYSTEMS IN COMMERCIAL DATA CENTERS FOR MAXIMUM COOLING PERFORMANCE by KASTURI RANGAN RAJAGOPALAN Presented to the Faculty of the Graduate School of The

More information

Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center

Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center Airflow Uniformity through Perforated Tiles in a Raised-Floor Data Center White Paper 121 Revision 1 by James W. VanGilder, P.E., APC by Schneider Electric Roger R. Schmidt, Ph.D., P.E., IBM Corporation

More information

11 Top Tips for Energy-Efficient Data Center Design and Operation

11 Top Tips for Energy-Efficient Data Center Design and Operation 11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal

More information

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015 EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Turbulence Modeling in CFD Simulation of Intake Manifold for a 4 Cylinder Engine

Turbulence Modeling in CFD Simulation of Intake Manifold for a 4 Cylinder Engine HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Turbulence Modeling in CFD Simulation of Intake Manifold for a 4 Cylinder Engine Dr MK

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY

EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY EXPERIMENTAL CHARACTERIZATION OF TRANSIENT TEMPERATURE EVOLUTION IN A DATA CENTER FACILITY Rajat Ghosh, Pramod Kumar Vikneshan Sundaralingam Yogendra Joshi yogendra.joshi@me.gatech.edu G.W. Woodruff School

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Computational Fluid Dynamics (CFD) can be used to numerically

More information

CFD Modeling of an Air-Cooled Data Center. Master s thesis in Applied Mechanics EMELIE WIBRON

CFD Modeling of an Air-Cooled Data Center. Master s thesis in Applied Mechanics EMELIE WIBRON CFD Modeling of an Air-Cooled Data Center Master s thesis in Applied Mechanics EMELIE WIBRON Department of Applied Mechanics CHALMERS UNIVERSITY OF TECHNOLOGY Gothenburg, Sweden 2015 MASTER S THESIS IN

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA

THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA Adam Kosík Evektor s.r.o., Czech Republic KEYWORDS CFD simulation, mesh generation, OpenFOAM, ANSA ABSTRACT In this paper we describe

More information

Trace Layer Import for Printed Circuit Boards Under Icepak

Trace Layer Import for Printed Circuit Boards Under Icepak Tutorial 13. Trace Layer Import for Printed Circuit Boards Under Icepak Introduction: A printed circuit board (PCB) is generally a multi-layered board made of dielectric material and several layers of

More information

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow 1 of 9 Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow A method utilizing Computational Fluid Dynamics (CFD) codes for determination of acceptable risk level

More information

Using CFD to improve the design of a circulating water channel

Using CFD to improve the design of a circulating water channel 2-7 December 27 Using CFD to improve the design of a circulating water channel M.G. Pullinger and J.E. Sargison School of Engineering University of Tasmania, Hobart, TAS, 71 AUSTRALIA Abstract Computational

More information

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi 2 Rajesh Dudi 1 Scholar and 2 Assistant Professor,Department of Mechanical Engineering, OITM, Hisar (Haryana)

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Chapter 2. Derivation of the Equations of Open Channel Flow. 2.1 General Considerations

Chapter 2. Derivation of the Equations of Open Channel Flow. 2.1 General Considerations Chapter 2. Derivation of the Equations of Open Channel Flow 2.1 General Considerations Of interest is water flowing in a channel with a free surface, which is usually referred to as open channel flow.

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information