Data Center Optimization: Beware of the Power Density Paradox

Size: px
Start display at page:

Download "Data Center Optimization: Beware of the Power Density Paradox"

Transcription

1 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 1 Data Center Optimization: Beware of the Power Density Paradox Avoid the trap balance high density deployments with available power, cooling and space by Karl Robohm and Steven Gunderson

2 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 2 INTRODUCTION DRIVEN BY THE NECESSITY TO DELIVER HIGH PERFORMANCE AND 24/7 enterprise-wide services to customers and employees, many corporate data centers are busting at the seams trying to support the explosive growth in servers, storage and network equipment. As a result, many organizations are running out of power, cooling or physical space in their data centers. Too often the decisions made to resolve these facility problems are based on vendor and analyst hype that does not take into account your specific environment. Your legacy systems, physical infrastructure and long term strategy all must be considered. Individual tactics such as high density blade servers and storage, data center containers, modular power systems, virtualization and cloud computing all offer some potential relief to limits on power, cooling and space but only when implemented appropriately. To increase capacity in a fixed space while at the same time trying to reduce power consumption per server, many IT shops are turning to smaller, denser servers and storage systems. They hope that by packing more gear into a smaller space they will delay or avoid the need for costly data center relocation, or the construction of an entire new data center. And this certainly makes sense, at least up to a point. AVOID THE TRAP. However, you need to plan carefully or you ll fall victim to the power-density paradox. The paradox is that by using more dense equipment (with its need for additional power, cooling and backup), you will eventually reach an inversion point where your total need for data center space Your challenge is to balance the density of servers increases, rather than falls. This translates into greater capital and operational costs, and other equipment in your data center with rather than the reductions you d been hoping for. the availability of power, cooling and space so Your challenge is to balance the density of servers and other equipment in your data you truly gain operating efficiencies and lower center with the availability of power, cooling and space so you truly gain operating net costs. efficiencies and lower net costs. This white paper describes the power-density paradox, and how to avoid its traps by balancing facilities capabilities with core IT needs. Such an approach can optimize the life span of your current facility or help you create a new data center optimized to meet the needs of a modern, high-density environment. Ignoring the impact of the power-density paradox will only: Increase overall data center operating expense (power and cooling) Increase capital expenditures for patchwork fixes (which also increase power and maintenance expense); and Raise the danger of application downtime, thus putting your entire organization at risk.

3 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 3 Roots of the Power-Density Paradox The power-density paradox stems from the great advances in server and storage technology over the last decade. Because many data centers have not changed to accommodate the new, far more densely populated environment, more organizations are facing its consequences or soon will. Consider how much application server technology has evolved since most data centers were designed 15 years ago. In the mid 1990s, floor-mounted minicomputers like the IBM AS/400 (which is still available today as the System-i) were just beginning to be replaced with rack-mounted servers taking only 3-5U of rack space. That s essentially a 14 fold increase in server density. By 2000 those rack-mounted servers had shrunk to 1U pizza box designs, only to be replaced beginning in 2002 by blade servers. These devices put multiple server motherboards (each with their own processor, memory, I/O connections and sometimes even a disk drive) on a single blade. The net change is an astounding 84X increase in density of servers per rack, with the total compute power increasing by several orders of magnitude. With every increase in the number of processors in a given space, substantially more power is required to run and cool them. Just managing the thermodynamics becomes a limitation to growth and reliability. The increased density also brings with it greater risk to the business when a rack overheats and systems shut down or fail. POWER UP. The denser the server environment, the more electricity is required to power and cool the space. For example, it takes 60 to 100 watts of power per square foot to operate legacy minicomputers or full racks of 3-5U servers. The same space filled with smaller, 1U servers would require at least 200 watts per square foot, and the latest blade servers require as much as 400 watts per square foot. COOL DOWN. Each additional watt of power consumed by the computing Because higher-density servers require more power environment must be offset with an equivalent amount of cooling. Denser data centers per square foot than lower-density servers, they also also require more air-moving capacity to deliver the colder air and remove warm air need more support equipment such as air from the space efficiently. conditioning, uninterruptible power supplies and Then there is the fact that many data centers were never designed to remove the backup generators. amount of heat put off by these devices. For example, the ceilings may not be high enough to let warm air rise from the servers; there may not be enough room under the raised floors to allow cool air to circulate sufficiently; or the CRAC (computer room air conditioning) units may not be properly placed to effectively cool all the racks and servers. GIVE ME SPACE. This need for more power and cooling therefore drives a need for more support space, creating the power-density paradox. Because higher-density servers require more power per square foot than lower-density servers, they also need more support equipment such as air conditioning, uninterruptible power supplies and backup generators. Because this equipment is usually housed in support space away from the raised floor, IT and facilities managers often pay too little attention to the need for such increased support space and its effect on overall data center costs and efficiency. As a result of these dependencies, you cannot simply take an existing facility and begin adding more dense servers and storage without addressing how these systems will be cooled. Without adding more CRAC units and air flow, you will reach a point where your only option is to rework your floor plan around the higher density environment. Without power and cooling upgrades, you may end up with very little net gain of compute capacity in your existing facility by going to higher density devices.

4 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 4 Floor Plan Options with 100 Watts/SQ. FT. Capacity Layout Using 5kw Racks Layout Using 10kw Racks Layout Using 20kw Racks SOURCE: TDS 2009 This diagram illustrates different layout options for a 2,000 square foot facility as rack density increases from 5kw to 20kw (based on 200kw total power and cooling capacity). While the actual layouts may vary, you cannot deploy more than 200kw of IT systems without upgrading the electrical and cooling infrastructure. As the power density (watts required per square foot) increases in the raised floor portion of the data center, so does the space needed for additional support equipment. In fact, at a density of about 400 watts per square foot, plan to allocate around 6 times the usable data center space for internal cooling and backup power. To cost effectively increase the power density capacity for an established facility, there must be adequate support space to house the additional power/cooling infrastructure, sufficient raised floor space to handle the increased airflow demands and of course sufficient power for the systems and support gear to operate. If any of these are inadequate, the data center will not scale. Data Center Space Allocation at Different Power Densities Square Feet of Space Required 5,000 4,000 3,000 2,000 1,000 Usable Space Support Space Generator UPS & Elec. CRACs Watts/Sq.Ft. 50W 100W 200W 400W Raised Floor 6-12 in in. 3 ft. 4+ ft. SOURCE: TDS 2009 This chart shows the relationship of support space to usable space at various levels of power density based on a facility with 2,000 square feet of raised floor. This example is limited to the support space required for the additional CRAC units, UPS (and related electrical) and backup generators, but does not include the additional space required for upgraded power cables, airflow, upgraded chillers and additional fuel storage required for the upgraded generator capacity. So unless you have been upgrading your power, cooling and air flow along the way, chances are good that any data center more than a few years old is incapable of automatically and economically supporting environments over 200 watts per square foot. To boost the capacity of your existing facility without raising costs, or to properly design a new data center, you must consider the power-density paradox.

5 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 5 The Need to Optimize IT Facilities The problems associated with the power-density paradox are often made worse by poor data center design and management practices. These may have been acceptable in an era of lower-density equipment but become intolerable as densities rise. For example, equipment racks may have been laid out haphazardly over the years as various business units required new server capacity. Because the new servers and racks were added without an overall plan for data center airflow and cooling, they often cause hot spots, inefficient cooling and increased power consumption. In addition, older data centers often may have only 12 to 18 of space under their raised floors for cooling (likely shared with network and power cabling), rather than the 36 or more required for modern, high density data centers. Reconfiguring the racks for hot aisle/cold aisle air flow will improve efficiency somewhat, but provide no real increase in overall capacity since the cold air flow is limited by the shallow raised floor. In the end, the organization is still limited by the fundamental capabilities of the data center infrastructure. WORKING AT CROSS PURPOSES. Another poor practice that s all too common is using the factory default settings for data center infrastructure equipment, even if those settings are not appropriate for your deployment. A good example of this can be found with the CRAC units. By default, CRAC systems run independently of one other and each unit will try to maintain the relative humidity and temperature around it in a specific range. This results in the CRAC units fighting against one another, with one unit cooling and another heating, one humidifying and another dehumidifying the same air. Besides wasting electricity, this causes extra wear and tear on the units, which leads to unnecessary (and expensive) If you are at the actual limits of your cooling downtime, maintenance and hardware replacement. capacity, you can also buy some time by installing The humidification systems within the CRAC units can themselves be another source of ultrasonic humidification (which actually helps waste. Like pans boiling water on the stove, these systems rely on steam generation. cool the environment) and turning off built-in Unfortunately steam has the obvious side effect of raising the data center s air humidification systems. temperature, making CRAC units work even harder (and use more power) to cool the data center environment. The result is a vicious circle that adds unnecessary heat that you ve then got to cool, increasing your spend on power. Again, this also causes extra wear, tear and maintenance for the CRAC units. There are simple solutions to some of these problems. One is to install a single control unit for all the CRAC units so they don t work against one another. If you are at the actual limits of your cooling capacity, you can also buy some time by installing ultrasonic humidification (which actually helps cool the environment) and turning off built-in humidification systems. This will create humidity more efficiently without raising the air temperature through a steam process.

6 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 6 Critical Risks of Ignoring the Paradox There are several big risks for those who choose to disregard the power-density paradox. RISK 1: WASTED HEATING AND COOLING COSTS. The first and most obvious risk of implementing highdensity servers without accounting for the power-density paradox is dramatic and unnecessary increases in power and cooling costs, as well as in maintenance of equipment such as CRAC units. If you are at the limits of available power, these extra heating and cooling demands can reduce the net power available for IT computers, storage and networking systems. RISK 2: UNANTICIPATED EQUIPMENT EXPENDITURES. The second risk is unanticipated capital and operating expenses for band-aid type solutions which attempt to keep a sub-optimal facility in operation. The use of specialized air handling equipment such as fan tiles or portable/standalone CRACs are warning signs that a data center may be approaching the end of its useful life. Even if these systems extend the life of the data center, they add to your power consumption and maintenance expense while introducing additional points of potential failure. RISK 3: DOWNTIME. Servers deployed in a high density environment are at much greater risk from unexpected downtime than those in lower-density environment. Even if the UPS continues to provide operational power to the devices during a loss of utility power, the facility will lose cooling and airflow until the generator kicks in, and the cooling system recycles. In some cases we have seen data temperatures rise from 70 degrees to over 100 in just 4 minutes before the cooling systems return online. This accelerated heating is caused by the hot exhaust of high density systems and the relatively small bank of reserve colder air in the space to offset it. The downtime caused by such a cooling failure could be minutes if the server detects a temperature spike and shuts down to prevent damage to the servers; or it could be much longer in the event the excess heat actually damages hardware. Depending on the architecture used to assure application software resiliency, this could quickly lead to application downtime, reduced overall performance/throughput, and financial risk to the business. When designing a new data center, ignoring the power-density paradox can lead to poor choices that waste money. Trying to minimize the amount of raised floor space by installing high-density servers may require more expensive power, cooling and backup systems. In many cases, this more than negates the space-saving advantages of high-density systems. When optimizing the critical resources of a data center, it is less expensive to purchase more real estate at $50 per square foot, when $1,000 - $2,000 per square foot in added MEP (mechanical, electrical and plumbing) infrastructure is required to support the higher power density. FACTORS TO WEIGH. Getting the maximum computing capability at the lowest total cost requires weighing a variety of factors, ranging from real estate and power costs to the proper configuration of CRAC units and the right choice of humidification equipment. Advances in processor technology have moved so quickly that designers cannot simply add more servers, storage and network gear into the same space without regard for the power, the thermodynamics of cooling this hardware and the support equipment required by high density servers. To maximize application uptime and minimize costs and risks, data center designers and facilities managers must understand the power-density paradox and act accordingly.

7 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 7 Boston Area Data Center Recovers 2,800 MWh Power per Year By anticipating the impact of power-density paradox, a 16,000 square foot, Tier 3 class data center in Boston was able to reduce its annual power requirements by 2,800 Megawatt hours. This was achieved by three infrastructure upgrade projects working in tandem to increase power and cooling efficiency and resulted in savings of $420,000 per year. (Of course, as power costs go up, future savings will be even greater). These efficiency improvements were implemented quickly and efficiently. Taking into account the power company rebates, these three projects had a combined payback of 8 months, with the high efficiency motors and pumps having a payback of only 3 months. In addition to these cost savings, the use of ultrasonic humidification also recovered 15% additional cooling capacity. Project High Efficiency Motors & Pumps Ultrasonic Humidification High Efficiency Transformers Turnkey Project Cost $180,000 $325,000 $184,000 Utility Company Rebates $135,000 $190,000 $82,000 Net Cost $45,000 $135,000 $102,000 Annual Power Reduction 1,250 MWh 1,050 MWh 525 MWh Annual Power Savings* $185,000 $156,000 $79,000 * Savings based on electric power cost of $0.15 per kwh While the amount of infrastructure needed for most corporate data centers is less than this example, these same approaches to conserve power and related expenses can pay off for facilities as small as 1,000 square feet. The Solution: Optimize and Balance The power-density paradox is a result of the physics of squeezing higher-density systems into smaller and smaller spaces. The fact is, nobody can outsmart the paradox, and you ignore it at your own peril. A better approach is to understand the impact it will have on your organization and develop a forward-looking plan based on a cross-disciplinary perspective. Cross-disciplinary means that any assessment involving your data center s computing power; electrical requirements and cooling facilities should come from a diverse group of business, technical and IT managers. The team should include IT, operations and facilities so they can all understand the effects of their choices on the overall data center environment. NO MORE SILOS. In practice, many corporate departments operate in isolated islands, or silos, that make decisions somewhat autonomously. This is fine for most day-to-day activities. But data centers by their nature are not autonomous. While IT equipment is purchased, installed and often maintained by IT, power and cooling are usually the responsibility of the facilities staff, which often doesn t understand the power and cooling needs of modern, high-density servers. Involving all the affected parties helps keep everyone focused on the organization s objectives to reduce costs, make the most of current assets and avoid unnecessary capital expenditures in today s recessionary environment.

8 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 8 Outside Experts Can Help Regardless whether you are trying to extend the life of a current facility or building a high density data center, this is not the time for on-the-job training. The power density paradox makes seemingly simple decisions more complex than appears on the surface. Involving expert outside assistance can help in several ways: An independent, third-party perspective can balance the needs and challenges facing the IT, facilities and finance groups. Specialized expertise in high-density data center design and operations can save time and money while providing a flexible path to longer term needs. Knowledge and experience with best practices tools, processes and efficient technologies to support modern, high density data centers may fill gaps in your staff s experience or availability. Expertise in modern HVAC and MEP infrastructure alternatives can extend the life of current facilities or be leveraged in the design of a new, high density facility. Qualifying for and obtaining utility rebates that can subsidize efficiency improvements in the data center, lowering capital costs and reducing operating expenses. Ideally, this expert resource will offer both a business and a technical perspective, provide unbiased advice untainted by vendor or analyst hype and can recommend and help implement the best technology, facility and operational options for you. WHAT YOU LEARN. Through such an assessment, you may learn you can delay building or relocating to a new data center. You may instead find the optimum approach is to mix some high-density systems with some lowerdensity systems, or to simply not use all the vertical space in each rack. You may find that you need to simply reprogram your CRAC units for your environment, consolidate the controls or move to For example, in a 40,000 square foot data center ultrasonic humidification systems which can provide tremendous savings. For example, in Massachusetts, the use of ultrasonic in a 40,000 square foot data center in Massachusetts, the use of ultrasonic humidification instead of steam resulted in savings of $900,000 per year in utility costs, along with humidification instead of steam resulted in $52,000 a year in reduced maintenance costs. savings of $900,000 per year in utility costs. Some of the investments in new facility infrastructure, such as ultrasonic humidification, can be recovered immediately through power company rebates. Depending on the size of your efficiency improvement, such rebates could cover 40 percent to 50 percent of the equipment and installation costs. You will, however, need to audit your power usage before and after the upgrades to prove the improvements you made led to the reduced power consumption. Another recommendation may be to allocate more space than you need right now, and build the data center out to support your requirements in a modular fashion. This can result in lower long-term costs than trying to squeeze as many servers as possible into the smallest area. Whatever the specific actions that result from such an assessment, you ll be making data center design and operation decisions based on a true understanding of data center operations. You won t be trapped into unnecessary spending or risk by the power-density paradox.

9 DATA CENTER OPTIMIZATION: BEWARE OF THE POWER DENSITY PARADOX 9 CONCLUSION Organizations facing severe cost, real estate and power constraints should not rush blindly into the use of ultra high-density servers and storage systems to save space and money in their data center. If this is done without proper planning, and a holistic analysis of business needs and the data center environment, the use of such equipment can actually increase costs and business risks. Conducting an overall assessment of the data center environment, perhaps with the help of qualified outside specialists, can produce dramatic short-term cost savings and delay or even eliminate the need for costly data center construction or relocations. About the Authors Karl Robohm leads the TDS Data Center practice. Karl has designed, built and managed over a half a million square feet of high density and high efficiency (green) data centers for commercial and carriergrade clients. Steven Gunderson co-founded and operated two commercial data center companies, Enclave Properties and CO Space, prior to his current leadership role at TDS. About Transitional Data Services (TDS) Since 2002, Transitional Data Services has provided data center consulting, systems development and technical operations services that help clients boost the performance of their technology operations and business processes. TDS provides independent assessments, recommendations and improvements for IT including data center designs, relocations, operational support, ERP, web and mobile applications. Our recommendations cross departmental and technology silos to achieve the best ROI for our clients. Since we do not operate as a vendor or VAR, we are unrestricted to a specific product portfolio and unbiased by the latest trends and highest commission. TDS clients include successful organizations of all sizes and focus including John Hancock, Monster.com, Boston Red Sox, Cedars Sinai and Liberty Mutual. For more information, please visit Transitional Data Services All rights reserved

Managing Today s Data Centers Avoiding the Impending Crisis

Managing Today s Data Centers Avoiding the Impending Crisis Managing Today s Data Centers Avoiding the Impending Crisis Steven Yellen Aperture Research Institute EXECUTIVE SUMMARY Organizations are facing an impending data center management crisis. The constant

More information

Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services

Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services Data Center & IT Infrastructure Optimization Trends & Best Practices Mickey Iqbal - IBM Distinguished Engineer IBM Global Technology Services IT Organizations are Challenged by a Set of Operational Issues

More information

Server Room Thermal Assessment

Server Room Thermal Assessment PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...

More information

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Energy management White paper. Greening the data center with IBM Tivoli software: an integrated approach to managing energy.

Energy management White paper. Greening the data center with IBM Tivoli software: an integrated approach to managing energy. Energy management White paper Greening the data center with IBM Tivoli software: an integrated approach to managing energy. May 2008 2 Contents 3 Key considerations for the green data center 3 Managing

More information

Can Your Data Center Infrastructure Handle the Heat of High Density? 5 Ways to Test Your Data Center Infrastructure before Installing Blades

Can Your Data Center Infrastructure Handle the Heat of High Density? 5 Ways to Test Your Data Center Infrastructure before Installing Blades Can Your Data Center Infrastructure Handle the Heat of High Density? 5 Ways to Test Your Data Center Infrastructure before Installing Blades Can Your Data Center Infrastructure Handle the Heat of High

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

EMC PERSPECTIVE Managing Energy Efficiency in the Data Center

EMC PERSPECTIVE Managing Energy Efficiency in the Data Center EMC PERSPECTIVE Managing Energy Efficiency in the Data Center A tactical approach can deliver immediate problem resolution plus long-term savings and efficiencies Managing Energy Efficiency in the Data

More information

Increasing Energ y Efficiency In Data Centers

Increasing Energ y Efficiency In Data Centers The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

abstract about the GREEn GRiD

abstract about the GREEn GRiD Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Enterprise Data Centre

Enterprise Data Centre Members Meeting The Challenges and Changes for the Data Centre Manager 1 Continuity Forum Members Meeting May 2009 Introduction Increase awareness of IT energy usage Understand processes and practices

More information

Strategies for Deploying Blade Servers in Existing Data Centers

Strategies for Deploying Blade Servers in Existing Data Centers Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

EXECUTIVE REPORT. Can Your Data Center Infrastructure Handle the Heat of High Density?

EXECUTIVE REPORT. Can Your Data Center Infrastructure Handle the Heat of High Density? EXECUTIVE REPORT Can Your Data Center Infrastructure Handle the Heat of High Density? If you re losing sleep wondering how your company can migrate to high density computing architectures, you re not alone.

More information

The art of the possible.

The art of the possible. IBM Scalable Modular Data Center The art of the possible. Rapidly deploying cost-effective, energy-efficient data centers APC InfraStruXure Rapidly deploying cost-effective, energy-efficient data centers

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

Energy Management Services

Energy Management Services February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the

More information

How To Power And Cool A Data Center

How To Power And Cool A Data Center Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Implementing Energy Efficient Data Centers

Implementing Energy Efficient Data Centers Implementing Energy Efficient Data Centers By Neil Rasmussen White Paper #114 Executive Summary Electricity usage costs have become an increasing fraction of the total cost of ownership (TCO) for data

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Smart Move: Five Steps to a Successful Data Center Relocation

Smart Move: Five Steps to a Successful Data Center Relocation SMART MOVE: FIVE STEPS TO A SUCCESSFUL DATA CENTER RELOCATION 1 Smart Move: Five Steps to a Successful Data Center Relocation A fast-growing number of organizations are relocating their data centers, but

More information

Data Center Definition and Solutions

Data Center Definition and Solutions 1 of 9 11/10/2009 6:08 AM Print Article Close Window From: www.cio.com Data Center Definition and Solutions Michael Bullock, CIO August 14, 2009 What are some top stakeholder concerns about data centers?

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Predictive Data Center Infrastructure Management (DCIM)

Predictive Data Center Infrastructure Management (DCIM) Predictive Data Center Infrastructure Management (DCIM) A toolset to maximize the return on capital expenditure in the physical data center Sherman Ikemoto, Matt Warner, Akhil Docca, Hassan Moezzi 11/21/2012

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

How Eight California Data Centers Reduced Energy by 20%

How Eight California Data Centers Reduced Energy by 20% How Eight California Data Centers Reduced Energy by 20% Sponsored by the California Energy Commission Public Interest Energy Research David Weightman, Energy Commission Specialist California Energy Commission

More information

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face

More information

WHITE PAPER Delivering Improved Energy Efficiency for the Datacenter

WHITE PAPER Delivering Improved Energy Efficiency for the Datacenter WHITE PAPER Delivering Improved Energy Efficiency for the Datacenter Sponsored by: NEC Jed Scaramella September 2008 Matthew Eastwood EXECUTIVE SUMMARY Global Headquarters: 5 Speen Street Framingham, MA

More information

DATA CENTER ASSESSMENT SERVICES

DATA CENTER ASSESSMENT SERVICES DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to

More information

Power Consumption and Cooling in the Data Center: A Survey

Power Consumption and Cooling in the Data Center: A Survey A M a r k e t A n a l y s i s Power Consumption and Cooling in the Data Center: A Survey 1 Executive Summary Power consumption and cooling issues in the data center are important to companies, as evidenced

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Creating Order from Chaos in Data Centers and Server Rooms

Creating Order from Chaos in Data Centers and Server Rooms Creating from in Data Centers and Server Rooms By Dennis Bouley White Paper #119 Executive Summary Data center professionals can rid themselves of messy racks, sub-standard under floor air distribution,

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group

Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group Impact of Virtualization on Data Center Physical Infrastructure White Paper #27 Tom Brey, IBM perations Work Group 1 Virtualization Two Steps WP #19 USING VIRTUALIZATIN T IMPRVE DATA CENTER EFFICIENCY

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems Data Center Cooling A guide from: Your partners in UPS Monitoring Systems The air in your server room, especially nearest the processors in your equipment, will rise to dangerous temperatures quickly if

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

Rethinking Data Center Design

Rethinking Data Center Design Rethinking Data Center Design Building the room around the rack can ease cooling challenges and save money By John Collins Segment Manager, Data Centers Eaton Corporation Executive summary For decades,

More information

Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10

Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10 Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10 Issue August 2007 Contents Executive Summary 2 Blade for Blade, Power is the Same 3 PAN Lowers Power by Reducing Server/CPU Count

More information

Data Center Efficiency in the Scalable Enterprise

Data Center Efficiency in the Scalable Enterprise FEATURE SECTION: POWERING AND COOLING THE DATA CENTER Data Center Efficiency in the Scalable Enterprise 8 DELL POWER SOLUTIONS Reprinted from Dell Power Solutions, February 2007. Copyright 2007 Dell Inc.

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

Raising Inlet Temperatures in the Data Centre

Raising Inlet Temperatures in the Data Centre Raising Inlet Temperatures in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Data Centers That Deliver Better Results. Bring Your Building Together

Data Centers That Deliver Better Results. Bring Your Building Together Data Centers That Deliver Better Results Bring Your Building Together 1 Meeting the high demands of your data center Meeting the increasing heat loads associated with growing computational needs requires

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency WHITE PAPER Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency 20A Dunklee Road Bow, NH 03304 USA 2007. All rights reserved. Sensatronics is a registered trademark of. 1 Abstract

More information

Reducing Data Center Power Consumption Through Efficient Storage

Reducing Data Center Power Consumption Through Efficient Storage NETAPP WHITE PAPER Reducing Data Center Power Consumption Through Efficient Storage Larry Freeman, NetApp, Inc. July 2009 WP-7010-0709 AN EIGHT-POINT PLAN FOR FIGHTING POWER CONSUMPTION The NetApp eight-point

More information

Data Center Trend: Distributed Power in the White Space

Data Center Trend: Distributed Power in the White Space Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize

More information

Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability

Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability Colocation and Cloud Hosting Solutions Build a strong and efficient physical infrastructure that delivers service reliability and profitability 2 Dependability and Deployment Speed that Improves Your Bottom

More information

Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk

Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Metering and Managing University of Sheffield Data Centres Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Summary ICT Electricity Use Footprint Data Centre Electricity Use European

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Greener Pastures for Your Data Center

Greener Pastures for Your Data Center W H I T E P A P E R Greener Pastures for Your Data Center 2 Executive Summary Following a green path, once a concept relegated to a small group of environmentalists and the U.S. Environmental Protection

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Smart Move: Five Steps to a Successful Data Center Relocation

Smart Move: Five Steps to a Successful Data Center Relocation 1 Smart Move: Five Steps to a Successful Data Center Relocation As organizations relocate their data centers, many lack the up-front planning that reduces the short-term risk of business disruption and

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Server Consolidation for SAP ERP on IBM ex5 enterprise systems with Intel Xeon Processors:

Server Consolidation for SAP ERP on IBM ex5 enterprise systems with Intel Xeon Processors: Server Consolidation for SAP ERP on IBM ex5 enterprise systems with Intel Xeon Processors: Lowering Total Cost of Ownership An Alinean White Paper Published by: Alinean, Inc. 201 S. Orange Ave Suite 1210

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

VISIT 2010 Fujitsu Forum Europe 0

VISIT 2010 Fujitsu Forum Europe 0 VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00

More information

Convergence of Complexity

Convergence of Complexity Convergence of Complexity Optimize Existing Data Center Space Measure And Allocate Energy Cost Plan for new data centers or additional capacity How to make your Data Center Last Longer, Gartner, December

More information

Nexsan 10 Minute White Paper. The Power/Density Paradox. The Result of High Density without Power Efficiency. Quick Summary

Nexsan 10 Minute White Paper. The Power/Density Paradox. The Result of High Density without Power Efficiency. Quick Summary Nexsan 10 Minute White Paper The Power/Density Paradox The Result of High Density without Power Efficiency Quick Summary Growing demand for capacity in ever-shrinking data center space has motivated some

More information

Sanjeev Gupta Product Manager Site and Facilities Services

Sanjeev Gupta Product Manager Site and Facilities Services IBM Global Technology Services IBM Project Big Green Delivering Client Value Sanjeev Gupta Product Manager Site and Facilities Services Data centers are at a tipping point and energy use and cost is the

More information

Solutions to Make Your Data Center Energy Effi cient

Solutions to Make Your Data Center Energy Effi cient Common $en e: Solutions to Make Your Data Center Energy Effi cient Energy effi ciency is a life style. It s also common sense. In a data center, the name of the game is effi ciency and how many compute

More information

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

Measure Server delta- T using AUDIT- BUDDY

Measure Server delta- T using AUDIT- BUDDY Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because

More information

Arch Rock Energy Optimizer in Action Data Center

Arch Rock Energy Optimizer in Action Data Center Arch Rock Energy Optimizer in Action Data Center Business Perspective Recent trends in Information Technology such as dense blade computing, server and storage virtualization, and cloud computing have

More information

Creating Order from Chaos in Data Centers and Server Rooms

Creating Order from Chaos in Data Centers and Server Rooms Creating from in Data Centers and Server Rooms White Paper 119 Revision 1 by Dennis Bouley > Executive summary Data center professionals can rid themselves of messy racks, sub-standard under floor air

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

Modernizing Vintage Data Centers

Modernizing Vintage Data Centers Modernizing Vintage Data Centers Improving the reliability, efficiency and effectiveness of older computing facilities by upgrading their power and cooling systems By John Collins Segment Manager, Data

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

Enabling an agile Data Centre in a (Fr)agile market

Enabling an agile Data Centre in a (Fr)agile market Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without

More information

NRDC case study. NRDC s New York Data Center Upgrade: Efficiency Case Study

NRDC case study. NRDC s New York Data Center Upgrade: Efficiency Case Study NRDC case study december 2014 CS:14-09-a NRDC s New York Data Center Upgrade: Efficiency Case Study DATA CENTER BUILD-OUT TEAM table of contents ARCHITECT: Croxton Collaborative Architects, PC GENERAL

More information

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009 IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities

More information

Datacenter Efficiency

Datacenter Efficiency EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Unleashing Stranded Power and Cooling Data

Unleashing Stranded Power and Cooling Data Unleashing Stranded Power and Cooling from New and Existing Data Centers An affordable, five-step approach to addressing power and cooling shortages By Dr. Kenneth Uhlman, P.E. Director of Data Center

More information

T: 0344 875 4555 ENQUIRIES@DATACENTRE-UK.COM

T: 0344 875 4555 ENQUIRIES@DATACENTRE-UK.COM T: 0344 875 4555 ENQUIRIES@DATACENTRE-UK.COM DATACENTRE UK INTRODUCTION Datacentre UK are specialist providers of energy efficient data centre and physical infrastructure solutions across the UK, Europe

More information