Fiber in the Data Center
|
|
|
- Estella Morgan
- 10 years ago
- Views:
Transcription
1 Fiber in the Data Center A NetClear White Paper Rudy Montgelas Senior Fiber Product Manager Ortronics/Legrand Lisa Huff Data Center Applications Engineer Berk-Tek, A Nexans Company March 2008 A New Generation of Low-Loss, Modular Cassette-Based Systems Enhance 10-Gb/s Performance
2 Today s data centers (DC) present a challenge in meeting critical business needs in the face of burgeoning transactions and exploding amounts of information that must be stored and managed. With over five exabytes of new information being generated each year globally, even modest data centers must flexibly meet demands for growth in a high-reliability environment. While expansion can be accommodated by adding new servers and storage, it is also met by increasing bandwidth to allow more transmissions per second. Data rates have progressively moved from 10 Mb/s through 100 Mb/s and 1 Gb/s to today s 10 Gb/s and tomorrow s 40 or 100 Gb/s. As data rates increase, the use of fiber-optic cabling in the DC is becoming more commonplace. Advances in optical technology make fiber more affordable, more practical, and easier to use in the data center. These improvements include: 50-micron laser-optimized multimode fiber (LOMF) that allows cable runs of 300 meters at 10 Gb/s with traditional LOMF. Up to 600 meters is possible with a new generation of enhanced LOMF, exemplified by Berk-Tek GIGAlite -XB cable. As will be shown, this second generation of LOMF gives even greater flexibility in meeting the needs of DCs. Vertical-cavity surface-emitting lasers (VCSELs) that lower the cost of optical transceivers. Since they are well matched to LOMF at a wavelength of 850 nm, they make the use of multimode fiber economically attractive. Cassette-based interconnects that speed the installation of fiber-based cabling systems and simplify the on-going management of the system. The Momentum series of cassettes from Ortronics/Legrand offer improved performance over legacy cassettes of just a few years ago. The Benefits of Cassette-Based Fiber Interconnects Multi-fiber cables terminated with industry-standard MTP /MPO array connectors simplify use of fiber in the DC. The cables significantly reduce congestion in pathways, provide the highest port densities (12 fibers in a 0.5 x 0.3-inch area), and simplify system design, installation, and management. While fiber ribbon cables are popular for array connections, new reduced-diameter cables, such as Berk-Tek s Micro Data Center Plenum (MDP) cable, are setting a new standard in DC cabling. As shown in Figure 1, the diameter of a 48-fiber MDP cable is less than half that of a stacked ribbon cable of the same capacity and only one-third of a similarly configured Loose- Tube Plenum (LTP) cable. When properly applied, reduced-diameter cables improve air flow and aid in dissipating heat in the computer room. * MTP is a registered trademark of US Connec Figure 1. Reduced-diameter cables save space in crowded conduits. The companion cassettes, as shown in Figure 2, perform the transition from the multi-fiber array to individual SC or LC patch cords. A single cassette can typically handle 12 or 24 fibers in a single unit and up to 12 cassettes fit in a standard 4U 19-inch rackmount fiber patch panel. Installation of the cassette is simple (Figure 3). The cassettes are inserted into the fiber patch panel, and the array cable is plugged into the back of the cassette and patch cords connect to the front. This plug-and-go simplicity means extremely fast and reliable installation when compared to field installing fiber connectors. Copyright 2008 Berk-Tek, a Nexans Company and Ortronics/Legrand, All rights reserved.
3 Design Considerations Using LOMF multi-fiber interconnect cables and cassettes is straightforward. A primary design consideration is ensuring that the system stays within the channel insertion loss budget for a particular application. This budget is simply predetermined by the application (such as 10GBASE-SR). Therefore, the attenuation of the patch cord and backbone cable, associated connector insertion loss, and the insertion loss value of the cassettes should not exceed the channel insertion loss budget. (A free link-loss calculator is available from NetClear at It is an easyto-use spreadsheet that automatically calculates loss based on component choices and link lengths.) Figure 2. A fiber cassette acts as a transition between a MTP/ MPO-based multi-fiber backbone and LC- or SC-terminated patch cords (shown with cover removed for clarity). The sum of these individual losses must be less than the maximum channel insertion loss specified for the application running over the cabling system. As new higher-data-rate networking protocols enter the market, the link budget for the channel diminishes. One of the reasons for shrinking link budgets is that the standards groups, which defined new high-speed protocols conservatively, accounted for certain link penalties. The available channel loss budget is what remains after these penalties are factored into the total loss budget. For example, intersymbol interference (ISI), which can cause bit errors when adjacent data pulses spread and overlap one another, is a major penalty in the overall power budget. As shown in Figure 4, the impact of ISI on overall loss budget is comparable to channel insertion loss, with over 75% of the total loss budget coming from these two factors Figure 3. Fiber cassettes offer the simplicity of plug-and-go application. Cassettes can mount in standard 19-inch or 23- inch rack-mount cabinets, wall-mount enclosures, and under-floor boxes. All components cable assemblies and cassettes are factory terminated and tested so that there is no field preparation involved. And because the components are provided with the test data on a label conveniently affixed to the cassette housing, any field testing results can be verified quickly and easily. The ISI penalty in the 10G standard was calculated using a 50-micron LOMF (OM-3) with a modal bandwidth of 2000 MHz km. The modal bandwidth is primarily limited by the fiber characteristic of differential model delay (DMD), which causes ISI due to pulse spreading. A new generation of LOMF improves the modal bandwidth to 4900 MHz km at 850 nm using today s VCSELs. As we will discuss next, this has important consequences on the application of fiber cassettes in the data center. Copyright 2008 Berk-Tek, a Nexans Company and Ortronics/Legrand, All rights reserved.
4 provides great flexibility for both the designer and installer. Figure 5 summarizes channel budgets and illustrates the maximum number of cassettes possible using different cassette grades. Figure 4. 75% of the total loss budget is allocated to ISI and channel insertion loss in IEEE 802.3ae. Channel Insertion Loss Assuming a fiber having an effective modal bandwidth of 2000 MHz km at 850nm and a fixed link length of 300 meters, the budget for channel insertion loss for 10-Gb/s Ethernet is a tight 2.6 db. With the new 4900 MHz km LOMF, and conservatively compensating for connector modal noise, it becomes possible to reallocate up to 1.9 db of the ISI penalty to the channel loss yielding a more generous 4.5 db budget of channel insertion loss. At the same time, fiber cassettes, backbone cables, and patch cords have been improved to offer lower component insertion loss. Ortronics Momentum cassettes are offered in two performance tiers, with progressively improved insertion loss: 0.75 db for high-performance cassettes and 0.50 db for premium-performance cassettes. This performance, which includes the loss of the rear panel MPO and front panel LC or SC connectors, represents an improvement over 1.25 db or 1.5 db for firstgeneration legacy cassettes. The combination of enhanced low-dmd fiber and improved cassette performance significantly increases flexibility in deploying a cabling system in a DC. With traditional OM3 LOMF and first-generation cassettes, achieving the channel insertion-loss budget over a full 300 meters was pushing the limits: the cable loss at 1.05 db and the insertion loss for 2 cassettes at 2.5 db produced a total loss of 3.55 db. This constrains the design flexibility. With improved fiber and cassettes, it is now possible (although not necessarily practical) to use as many as seven cassettes in the path. The extra system margin Two things need to be noted about Figure 5: 1. The improved fiber has an attenuation of 3.0 db/km (as opposed to 3.5 db/km for OM-3 fiber), which yields a loss of 0.9 db over 300 meters. 2. The graphic is for 300-meter channels. Most channels in DC applications are under 100 meters, which means additional power is reallocated to the budget. Figure 6 shows the distribution of real-world multi-fiber cable backbone lengths commonly used in the DC. Cable lengths over 25 meters are the exception: the vast majority of backbone cables are shorter. Figure 5. Low DMD cable and improved cassettes can allow more connections in the channel. Figure 6. Most backbone cables in a DC are much shorter than the 300 meters maximum allowed by standards and the 600 meters possible with such cables as the GIGAlite-XB. Copyright 2008 Berk-Tek, a Nexans Company and Ortronics/Legrand, All rights reserved.
5 It s the System That Counts The performance of a fiber-based cabling solution needs to be viewed at the system level and not just as an assembly of components. The newer high-performance and premium-performance fiber cassettes are perfect examples. Because the cassette s performance is primarily attributed to improved connector end-face polishing and connector end preparation at the factory, it is essential that the attached backbone cable and patch cords are prepared with the same high-quality process. Otherwise, the improved system-level insertion loss performance may not be realized. Simply put, to achieve improved performance you need high-performance or premium cassettes and matching cables. Similarly, to allow the ISI penalty to be reallocated to the channel budget, all fibers backbone, patch, and fiber internal to the cassette must use the improved high-performance, low-dmd cable. The example in Figure 5 is based on worst-case performance at 300 meters. For other channel lengths, the calculations can be easily modified. Such systems will easily accommodate longer channels with fewer cassettes or shorter channels with the potential of additional cassettes. The important consideration is that, by using worst-case maximum numbers, real-world typical performance will provide an additional comfortable margin. The increased flexibility in system configuration today translates to peace of mind knowing you will not be restricted tomorrow. The use of multi-fiber cable and cassettes, for example, will ease the transition to future parallel transmissions being considered for 40 Gb/s and 100 Gb/s systems now being defined. What s more, the easier installation, the simplified management, and the higher performance combine to offer a lower total cost of ownership. Conclusion Cassette/multi-fiber cabling systems in the DC have obvious advantages in space savings and simple installation. Low-DMD fiber, such as Berk-Tek s GIGAlite-XB, combined with improved connector performance in MOMENTUM 3 cassettes offer flexibility for longer runs or more connections. Gone are the severe limitations on the number of cassettes that you can use in a channel which opens up the widest range of cabling and equipment topologies to keep the growth and evolution of DCs fluid and easily managed. What to Look for in a Fiber Cassette Low Insertion Loss. The lower the insertion loss, the more cassettes that can be used in the channel and the greater flexibility you have in your DC topology Compatibility with Low-DMD Fibers. A cassette using low-dmd fiber is already compatible with systems using low-dmd fiber. This allows the ISI penalty to be reallocated to the channel insertion loss. Internal Fiber Management. The cassette should have internal guides to keep the fibers from bending too tightly. Comprehensive Performance Documentation Conveniently Displayed. The cassettes should be supplied with factory test results. Because such data is often misfiled, lost, or located inside the cassettes, Ortronics/Legrand now affixes the performance data to a label on the outside of the housing. Protected Array Connection. Many cassettes are designed so that the array connections stick out from the back of the cassette, increasing the chance they will be inadvertently bumped or damaged. Cassettes that have the connection located in a recess in the cassette housing provide better protection. Choice of patchcord connectors. The LC interface is the most popular (and recommended) because it allows the best combination of high-density, lowloss, and compatibility with equipment vendors. Some users may prefer other options, such as the SC or MT-RJ. Protected, recessed fiber array connection Convenient, accessible performance data Various adapter interface options up to 24 fibers Copyright 2008 Berk-Tek, a Nexans Company and Ortronics/Legrand, All rights reserved. 5
6 Berk-Tek, A Nexans Company 132 White Oak Road New Holland, PA Tel: 800-BERK-TEK; Fax: Ortronics/Legrand 125 Eugene O Neill Drive New London, CT Tel: ; Fax: Copyright 2008 Berk-Tek, a Nexans Company and Ortronics/Legrand, All rights reserved. 6
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand
Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems Rudolph A Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand November, 006 Introduction: Optical communication systems provide
Data Center Design for 40/100G
Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber
Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center
The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center Doug Coleman, Manager, Technology & Standards, Corning Cable Systems Optical connectivity with OM3/OM4 laser-optimized
The Need for Low-Loss Multifiber Connectivity
WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially
How To Make A Data Center More Efficient
Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING
Loss & Continuity Testing with MPO/ MTP Connectors
Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular
Overcoming OM3 Performance Challenges
White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G FIBER POLARITY: 10G and 40/100G OPTIONS Why is this significant in the data center? Data centers will be one of the first places where we
With the advent of Gigabit Ethernet
INTERNATIONAL JOURNAL OF NETWORK MANAGEMENT Int. J. Network Mgmt 2001; 11:139 146 (DOI: 10.1002/nem.396) The importance of modal bandwidth in Gigabit Ethernet systems By David N. Koon Ł This article deals
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber
Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure
Data Center Optimization: Component Choice and Innovative Design Combine to Allow the Creation of an Enabling Infrastructure Data Center Spaces Data Center Spaces as Defined by the TIA 942 Standard Source:
MPO. Fast Fibre Solution for Data Centres
MPO Fast Fibre Solution for Data Centres Benefits The Plug & Play MPO solution of Nexans Cabling Solutions provides a comprehensive line of pre-terminated and pre-tested assemblies to meet the current
Obsolete Fiber Technology? Not in my Data Center!
Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are
DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com
DATA CENTER NETWORK INFRASTRUCTURE Cable and Connectivity for the Most Demanding Networks Customer-focused, technology-driven, quality-assured for an unparalleled RETURN ON infrastructure investment DATA
Patch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations
The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com Contents Introduction 3 CommScope solution overview 3 InstaPATCH
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper
The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper Optical Fiber WP1150 Issued: October 2007 Supersedes: October 2006 ISO 9001 Registered
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8
Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,
Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network
Optical Fiber Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Carl Roberts [email protected] Cabling considerations for DCs and
Corning Cable Systems Optical Cabling Solutions for Brocade
Corning Cable Systems Optical Cabling Solutions for Brocade Building high-density, high-port-count, structured cabling solutions to scale storage area networks to thousands of ports Contents Executive
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration
The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer [email protected] Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards 40G & 100G
OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers
Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds
Zone Distribution in the Data Center
Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling
Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices
Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices Robert Reid (Panduit) Frank Yang (CommScope, Inc) 1 The Presenters Robert Reid Sr. Product Development Manager at Panduit Frank Yang Marketing
Plug & Play Gigabit Ethernet Media Conversion Module. Application Note
Plug & Play Gigabit Ethernet Media Conversion Module Application Note The Plug & Play Universal Systems Media Converter Module offers the best of both worlds easy fiber optic scalability and future proofing
Secure/Keyed LC System Solutions Overview
Secure/Keyed LC System Solutions Overview Designing performance and efficiency into your secure network Introduction In recent years, physically discrete fiber connection systems have emerged to respond
Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com
Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH
The Three Principles of Data Center Infrastructure Design WHITE PAPER
The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design Understand These Three Principles and You ll: Lower your total cost of ownership
Fiber Selection and Standards Guide for Premises Networks
Fiber Selection and Standards Guide for Premises Networks WP1160 Issued: November 2013 Supersedes: November 2012 Authors: Carl Roberts and Dr. Russell Ellis Introduction There are several main types of
CISCO 10GBASE X2 MODULES
DATA SHEET CISCO 10GBASE X2 MODULES Figure 1. Cisco 10GBASE X2 and Xenpak Module PRODUCT OVERVIEW The Cisco 10GBASE X2 modules (Figure 1) offers customers a wide variety of 10 Gigabit Ethernet connectivity
Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network
Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network WP4270 Issued: June 2011 Authors: Carl Roberts and Merrion Edwards Introduction
Data Center Cabling Technology and Trends
Data Center Cabling Technology and Trends Lisa A. Huff Data Center Applications Engineer Agenda: Data Center Cabling Market and Technology Trends Standards Impact on Structured Cabling Future Cabling Considerations
Best Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary
Arista and Leviton Technology in the Data Center
Visit: www.leviton.com/aristanetworks Arista and Leviton Technology in the Data Center Customer Support: 1-408-547-5502 1-866-476-0000 Product Inquiries: 1-408-547-5501 1-866-497-0000 General Inquiries:
Attaching the PA-A1-ATM Interface Cables
CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?
Will Your Fiber Optic Cable Plant Support Gigabit Ethernet? GBE, as the name says, is Ethernet scaled up to gigabit speeds, providing a migration path from Ethernet at 10 MB/s to Fast Ethernet at 100 MB/s
The 8-Fiber Solution for Today s Data Center
The 8-Fiber Solution for Today s Data Center Bill Charuk, SR Product Manager, Data Center Solutions Introduction Data center infrastructure is constantly evolving. Fiber optic installations have used the
How To Make A Fibre Cable For A Data Centre
LANmark-OF Fibre Optic Solutions for Data Centres Complex Data Centres require fibre solutions CORE SWITCH ACCESS SWITCH SERVER SAN SWITCH LANmark-OF Slimflex Patch Cords LANmark-OF Single Mode LANmark-OF
How To Properly Maintain A Fiber Optic Infrastructure
How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope
AMP NETCONNECT Data Center Cabling Solutions
AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision
10G and Beyond in the Data Center with OM3 Fiber
10G and Beyond in the Data Center with OM3 Fiber Doug Coleman, Manager Technology and Standards [email protected] Overview Optical Trends in Data Center Networks The time is NOW for 10G optical
Cabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
Polymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
DATA CENTER SOLUTIONS GUIDE
DATA CENTER SOLUTIONS GUIDE designed to be better. Power Cabinets Racks Pathways Aisle Containment Connectivity and Cabling RACKS AND CABINETS Legrand s cabinets and racks, designed for all your network
PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS
PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS Bandwidth Requirements Push Fiber Optic Solutions Offices, Operations
MIGRATING TO A 40 GBPS DATA CENTER
White Paper MIGRATING TO A 40 GBPS DATA CENTER Juniper QSFP+ LX4 technology removes cabling cost barriers for migrating from 10 Gbps to in data center networks Copyright 2014, Juniper Networks, Inc. 1
Issues Affecting the Design and Choice of Cabling Infrastructures within Data Centres
Issues Affecting the Design and Choice of Cabling Infrastructures within Data Centres White Paper Nexans Cabling Solutions September 2006 Executive Summary Planning for the unknown is always a difficult
Fibre optic testing best practices
Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is
Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center
Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center WP6046 Issued: June 2012 Introduction Our world is in a rapid state of change in terms of the way we communicate and are connected
Corning Cable Systems Optical Cabling Solutions for Brocade
Corning Cable Systems Optical Cabling Solutions for Brocade Building high-density, high-port-count, structured cabling solutions to scale Storage Area Networks (SANs) to thousands of ports. CONTENTS Executive
Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels
Fiber Systems Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels 1 Introduction Data centers are the central location for data interchange and are found in enterprises, government
TIA Releases Guidelines for Maintaining Polarity Using Array Connectors
Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General
Enterprise Networks EMEA. Core Products FOR DATA CENTRES
Enterprise Networks EMEA Core Products FOR DATA CENTRES EMEA Data Centre Core Products 1 Data Centres GET IT RIGHT, Right Now. Corning Cable Systems offers tens of thousands of fibre optic products for
How To Get A Better Signal From A Fiber To A Coax Cable
Gigabit Transmission What s the Limit? Fanny Mlinarsky Page 1 What s the Limit? Speed Faster higher frequency higher attenuation less headroom Distance Longer higher attenuation more jitter less headroom
The Conversion Technology Experts. Fiber Optics Basics
The Conversion Technology Experts Fiber Optics Basics Introduction Fiber optic technology is simply the use of light to transmit data. The general use of fiber optics did not begin until the 1970s. Robert
Optimizing Infrastructure Support For Storage Area Networks
Optimizing Infrastructure Support For Storage Area Networks December 2008 Optimizing infrastructure support for Storage Area Networks Mission critical IT systems increasingly rely on the ability to handle
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER
ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect Introduction
Plug & Play Universal Systems
Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution
DATA CENTER DESIGN BEST PRACTICES: EFFICIENCIES BEYOND POWER AND COOLING
ORTRONICS DATA CENTER DESIGN BEST PRACTICES: EFFICIENCIES BEYOND POWER AND COOLING Cindy Montstream, RCDD/NTS, EE, CPLP Director of elearning and Standards DATA COMMUNICATIONS Legrand, North America designed
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
SYSTIMAX Copper Solutions Designed for the Digital Generation
SYSTIMAX Copper Solutions Designed for the Digital Generation SYSTIMAX Structured Connectivity Solutions www.systimax.com SYSTIMAX Solutions is the global leader in the enterprise cabling sector with a
Upgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
WHITE PAPER. 50 versus 62.5 micron multimode fiber
WHITE PAPER 50 versus 62.5 micron multimode fiber www.ixiacom.com 915-6919-01 Rev. A, July 2014 2 Table of Contents What are 50μm fiber and 62.5μm fiber?... 4 Why two standards?... 4 Which technology should
Top of Rack: An Analysis of a Cabling Architecture in the Data Center
SYSTIMAX Solutions Top of Rack: An Analysis of a Cabling Architecture in the Data Center White paper Matthew Baldassano, Data Center Business Unit CommScope, Inc, June 2010 www.commscope.com Contents I.
FOCONEC. Network Connectivity & Cabling Management. Overview: Features: Brighter Future
CORDS & CABLE ASSEMBLIES Standard Simplex/Duplex Patch Cords Overview: FOCONEC supplies full series of standard simplex, duplex patch cords or pigtails, designed for interconnection or cross connection
HP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable
Overview Models HP 0.5 m Multimode OM3 LC/LC Optical Cable HP 1 m Multimode OM3 LC/LC Optical Cable HP 2 m Multimode OM3 LC/LC Optical Cable HP 5 m Multimode OM3 LC/LC Optical Cable HP 15 m Multimode OM3
Enabling 21 st Century Connectivity
Enabling 21 st Century Connectivity First MXC Adopters meeting March 11, 2014 MXC is a trademark of US Conec Presenters Victor Krutul Director Marketing, Intel Corp Mike Hughes Director, Product Management,
Parallel SMF (PSM) in the Data Centre
1 Parallel SMF (PSM) in the Data Centre - End User Survey - Alan Flatman, Independent + Brad Booth, Independent 2 Contributors A big thank you to the following people who provided introductions to end
Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications
Data Sheet Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
Implementing Fast Ethernet
Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast
High density Fiber Optic connections in the Data Center. Phil Ward Datacenter Product Market Manager. HUBER+SUHNER AG
High density Fiber Optic connections in the Data Center Phil Ward Datacenter Product Market Manager. HUBER+SUHNER AG How to make fast connections. Phill Ward Bicsi National 2 Conference India Projected
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables
Data Center Architecture with Panduit, Intel, and Cisco
Data Center Architecture with Panduit, Intel, and Cisco 0GBASE-T Application Note Integrating Panduit Category 6A Interconnects with the Cisco Nexus TM and Intel Ethernet Server Adapter X0-T 0 PANDUIT
100BASE-SX Fast Ethernet:
100BASE-SX Fast Ethernet: A Cost Effective Migration Path for Fiber in the Horizontal Prepared by the Fiber Optics LAN Section of the Telecommunications Industry Association February 2000 2000 TIA Fiber
Uniprise Solutions. Ten Good Reasons To Choose CommScope. www.commscope.com
Uniprise Solutions Ten Good Reasons To Choose CommScope Make connections not compromises only with CommScope. Here at CommScope, we cherish our rich history, which traces back to the formation of cable
Infrastructure for the next three generations
Infrastructure for the next three generations Demand for bandwidth and storage is expanding at a breathtaking rate within the data center, which means that the environment is rapidly evolving, making the
www.commscope.com Data Center Topology Guide
www.commscope.com Data Center Topology Guide Data Center Areas 1 Network Operations Center (NOC) The network operations center or NOC is the location where control of all data center networking, server
Living Infrastructure Solution Guide. www.commscope.com
Living Infrastructure Solution Guide Transform your data center into a living infrastructure One-size-fits-all practices and increased pressure affect data center performance In today s data center environment,
Cisco SFP Optics for Gigabit Ethernet Applications
Cisco SFP Optics for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output device that plugs into a Gigabit
HUBER+SUHNER AG Phil Ward
The challenges of building and maintaining Fiber Optic connectivity in the modern Data Center HUBER+SUHNER AG Phil Ward What is our common Global Objective? To connect different types of equipment together
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
Pretium EDGE HD Solutions
Pretium EDGE HD Solutions for Enterprise Data Centers and Storage Area Networks Corning Cable Systems Pretium EDGE HD Solutions create a fiber optic tip-to-tip solution for Data Centers and Storage Area
Data Centre & Enterprise Solutions. RapidNet
H E L L E R M A N N T Y T O N Data Centre & Enterprise Solutions RapidNet data centre & Enterprise solutions HellermannTyton is a leading global manufacturer of network cabling solutions which connect,
Arista 40G Cabling and Transceivers: Q&A
Arista 40G Cabling and Transceivers: Q&A 40G Cabling Technical Q&A Document 40Gigabit Cables and Transceivers Q. What 40G cables and transceivers are available from Arista? A. Arista supports a full range
Security & Surveillance Cabling Systems
Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.
Simplified 40-Gbps Cabling Deployment Solutions with Cisco Nexus 9000 Series Switches
Simplified 40-Gbps Cabling Deployment Solutions with Cisco Nexus 9000 Series Switches Panduit and Cisco Accelerate Implementation of Next-Generation Data Center Network Architecture 2013 Cisco Panduit.
Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company
Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs
Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village
Brno, Marec 2014 Physical Infrastructure trends and certification requirements for Datacenters Ing. Peter Potrok PROFiber Networking s.r.o. Psiber s Global Village London Munich San Diego Boston Paris
Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations
The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: [email protected] http://www.thefoa.org Technical Bulletin Guidelines For Testing